HomeMy WebLinkAboutNEW Manual J Updated 9 @ Load Short Form Job: 1572 wri htsoft Date: 7/23/2021 House By: Chris Bateman Air CaICs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project Information For: Durden Residence,NisAirAir Conditioning 5113 Sunset Blvd,Fort Pierce,FL 34982 Design Information Htg Clg Infiltration Outside db(°F) 41 90 Method Simplified Inside db(°F) 70 75 Construction quality Average Design TD(°F) 29 15 Fireplaces 0 Daily range - L Inside humidity(%) 30 50 Moisture difference(gr/Ib) 2 57 HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond MI14XC1S030-230A** AHRI ref Coil CBA27UHE-030-230*++TDR AHRI ref 10259437 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 6.1 kW Sensible cooling 20300 Btuh Heating output 20690 Btuh Latent cooling 8700 Btuh Temperature rise 19 °F Total cooling 29000 Btuh Actual airflow 967 cfm Actual airflow 967 cfm Air flow factor 0.048 cfm/Btuh Air flow factor 0.051 cfim/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.77 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) Master Bed 182 3040 1899 147 97 WIC 33 573 215 28 11 Master Bath 140 2298 1104 111 56 Laundry 55 602 904 29 46 Pantry 18 107 72 5 4 Kitchen DR 363 4133 6327 200 322 Great Room 149 2836 3494 137 178 Bed 3 143 2789 1925 135 98 Bath 44 597 249 29 13 Bed 2 150 1873 2244 91 114 Foyer 104 1141 565 55 29 Hall 28 0 0 0 0 Hall 2 78 0 0 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft, 2021-Nov-15 14:33:12 At M;.ek „n"e a«awa.=mP=. Right-Sute®UrrVersa12021 21.0.10 RSU29066 Page 1 ACCP. ...swrightsoft HVAC\5113 Sunset Blvd PSL Prop.rup Calc=MA Front Door faces: N House 1484 19990 18999 967 967 Other equip loads 1429 759 Equip.@ 0.95 RSM 18849 Latent cooling 5904 TOTALS 1484 21419 24753 967 967 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft, 2021-Nov-15 14:33:12 A II,-=Iae,-"e--.,I—— Right-Sute®Urrversa1202121.0.10RSU29066 Page 2 ACCP. ...swrightsoft HVAC\5113 SLmet Blvd PSL Prop.rup Calc=MJ8 Front Door faces: N Building Analysis Job: 1572 +� wrightsoft° gna Date: 7/23/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Durden Residence,NisAirAir Conditioning 5113 Sunset Blvd,Fort Pierce,FL 34982 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(°F) 70 75 Elevation: 26 ft Design TD(°F) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 2.4 56.9 Dry bulb(°F) 41 90 Infiltration: Daily range(°F) - 15 ( L ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 amme Component Btuh/ft2 Btuh %of load Walls 3.1 3680 17.2 ventilation Glazing 17.4 2390 11.2 Walls Doors 3.7 74 0.3 Ceilings 1.0 1471 6.9 Ducts Floors 3.2 4732 22.1 Glazing Infiltration 2.4 2864 13.4 Ducts 4779 22.3 Piping 0 0 Other Humidification 0 0 Ceilings Ventilation 1429 6.7 Infiltration Adjustments 0 Total 21419 100.0 Floors • • Component Btuh/ft2 Btuh %of load Walls 1.9 2287 11.6 Walls Ventilation Glazing 23.9 3285 16.6 Doors 3.7 75 0.4 Internal Gains Ceilings 1.5 2171 11.0 Glazing Floors 0 0 0 Infiltration 0.7 777 3.9 Ducts 5385 27.3 Ventilation 759 3.8 Other Internal gains 5020 25.4 Ceilings Blower 0 0 Adjustments 0 Infiltration Ducts Total 1 1197581 100.0 Latent Cooling Load=5904 Btuh Overall U-value=0.099 Btuh/ft2-°F Data entries checked. wrightsoft- 2021-Nov-15 14:33:12 �� ^a,k° „� Right-SriteO Uriversal 2021 21.0.10 RSU29066 Page 1 s\WrightsoftHVAC\5113 Sunset Blvd PSLProp.rup Calc=MA Front Door faces: N Component Constructions Job: 1572 +� wrightsoft C p C i Date: 7/23/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Durden Residence,NisAirAir