HomeMy WebLinkAboutFIRE ALARM CONTROL PANEL SPECIFICATIONPFC-4064 Conventional Fire Alarm Control Panel 8830139 - REV E • 9/19 page 1 OF 5 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com Features • 6 programmable Initiating Device Circuits • System is expandable to 192 input circuits using the IDC-6 expansion module • 5.0 amp power Supply • 4 Notification Circuit rated at 3.0 Amps • Strobe Synchronization for gentex, aMSeCO, System Sensor and Cooper/Wheelock • One programmable auxiliary output rated at 1.0 a • 4 x 20 LCD display with system LeDs for clear system status • P-Link RS-485 bus supports 31 system accessories • Built-in ethernet Connection with listed Ip Communicator • Ability to E-mail system status, reports and system configuration • Service Reminder e-mails Dimensions 18 1/2” H x 14 1/4 W x 4 3/4” D enclosure 18 gauge cold rolled steel with removable locked door with Lexan viewing window aC Mains 5.0 amp @ 120 VaC 60 Hz 2.0 amp @ 240 VaC 50 Hz Battery 70 ma Standby 235 mA Alarm Temperature and Humidity Range 32° to 120° (0°C to 49°C) with a maximum humidity of 93% non-condensing. Standards NFpa 70, 72 Description The pFC-4064 Conventional Fire panel is a compact, expandable panel designed to monitor all facets of a fire alarm system and communicate the status to a monitoring station. The pFC-4064 panel is a listed and approved microprocessor based conventional fire panel and complies with UL-864, NFpa-70, and NFpa-72. The panel is provided with six (6) inputs and four (4) 24VDC, 3.0 Amp Notification Appliance Circuits (NAC) with strobe synchronization. The 5.0 Amp power supply provides ample power to meet any jurisdictions requirements and will charge up to two (2) 55 amp/hour batteries. In addition, the panel has the potter p-Link for connection to system accessories. The panel also has a 1.0 amp auxiliary power output for controlling ancillary fire alarm functions. The control panel is in a metal cabinet with a key lock and lexan window for viewing the system status. The printed circuit assembly is mounted for quick removal and installation to allow the cabinet to be installed with minimal effort. The cabinet houses up to two (2) 7 AH or two (2) 12 AH batteries. The display is an eighty (80) character LCD with system status LEDs. The system status is clearly displayed and the panel includes a history buffer for past events. The key pad allows navigation into the system menu, limited programming and system control. The condition and events on the panel are clearly displayed to allow the user and installer to determine the system status. The panel will support up to thirty-one (31) system accessories. Technical Specifications LISTED 8830139 - REV E • 9/19 page 2 OF 5 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com PFC-4064 Conventional Fire Alarm Control Panel 2-Wire Smoke Detector Compatibility Detector Model Identifier Base Model Identifier SYSTEM SENSOR (Brk) (Max. No. Of Detectors Per Zone Is 20) 1400 a N/a N/a 2400 a N/a N/a 2400TH a N/a N/a 2W-B a N/a N/a 2WT-B a N/a N/a DETECTION SYSTEM (Max. No. Of Detectors Per Zone Is 25) DS250 a MB2W/MB2WL a DS250TH a MB2W/MB2WL a ESL (Max. No. Of Detectors Per Zone Is 25) 611U S10 601U S00 611UD S10 601U S00 611UT S10 601U S00 612U S10 601U S00 612UD S10 601U S00 613U5 S10 601U S00 611UD S10 609U10 S00 612UD S10 609U10 S00 425C S10 N/a N/a 425CT S10 N/a N/a HOCHIKI (Max. No. Of Detectors Per Zone Is 25) SLR-24 HD-3 HSC-221R HB-71 HSB-221 HB-54 HSB-221N HB-54 NS6-221 NS4-221 NS6-220 HB-3 SLR-24H HD-3 HSC-221R HB-71 HSB-221 HB-54 HSB-221N HB-54 NS6-221 NS4-221 SIJ-24 HD-3 HSC-221R HB-71 HSB-221 HB-54 HSB-221N HB-54 NS6-221 NS4-221 8830139 - REV E • 9/19 PAgE 3 OF 5 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com PFC-4064 Conventional Fire Alarm Control Panel Detector Model