Conventional Fire Alarm Control Panel
8830139 - REV E • 9/19 page 1 OF 5
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
Features
• 6 programmable Initiating Device Circuits
• System is expandable to 192 input circuits using the IDC-6
expansion module
• 5.0 amp power Supply
• 4 Notification Circuit rated at 3.0 Amps
• Strobe Synchronization for gentex, aMSeCO, System Sensor
and Cooper/Wheelock
• One programmable auxiliary output rated at 1.0 a
• 4 x 20 LCD display with system LeDs for clear system status
• P-Link RS-485 bus supports 31 system accessories
• Built-in ethernet Connection with listed Ip Communicator
• Ability to E-mail system status, reports and system configuration
• Service Reminder e-mails
Dimensions 18 1/2” H x 14 1/4 W x 4 3/4” D
enclosure 18 gauge cold rolled steel with removable locked
door with Lexan viewing window
aC Mains 5.0 amp @ 120 VaC 60 Hz
2.0 amp @ 240 VaC 50 Hz
Battery 70 ma Standby
235 mA Alarm
Temperature
and Humidity
Range
32° to 120° (0°C to 49°C) with a maximum
humidity of 93% non-condensing.
Standards NFpa 70, 72
Description
The pFC-4064 Conventional Fire panel is a compact, expandable panel
designed to monitor all facets of a fire alarm system and communicate
the status to a monitoring station. The pFC-4064 panel is a listed and
approved microprocessor based conventional fire panel and complies
with UL-864, NFpa-70, and NFpa-72. The panel is provided with
six (6) inputs and four (4) 24VDC, 3.0 Amp Notification Appliance
Circuits (NAC) with strobe synchronization. The 5.0 Amp power
supply provides ample power to meet any jurisdictions requirements
and will charge up to two (2) 55 amp/hour batteries. In addition, the
panel has the potter p-Link for connection to system accessories.
The panel also has a 1.0 amp auxiliary power output for controlling
ancillary fire alarm functions.
The control panel is in a metal cabinet with a key lock and lexan
window for viewing the system status. The printed circuit assembly is
mounted for quick removal and installation to allow the cabinet to be
installed with minimal effort. The cabinet houses up to two (2) 7 AH or
two (2) 12 AH batteries.
The display is an eighty (80) character LCD with system status LEDs.
The system status is clearly displayed and the panel includes a history
buffer for past events. The key pad allows navigation into the system
menu, limited programming and system control. The condition and
events on the panel are clearly displayed to allow the user and installer
to determine the system status.
The panel will support up to thirty-one (31) system accessories.
Technical Specifications
LISTED
8830139 - REV E • 9/19 page 2 OF 5
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PFC-4064
Conventional Fire Alarm Control Panel
2-Wire Smoke Detector Compatibility
Detector Model Identifier Base Model Identifier
SYSTEM SENSOR (Brk) (Max. No. Of Detectors Per Zone Is 20)
1400 a N/a N/a
2400 a N/a N/a
2400TH a N/a N/a
2W-B a N/a N/a
2WT-B a N/a N/a
DETECTION SYSTEM (Max. No. Of Detectors Per Zone Is 25)
DS250 a MB2W/MB2WL a
DS250TH a MB2W/MB2WL a
ESL (Max. No. Of Detectors Per Zone Is 25)
611U S10 601U S00
611UD S10 601U S00
611UT S10 601U S00
612U S10 601U S00
612UD S10 601U S00
613U5 S10 601U S00
611UD S10 609U10 S00
612UD S10 609U10 S00
425C S10 N/a N/a
425CT S10 N/a N/a
HOCHIKI (Max. No. Of Detectors Per Zone Is 25)
SLR-24 HD-3 HSC-221R HB-71
HSB-221 HB-54
HSB-221N HB-54
NS6-221
NS4-221
NS6-220 HB-3
SLR-24H HD-3 HSC-221R HB-71
HSB-221 HB-54
HSB-221N HB-54
NS6-221
NS4-221
SIJ-24 HD-3 HSC-221R HB-71
HSB-221 HB-54
HSB-221N HB-54
NS6-221
NS4-221
8830139 - REV E • 9/19 PAgE 3 OF 5
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PFC-4064
Conventional Fire Alarm Control Panel
Detector Model Identifier Base Model Identifier
FENWAL (Max. No. Of Detectors Per Zone Is 25)
CpD-7051 I51Fe1 2-WIRe Fe51a
pSD-7155 p55Fe1 2WRLT Fe52a
pSD-7156 p56Fe1 2WRB Fe55a
all of the above Fenwal detectors and bases can be used in any combination.