Conditioning 5113 Sunset Blvd,Fort Pierce,FL 34982 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(T) 70 75 Elevation: 26 ft Design TD(T) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(grAb) 2.4 56.9 Dry bulb(T) 41 90 Infiltration: Daily range(T) - 15 ( L ) Method Simplified Wet bulb(T) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuh/ftUF W-T/Btuh Btuh/ft' Btuh Btuh/ft' Btuh Walls Blk Wall,Stucco Ext,R-4.1 Ext Bd inl,8"Thk, 1/2"Gyp Bd Int Fnsh n 199 0.109 5.1 3.15 628 2.02 402 e 229 0.109 5.1 3.15 722 2.02 462 s 212 0.109 5.1 3.15 668 2.02 427 w 378 0.109 5.1 3.15 1191 2.02 762 all 1018 0.109 5.1 3.15 3209 2.02 2053 Partitions Fnn Wall, 1/2"Gyp Bd Ext,R-11 Cav Ins, 1/2"Gyp Bd Int Fnsh,ZV", 16" 160 0.101 11.0 2.94 471 1.46 234 OC Stud Windows Impact,Clear Low-e: Impact,Clear Low-e;NFRC rated(SHGC=0.24); n 5 0.580 0 16.8 80 11.5 55 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(2.2 ft window ht, 1 ft sep.);6.8 ft head ht W 5 0.580 0 16.8 80 28.1 134 all 10 0.580 0 16.8 160 19.8 189 Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.24); n 16 0.580 0 16.8 262 11.5 179 50%blinds 45°,medium;50%outdoor insect screen;foreground=green a 16 0.580 0 16.8 262 28.1 439 grass(0.23); 1 ft overhang(5.2 ft window ht, 1 ft sep.);6.8 ft head ht e 31 0.580 0 16.8 525 28.1 878 w 16 0.580 0 16.8 262 28.1 439 all 78 0.580 0 16.8 1312 24.8 1935 Impact,Clear Low-e: Impact,Clear Low-e;NFRC rated(SHGC=0.24); w 10 0.580 0 16.8 160 28.1 267 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(3.17 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Low-e: Impact,Clear Low-e;NFRC rated(SHGC=0.21); w 40 0.650 0 18.8 758 16.0 645 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23);8 ft overhang(6.7 ft window ht, 1 ft sep.);6.8 ft head ht Doors Fbrgls Door a 20 0.127 7.0 3.69 74 3.73 75 Ceilings Attic,Shngl Roof,R-30 Ceil Ins, 1/2"Gyp Bd Int Fnsh 1484 0.034 30.0 0.99 1471 1.46 2171 wrightsoft"' 2021-Nov-1514:33:12 i.. ftHVAC\5113Su Right-Sute®Universal 2021 21.0.10 RSU29066 Page 1 'CA ...s\Wrightso1set Blvd PSLProp.rup Calc=MJ8 Front Door faces: N Floors On Grade Depth,Tile Flr Fnsh 165 0.989 0 28.7 4732 0 0 t 411— wrightsoft- 2021-Nov-1514:33:12 {1 Right-Sute®Universal2021 21.0.10 RSU29066 Page 2 MrightsoftHVACW113SusetBlvdPSLProp.ryo Calc=MJ8 FrontDoorfaces:N Pro S Job: 1572 +� wrightsoft° Project Date: 7/23/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Durden Residence,NisAirAir Conditioning 5113 Sunset Blvd,Fort Pierce,FL 34982 Notes: Design Information Weather: St Lucie Co Intl,FL,US Winter Design Conditions Summer Design Conditions Outside db 41 °F Outside db 90 °F Inside db 70 °F Inside db 75 °F Design TD 29 °F Design TD 15 °F Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 15211 Btuh Structure 13614 Btuh Ducts 4779 Btuh Ducts 5385 Btuh Central vent(45 cfm) 1429 Btuh Central vent(45 cfm) 759 Btuh Outside air Outside air Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 21419 Btuh Use manufacturer's data n Rate/swin multiplier 0.95 Infiltration Equipmen�sensible load 18849 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2575 Btuh Ducts 1596 Btuh Central vent(45 cfm) 1733 Btuh Heating Cooling Outside air Area(ft�) 1484 1484 Equipment latent load 5904 Btuh Volume(ft3) 11981 11981 Air changes/hour 0.45 0.23 Equipment Total Load(Sen+Lat) 24753 Btuh Equiv.AVF(cfm) 90 46 Req.total capacity at 0.70 SHR 2.2 ton Heating Equipment Summary Cooling Equipment Summary Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1S030-230A** AHRI ref Coil CBA27UHE-030-230*++TDR AHRI ref 10259437 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 6.1 kW Sensible cooling 20300 Btuh Heating output 20690 Btuh Latent cooling 8700 Btuh Temperature rise 19 °F Total cooling 29000 Btuh Actual airflow 967 cfm Actual airflow 967 cfm Air flow factor 0.048 cfm/Btuh Air flow factor 0.051 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.77 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wr19"tsoft- 2021-Nov-15 14:33:12 .