HomeMy WebLinkAboutNEW Manual J Updated 9 @ Load Short Form Job: 1621 wri htsoft Date: 9/20/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyrrie@aircalcs.com Project Information For: Key Largo Spec,NisAirAir Conditioning 6006 Spruce Dr,Fort Pierce,FL 34982 Design Information Htg Clg Infiltration Outside db(°F) 41 90 Method Simplified Inside db(°F) 70 75 Construction quality Average Design TD(°F) 29 15 Fireplaces 0 Daily range - L Inside humidity(%) 30 50 Moisture difference(gr/Ib) 2 57 HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1-041-230A** AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259425 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 7.9 kW Sensible cooling 26950 Btuh Heating output 26975 Btuh Latent cooling 11550 Btuh Temperature rise 19 °F Total cooling 38500 Btuh Actual airflow 1283 cfm Actual airflow 1283 cfm Air flow factor 0.050 cfm/Btuh Air flow factor 0.051 cfim/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.78 ROOM NAME Area Htg load Clg load Htg AVF CIg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) Laundry 36 432 842 22 43 Bed 2 136 2421 1754 121 90 Bath 42 59 107 3 6 Bath 2 51 773 535 39 27 Hall 30 0 0 0 0 Bed 3 153 3225 2587 161 132 Bed 4 157 2507 1922 126 98 Foyer GR 426 5261 6266 263 321 Pantry 14 0 0 0 0 Kitchen DR 411 4673 7072 234 362 Master Bath 95 2084 976 104 50 Hers 20 409 161 20 8 His 9 12 21 1 1 Master Bed 222 3779 2833 189 145 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft, 2021-Nov-15 15:46:51 A Right-Sute®UrrVersa12021 21.0.10 RSU29066 Page 1 ACCA ..zits\W rightsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Front Door faces:N House 1801 25634 25078 1283 1283 Other equip loads 1769 939 Equip.@ 0.95 RSM 24820 Latent cooling 7383 TOTALS 1801 27403 32203 1283 1283 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft, 2021-Nov-15 15:46:51 A- II,-=Iae,-"e—«awa.—,, Right-Sute®Urrversa1202121.0.10RSU29066 Page ACCA ...rts\W rightsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Front Door faces:N Building Job: 1621 +� wrightsoft° 9 Analysis Date: 9/20/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Key Largo Spec,NisAirAir Conditioning 6006 Spruce Dr,Fort Pierce,FL 34982 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(°F) 70 75 Elevation: 26 ft Design TD(°F) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 2.4 56.9 Dry bulb(°F) 41 90 Infiltration: Daily range(°F) - 15 ( L ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 amme Component Btuh/ft2 Btuh %of load Walls 3.1 4650 17.0 Ventilation Glazing 17.4 3777 13.8 walls Doors 0 0 0 Ceilings 1.0 1785 6.5 Ducts Floors 3.2 5734 20.9 Infiltration 2.2 3184 11.6 Glazing Ducts 6504 23.7 Piping 0 0 Humidification 0 0 Ceilings Ventilation 1769 6.5 Infiltration Adjustments 0 Total 27403 100.0 Floors Component Btuh/ft2 Btuh %of load Walls 1.9 2867 11.0 Walls Ventilation Glazing 21.8 4720 18.1 Doors 0 0 0 Internal Gains Ceilings 1.8 3250 12.5 Glazing Floors 0 0 0 Infiltration 0.6 890 3.4 Ducts 7252 27.9 Ventilation 939 3.6 Internal gains 6100 23.4 Blower 0 0 Ceilings Adjustments 0 Infiltration Ducts Total 26017 100.0 Latent Cooling Load=7383 Btuh Overall U-value=0.104 Btuh/ft2--°F Data entries checked. wrightsoft" 2021-Nov-1 5 15:46:51 ^.