HomeMy WebLinkAboutAPPROVED, SLC DAY PERMIT CALCS AND MANUAL JProject Summary Job:
:
- wrightsoft@ Entire House
By.
QUICK CALCS, INC.
317 ST_ LUCIE LANE, FT. PIERCE, FL 34946 Phore:772-466-6799 Email: QUICKCALCS AOL.CCM
Project Information
For: ROBERT DAY
3175 COLUM BRINA CIRCLE, PORT ST. LUCIE, FL34952
Notes:
Weather: Fort Pierce, FL, US
Winter Design Conditions
Outside db 42 °F
Inside db 70 °F
Design TD 28 °F
Heating Summary
Structure
Ducts
Central vent (0 &n)
(none)
Humidification
Piping
Equipment load
Infiltration
Method
Construction quality
Fireplaces
5799 Btuh
1340 Btu h
0 Btuh
0 Btuh
0 Btuh
7139 Btuh
Simplified
Average
0
Heat' Coolingg
26U
Area (ft2)
26?
Volume (ff3)
2080
2080
Air changes/hour
0.61
0.32
Equiv.AVF (cfm)
21
11
Heating Equipment Summary
Make Daikin
Trade DAIKIN
Model RXB24AXVJU
AHRI ref 10575515
Summer Design Conditions
Outside db
90 °F
Inside db
75 °F
Design TD
15 °F
Daily range
M
Relative humidity
50 %
Moisture difference
61 grub
Sensible Cooling Equipment Load Sizing
Structure
16945
Btuh
Ducts
1742
Btuh
Central vent (0 cfm)
0
Btuh
(none)
Blower
0
Btuh
Use manufacturer's data n
Rate/swing multiplier 0.95
Equipment sensible load 17752 Btuh
Latent Cooling Equipment Load Sizing
Structure
1263
Btuh
Ducts
533
Btuh
Central vent (0 cfm)
0
Btuh
(none)
Equipment latent load
1796
Btuh
Equipment Total Load (Sen+Lat)
19549
Btuh
Req. total capacity at 0.70 SHR
2.1
ton
Cooling Equipment Summary
Make
Daikin
Trade
DAIKIN
Cond
RXB24AXVJU
Coil
FTXB24AXVJU
AHRI ref
10575515
Efficiency
9 HSPF
Efficiency 11.0 EER, 17 SEER
Heating input
Sensible cooling
14840
Btuh
Heating output
21200
Btuh @ 47-F
Latent cooling
6360
Btuh
Temperature rise
27
°F
Total cooling
21200
Btuh
Actual airflow
707
cfm
Actual airflow
707
cfm
Air flow factor
0.099
cfn/Btuh
Airflawfactor
0.038
cfm/Btuh
Static pressure
0
in H2O
Static pressure
0
in H2O
Space thermostat
Load sensible heat ratio
0.91
Capacity balance point
-16 *F
Backup:
Input = 2 kW, Output=
7262 Btuh,100 AFUE
Calculations approved
byACCA to meet all requirements of Manual J 8th Ed.
w rightsoft- 2022-JarF31 11:30:14
— Rig7t &RuO Uriversal 2021 21.0.08 RSW8101 Page 1
ACCk...QUICMDoamerislWrighsoftHVACDAY ROB ERT.rtQ Calc=MJ8 FrortDourfaces E
wrightsoft' Right-J® Worksheet Job:
Entire House Date.
By.
QUICK CALCS, INC.
