MANUFACTURERS TRUSS PLANS MUST BE REVIEWED AND APPROVED BY ENGINEER OF
RECORD PER FAC 61GI6-31,003
07/19/2007 3 Comment PROVIDE TRUSS CONNECTOR CHART PER FIBC 106.3.5
07/19/2007 4 Comment PROVIDE AREA TABULATION ON DRAWINGS PER FBC 106.3.5
07/19/2007 5 Comment BATHROOM DOOR MUST COMPLY WITH FBC SECTION 11-11
07/1912007 6 Comment PROVIDE ATTIC ACCESS PER FRG 807
07/19/2007 7 Comment EXHAUST FANS MUST COMPLY WITH PRO SECTION 1506
07/19/2007 8 Comment PROVIDE ELECTRIC RISER AND LOAD CALCS PER NFPA 70
07/19/2007 9 Comment PROVIDE SMOKE DETECTORS PER FRC 313.1
07/1912007 10 Comment IF BBQ REQUIRES GAS PIPING, PROVIDE GAS PIPING SCHEMATIC, TANK LOCATION AND
SUBCONTRACTOR AGREEMENT
07/1912007 11 Comment COMMENTS MAILED TO -CONTRACTOR AND OWNER .
Zoning Review Pending . Wla Galbraith 07/1312007
07113/2007 1 Comment ACCORDING TO RV THE PROPOSE[ FFE IS GOING TO MATCH THE EXISTING BUT THE
SURVEY IS MISS G ISTING FFE. WE NEED A CORRECTED SEALED SURVEY WITH THE
EXISTING FFE.
WE NEED 2 COR CTED EALED SURVEYS
07/1312007 2 Comment 7/13 FAX CONTRACTOR