-k-I-11 °^.111—,1^,p°11 Right-SUteOUriversal2021 21.0.10 RSU29066 Page 1 ACCA nts\W rightsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Front Door faces:N om Constructions Job: 1621 +� wrightsoft Component Date: 9/20/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project • • For: Key Largo Spec,NisAirAir Conditioning 6006 Spruce Dr,Fort Pierce,FL 34982 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(T) 70 75 Elevation: 26 ft Design TD(T) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(grAb) 2.4 56.9 Dry bulb(T) 41 90 Infiltration: Daily range(T) - 15 ( L ) Method Simplified Wet bulb(T) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuh/ftUF W-T/Btuh Btuh/ft' Btuh Btuh/ft' Btuh Walls Blk Wall,Stucco Ext,R-4.1 Ext Bd inl,8"Thk, 1/2"Gyp Bd Int Fnsh ne 371 0.109 5.1 3.15 1169 2.02 748 se 251 0.109 5.1 3.15 791 2.02 506 sw 228 0.109 5.1 3.15 717 2.02 459 nw 387 0.109 5.1 3.15 1220 2.02 780 all 1237 0.109 5.1 3.15 3897 2.02 2493 Partitions Fnn Wall, 1/2"Gyp Bd Ext,R-11 Cav Ins, 1/2"Gyp Bd Int Fnsh,2"A", 16" 257 0.101 11.0 2.94 754 1.46 374 OC Stud Windows Impact,Clear Low-e: Impact,Clear Low-e;NFRC rated(SHGC=0.22); se 47 0.620 0 18.0 841 21.4 1001 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(5.2 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.24); se 40 0.580 0 16.8 676 10.1 405 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23);4.7 ft overhang(6.7 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.24); sw 7 0,580 0 16.8 111 20.3 134 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(2.2 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Low-e: Impact,Clear Low-e;NFRC rated(SHGC=0.24); sw 31 0.580 0 16.8 525 21.8 681 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(5.2 ft window ht, 1 ft sep.);6.8 ft head ht nw 31 0.580 0 16.8 525 22.6 706 all 62 0.580 0 16.8 1050 22.2 1387 Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.24); nw 5 0.580 0 16.8 79 22.6 106 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(2.17 ft window ht, 1 ft sep.);6.8 ft head ht 'Pk wrightsoft"' 2021-Nov-1515:46:51 --k=de-•,.ea«a-a. P=. Right-Sute®Unversa1202121.0.10RSU29066 Pagel ACCA nts\W rightsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Front Door faces:N Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.24); nw 16 0.580 0 16.8 262 22.6 353 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23);8 ft overhang(5.2 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Lowe: Impact,Clear Low-e;NFRC rated(SHGC=0.21); nw 40 0.650 0 18.8 758 22.0 886 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23);8 ft overhang(6.7 ft window ht, 1 ft sep.);6.8 ft head ht Doors (none) Ceilings Attic,Metal Roof,R-30 Ceil Ins, 1/2"Gyp Bd Int Fnsh 1801 0.034 30.0 0.99 1785 1.80 3250 Floors On Grade Depth,Tile Flr Fnsh 200 0.989 0 28.7 5734 0 0 'Pk wrightsoft- 2021-Nov-1515:46:51 --1-de-•,.e a«a-a. P=. Right-Sutee Uriversa12021 21.0.10 RSU29066 Page 2 ACCA its\W rightsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Frord Door faces:N Pro S Job: 1621 +� wrightsoft° Project Date: 9/20/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Keyy Largo Spec,NisAirAir Conditioning 6006 Spruce Dr,Fort Pierce,FL 34982 Notes: Design Information Weather: St Lucie Co Intl,FL,US Winter Design Conditions Summer Design Conditions Outside db 41 °F Outside db 90 °F Inside db 70 °F Inside db 75 °F Design TD 29 °F Design TD 15 °F Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 19130 Btuh Structure 17826 Btuh Ducts 6504 Btuh Ducts 7252 Btuh Central vent(56 cfm) 1769 Btuh Central vent(56 cfm) 939 Btuh Outside air Outside air Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 27403 Btuh Use manufacturer's data n Rate/swin multiplier 0.95 Infiltration Equipmen�sensible load 24820 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3032 Btuh Ducts 2206 Btuh Central vent(56 cfm) 2145 Btuh Heating Coolingg