Retrofit Base Adaptor 70-501000-003, Identifier MAFE1 (for series 70-201000 Bases, Models -001, -002, -003, and -005).
Duct Housing with Detector Base DH-51, Identifier DH22FE5 (for CPD-7051 and PSD-7155 detectors only).
POTTER (Max. No. Of Detectors Per Zone Is 25)
CpS-24 HD-3 (HOCHIKI)SB-46 HB-4 (HOCHIKI)
SB-93 HB-3 (HOCHIKI)
pS-24H HD-3 (HOCHIKI)SB-46 HB-71 (HOCHIKI)
HB-54 (HOCHIKI)
IS-24 HD-3 (HOCHIKI)SB-46 HB-71 (HOCHIKI)
HB-54 (HOCHIKI)
NOTE: If using a mix of System Sensor and other smoke detectors, a maximum of 20 detectors shall be permitted.
8830139 - REV E • 9/19 page 4 OF 5
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PFC-4064
Conventional Fire Alarm Control Panel
User Interface
Ethernet/I.P. Connection
P-Link
The pFC-4064 is shipped standard with an ethernet connection.
This connection is the programming port and may be connected
to a building Wide Area Network (WAN) or Local Area Network
(LAN). Once connected to the Internet, the panel may be selectively
programmed to e-mail alarm conditions, trouble conditions,
supervisory conditions, test, event History and detector status. an
e-mail may be sent to the panel and the panel will e-mail the event
history, detector status, configuration file or server status to an
authorized e-mail account. In addition, reminders may be set to send
an e-mail for service, testing or other conditions.
In addition, the ethernet connection is UL listed as an Ip
communicator. The Ip communicator is listed to report to the UL
listed Sur-gard III Ip receiver. The Ip communicator replaces the
traditional less reliable alarm communicator transmitter that utilized
telephone lines. The Ip communicator is an active method of
connection and communication to the monitoring station.
The pFC-4064 has a proprietary communication protocol that
communicates through a RS-485 connection to field devices. Up
to 31 devices may be connected to a single P-Link connection. The
p-Link includes the communication terminals and regulated 24 VDC
connection for the field devices. The field devices may be any of the
following:
IDC-6 – Initiating device circuit expander, provides an additional six
(6) inputs.
RA-6075R – 2 x 16 LCD annunciator with a key pad in a locked
metal enclosure.
RA-6500R(F) – 4 x 40 LCD annunciator with a key pad in a locked
metal enclosure. Flush mount version available.
LED-16(F) – 16 LeD annunciator with common indicators in a
locked metal enclosure. Flush mount version available.
PSN-1000(E) – 10 amp, remote intelligent power supply with 6
NaCs, 2 Inputs and a p-Link repeater.
CA-4064 – Class a convertor that converts the NaCs and p-Link
connection.
UD-2000 – UL listed, Dual line telephone alarm communicator.
DRV-50 – LeD driver expander, used to connect up to 50 LeDs in a
graphic display .
FCB-1000 – Fire communication bridge, provides remote mounting
of the ethernet connection.
FIB-1000 – Fiber interface module, used to extend p-Link to multi-
mode fiber (2 required).
RLY-5 – Relay module, provides 5 form C relay contacts rated at 3.0
amps 24VDC/125aC.
SPG-1000 – Serial parallel gateway, allows for the connection to a
serial or parallel printer.
The fire alarm control panel has a 4 x 20 LCD display to provide
information to the system status. The keypad has navigation keys
to allow manipulation of the Menu on board the panel. The panel is
shipped standard with the following LeDs:
• aC power - green
• alarm - Red
• earth Fault - amber
• Supervisory - amber
• Silenced - amber
• Trouble - amber
The common buttons include a Silence, Reset, acknowledge, and
Drill. all of the buttons are accessible once the locked door is
opened.
The FIB-1000, FCB-1000 and the SPG-1000 may be installed in the
stacker bracket or ordered with the optional rack mount enclosure.
MC-1000 Multi-Connect allows up to sixty-three panels to share a
single reporting technology.
AE-2 – Two card expansion cabinet.
AE-8 – eight card expansion cabinet.
AE-14 – Fourteen card expansion cabinet.