Identifier Base Model Identifier FENWAL (Max. No. Of Detectors Per Zone Is 25) CpD-7051 I51Fe1 2-WIRe Fe51a pSD-7155 p55Fe1 2WRLT Fe52a pSD-7156 p56Fe1 2WRB Fe55a all of the above Fenwal detectors and bases can be used in any combination. Retrofit Base Adaptor 70-501000-003, Identifier MAFE1 (for series 70-201000 Bases, Models -001, -002, -003, and -005). Duct Housing with Detector Base DH-51, Identifier DH22FE5 (for CPD-7051 and PSD-7155 detectors only). POTTER (Max. No. Of Detectors Per Zone Is 25) CpS-24 HD-3 (HOCHIKI)SB-46 HB-4 (HOCHIKI) SB-93 HB-3 (HOCHIKI) pS-24H HD-3 (HOCHIKI)SB-46 HB-71 (HOCHIKI) HB-54 (HOCHIKI) IS-24 HD-3 (HOCHIKI)SB-46 HB-71 (HOCHIKI) HB-54 (HOCHIKI) NOTE: If using a mix of System Sensor and other smoke detectors, a maximum of 20 detectors shall be permitted. 8830139 - REV E • 9/19 page 4 OF 5 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com PFC-4064 Conventional Fire Alarm Control Panel User Interface Ethernet/I.P. Connection P-Link The pFC-4064 is shipped standard with an ethernet connection. This connection is the programming port and may be connected to a building Wide Area Network (WAN) or Local Area Network (LAN). Once connected to the Internet, the panel may be selectively programmed to e-mail alarm conditions, trouble conditions, supervisory conditions, test, event History and detector status. an e-mail may be sent to the panel and the panel will e-mail the event history, detector status, configuration file or server status to an authorized e-mail account. In addition, reminders may be set to send an e-mail for service, testing or other conditions. In addition, the ethernet connection is UL listed as an Ip communicator. The Ip communicator is listed to report to the UL listed Sur-gard III Ip receiver. The Ip communicator replaces the traditional less reliable alarm communicator transmitter that utilized telephone lines. The Ip communicator is an active method of connection and communication to the monitoring station. The pFC-4064 has a proprietary communication protocol that communicates through a RS-485 connection to field devices. Up to 31 devices may be connected to a single P-Link connection. The p-Link includes the communication terminals and regulated 24 VDC connection for the field devices. The field devices may be any of the following: IDC-6 – Initiating device circuit expander, provides an additional six (6) inputs. RA-6075R – 2 x 16 LCD annunciator with a key pad in a locked metal enclosure. RA-6500R(F) – 4 x 40 LCD annunciator with a key pad in a locked metal enclosure. Flush mount version available. LED-16(F) – 16 LeD annunciator with common indicators in a locked metal enclosure. Flush mount version available. PSN-1000(E) – 10 amp, remote intelligent power supply with 6 NaCs, 2 Inputs and a p-Link repeater. CA-4064 – Class a convertor that converts the NaCs and p-Link connection. UD-2000 – UL listed, Dual line telephone alarm communicator. DRV-50 – LeD driver expander, used to connect up to 50 LeDs in a graphic display . FCB-1000 – Fire communication bridge, provides remote mounting of the ethernet connection. FIB-1000 – Fiber interface module, used to extend p-Link to multi- mode fiber (2 required). RLY-5 – Relay module, provides 5 form C relay contacts rated at 3.0 amps 24VDC/125aC. SPG-1000 – Serial parallel gateway, allows for the connection to a serial or parallel printer. The fire alarm control panel has a 4 x 20 LCD display to provide information to the system status. The keypad has navigation keys to allow manipulation of the Menu on board the panel. The panel is shipped standard with the following LeDs: • aC power - green • alarm - Red • earth Fault - amber • Supervisory - amber • Silenced - amber • Trouble - amber The common buttons include a Silence, Reset, acknowledge, and Drill. all of the buttons are accessible once the locked door is opened. The FIB-1000, FCB-1000 and the SPG-1000 may be installed in the stacker bracket or ordered with the optional rack mount enclosure. MC-1000 Multi-Connect allows up to sixty-three panels to share a single reporting technology. AE-2 – Two card expansion cabinet. AE-8 – eight card expansion cabinet. AE-14 – Fourteen card expansion cabinet. 