Outside air Area(ft�) 1801 1801 Equipment latent load 7383 Btuh Volume(ft3) 15772 15772 Air changes/hour 0.38 0.20 Equipment Total Load(Sen+Lat) 32203 Btuh Equiv.AVF(cfm) 100 53 Req.total capacity at 0.70 SHR 3.0 ton Heating Equipment Summary Cooling Equipment Summary Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1-041-230A** AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259425 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 7.9 kW Sensible cooling 26950 Btuh Heating output 26975 Btuh Latent cooling 11550 Btuh Temperature rise 19 °F Total cooling 38500 Btuh Actual airflow 1283 cfm Actual airflow 1283 cfrn Air flow factor 0.050 cfm/Btuh Air flow factor 0.051 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.78 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wriQhtsoft- 2021-Nov-15 15:46:51 ^.,.I,1 °.,,....°..,,ill,., Right-Sute®Uriversal202l 2l.O.10 RSU29066 Page 1 ACCA nts\W rightsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Front Door faces:N + wrightsoft°° Right-J®Worksheet Job: 1621 House Date: 9/20/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name House Laundry 2 E)posed wal I 199.9 It 5.5 ft 3 Room height 8.8 ft 8.0 It heat/000l 4 Room dimensions 5.5 x 6.5 It 5 Room area 1800.8 fF 35.8 ft Ty Construction U-value Or HTM Area (ft) Load Area (ft) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 371 371 1169 748 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 338 251 791 506 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.39 47 6 841 1001 0 0 0 0 Impaa Clear Low-e 0.580 se 16.82 10.07 40 40 676 405 0 0 0 0 11 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 266 228 717 459 0 0 0 0 Impaa Clear Low-e 0.580 sw 16.82 20.25 7 2 111 134 0 0 0 0 ���--GGG Impaa Clear Low-e 0.580 sw 16.82 21.82 31 4 525 681 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 479 387 1220 780 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 5 0 79 106 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 31 0 525 706 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 16 0 262 353 0 0 0 0 Impact,Clear Low-e 0.650 nw 18.85 22.04 40 0 758 886 0 0 0 0 P Fmi Wall,1/2"Gyp B 0.101 2.94 1.46 257 257 754 374 44 44 129 64 C Attic,Metal Roof,R 0.034 0.99 1.80 1801 1801 1785 3250 36 36 35 65 F On Grade Depth,Tile 0.989 28.68 0.00 1801 200 5734 0 36 6 158 0 6 c)AED excursion 447 -30 Envelope loss/gain 15946 10836 322 98 12 a) Infiltration 3184 890 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 5 1150 0 0 Appliances/other 4950 500 Subtotal(lines 6 to 13) 19130 17826 322 598 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 19130 17826 322 598 15 Dud loads 34% 41%1 6504 7252 34% 41%1 110 243 FFTotal room load 25634 25078 432 842 Airrequired(dm) 1283 1283 22 43 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. �� rigF�tsoft° 2021-Nov-1515:46:51 Right-Suite@Unversa12021 21.0.10 RSU29066 Page 1 nts\W ri htsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Front Door faces:N + wrightsoft°° Right-J®Worksheet Job: 1621 House Date: 9/20/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Bed 2 Bath 2 E)posed wal I 24.0 It 0 It 3 Room height 8.0 It heat/000l 8.0 It heat/000l 4 Room dimensions 1.0 x 135.8 It 7.0 x 6.0 It 5 Room area 135.8 fF 42.0 ft Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 se 16.82 10.07 0 0 0 0 0 0 0 0 11 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 84 68 216 138 0 0 0 0 Impaa Clear Low-e 0.580 sw 16.82 20.25 0 0 0 0 0 0 0 0 ���--GGG Impaa Clear Low-e 0.580 sw 16.82 21.82 16 2 262 340 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.650 