�. ^.,.I,1,,..,k,�.,.I�---..1..,,�r,, Right-Sute®Uriversal 202l 2l.O.10 RSU29066 Page 1 ACCA ...swrightsoft HVAC\5113 Sunset Blvd PSL Prop.rup Calc=MA Front Door faces: N + wrightsoft°° Right-J®Worksheet Job: 1572 House Date: 7/23/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name House Master Bed 2 E)posed wal I 165.0 It 27.0 It 3 Room height 8.1 ft 8.6 It heat/000l 4 Room dimensions 14.0 x 13.0 It 5 Room area 1484.0 fF 182.0 ft Ty Consh'ucton U-value Or HTM Area (ft) Load Area (ft) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 n 3.15 2.02 220 199 628 402 112 96 303 194 T-jImpact,Clear Lowe 0.580 n 16.82 11.48 5 0 80 55 0 0 0 0 Impaa Clear Low-e 0.580 n 16.82 11.48 16 0 262 179 16 0 262 179 V[: Blk Wall,Stucco Ext 0.109 a 3.15 2.02 296 229 722 462 0 0 0 0 11 Impaa Clear Low-e 0.580 a 16.82 28.13 16 0 262 439 0 0 0 0 Impaa Clear Low-e 0.580 a 16.82 28.13 31 0 525 878 0 0 0 0 D Fbrgls Door 0.127 e 3.69 3.73 20 20 74 75 0 0 0 0 W Blk Wall,Stucco Ext 0.109 s 3.15 2.02 212 212 668 427 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 3.15 2.02 448 378 1191 762 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 5 0 80 134 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 10 0 160 267 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 16 0 262 439 0 0 0 0 Impact,Clear Low-e 0.650 w 18.85 16.05 40 34 758 645 0 0 0 0 P Fmi Wall,1/2"Gyp B 0.101 2.94 1.46 160 160 471 234 120 120 354 176 C Attic,Shngl Roof,R 0.034 0.99 1.46 1484 1484 1471 2171 182 182 180 266 F On Grade Depth,Tile 0.989 28.68 0.00 1484 165 4732 0 182 27 774 0 6 c)AED excursion 249 -101 Envelope loss/gain 12348 7817 1874 714 12 a) Infiltration 2864 777 272 74 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 4 920 0 0 Appliancestother 4100 500 Subtotal(lines 6 to 13) 15211 13614 2146 1288 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 0 0 167 73 14 Subtotal 15211 13614 2314 1361 15 Dud loads 31% 40%1 4779 5385 31% 40%1 727 538 FFTotal room load 19990 18999 3040 1899 Airrequired(dm) 967 967 147 97 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Nov-1514:33:12 ACCP. s\Wrig htsoftHVA w.............. Right-Sute®Universal 202121.0.10RSU29066 Pagel C\5113SuisetBlvdPSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft°° Right-J®Worksheet Job: 1572 House Date: 7/23/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name WIC Master Bath 2 E)posed wal I 5.5 ft 20.0 It 3 Room height 8.0 It heat/000l 8.0 It heat/000l 4 Room dimensions 6.0 x 5.5 It 1.0 x 139.5 It 5 Room area 33.0 it' 139.5 fF Ty Consh'ucton U-value Or HTM Area (ft) Load Area (ft) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 n 3.15 2.02 44 44 139 89 64 59 187 119 T-jImpact,Clear Lowe 0.580 n 16.82 11.48 0 0 0 0 5 0 80 55 Impaa Clear Low-e 0.580 n 16.82 11.48 0 0 0 0 0 0 0 0 V[: Blk Wall,Stucco Ext 0.109 a 3.15 2.02 0 0 0 0 0 0 0 0 11 Impaa Clear Low-e 0.580 a 16.82 28.13 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 a 16.82 28.13 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 e 3.69 3.73 