8830139 - REV E • 9/19 page 5 OF 5
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PFC-4064
Conventional Fire Alarm Control Panel
BOTTOM
LEFT SIDE
TOP
18.60"18.10"DEPTH
4.63"
3.95"
14.48"
14.78"
RIGHT SIDE
Dimensions
Ordering Information
Model Description Stock No.
pFC-4064 Fire alarm Control panel 3992360
Replacement Board 3992363
8830146 - REV B • 6/19 page 1 OF 3
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com
UD-2000
Digital Alarm Communicator
Description
The UD-2000 Digital alarm Communicator Transmitter (DaCT)
provides for up to two (2) phone lines for communication to a
monitoring station. The UD-2000 communicates using the SIa-
DCS or ademco Contact ID protocols. When enabled, the DaCT
automatically monitors each phone line or voltage and has the
ability to seize the line and connect with a remote receiver. Once the
communication is complete, the DaCT will hang up.
The DaCT is provided with terminal blocks for each phone line and
two RJ45 cords. In order for the DaCT to work properly, it must be
installed on a plain old telephone service (pOTS) line or equivalent
deemed by the authority having jurisdiction. The DaCT must be
installed before any other equipment to ensure it can seize the phone
line.
phone lines are high voltage and should be run in a separate conduit
from other circuits. The wire conductors connecting the DaCT to the
phone system should be 26 aWg or larger.
Technical Specifications
Operating Voltage 22.0-24.0V
Standby Current 16ma
alarm Current 23ma
Max UD-2000s per panel 1
Dimensions 4”W * 6”H * 1-5/8”D
Operating Tempuratures 0°C - 49°C (32°F- 120°F)
Operating Humidity Range 10% - 93% @ 30°C (86°F)
(non-condensing)
Mounting Options In FaCp Behind keypad
Shipping Weight 0.47 lbs
Features
• allows for communication to Monitoring Station
• Communicates using SIa-DCS or ademco Contact ID protocols
• For use with Ipa, aFC, and aRC series addressable panels and
pFC-4064 Conventional panel
• Status LeDs indicate operation of DaCT card
• Installs with ease behind main panel LCD display via User
Interface bracket
• Device address is set internally to address 1
• Includes two (2) RJ45 phone cords
8830146 - REV B • 6/19 page 2 OF 3
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com
UD-2000
Digital Alarm Communicator
Installation
Install in accordance with compatible fire alarm control panel installation manual
The UD-2000 DaCT is connected to the control panel using the provided four-wire cable connection (p/N 5210514) between p4 and UD-2000 p1. The
connection is power limited and supervised.
1. power system down.
2. Slide the UD-2000 into the card guides located under the User Interface bracket.
3. Secure the UD-2000 to the User Interface bracket using the provided #6-32x3/8” screw
4. Install the provided four-wire conductor jumper between UD-2000 p1 and p4.
1
2
3
4 5
6
7
8 1 - Grey
2 - Ta n
3 - Black
4 - Red
5 - Green
6 - Ye llow
7 - Blue
8 - Brown
1
2
3
4 5
6
7
8
Plain Old Te lephone (POTS) lines
RJ31X Phone Jack to UD-2000
Ring (Grey)
Line In From Te lco
UD-2000 Communicator
Tip (Brown)Out to Premises Phones
Ring (Red)
Tip (Green)
Ring (Grey)
Tip (Brown)Out to Premises Phones
Ring (Red)
Tip (Green)
Line In From Te lco
Te lco 2
TipRingTip Ring TipRingTip Ring
Phone 2Telco 1 Phone 1
Te lco Ti p = Red
Te lco Ring = Green
Phone Tip = Brown
Phone Ring = Grey
8830146 - REV B • 6/19 page 3 OF 3
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com
UD-2000
Digital Alarm Communicator
UD-2000 DACT Installation on
Small Platform Panel
UD-2000 DACT Installation on
Large Platform Panel
Slides in guides under main board.
Screw
DWG #593-32A
Slides in guides under main board.
Screw
DWG #593-32A
DETAIL E SCALE 1 : 1
DETAIL D SCALE 1 : 1
p Connector on
small platform
control panel
p Connector
on main board
DETAIL B SCALE 1 : 1
Fig 1 Fig 2
Ordering Information
Model Description Stock No.
UD-2000 Digital Alarm Communicator 3992769
Agency Listings
Photoelectric
Smoke Detectors
System Sensor i3™ series smoke detectors represent
significant advancement in conventional detection.
The i3 family is founded on three principles: installation
ease, intelligence, and instant inspection.