8830139 - REV E • 9/19 page 5 OF 5 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com PFC-4064 Conventional Fire Alarm Control Panel BOTTOM LEFT SIDE TOP 18.60"18.10"DEPTH 4.63" 3.95" 14.48" 14.78" RIGHT SIDE Dimensions Ordering Information Model Description Stock No. pFC-4064 Fire alarm Control panel 3992360 Replacement Board 3992363 8830146 - REV B • 6/19 page 1 OF 3 Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com UD-2000 Digital Alarm Communicator Description The UD-2000 Digital alarm Communicator Transmitter (DaCT) provides for up to two (2) phone lines for communication to a monitoring station. The UD-2000 communicates using the SIa- DCS or ademco Contact ID protocols. When enabled, the DaCT automatically monitors each phone line or voltage and has the ability to seize the line and connect with a remote receiver. Once the communication is complete, the DaCT will hang up. The DaCT is provided with terminal blocks for each phone line and two RJ45 cords. In order for the DaCT to work properly, it must be installed on a plain old telephone service (pOTS) line or equivalent deemed by the authority having jurisdiction. The DaCT must be installed before any other equipment to ensure it can seize the phone line. phone lines are high voltage and should be run in a separate conduit from other circuits. The wire conductors connecting the DaCT to the phone system should be 26 aWg or larger. Technical Specifications Operating Voltage 22.0-24.0V Standby Current 16ma alarm Current 23ma Max UD-2000s per panel 1 Dimensions 4”W * 6”H * 1-5/8”D Operating Tempuratures 0°C - 49°C (32°F- 120°F) Operating Humidity Range 10% - 93% @ 30°C (86°F) (non-condensing) Mounting Options In FaCp Behind keypad Shipping Weight 0.47 lbs Features • allows for communication to Monitoring Station • Communicates using SIa-DCS or ademco Contact ID protocols • For use with Ipa, aFC, and aRC series addressable panels and pFC-4064 Conventional panel • Status LeDs indicate operation of DaCT card • Installs with ease behind main panel LCD display via User Interface bracket • Device address is set internally to address 1 • Includes two (2) RJ45 phone cords 8830146 - REV B • 6/19 page 2 OF 3 Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com UD-2000 Digital Alarm Communicator Installation Install in accordance with compatible fire alarm control panel installation manual The UD-2000 DaCT is connected to the control panel using the provided four-wire cable connection (p/N 5210514) between p4 and UD-2000 p1. The connection is power limited and supervised. 1. power system down. 2. Slide the UD-2000 into the card guides located under the User Interface bracket. 3. Secure the UD-2000 to the User Interface bracket using the provided #6-32x3/8” screw 4. Install the provided four-wire conductor jumper between UD-2000 p1 and p4. 1 2 3 4 5 6 7 8 1 - Grey 2 - Ta n 3 - Black 4 - Red 5 - Green 6 - Ye llow 7 - Blue 8 - Brown 1 2 3 4 5 6 7 8 Plain Old Te lephone (POTS) lines RJ31X Phone Jack to UD-2000 Ring (Grey) Line In From Te lco UD-2000 Communicator Tip (Brown)Out to Premises Phones Ring (Red) Tip (Green) Ring (Grey) Tip (Brown)Out to Premises Phones Ring (Red) Tip (Green) Line In From Te lco Te lco 2 TipRingTip Ring TipRingTip Ring Phone 2Telco 1 Phone 1 Te lco Ti p = Red Te lco Ring = Green Phone Tip = Brown Phone Ring = Grey 8830146 - REV B • 6/19 page 3 OF 3 Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com