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 s 3.15 2.02 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 3.15 2.02 0 0 0 0 96 91 287 184 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 5 0 80 134 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.650 w 18.85 16.05 0 0 0 0 0 0 0 0 P Frm Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic,Shngl Roof,R 0.034 0.99 1.46 33 33 33 48 140 140 138 204 F On Grade Depth,Tile 0.989 28.68 0.00 33 6 158 0 140 20 574 0 6 c)AED excursion -12 -16 Envelope loss/gain 329 125 1346 680 12 a) Infiltration 107 29 390 106 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancestother 0 0 Subtotal(lines 6 to 13) 436 154 1736 786 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 0 0 13 6 14 Subtotal 436 154 1749 791 15 Dud loads 31% 40% 1371 61 31% 40%1 549 313 FFTotal room load 573 215 2298 1104 Air required(dm) 28 11 111 56 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Nov-1514:33:12 ACCP. HVA w.............. Right-Sute®Urr versa 120212 1.0.10 RSU29066 Page 2 s\Wrihtsoft C\51 g 13SursetBlvdPSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft°° Right-J®Worksheet Job: 1572 House Date: 7/23/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Laundry Pantry 2 E)posed wal I 5.5 ft O ft 3 Room height 8.0 It heat/000l 8.0 It heat/000l 4 Room dimensions 5.5 x 10.0 It ft 5.0 x 3.5 5 Room area 55.0 ft 17.5 ft Ty Conshvcton U-value Or HTM Area (ft) Load Area (ft) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 n 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact,Clear Lowe 0.580 n 16.82 11.48 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 n 16.82 11.48 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 a 3.15 2.02 0 0 0 0 0 0 0 0 11 Impaa Clear Low-e 0.580 a 16.82 28.13 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 a 16.82 28.13 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 e 3.69 3.73 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 s 3.15 2.02 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 3.15 2.02 44 44 139 89 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.650 w 18.85 16.05 0 0 0 0 0 0 0 0 P Fmi Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic,Shngl Roof,R 0.034 0.99 1.46 55 55 55 80 18 18 17 26 F On Grade Depth,Tile 0.989 28.68 0.00 55 6 158 0 18 0 0 0 6 c)AED excursion -51 -2 Envelope loss/gain 351 118 17 24 12 a) Infiltration 107 29 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancestother 500 0 Subtotal(lines 6 to 13) 458 647 17 24 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 64 28 14 Subtotal 458 647 82 52 15 Dud loads 31% 40%1 144 256 31% 40%1 26 20 FFTotal room load 602 904 107 72 Airrequired(dm) 29 46 5 4 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Nov-1514:33:12 ACCP. HVA w.............. Right-Sute®Urr versa 120212 1.0.10 RSU29066 Page 3 s\Wrihtsoft C\51 g 13SuisetBlvdPSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft°° Right-J®Worksheet Job: 1572 House Date: 7/23/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Kitchen DR Great Room 2 E)posed wal I 27.5 ft 24.5 ft 3 Room height 8.0 ft heat/000l 8.0 ft heat/000l 4 Room dimensions 1.0 x 362.5 ft 11.0 x 13.5 ft 5 Room area 362.5 ft' 148.5 fF Ty Conshvcton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 n 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact,Clear Lowe 0.580 n 16.82 11.48 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 n 16.82 11.48 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 a 3.15 2.02 0 0 0 0 0 0 0 