Features
Plug-in detector line, mounting base included•
Large wire entry port•
In-line terminals with SEMS screws•
Mounts to octagonal and single-gang back boxes, 4-square back •
boxes, or direct to ceiling
Stop-Drop ’N Lock attachment to base•
Removable detector cover and chamber•
Built-in remote maintenance signaling•
Drift compensation and smoothing algorithms•
Simplified sensitivity measurement •
Wide-angle, dual-color LED indication•
Loop testing via EZ Walk feature•
Built-in test switch•
Installation ease. The i3 line redefines installation ease with its
plug-in design. This allows an installer to pre-wire bases (included
with heads). The large wire entry port and in-line terminals provide
ample room for neatly routing the wiring inside the base. The base
accommodates a variety of back box mounting methods as well as
direct mounting with drywall anchors. To complete the installation, i3
heads plug into the base with a simple Stop-Drop ’N Lock™ action.
Intelligence. i3 detectors offer a number of intelligent features
to simplify testing and maintenance. Drift compensation and
smoothing algorithms are standard with the i3 line to minimize
nuisance alarms. 2-wire i3 detectors can generate a remote LED-
indicated maintenance signal when connected to the 2W-MOD2
loop test/maintenance module or a panel equipped with the i3
protocol. The SENS-RDR, a wireless device, displays the sensitivityof i3
detectors in terms of percent-per-foot obscuration.
Instant inspection. The i3 series provides wide-angle red and
green LED indicators for instant inspection of the detector’s
condition: normal standby, out-of-sensitivity, alarm, or freeze trouble.
When connected to the 2W-MOD2 loop test/maintenance module
or a panel with the i3 protocol, the EZ Walk loop test feature is
available on 2-wire i3 detectors. This feature verifies the initiating loop
wiring by providing LED status indication at each detector.
2093290-01-E7272-1653:1523011446S911 3180932
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2009 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0318-007 • 6/09 • #2169
Ordering Information
Model Thermal Wiring Alarm Current
2W-B No 2-wire 130 mA max. limited by control panel
2WT-B Yes 2-wire 130 mA max. limited by control panel
4W-B No 4-wire 20 mA @ 12 V, 23 mA @ 24 V
4WT-B Yes 4-wire 20 mA @ 12 V, 23 mA @ 24 V
Accessories
2W-MOD2 2-wire loop test / maintenance module RT Removal / replacement tool
SENS-RDR Sensitivity reader A77-AB2 Retrofit adapter bracket, 6.6 inch (16.76 cm) diameter
Smoke Detector Specifications
Architectural/Engineering Specifications
Smoke detector shall be a System Sensor i3 Series model number_______, listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems. The
detector shall be a photoelectric type (Model 2W-B, 4W-B) or a combination photoelectric/thermal (Model 2WT-B, 4WT-B) with thermal sensor rated at 135°F
(57.2°C). The detector shall include a mounting base for mounting to 3½-inch and 4-inch octagonal, single-gang, and 4-inch square back boxes with a plaster
ring, or direct mount to the ceiling using drywall anchors. Wiring connections shall be made by means of SEMS screws. The detector shall allow pre-wiring of the
base and the head shall be a plug-in type. The detector shall have a nominal sensitivity of 2.5 percent-per-foot nominal as measured in the UL smoke box. The
detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms. The detector shall provide dual-
color LED indication that blinks to indicate power up, normal standby, out of sensitivity, alarm, and freeze trouble (Model 2WT-B, 4WT-B) conditions. When used
in conjunction with the 2W-MOD2 module, 2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel
and shall provide a loop testing capability to verify the circuit without testing each detector individually.