UD-2000 Digital Alarm Communicator UD-2000 DACT Installation on Small Platform Panel UD-2000 DACT Installation on Large Platform Panel Slides in guides under main board. Screw DWG #593-32A Slides in guides under main board. Screw DWG #593-32A DETAIL E SCALE 1 : 1 DETAIL D SCALE 1 : 1 p Connector on small platform control panel p Connector on main board DETAIL B SCALE 1 : 1 Fig 1 Fig 2 Ordering Information Model Description Stock No. UD-2000 Digital Alarm Communicator 3992769 Agency Listings Photoelectric Smoke Detectors System Sensor i3™ series smoke detectors represent significant advancement in conventional detection. The i3 family is founded on three principles: installation ease, intelligence, and instant inspection. Features Plug-in detector line, mounting base included• Large wire entry port• In-line terminals with SEMS screws• Mounts to octagonal and single-gang back boxes, 4-square back • boxes, or direct to ceiling Stop-Drop ’N Lock attachment to base• Removable detector cover and chamber• Built-in remote maintenance signaling• Drift compensation and smoothing algorithms• Simplified sensitivity measurement • Wide-angle, dual-color LED indication• Loop testing via EZ Walk feature• Built-in test switch• Installation ease. The i3 line redefines installation ease with its plug-in design. This allows an installer to pre-wire bases (included with heads). The large wire entry port and in-line terminals provide ample room for neatly routing the wiring inside the base. The base accommodates a variety of back box mounting methods as well as direct mounting with drywall anchors. To complete the installation, i3 heads plug into the base with a simple Stop-Drop ’N Lock™ action. Intelligence. i3 detectors offer a number of intelligent features to simplify testing and maintenance. Drift compensation and smoothing algorithms are standard with the i3 line to minimize nuisance alarms. 2-wire i3 detectors can generate a remote LED- indicated maintenance signal when connected to the 2W-MOD2 loop test/maintenance module or a panel equipped with the i3 protocol. The SENS-RDR, a wireless device, displays the sensitivityof i3 detectors in terms of percent-per-foot obscuration. Instant inspection. The i3 series provides wide-angle red and green LED indicators for instant inspection of the detector’s condition: normal standby, out-of-sensitivity, alarm, or freeze trouble. When connected to the 2W-MOD2 loop test/maintenance module or a panel with the i3 protocol, the EZ Walk loop test feature is available on 2-wire i3 detectors. This feature verifies the initiating loop wiring by providing LED status indication at each detector. 2093290-01-E7272-1653:1523011446S911 3180932 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2009 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. A05-0318-007 • 6/09 • #2169 Ordering Information Model Thermal Wiring Alarm Current 2W-B No 2-wire 130 mA max. limited by control panel 2WT-B Yes 2-wire 130 mA max. limited by control panel 4W-B No 4-wire 20 mA @ 12 V, 23 mA @ 24 V 4WT-B Yes 4-wire 20 mA @ 12 V, 23 mA @ 24 V Accessories 2W-MOD2 2-wire loop test / maintenance module RT Removal / replacement tool SENS-RDR Sensitivity reader A77-AB2 Retrofit adapter bracket, 6.6 inch (16.76 cm) diameter Smoke Detector Specifications Architectural/Engineering Specifications Smoke detector shall be a System Sensor i3 Series model number_______, listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems. The detector shall be a photoelectric type (Model 2W-B, 4W-B) or a combination photoelectric/thermal (Model 2WT-B, 4WT-B) with thermal sensor rated at 135°F (57.2°C). The detector shall include a mounting base for mounting to 3½-inch and 4-inch octagonal, single-gang, and 4-inch square back boxes with a plaster ring, or