0 11 Impaa Clear Low-e 0.580 a 16.82 28.13 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 a 16.82 28.13 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 e 3.69 3.73 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 s 3.15 2.02 0 0 0 0 108 108 340 218 Blk Wall,Stucco Ext 0.109 w 3.15 2.02 220 170 537 343 88 72 228 146 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 10 0 160 267 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 16 0 262 439 Impact,Clear Low-e 0.650 w 18.85 16.05 40 34 758 645 0 0 0 0 P Fmi Wall,1/2"Gyp B 0.101 2.94 1.46 0 01 01 0 0 0 0 0 C Attic,Shngl Roof,R 0.034 0.99 1.46 363 363 359 530 149 149 147 217 F On Grade Depth,Tile 0.989 28.68 0.00 363 28 789 0 149 25 703 0 6 c)AED excursion 433 -5 Envelope loss/gain 2602 2219 1681 1014 12 a) Infiltration 536 145 477 130 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 2 460 2 460 Appliancestother 1700 900 Subtotal(lines 6 to 13) 3138 4524 2158 2504 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 7 10 0 0 14 Subtotal 3145 4534 2158 2504 15 Dud loads 31% 40% 9881 1793 31% 40%1 678 990 FFTotal room load 4133 6327 2836 3494 Airrequired(dm) 200 322 137 178 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Nov-1514:33:12 ACCP. HVA w.............. Right-Sute®Urr versa 120212 1.0.10 RSU29066 Page 4 s\Wrihtsoft C\51 g 13SursetBlvdPSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft°° Right-J®Worksheet Job: 1572 House Date: 7/23/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Bed 3 Bath 2 E)posed wal I 24.0 It 5.5 ft 3 Room height 8.0 It heat/000l 8.0 It heat/000l 4 Room dimensions 11.0 x 13.0 It 5.5 x 8.0 It 5 Room area 143.0 fF 44.0 ft Ty Consh'ucton U-value Or HTM Area (ft) Load Area (ft) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 n 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact,Clear Lowe 0.580 n 16.82 11.48 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 n 16.82 11.48 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 a 3.15 2.02 88 72 228 146 44 44 139 89 11 Impaa Clear Low-e 0.580 a 16.82 28.13 16 0 262 439 0 0 0 0 Impaa Clear Low-e 0.580 a 16.82 28.13 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 e 3.69 3.73 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 s 3.15 2.02 104 104 328 210 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 3.15 2.02 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.650 w 18.85 16.05 0 0 0 0 0 0 0 0 P Fmi Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic,Shngl Roof,R 0.034 0.99 1.46 143 143 142 209 44 44 44 64 F On Grade Depth,Tile 0.989 28.68 0.00 143 24 688 0 44 6 158 0 6 c)AED excursion -10 -13 Envelope loss/gain 1648 994 340 140 12 a) Infiltration 468 127 107 29 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancestother 250 0 Subtotal(lines 6 to 13) 2116 1371 447 169 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 6 9 7 10 14 Subtotal 2122 1379 454 179 15 Dud loads 31% 40%1 667 546 31% 40%1 143 71 FFTotal room load 2789 1925 597 249 Airrequired(dm) 135 98 29 13 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Nov-1514:33:12 ACCP. HVA w.............. Right-Sute®Urr versa 120212 1.0.10 RSU29066 Page 5 s\Wrihtsoft C\51 g 13SursetBlvdPSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft°° Right-J®Worksheet Job: 1572 House Date: 7/23/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Bed 2 Foyer 2 E)posed wal I 11.5 It 8.0 ft 3 Room height 8.0 It heat/000l 8.0 ft heat/cool 4 Room dimensions 11.5 x 13.0 It 8.0 x 13.0 It 5 Room area 149.5 fF 104.0 