Electrical Specifications
Operating Voltage Nominal: 12/24 V non-polarized
Minimum: 8.5 V
Maximum: 35 V
Maximum Ripple Voltage 30% peak to peak of applied voltage
Standby Current 2-wire: 50 µA maximum average; 4-wire: 50 µA maximum average
Maximum Alarm Current 2-wire: 130 mA limited by control panel; 4-wire: 20 mA @12 V, 23 mA @ 24 V
Peak Standby Current 2-wire: 100 µA; 4-wire: n/a
Alarm Contact Ratings 2-wire: n/a; 4-wire: 0.5 A @ 30 V AC/DC
Physical Specifications
Dimensions (including base)5.3 inches (127 mm) diameter; 2.0 inches (51 mm) height
Weight 6.3 oz (178 g)
Operating Temperature Range 2W-B and 4W-B: 32°F to 120°F (0°C to 49°C); 2WT-B and 4WT-B: 32°F to 100°F (0°C to 37.8°C)
Operating Humidity Range 0 to 95% RH non-condensing
Thermal Sensor 135°F (57.2°C) fixed
Freeze Trouble 2WT-B and 4WT-B only: 41°F (5°C)
Sensitivity 2.5%/ft nominal
Input Terminals 14 to 22 AWG
Mounting 3½-inch octagonal back box
4-inch octagonal back box
Single-gang back box
4-inch square back box with a plaster ring
Direct mount to ceiling
LED Modes Power-Up Sequence for LED Indication
LED Mode Green LED Red LED Condition Duration
Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds
Normal (standby)Blink every 5 seconds off
Out of sensitivity off Blink every 5 seconds
Freeze trouble off Blink every 10 seconds
Alarm off Solid
Agency Listings
7125-1653:0504
7135-1653:0503
S5512
S4011
FM approved except
for ALERT models
3057383, 3057072
AVDS865-05 • 2/22/2018 • Page 1
Features
• Updated Modern Aesthetics
• Small profile devices for Horns and Horn Strobes
• Plug-in design with minimal intrusion into the back box
• Tamper-resistant construction
• Automatic selection of 12- or 24-volt operation at 15 and 30
candela
• Field-selectable candela settings on wall units:
15, 30, 75, 95, 110, 135, and 185
• Horn rated at 88+ dBA at 16 volts
• Rotary switch for horn tone and two volume selections
• Mounting plate for all standard and all compact wall units
• Mounting plate shorting spring checks wiring continuity before
device installation
• Electrically compatible with legacy SpectrAlert and SpectrAlert
Advance devices
• Compatible with MDL3 sync module
• Strobes and Horn Strobes listed for wall mounting only
• Horns listed for wall or ceiling use
The System Sensor L-Series offers the most versatile and
easy-to-use line of horns, strobes, and horn strobes in the industry
with lower current draws and modern aesthetics. With white and red
plastic housings, standard and compact devices, and plain, FIRE,
and FUEGO-printed devices, System Sensor L-Series can
meet virtually any application requirement.
The L-Series line of wall-mount horns, strobes, and horn strobes
include a variety of features that increase their application versatility
while simplifying installation. All devices feature plug-in designs
with minimal intrusion into the back box, making installations fast
and foolproof while virtually eliminating costly and time-consuming
ground faults.
To further simplify installation and protect devices from construction
damage, the L-Series utilizes a universal mounting plate for all
models with an onboard shorting spring, so installers can test wiring
continuity before the device is installed.
Installers can also easily adapt devices to a suit a wide range
of application requirements using field-selectable candela settings,
automatic selection of 12- or 24-volt operation, and a rotary switch
for horn tones with two volume selections.
Indoor Selectable-
Output Horns,
Strobes, and
Horn Strobes for
Wall Applications
System Sensor L-Series audible visible notification
products are rich with features guaranteed to cut
installation times and maximize profits with lower
current draw and modern aesthetics.
AVDS865-05 • 2/22/2018 • Page 2
L-Series Specifications
Architect/Engineer Specifications
General
L-Series standard horns, strobes, and horn strobes shall mount to a standard 2 x 4 x 17/8-inch back box, 4 × 4 × 1½-inch back box, 4-inch
octagon back box, or double-gang back box. L-Series compact products shall mount to a single-gang 2 × 4 × 17⁄8 -inch back box. A universal
mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be
used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series
products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output
and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs
shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor
L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.
Strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, and 185.
Strobe
The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe
shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible
signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and
associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective
service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act
requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist
of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a
temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe
models shall operate on a coded or non-coded power supply.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The
module shall synchronize Strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns
on horn strobe models over a single pair of wires. The module shall mount to a 411/16 × 411/16 × 21/8-inch back box. The module shall also
control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more
synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 32°F to 120°F (0°C to 49°C)
Humidity Range 10 to 93% non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC or regulated 24 DC/FWR1
Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Wall-Mount Dimensions (including lens)5.6˝ L × 4.7˝ W × 1.91˝ D (143 mm L × 119 mm W × 49 mm D)
Compact Wall-Mount Dimensions (including lens)5.26” L x 3.46” W x 1.91” D (133 mm L x 88 mm W x 49 mm D)
Horn Dimensions 5.6˝ L × 4.7˝ W × 1.25˝ D (143 mm L × 119 mm W × 32 mm D)
Compact Horn Dimensions 5.25” L x 3.45” W x 1.25” D (133 mm L x 88 mm W x 32 mm D)
1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.