nw 18.85 22.04 0 0 0 0 0 0 0 0 P Fmi Wall,1/2"Gyp B 0.101 2.94 1.46 108 108 317 158 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 1.80 136 136 135 245 42 42 42 76 F On Grade Depth,Tile 0.989 28.68 0.00 136 24 688 0 42 0 0 0 6 c)AED excursion 57 -4 Envelope loss/gain 1618 938 42 72 12 a) Infiltration 184 51 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 250 0 Subtotal(lines 6 to 13) 1802 1240 42 72 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 4 7 2 4 14 Subtotal 1806 1247 44 76 15 Dud loads 34% 41%1 614 507 34% 41%1 15 31 FFTotal room load 2421 1754 59 107 Airrequired(dm) 121 90 3 6 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. �� rigF�tsoft° 2021-Nov-1515:46:51 Right-Srite@ Uriversal202l 2l.O.10 RSU29066 Page 2 nts\W ri htsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Front Door faces:N + wrightsoft°° Right-J®Worksheet Job: 1621 House Date: 9/20/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Bath 2 Hall 2 E)posed wal I 6.0 ft O ft 3 Room height 8.0 It heat/000l 8.0 ft heat/cool 4 Room dimensions 8.5 x 6.0 It 3.5 x 8.5 It 5 Room area 51.0 ft2 29.8 tt Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 se 16.82 10.07 0 0 0 0 0 0 0 0 11 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 48 41 130 83 0 0 0 0 Impaa Clear Low-e 0.580 sw 16.82 20.25 7 2 111 134 0 0 0 0 ���--GGG Impaa Clear Low-e 0.580 sw 16.82 21.82 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.650 nw 18.85 22.04 0 0 0 0 0 0 0 0 P Fmi Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 1.80 51 51 51 92 30 30 29 54 F On Grade Depth,Tile 0.989 28.68 0.00 51 6 172 0 30 0 0 0 6 c)AED excursion 29 -3 Envelope loss/gain 464 338 29 51 12 a) Infiltration 105 29 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 569 367 29 51 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 7 13 -29 -51 14 Subtotal 577 380 0 0 15 Dud loads 34% 41% 1961 155 34% 41%1 0 0 qT.0, tal room load 773 535 0 0 quired(dm) 39 27 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. �� rigF�tsoft° 2021-Nov-1515:46:51 Right-Srite@ Uriversal202l 2l.O.10 RSU29066 Page 3 nts\W ri htsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Front Door faces:N + wrightsoft°° Right-J®Worksheet Job: 1621 House Date: 9/20/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Bed 3 Bed 4 2 E)posed wal I 25.5 It 21.0 It 3 Room height 8.0 It heat/000l 8.0 It heat/000l 4 Room dimensions 1.0 x 153.3 It 1.0 x 157.0 It 5 Room area 153.3 ft' 157.0 ft= Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 64 64 202 129 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 se 16.82 10.07 0 0 0 0 0 0 0 0 11 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 108 92 291 186 0 0 0 0 Impaa Clear Low-e 0.580 sw 16.82 20.25 0 0 0 0 0 0 0 0 ���--GGG Impaa Clear Low-e 0.580 sw 16.82 21.82 16 2 262 340 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 96 80 253 162 104 88 279 178 Impact,Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 16 0 262 353 16 0 262 353 Impact,Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.650 nw 18.85 22.04 0 0 0 0 0 0 0 0 P Fmi Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 1.80 153 153 152 277 157 157 156 283 F On Grade Depth,Tile 0.989 28.68 0.00 153 26 731 0 157 21 602 0 6 c)AED excursion 133 65 Envelope loss/gain 1953 1452 1501 1009 12 a) Infiltration 447 125 368 103 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 250 250 Subtotal(lines 6 to 13) 2399 1827 1869 1362 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 7 13 2 4 14 Subtotal 2407 1839 1871 1366 15 Dud loads 