fF Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 n 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact,Clear Lowe 0.580 n 16.82 11.48 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 n 16.82 11.48 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 a 3.15 2.02 92 61 192 123 64 44 138 88 11 Impaa Clear Low-e 0.580 a 16.82 28.13 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 a 16.82 28.13 31 0 525 878 0 0 0 0 D Fbrgls Door 0.127 e 3.69 3.73 0 0 0 0 20 20 74 75 W Blk Wall,Stucco Ext 0.109 s 3.15 2.02 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 3.15 2.02 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.650 w 18.85 16.05 0 0 0 0 0 0 0 0 P Fmi Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic,Shngl Roof,R 0.0341 0.99 1.46 150 150 148 219 104 104 103 152 F On Grade Depth,Tile 0.989 28.68 0.00 150 12 330 0 104 8 229 0 6 c)AED excursion 70 -26 Envelope loss/gain 1194 1289 545 289 12 a) Infiltration 224 61 156 42 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancestother 250 0 Subtotal(lines 6 to 13) 1418 1599 701 332 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 6 9 167 73 14 Subtotal 1425 1608 868 405 15 Dud loads 31% 40%1 448 636 31% 40%1 273 160 FFTotal room load 1873 2244 1141 565 Airrequired(dm) 91 114 55 29 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Nov-1514:33:12 ACCP. HVA w.............. Right-Sute®Urr versa 120212 1.0.10 RSU29066 Page 6 s\Wrihtsoft C\51 g 13SursetBlvdPSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft°° Right-J®Worksheet Job: 1572 House Date: 7/23/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Hall Hall 2 2 E)posed wal I O ft 6.0 ft 3 Room height 8.0 It heat/000l 8.0 It heat/000l 4 Room dimensions 5.5 x 5.0 It 6.0 x 13.0 It 5 Room area 27.5 it' 78.0 ft Ty Consh'ucton U-value Or HTM Area (ft) Load Area (ft) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 n 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact,Clear Lowe 0.580 n 16.82 11.48 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 n 16.82 11.48 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 a 3.15 2.02 0 0 0 0 8 8 25 16 11 Impaa Clear Low-e 0.580 a 16.82 28.13 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 a 16.82 28.13 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 e 3.69 3.73 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 s 3.15 2.02 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 3.15 2.02 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.650 w 18.85 16.05 0 0 0 0 0 0 0 0 P Fmi Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 40 40 118 58 C Attic,Shngl Roof,R 0.034 0.99 1.46 28 28 27 40 78 78 77 114 F On Grade Depth,Tile 0.989 28.68 0.00 28 0 0 0 78 6 172 0 6 c)AED excursion -3 -14 Envelope loss/gain 27 37 392 174 12 a) Infiltration 0 0 19 5 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancestother 0 0 Subtotal(lines 6 to 13) 27 37 412 180 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution -27 -37 -412 -180 14 Subtotal 0 0 0 0 15 Dud loads 31% 40% 01 0 31% 40%1 0 0 qT.0, tal room load 0 0 0 quired(dm 0) 0 0 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Nov-1514:33:12 ACCP. HVA w.............. Right-Sute®Urr versa 120212 1.0.10 RSU29066 Page 7 s\Wrihtsoft C\51 g 13SursetBlvdPSLProp.rp Calc=MJ8 Front Door faces: N Duct System Summary Job: 1572 +� wrightsoft D S S Date: 7/23/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.mm Project Information For: Durden Residence,Nis,4irAir Conditioning 5113 Sunset Blvd,Fort