2. Strobe products will operate at 12 V nominal only for 15 cd and 30 cd.
AVDS865-05 • 2/22/2018 • Page 3
Horn and Horn Strobe Output (dBA)
Switch
Position Sound Pattern dB
8–17.5
Volts
16–33
Volts
DC DC FWR
1 Temporal High 84 89 89
2 Temporal Low 75 83 83
3 Non-Temporal High 85 90 90
4 Non-Temporal Low 76 84 84
5 3.1 KHz Temporal High 83 88 88
6 3.1 KHz Temporal Low 76 82 82
7 3.1 KHz Non-Temporal High 84 89 89
8 3.1 KHz Non-Temporal Low 77 83 83
9*Coded High 85 90 90
10*3.1 KHz Coded High 84 89 89
* Settings 9 and 10 are not available on 2-wire horn strobes. Temporal coding must
be provided by the NAC. If the NAC voltage is held constant, the horn output remains
constantly on.
UL Max. Strobe Current Draw (mA RMS)
Candela
8–17.5 Volts 16–33 Volts
DC DC FWR
Candela
Range
15 88 43 60
30 143 63 83
75 N/A 107 136
95 N/A 121 155
110 N/A 148 179
135 N/A 172 209
185 N/A 222 257
UL Max. Current Draw (mA RMS), Wall Horn Strobe, Candela Range (15–185 cd)
DC Input
8–17.5 Volts 16–33 Volts
15cd 30cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd
Temporal High 98 158 54 74 121 142 162 196 245
Temporal Low 93 154 44 65 111 133 157 184 235
Non-Temporal High 106 166 73 94 139 160 182 211 262
Non-Temportal Low 93 156 51 71 119 139 162 190 239
3.1K Temporal High 93 156 53 73 119 140 164 190 242
3.1K Temporal Low 91 154 45 66 112 133 160 185 235
3.1K Non-Temporal High 99 162 69 90 135 157 175 208 261
3.1K Non-Temporal Low 93 156 52 72 119 138 162 192 242
FWR Input
16–33 Volts
15cd 30cd 75cd 95cd 110cd 135cd 185cd
Temporal High 83 107 156 177 198 234 287
Temporal Low 68 91 145 165 185 223 271
Non-Temporal High 111 135 185 207 230 264 316
Non-Temportal Low 79 104 157 175 197 235 283
3.1K Temporal High 81 105 155 177 196 234 284
3.1K Temporal Low 68 90 145 166 186 222 276
3.1K Non-Temporal High 104 131 177 204 230 264 326
3.1K Non-Temporal Low 77 102 156 177 199 234 291
UL Max. Horn Current Draw (mA RMS)
Sound Pattern dB
8–17.5 Volts 16–33 Volts
DC DC FWR
Temporal High 39 44 54
Temporal Low 28 32 54
Non-Temporal High 43 47 54
Non-Temporal Low 29 32 54
3.1 KHz Temporal High 39 41 54
3.1 KHz Temporal Low 29 32 54
3.1 KHz Non-Temporal High 42 43 54
3.1 KHz Non-Temporal Low 28 29 54
Coded High 43 47 54
3.1 KHz Coded High 42 43 54
UL Current Draw Data
Horn Tones and Sound Output Data
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
www.systemsensor.com
©2018 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com
for current product information, including the latest version of this data sheet.
AVDS865-05 • 2/22/2018
L-Series Dimensions
Model Description
Wall Horn Strobes
P2RL 2-Wire, Horn Strobe, Red
P2WL 2-Wire, Horn Strobe, White
P2GRL 2-Wire, Compact Horn Strobe, Red
P2GWL 2-Wire, Comp 2 fils act Horn Strobe, White
P2RL-P 2-Wire, Horn Strobe, Red, Plain
P2WL-P 2-Wire, Horn Strobe, White, Plain
P2RL-SP 2-Wire, Horn Strobe, Red, FUEGO
P2WL-SP 2-Wire, Horn Strobe, White, FUEGO
P4RL 4-Wire, Horn Strobe, Red
P4WL 4-Wire, Horn Strobe, White
Wall Strobes
SRL Strobe, Red
SWL Strobe, White
SGRL Compact Strobe, Red
SGWL Compact Strobe, White
SRL-P Strobe, Red, Plain
SWL-P Strobe, White, Plain
SRL-SP Strobe, Red, FUEGO
SWL-CLR-ALERT Strobe, White, ALERT
L-Series Ordering Information
Notes:
All -P models have a plain housing (no “FIRE” marking on cover).