34% 41% 8181 748 34% 41%1 636 556 FFTotal room load 3225 2587 2507 1922 Airrequired(dm) 161 132 126 98 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. �� rigF�tsoft° 2021-Nov-1515:46:51 Right-Sute@Unversal202121.0.10RSU29066 Page nts\W ri htsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Front Door faces:N + wrightsoft°° Right-J®Worksheet Job: 1621 House Date: 9/20/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Foyer GR Pantry 2 E)posed wal I 34.5 It 0 It 3 Room height 9.5 It heat/000l 8.0 It heat/000l 4 Room dimensions 1.0 x 426.3 It 2.5 x 5.5 It 5 Room area 426.3 fF 13.8 ft Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 223 152 478 306 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.39 31 4 561 668 0 0 0 0 Impact,Clear Low-e 0.580 se 16.82 10.07 40 40 676 405 0 0 0 0 11 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 sw 16.82 20.25 0 0 0 0 0 0 0 0 ���--GGG Impact Clear Low-e 0.580 sw 16.82 21.82 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.650 nw 18.85 22.04 0 0 0 0 0 0 0 0 P Fmi Wall,1/2"Gyp B 0.101 2.94 1.46 105 105 307 152 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 1.80 426 426 423 769 14 14 14 25 F On Grade Depth,Tile 0.989 28.68 0.00 426 35 989 0 14 0 0 0 6 c)AED excursion -76 -1 Envelope loss/gain 3435 2224 14 24 12 a) Infiltration 489 137 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 3 690 0 0 Appliances/other 1400 0 Subtotal(lines 6 to 13) 3924 4451 14 24 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 2 4 -14 -24 14 Subtotal 3926 4454 0 0 15 Dud loads 34% 41% 13351 1812 34% 41%1 0 0 Total room load 5261 6266 0 100 T.0, quired(dm) 263 321 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. �� rigF�tsoft° 2021-Nov-1515:46:51 Right-Srite@ Uriversal202l 2l.O.10 RSU29066 Page 5 nts\W ri htsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Front Door faces:N + wrightsoft°° Right-J®Worksheet Job: 1621 House Date: 9/20/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Kitchen DR Master Bath 2 E)posed wal I 28.0 ft 19.5 ft 3 Room height 9.5 ft heat/000l 8.0 ft heat/000l 4 Room dimensions 1.0 x 410.5 ft 10.5 x 9.0 ft 5 Room area 410.5 ft' 94.5 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 71 71 224 144 72 72 227 145 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.580 se 16.82 10.07 0 0 0 0 0 0 0 0 11 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 sw 16.82 20.25 0 0 0 0 0 0 0 0 ���--GGG Impaa Clear Low-e 0.580 sw 16.82 21.82 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 195 139 438 280 84 79 250 160 Impact,Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 5 0 79 106 Impact,Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 16 0 262 353 0 0 0 0 Impact,Clear Low-e 0.650 nw 18.85 22.04 40 0 758 886 0 0 0 0 P Fmi Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 1.80 411 411 407 741 95 95 94 171 F On Grade Depth,Tile 0.989 28.68 0.00 411 28 803 0 95 20 559 0 6 c)AED excursion 279 9 Envelope loss/gain 2892 2683 1209 590 12 a) Infiltration 583 163 342 96 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 2 460 0 0 Appliances/other 1700 0 Subtotal(lines 6 to 13) 3475 5005 1550 686 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 12 21 5 8 14 Subtotal 3487 5027 1555 694 15 Dud loads 34% 41%1 11861 2045 34% 41% 529 282 qT.0, tal room load 4673 7072 2084 976 quired(dm) 234 362 104 50 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. �� rigF�tsoft° 2021-Nov-1515:46:51 Right-Sute@ Urrversa12021 21.0.10 RSU29066 Page 6 nts\W ri htsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Front