direct mount to the ceiling using drywall anchors. Wiring connections shall be made by means of SEMS screws. The detector shall allow pre-wiring of the base and the head shall be a plug-in type. The detector shall have a nominal sensitivity of 2.5 percent-per-foot nominal as measured in the UL smoke box. The detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms. The detector shall provide dual- color LED indication that blinks to indicate power up, normal standby, out of sensitivity, alarm, and freeze trouble (Model 2WT-B, 4WT-B) conditions. When used in conjunction with the 2W-MOD2 module, 2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel and shall provide a loop testing capability to verify the circuit without testing each detector individually. Electrical Specifications Operating Voltage Nominal: 12/24 V non-polarized Minimum: 8.5 V Maximum: 35 V Maximum Ripple Voltage 30% peak to peak of applied voltage Standby Current 2-wire: 50 µA maximum average; 4-wire: 50 µA maximum average Maximum Alarm Current 2-wire: 130 mA limited by control panel; 4-wire: 20 mA @12 V, 23 mA @ 24 V Peak Standby Current 2-wire: 100 µA; 4-wire: n/a Alarm Contact Ratings 2-wire: n/a; 4-wire: 0.5 A @ 30 V AC/DC Physical Specifications Dimensions (including base)5.3 inches (127 mm) diameter; 2.0 inches (51 mm) height Weight 6.3 oz (178 g) Operating Temperature Range 2W-B and 4W-B: 32°F to 120°F (0°C to 49°C); 2WT-B and 4WT-B: 32°F to 100°F (0°C to 37.8°C) Operating Humidity Range 0 to 95% RH non-condensing Thermal Sensor 135°F (57.2°C) fixed Freeze Trouble 2WT-B and 4WT-B only: 41°F (5°C) Sensitivity 2.5%/ft nominal Input Terminals 14 to 22 AWG Mounting 3½-inch octagonal back box 4-inch octagonal back box Single-gang back box 4-inch square back box with a plaster ring Direct mount to ceiling LED Modes Power-Up Sequence for LED Indication LED Mode Green LED Red LED Condition Duration Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds Normal (standby)Blink every 5 seconds off Out of sensitivity off Blink every 5 seconds Freeze trouble off Blink every 10 seconds Alarm off Solid Agency Listings 7125-1653:0504 7135-1653:0503 S5512 S4011 FM approved except for ALERT models 3057383, 3057072 AVDS865-05 • 2/22/2018 • Page 1 Features • Updated Modern Aesthetics • Small profile devices for Horns and Horn Strobes • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Automatic selection of 12- or 24-volt operation at 15 and 30 candela • Field-selectable candela settings on wall units: 15, 30, 75, 95, 110, 135, and 185 • Horn rated at 88+ dBA at 16 volts • Rotary switch for horn tone and two volume selections • Mounting plate for all standard and all compact wall units • Mounting plate shorting spring checks wiring continuity before device installation • Electrically compatible with legacy SpectrAlert and SpectrAlert Advance devices • Compatible with MDL3 sync module • Strobes and Horn Strobes listed for wall mounting only • Horns listed for wall or ceiling use The System Sensor L-Series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry with lower current draws and modern aesthetics. With white and red plastic housings, standard and compact devices, and plain, FIRE, and FUEGO-printed devices, System Sensor L-Series can meet virtually any application requirement. The L-Series line of wall-mount horns, strobes, and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. To further simplify installation and protect devices from construction damage, the L-Series utilizes a universal mounting plate for all models with an onboard shorting spring, so installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections. Indoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications System Sensor L-Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. AVDS865-05 • 2/22/2018 • Page 