All -SP models have “FUEGO” marking on cover.
All -ALERT models have “ALERT” marking on cover.
*Horn-only models are listed for wall or ceiling use.
Model Description
Horns*
HRL*Horn, Red
HWL*Horn, White
HGRL*Compact Horn, Red
HGWL*Compact Horn, White
Accessories
TR-2 Universal Wall Trim Ring Red
TR-2W Universal Wall Trim Ring White
SBBRL Wall Surface Mount Back Box, Red
SBBWL Wall Surface Mount Back Box, White
SBBGRL Compact Wall Surface Mount Back Box, Red
SBBGWL Compact Wall Surface Mount Back Box, White
4.70"
(11.94 cm)1.91"
(4.85 cm)
1.25"
(3.18 mm)
5.67"
(14.4 cm)
A0549-00A0550-00
Compact Strobe, Horn Strobe Compact Horn
Strobe, Horn Strobe Horn
A0548-00 A0547-00
4.7"
119 mm
5.67"
144 mm
1.25"
32 mm
3.46"
88 mm
1.91"
48.5 mm
1.25"
32 mm
5.27"
133.9 mm
3.46"
88 mm 1.25"
32 mm
5.27"
133.9 mm
Wall Surface Mount Back Box
SBBRL/SBBWL
A0554-01
4.82"
(12.24 cm)1.85"
(4.69 cm)
5.78"
(14.68 cm)
A0557-00
1.55"
(3.9 cm)
3.57"
(9.1 cm)
5.38"
(13.7 cm)
Compact Wall Surface Mount Back Box
SBBGRL, SBBGWL
• UL and cUL Listed, FM Approved, CSFM Listed, MEA
Approved, ADA Compliant
• Single or Dual Action
• Terminal connectors
• 10 Amp Snap Action Switch
• Gold plated SPST contacts
• Optional auxiliary contacts
• Mounts on standard single gangbox
• Surface backboxes available
• High-gloss red enamel finish
• Glass breakrod
• Made in the U.S.A.
Potter Electric Signal Co., LLC • St. Louis, MO • Cust Service: 866-240-1870 • Tech Support:866-956-1211• Canada 888-882-1833 • www.pottersignal.com
PAGE 1 OF 1
PULL STATION SERIES
DIE-CAST METAL
MANUAL PULL STATIONS
PRINTED IN USA MKT. #8900097 - REV L
9/10
Description
The Potter Pull Station Series offers a complete line of die-cast pull
stations for a variety of applications focusing mainly on fire alarm
systems. The pull stations are available in single or dual action
models. All of the pull stations have a 10-amp snap action switch and
a dedicated terminal block for the ease of wire connections. All of
the metal is completely coated to inhibit corrosion and provide for a
uniform and quality finish.
The standard models have a hex key reset, however a key reset is also
available. The models are available with shallow and deep surface
mount back boxes and as a weatherproof version.
Operation
The Potter single action series of pull stations operate by pulling
the white operating handle straight down and the handle will lock
into place. The dual action stations require the lifting of the front
cover and then pulling the white operating handle straight down. The
stations are reset by opening the front and placing the handle in the
normal position.
Ordering Information
Type Model Number Stock Number Contact Type
Single Action
P32-1T 1000447 SPST
RMS-2T 1000477 DPST
RMS-6T 1000478 DPDT
RMS-1T-KL 1000451 SPST
RMS-1T-KO 1000450 SPST, key operated, no pull
Weather Proof RMS-1T-WP 1000401
SPSTDual Action P32-1T-LP 1000476
Weather Proof Dual Action RMS-1T-WP-LP 1000403
Accessories Notes
Dual Action RMS-LP 1000480 Converts single action to dual action
Back Box P32-BB 1000444 Surface mount back box
Back Box P32-DBB 1000445 Deep surface mount back box
Glass Rods RMS-GB 1000470 Replacement glass rods (10 per pkg)
Engineering Specifications
The contractor shall furnish and install the Potter series of pull
stations as indicated. The pull station shall be die cast construction
with a "T" type pull handle that is ADA compliant. Single action pull
stations shall be a P32-1T. Dual action pull stations shall be the Potter
P32-1T-LP. Any manual pull station installed in an outdoor or wet
location shall be a RMS-1T-WP weather proof unit. The contact shall
be a single pole, single throw switch rated at 1 amp 30V DC/125V
AC. The device shall have a terminal block for ease of wiring. Once
activated, the pull station shall be reset by opening the front cover.