Door faces:N + wrightsoft°° Right-J®Worksheet Job: 1621 House Date: 9/20/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Hers His 2 E)posed wal I 4.0 ft O ft 3 Room height 8.0 It heat/000l 8.0 It heat/000l 4 Room dimensions 5.0 x 4.0 It 1.0 x 8.9 It 5 Room area 20.0 it' 8.9 ft Ty Construction U-value Or HTM Area (ft) Load Area (ft) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 32 32 101 64 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 se 16.82 10.07 0 0 0 0 0 0 0 0 11 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 sw 16.82 20.25 0 0 0 0 0 0 0 0 ���--GGG Impaa Clear Low-e 0.580 sw 16.82 21.82 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Low-e 0.650 nw 18.85 22.04 0 0 0 0 0 0 0 0 P Fmi Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 1.80 20 20 20 36 9 9 9 16 F On Grade Depth,Tile 0.989 28.68 0.00 20 4 115 0 9 0 0 0 6 c)AED excursion -6 -1 Envelope loss/gain 235 95 9 15 12 a) Infiltration 70 20 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 305 114 9 15 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 305 114 9 15 15 Dud loads 34% 41% 1041 47 34% 41%1 3 6 qT.0, tal room load 409 161 12 21 quired(dm) 20 8 1 1 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. �� rigF�tsoft° 2021-Nov-1515:46:51 Right-Srite@ Uriversal202l 2l.O.10 RSU29066 Page 7 nts\W ri htsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Front Door faces:N + wrightsoft°° Right-J®Worksheet Job: 1621 House Date: 9/20/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Master Bed 2 E)posed wal I 31.9 It 3 Room height 8.5 It heat/000l 4 Room dimensions 1.0 x 222.4 It 5 Room area 222.4 ft Ty Construction U-value Or HTM Area (ft2) Load Area Load number (BtuhV-°F) (BtuhAF) or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 132 132 415 266 W Blk Wall,Stucco Ext 0.109 se 3.15 2.02 115 99 312 200 EG Impact,Clear Lowe 0.620 se 17.98 21.39 16 2 280 334 CG Impact,Clear Lowe 0.580 se 16.82 10.07 0 0 0 0 11 W Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 26 26 80 51 Impact,Clear Lowe 0.580 sw 16.82 20.25 0 0 0 0 G Impact,Clear Lowe 0.580 sw 16.82 21.82 0 0 0 0 W Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 Impact,Clear Lowe 0.580 nw 16.82 22.64 0 0 0 0 G Impact,Clear Lowe 0.580 nw 16.82 22.64 0 0 0 0 Impact,Clear Lowe 0.580 nw 16.82 22.64 0 0 0 0 Impact,Clear Lowe 0.650 nw 18.85 22.04 0 0 0 0 P Frm Wall,1/2"Gyp B 0.101 2.94 1.461 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 1.80 222 222 220 401 F On Grade Depth,Tile 0.989 28.68 0.00 222 32 915 0 6 c)AED excursion -4 Envelope loss/gain 2224 1247 12 a) Infiltration 596 167 b) Room ventilation 0 0 13 Internal gains: Occupants@ 230 0 0 Appliances/other 600 Subtotal(lines 6 to 13) 2820 2014 Less extemalload 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 2820 2014 15 Dudloads 34% 41% 959 819 Total room load 3779 2833 Air required(cfm) 189 145 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. �� rigF�tsoft° 2021-Nov-1515:46:51 Right-Srite@ Uriversal202l 2l.O.10 RSU29066 Page 8 nts\W ri htsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Front Door faces:N Duct System Summary Job: 1621 +� wrightsoft D S S Date: 9/20/2021 House By: Chris Bateman Air CaICS, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project Information For: Key Largo Spec,NisAirAir Conditioning 6006 Spruce Dr,Fort Pierce,FL 34982 Heating Cooling External static pressure 0.70 in H2O 0.70 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 0.70 in H2O 0.70 in H2O Supply/return available pressure 0.494/0.206 in H2O 0.494/0.206 in H2O Lowest