2 L-Series Specifications Architect/Engineer Specifications General L-Series standard horns, strobes, and horn strobes shall mount to a standard 2 x 4 x 17/8-inch back box, 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-gang back box. L-Series compact products shall mount to a single-gang 2 × 4 × 17⁄8 -inch back box. A universal mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, and 185. Strobe The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize Strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 411/16 × 411/16 × 21/8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens)5.6˝ L × 4.7˝ W × 1.91˝ D (143 mm L × 119 mm W × 49 mm D) Compact Wall-Mount Dimensions (including lens)5.26” L x 3.46” W x 1.91” D (133 mm L x 88 mm W x 49 mm D) Horn Dimensions 5.6˝ L × 4.7˝ W × 1.25˝ D (143 mm L × 119 mm W × 32 mm D) Compact Horn Dimensions 5.25” L x 3.45” W x 1.25” D (133 mm L x 88 mm W x 32 mm D) 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. Strobe products will operate at 12 V nominal only for 15 cd and 30 cd. AVDS865-05 • 2/22/2018 • Page 3 Horn and Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 9*Coded High 85 90 90 10*3.1 KHz Coded High 84 89 89 * Settings 9 and 10 are not available on 2-wire horn strobes. Temporal coding must be provided by the NAC. If the NAC voltage is held constant, the horn output remains constantly on. UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC DC FWR Candela Range 15 88 43 60 30 143 63 83 75 N/A 107 136 95 N/A 121 155 110 N/A 148 179 135 N/A 172 209 185 N/A 222 257 UL Max. Current Draw (mA RMS), Wall Horn Strobe, Candela Range (15–185 cd) DC Input 8–17.5 Volts 16–33 Volts 15cd 30cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd Temporal High 98 158 54 74 121 142 162 196 245 Temporal Low 93 154 44 65 111 133 157 184 235 Non-Temporal High 106 166 73 94 139 160 182 211 262 Non-Temportal Low 93 156 51 71 119 139 162 190 239 3.1K Temporal High 93 156 53 73 119 140 164 190 242 3.1K Temporal Low 91 154 45 66 112 133 160 185 235 3.1K Non-Temporal High 99 162 69 90 135 157 175 208 261 3.1K Non-Temporal Low 93 156 52 72 119 138 162 192 242 FWR Input 16–33 Volts 15cd 30cd 75cd 95cd 110cd 135cd 185cd Temporal High 83 107 156 177 198 234 287 Temporal Low 68 91 145 165 185 223 271 Non-Temporal High 111 135 185 207 230 264 316 Non-Temportal Low 79 104 157 175 197 235 283 3.1K Temporal High 81 105 155 177 196 234 284 3.1K Temporal Low 68 90 145 166 186 222 276 3.1K Non-Temporal High 104 131 177 204 230 264 326 3.1K Non-Temporal Low 77 102 156 177 199 234 291 UL Max. Horn Current Draw (mA RMS) Sound Pattern dB 8–17.5 Volts 16–33 Volts DC DC FWR Temporal High 39 44 54 Temporal Low 28 32 54 Non-Temporal High 43 47 54 Non-Temporal Low 29 32 54 3.1 KHz Temporal High 39 41 54 3.1 KHz Temporal Low 29 32 54 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 UL Current Draw Data Horn Tones and Sound Output Data 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 www.systemsensor.com ©2018 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS865-05 • 2/22/2018 L-Series Dimensions Model Description Wall Horn Strobes P2RL 2-Wire, Horn Strobe, Red P2WL 2-Wire, Horn Strobe, White P2GRL 2-Wire, Compact Horn Strobe, Red P2GWL 2-Wire, Comp 2 fils act Horn Strobe, White P2RL-P 2-Wire, Horn Strobe, Red, Plain P2WL-P 2-Wire, Horn Strobe, White, Plain P2RL-SP 2-Wire, Horn Strobe, Red, FUEGO P2WL-SP 2-Wire, Horn Strobe, White, FUEGO P4RL 4-Wire, Horn Strobe, Red P4WL 4-Wire, Horn Strobe, White Wall Strobes SRL Strobe, Red SWL Strobe, White SGRL Compact Strobe, Red SGWL Compact Strobe, White SRL-P Strobe, Red, Plain SWL-P Strobe, White, Plain SRL-SP Strobe, Red, FUEGO SWL-CLR-ALERT Strobe, White, ALERT L-Series Ordering Information Notes: All -P models have a plain housing (no “FIRE” marking on cover). All -SP