Opening of the cover in a normal state shall initiate an alarm.
Specifications
Switch Rating: 1 Amp @ 30 VDC
10 Amps @ 125 VAC
Pull Station Dimensions: 4-3/4" H x 3-1/4" W x 7/8" D
Color: Red with raised white letters, white pull bar with raised red letters
For special application manual stations see bulletin #8910014.
For explosion proof manual stations see bulletin #8880014.
DITEK Surge Protection, Largo, FL 33771 ♦ Sales: 800-753-2345 ♦ www.diteksurgeprotection.com ♦ SPS-100057-001 Rev 18 01/22
Every precaution has been taken to ensure that this literature is accurate and complete. DITEK Corporation assumes no responsibility and disclaims all liability for damages resulting from the use of this information or for any errors or omissions.
Technical Specifications
Part Number: DTK-120HW DTK-240HW DTK-120/240HW
Voltage Configuration:
Single Ф
(2W +G)
120VAC
Single Ф
(2W +G)
240VAC
Split Ф
(3W +G)
120/240VAC
MCOV: 150V/300V 320V/640V 150V/300V
Voltage Protection
Rating:
700V L-G, L-N
1500V N-G
1200V L-G, L-N
2000V N-G
700V L-G, L-N
1500V L-L, N-G
Surge Current Rating: 50,000A 50,000A 100,000A
SCCR: 100,000A
Nominal Discharge
Current Rating (In): 10kA
Mechanical Specifications
Connection Method: ¾” NPT Male, 18-inch 12 AWG Leads
Housing: NEMA 4X Polycarbonate
Operating
Temperature: -31°F - 176°F (-35°C - 80°C)
Maximum Humidity: 95% non-condensing
Dimensions: 3.5” L x 1.89” W x 3.4” H
(88.9 mm x 48.3 mm x 86.4 mm)
Weight: 0.55 lb (0.25 kg)
Quality Standards & Approvals
Certifications: UL1449 4th Edition, CSA C22.2 No. 269.1-17
SPD Type: Type 1
Warranty: 10 Year Limited Warranty
Product Features
Approved for 20A circuit breakers
NEMA 4X weatherproof enclosure
allows for use in harsh environments
Diagnostic LED provides positive
indication of system power and SPD
function
Complies with ANSI/IEEE C62.41
and C62.45 Category B standards
Applications
Fire Alarm Control Panels
Residential Electrical Panels
Equipment Panels
Pumps, Motors, Lift Pump Stations
Accessories
Flush Mount Kit – DTK-FMK
DITEK’s DTK-HW Series of surge protective devices are
designed and manufactured to meet the standards of the life
safety industry. These compact, parallel-mount SPD’s are
available for 120V, 240V and 120/240V systems; and are widely
used to protect fire alarm panels and other dedicated branch
circuit loads. Their small footprint enables installation in a variety
of locations.
ELOCK-FA
CIRCUIT LOCKOUT KIT
• Circuit lockout tab
• Hex key
• Breaker, legend, and door labels
NFPA 2016 CODE COMPLIANCE
•• 10.6.5.2 Circuit Identification and Accessibility.
• 10.6.5.2.1 The location of the branch circuit disconnecting
means shall be permanently identified at the control unit.
• 10.6.5.2.2 System circuit disconnecting means shall be
permanently identified as to its purpose in accordance with
the following:
(1) “FIRE ALARM” for fire alarm systems
(2) “EMERGENCY COMMUNIC (2) “EMERGENCY COMMUNICATIONS” for emergency
communications systems
(3) “FIRE ALARM/ECS” for combination fire alarm
and emergency communications systems
• 10.6.5.2.3 For fire alarm and/or signaling systems, the circuit
disconnecting means shall have a red marking.
• 10.6.5.2.4 The red marking shall not damage the overcurrent
p protective devices or obscure the manufacturer’s markings.
• 10.6.5.2.5 The circuit disconnecting means shall be accessible
only to authorized personnel.
• 10.6.5.3 Mechanical Protection. The branch circuit(s)
and connections shall be protected against physical damage.
• 10.6.5.4 Circuit Breaker Lock. Where a circuit breaker is the
disconnecting means, a listed breaker locking device shall be
installed. installed.
www.1sae.com | toll free 1.800.486.1723 | fax 508.485.4740
© Copyright 2019 Space Age Electronics, Inc. | This document is subject to change without notice | SS10101 | Rev. 2