friction rate 0.276 in/100ft 0.276 in/100ft Actual airflow 1283 cfm 1283 cfm Total effective length(TEL) 254 ft SupplyDetail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FIR (in) (in) Matl Ln(ft) Ln(ft) Trunk Bat, c 107 4 7 0.456 4.0 Ox0 VIFx 13.1 95.0 st1 Bath h 773 46 33 0.340 4.0 Ox0 VIFx 25.2 120.0 st3 Bed 2 h 2421 145 108 0.460 6.0 Ox 0 VI Fx 12.3 95.0 st1 Bed 3 h 3225 194 159 0.331 7.0 Ox 0 VI Fx 29.1 120.0 st3 Bed 4 h 2507 151 118 0.342 7.0 Ox 0 VI Fx 24.2 120.0 st3 FoyerGR c 3133 158 192 0.372 7.0 Ox0 VIFx 32.8 100.0 st2 Foyer GR-A c 3133 158 192 0.372 7.0 Ox0 VI Fx 32.9 100.0 st2 Hers h 409 25 10 0.276 4.0 Ox 0 VI Fx 48.8 130.0 st4 His c 21 1 1 0.292 4.0 Ox0 VI Fx 44.3 125.0 st4 Kitchen DR-A c 3536 140 217 0.372 7.0 Ox 0 VI Fx 32.7 100.0 st2 Kitchen DR-B c 3536 140 217 0.373 7.0 Ox 0 VI Fx 32.4 100.0 st2 Laundry c 842 26 52 0.457 4.0 Ox0 VI Fx 13.1 95.0 st1 Master Bath h 2084 125 60 0.281 6.0 Ox 0 VI Fx 50.7 125.0 st4 Master Bed h 1889 114 87 0.285 6.0 Ox 0 VI Fx 48.5 125.0 st4 Master Bed-A h 1889 114 87 0.292 6.0 Ox 0 VI Fx 44.1 125.0 st4 SupplyTrunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st4 PeakAVF 378 245 0.276 855 9.0 0 x 0 VinlFlx st2 st3 PeakAVF 391 310 0.331 885 9.0 0 x 0 VinlFlx st1 st1 PeakAVF 566 476 0.331 720 12.0 0 x 0 VinlFlx st2 PeakAVF 974 1064 0.276 762 16.0 0 x 0 VinlFlx wrightsoft® 2021-Nov-1515:46:52 A= A MIT-Io-•1 �-1,.-y1.m �, Right-Suite®Universal 2021 21.0.10 RSU29066 Page 1 ACCA ...ntsmrightsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Front Door faces:N TableReturn Branch Detail Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size(in) (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening(in) Matl Trunk rb5 Ox0 151 118 74.8 0.276 564 7.0 Ox 0 VIFx rt1 rb6 Ox0 194 159 66.5 0.310 555 8.0 Ox 0 VIFx rt1 rb7 Ox0 145 108 62.4 0.331 544 7.0 Ox 0 VIFx rt1 rb1 Ox0 798 970 62.7 0.329 549 18.0 Ox 0 VIFx rt1 rb8 Ox0 252 185 0 0 0 0 Ox 0 VIFx TableReturn Trunk Detail Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk rt1 PeakAVF 1288 1355 0.276 767 1&0 0 x 0 VInIFIX Bolditalic values have been manually overridden wrightsoft® 2021-Nov-1515:46:52 M;=ek ", _ -.=mP=. Right-Site®Uriversal 2021 21.0.10 RSU29066 Page 2 ACCA ...rts\W rightsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Front Door faces:N Manual S ComplianceReport Job: 1621 +� wrightsoft° Date: 9/20/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project Information For: Key Largo Spec,NisAirAir Conditioning 6006 Spruce Dr,Fort Pierce,FL 34982 Cooling Equipment Design Conditions Outdoor design DB: 90.4°F Sensible gain: 26017 Btuh Entering coil DB: 76.7°F Outdoor design WB: 77.4°F Latent gain: 7383 Btuh Entering coil WB: 63.9°F Indoor design DB: 75.0°F Total gain: 33400 Btuh Indoor RH: 50% Estimated airflow: 1283 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitAC Manufacturer: Lennox Model: ML14XC1-041-230A**+CBA27UHE-048-230*++TDR Actual airflow: 1283 cfm Sensible capacity: 26950 Btuh 104%of load Latent capacity: 11550 Btuh 156%of load Total capacity: 38500 Btuh 115%of load SHR: 70% Heating Equipment Design Conditions Outdoor design DB: 41.0°F Heat loss: 27403 Btuh Entering coil DB: 68.3°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Elecstrip Manufacturer: Model: Actual airflow: 1283 cfm Output capacity: 7.9 kW 98%of load Temp.rise: 50 °F Meets all requirements ofACCA Manual S. wrightsoft, 2021-Nov-15 15:46:52 A II,-=Io-•", _ -.=—— Right-Sute®Universa12021 21.0.10 RSU29066 Page 1 ACCA nts\W rightsoft HVAC\6006 Spruce Dr PSL Prop.rup Calc=MJ8 Front Door faces:N