models have “FUEGO” marking on cover. All -ALERT models have “ALERT” marking on cover. *Horn-only models are listed for wall or ceiling use. Model Description Horns* HRL*Horn, Red HWL*Horn, White HGRL*Compact Horn, Red HGWL*Compact Horn, White Accessories TR-2 Universal Wall Trim Ring Red TR-2W Universal Wall Trim Ring White SBBRL Wall Surface Mount Back Box, Red SBBWL Wall Surface Mount Back Box, White SBBGRL Compact Wall Surface Mount Back Box, Red SBBGWL Compact Wall Surface Mount Back Box, White 4.70" (11.94 cm)1.91" (4.85 cm) 1.25" (3.18 mm) 5.67" (14.4 cm) A0549-00A0550-00 Compact Strobe, Horn Strobe Compact Horn Strobe, Horn Strobe Horn A0548-00 A0547-00 4.7" 119 mm 5.67" 144 mm 1.25" 32 mm 3.46" 88 mm 1.91" 48.5 mm 1.25" 32 mm 5.27" 133.9 mm 3.46" 88 mm 1.25" 32 mm 5.27" 133.9 mm Wall Surface Mount Back Box SBBRL/SBBWL A0554-01 4.82" (12.24 cm)1.85" (4.69 cm) 5.78" (14.68 cm) A0557-00 1.55" (3.9 cm) 3.57" (9.1 cm) 5.38" (13.7 cm) Compact Wall Surface Mount Back Box SBBGRL, SBBGWL • UL and cUL Listed, FM Approved, CSFM Listed, MEA Approved, ADA Compliant • Single or Dual Action • Terminal connectors • 10 Amp Snap Action Switch • Gold plated SPST contacts • Optional auxiliary contacts • Mounts on standard single gangbox • Surface backboxes available • High-gloss red enamel finish • Glass breakrod • Made in the U.S.A. Potter Electric Signal Co., LLC • St. Louis, MO • Cust Service: 866-240-1870 • Tech Support:866-956-1211• Canada 888-882-1833 • www.pottersignal.com PAGE 1 OF 1 PULL STATION SERIES DIE-CAST METAL MANUAL PULL STATIONS PRINTED IN USA MKT. #8900097 - REV L 9/10 Description The Potter Pull Station Series offers a complete line of die-cast pull stations for a variety of applications focusing mainly on fire alarm systems. The pull stations are available in single or dual action models. All of the pull stations have a 10-amp snap action switch and a dedicated terminal block for the ease of wire connections. All of the metal is completely coated to inhibit corrosion and provide for a uniform and quality finish. The standard models have a hex key reset, however a key reset is also available. The models are available with shallow and deep surface mount back boxes and as a weatherproof version. Operation The Potter single action series of pull stations operate by pulling the white operating handle straight down and the handle will lock into place. The dual action stations require the lifting of the front cover and then pulling the white operating handle straight down. The stations are reset by opening the front and placing the handle in the normal position. Ordering Information Type Model Number Stock Number Contact Type Single Action P32-1T 1000447 SPST RMS-2T 1000477 DPST RMS-6T 1000478 DPDT RMS-1T-KL 1000451 SPST RMS-1T-KO 1000450 SPST, key operated, no pull Weather Proof RMS-1T-WP 1000401 SPSTDual Action P32-1T-LP 1000476 Weather Proof Dual Action RMS-1T-WP-LP 1000403 Accessories Notes Dual Action RMS-LP 1000480 Converts single action to dual action Back Box P32-BB 1000444 Surface mount back box Back Box P32-DBB 1000445 Deep surface mount back box Glass Rods RMS-GB 1000470 Replacement glass rods (10 per pkg) Engineering Specifications The contractor shall furnish and install the Potter series of pull stations as indicated. The pull station shall be die cast construction with a "T" type pull handle that is ADA compliant. Single action pull stations shall be a P32-1T. Dual action pull stations shall be the Potter P32-1T-LP. Any manual pull station installed in an outdoor or wet location shall be a RMS-1T-WP weather proof unit. The contact shall be a single pole, single throw switch rated at 1 amp 30V DC/125V AC. The device shall have a terminal block for ease of wiring. Once activated, the pull station shall be reset by opening the front