Pierce,FL 34982 Heating Cooling External static pressure 0.70 in H2O 0.70 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 0.70 in H2O 0.70 in H2O Supply/return available pressure 0.485/0.215 in H2O 0.485/0.215 in H2O Lowest friction rate 0.285 in/100ft 0.285 in/100ft Actual airflow 967 cfm 967 cfm Total effective length(TEL) 245 ft SupplyDetail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FIR (in) (in) Matl Ln(ft) Ln(ft) Trunk Bat, h 597 35 15 0.294 4.0 Ox0 VIFx 45.3 120.0 st3 Bed 2 c 2244 109 137 0.371 6.0 Ox 0 VI Fx 30.9 100.0 st1 Bed 3 h 2789 162 118 0.285 7.0 Ox 0 VI Fx 50.1 120.0 st3 Foyer h 1141 66 34 0.364 5.0 Ox0 VIFx 33.5 100.0 st1 Great Room c 3494 165 213 0.287 8.0 Ox 0 VI Fx 49.3 120.0 st3 Kitchen DR c 3164 120 193 0.365 7.0 Ox 0 VI Fx 33.0 100.0 st1 Kitchen DR-A c 3164 120 193 0.365 7.0 Ox 0 VI Fx 33.0 100.0 st1 Laundry c 904 35 55 0.371 5.0 Ox0 VI Fx 26.0 105.0 st2 Master Bath h 2298 133 67 0.372 6.0 Ox 0 VI Fx 25.6 105.0 st2 Master Bed h 1520 88 58 0.373 5.0 Ox 0 VI Fx 25.0 105.0 st2 Master Bed-A h 1520 88 58 0.361 5.0 Ox 0 VI Fx 29.5 105.0 st2 Pantry h 107 6 4 0.361 4.0 Ox0 VI Fx 34.6 100.0 st1 WIC h 573 33 13 0.371 4.0 Ox 0 VI Fx 26.0 105.0 st2 SupplyDetail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st3 PeakAVF 361 346 0.285 817 9.0 0 x 0 VinlFlx st1 st1 PeakAVF 782 908 0.285 850 14.0 0 x 0 VinlFlx st2 PeakAVF 378 252 0.361 856 9.0 0 x 0 VinlFlx wrightsoft® 2021-Nov-1514:33:13 AM,.ek,Iae„-H.1h..., p,�, Right-Suite®Universal 2021 21.0.10 RSU29066 Page 1 ..s\wrightsoft HVAC\5113 Sunset Blvd PSL Prop.rup Calc=MJ8 Front Door faces: N TableReturn Branch Detail Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size(in) (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening(in) Matl Trunk rb5 Ox0 210 129 75.2 0.285 601 8.0 Ox 0 VIFx rt1 rb1 Ox0 515 563 69.2 0.310 527 14.0 Ox 0 VIFx rt1 rb2 Ox0 109 137 0 0 0 0 Ox 0 VIFx rb3 Ox 0 162 118 0 0 0 0 Ox 0 VI Fx rb4 Ox0 165 213 0 0 0 0 Ox 0 VIFx TableReturn Trunk Detail Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk rt1 PeakAVF 725 692 0.285 519 16.0 0 x 0 VInIFIX wrightsoft® 2021-Nov-1514:33:13 AI,--I--.e-1-,C-p,, Rig1t-Sute®Uriversal202121.0.10RSU29066 Page 2 ..s\WrightsoftHVAC\5113SLmet Blvd PSLProp.rup Calc=MJB Front Door faces: N Manual S ComplianceReport Job: 1572 +� wrightsoft° Date: 7/23/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project Information For: Durden Residence,NisAirAir Conditioning 5113 Sunset Blvd,Fort Pierce,FL 34982 Cooling Equipment Design Conditions Outdoor design DB: 90.4°F Sensible gain: 19758 Btuh Entering coil DB: 76.8°F Outdoor design WB: 77.4°F Latent gain: 5904 Btuh Entering coil WB: 64.0°F Indoor design DB: 75.0°F Total gain: 25662 Btuh Indoor RH: 50% Estimated airflow: 967 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitAC Manufacturer: Lennox Model: ML14XC1S030-230A**+CBA27UHE-030-230*++TDR Actual airflow: 967 cfm Sensible capacity: 20300 Btuh 103%of load Latent capacity: 8700 Btuh 147%of load Total capacity: 29000 Btuh 113%of load SHR: 70% Heating Equipment Design Conditions Outdoor design DB: 41.0°F Heat loss: 21419 Btuh Entering coil DB: 68.2°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Elecstrip Manufacturer: Model: Actual airflow: 967 cfm Output capacity: 6.1 kW 97%of load Temp.rise: 50 °F Meets all requirements ofACCA Manual S. wrightsoft, 2021-Nov-15 14:33:13 M;.ek „n"e a«awa.=mP=. Right-Sute®Uriversal 2021 2l.O.10 RSU29066 Page 1 swrightsoft HVAC\5113 Sunset Blvd PSL Prop.rup Calc=MA Front Door faces: N