cover. Opening of the cover in a normal state shall initiate an alarm. Specifications Switch Rating: 1 Amp @ 30 VDC 10 Amps @ 125 VAC Pull Station Dimensions: 4-3/4" H x 3-1/4" W x 7/8" D Color: Red with raised white letters, white pull bar with raised red letters For special application manual stations see bulletin #8910014. For explosion proof manual stations see bulletin #8880014. DITEK Surge Protection, Largo, FL 33771 ♦ Sales: 800-753-2345 ♦ www.diteksurgeprotection.com ♦ SPS-100057-001 Rev 18 01/22 Every precaution has been taken to ensure that this literature is accurate and complete. DITEK Corporation assumes no responsibility and disclaims all liability for damages resulting from the use of this information or for any errors or omissions. Technical Specifications Part Number: DTK-120HW DTK-240HW DTK-120/240HW Voltage Configuration: Single Ф (2W +G) 120VAC Single Ф (2W +G) 240VAC Split Ф (3W +G) 120/240VAC MCOV: 150V/300V 320V/640V 150V/300V Voltage Protection Rating: 700V L-G, L-N 1500V N-G 1200V L-G, L-N 2000V N-G 700V L-G, L-N 1500V L-L, N-G Surge Current Rating: 50,000A 50,000A 100,000A SCCR: 100,000A Nominal Discharge Current Rating (In): 10kA Mechanical Specifications Connection Method: ¾” NPT Male, 18-inch 12 AWG Leads Housing: NEMA 4X Polycarbonate Operating Temperature: -31°F - 176°F (-35°C - 80°C) Maximum Humidity: 95% non-condensing Dimensions: 3.5” L x 1.89” W x 3.4” H (88.9 mm x 48.3 mm x 86.4 mm) Weight: 0.55 lb (0.25 kg) Quality Standards & Approvals Certifications: UL1449 4th Edition, CSA C22.2 No. 269.1-17 SPD Type: Type 1 Warranty: 10 Year Limited Warranty Product Features  Approved for 20A circuit breakers  NEMA 4X weatherproof enclosure allows for use in harsh environments  Diagnostic LED provides positive indication of system power and SPD function  Complies with ANSI/IEEE C62.41 and C62.45 Category B standards Applications  Fire Alarm Control Panels  Residential Electrical Panels  Equipment Panels  Pumps, Motors, Lift Pump Stations Accessories  Flush Mount Kit – DTK-FMK DITEK’s DTK-HW Series of surge protective devices are designed and manufactured to meet the standards of the life safety industry. These compact, parallel-mount SPD’s are available for 120V, 240V and 120/240V systems; and are widely used to protect fire alarm panels and other dedicated branch circuit loads. Their small footprint enables installation in a variety of locations. ELOCK-FA CIRCUIT LOCKOUT KIT • Circuit lockout tab • Hex key • Breaker, legend, and door labels NFPA 2016 CODE COMPLIANCE •• 10.6.5.2 Circuit Identification and Accessibility. • 10.6.5.2.1 The location of the branch circuit disconnecting means shall be permanently identified at the control unit. • 10.6.5.2.2 System circuit disconnecting means shall be permanently identified as to its purpose in accordance with the following: (1) “FIRE ALARM” for fire alarm systems (2) “EMERGENCY COMMUNIC (2) “EMERGENCY COMMUNICATIONS” for emergency communications systems (3) “FIRE ALARM/ECS” for combination fire alarm and emergency communications systems • 10.6.5.2.3 For fire alarm and/or signaling systems, the circuit disconnecting means shall have a red marking. • 10.6.5.2.4 The red marking shall not damage the overcurrent p protective devices or obscure the manufacturer’s markings. • 10.6.5.2.5 The circuit disconnecting means shall be accessible only to authorized personnel. • 10.6.5.3 Mechanical Protection. The branch circuit(s) and connections shall be protected against physical damage. • 10.6.5.4 Circuit Breaker Lock. Where a circuit breaker is the disconnecting means, a listed breaker locking device shall be installed. installed. www.1sae.com | toll free 1.800.486.1723 | fax 508.485.4740 © Copyright 2019 Space Age Electronics, Inc. | This document is subject to change without notice | SS10101 | Rev. 2