317 ST, L UCIE LANE, FT. PIERCE, FL 34946 Phone: 772-466-6799 Email:11UICKCALCS@4oL.00M
1
Room name
Entire House
ENLCOSED ROOM
2
Eased Aril
46.0 ft
46.0 ft
3
Room height
8.0 ft
8.0 8 heakool
4
Room dimensions
26.0 x 10.0 It
5
Room area
260.0 f 260B
iF
Ty
Conslruttion
U-value
Or
HTM
Area (ft)
Load
Area (fF)
Load
number
(Btuhl 2F)
(Btuhj )
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N1P/S
Heat
Cool
Gross
N1PIS
Heat I
Cool
6
W
1213-0sw
0.097
n
2.72
2,34
80
80
217
187
80
80
217
187
W
1213-05w
0.097
s
2.72
2.34
60
41
111
95
80
41
ill
95
1013-w
0.600
s
16.80
12.02
19
39
324
232
19
19
324
232
`!A-clom
1270
s
35.56
34.77
20
40
711
695
20
20
7111
695
11
W
1213-0stiv
11.097
w
2.72
2.34
208
128
348
299
208
128
348
299
L—G
1 A-c1 om
1.270
w
35.56
87 %
80
12
2845
6965
80
6
2845
6965
C
17A-20zd
0.043
120
1.29
260
260
313
335
260
260
313
335
F
19A 19b*
0.049
II
11
1.08
0.58
260
I
260
280
150
4
260
260
280
150
6
c) AED exojrsion
3483
3483
Envelope fosslgain
5148
12442
5148
12442
12
a) Infiltration
651
183
651
183
b) Room ventilation
0
0
0
0
13
Internal gains' Occupants@ 230
4
920
4
920
Applianoasbther
3400
3400
Subtotal (llnes6 to 13)
5799
16945
5799
16945
Less e)dernat load
0
0
0
0
Less transfer
01
0
0
0
Redistribution
0
0
0
0
14
Subtotal
5799
16945
5799
16945
151
Dudloads
1 23%
10%
1340
1742
23%
10%
1340
1742
Total room load
7139
18687
7139
18687
Air required (drn)
707
707
707
707
Calculations aDDroved bvACCAto meet all requirements of Manual J 8th Ed.
ft-- 2D22-Jan-31 11:30:14
wri hts9 RigYkSata®Uriversal202121.0.0BRSU08101 Page 1
--QUtCKVOoamertslWri hlsoR HVACDA'r; ROBERT,ri.p CaIc=MJ8 FrorB OooriacEs: E
Job #
Performed far.
RCBERT DVV
3175CCLWBRim QRa-E
PCRT ST LUCIE, FL3�2
Sheet 1
EXISTING MOBILE HOME
ENLCOSED ROOM
21,200 BTU MINI
SPLIT SYSTEM
707 cfrn 707 cfrn
QUICK CALLS, INC.
317 ST.LUCIE LANE
Fr- P IE RCE, FL 34946
Phone:772-466-6799
CJICKCALCS AOL-COM
Scale: 1 : 50
Paja 1
R4tsuwDunvasd m
21.(103RSLM)B101
2322,b-0 11:3327
---1VW j15dt I VACTW, RCBERT.w
FORM R405-2020
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: ROBERT DAY
Builder Name:
Street: 3175 COLUMBRINA CIRCLE
Permit Office:
City, State, Zip: PORT ST. LUCIE, FL,
Permit Number:
Owner: ROBERT DAY
Jurisdiction:
Design Location: FL, Fort Pierce
County: St. Lucie(Florida Climate Zone 2)
1. New construction or existing
Addition
10. Wall Types(368.0 sqft.)
Insulation Area
2. Single family or multiple family
Detached
a. Frame - Wood, Exterior
R=11.0 368.00 ftZ
b. NIA
R= ft
3. Number of units, if multiple family
1
c. NIA
R= ft2
4. Number of Bedrooms
0
d. NIA
R= ft2
5. Is this a worst case?
No
11. Ceiling Types(260,0 sgft.)
Insulation Area
a• Under Attic (Vented)
R=19.0 260.00 ft2
6. Conditioned floor area above grade (ft)
260
b. NIA
R= ft2
Conditioned floor area below grade (ft2)
0
c. NIA
R= ftZ
7. Windows(119.4 sgft.) Description
Area
12. Ducts, location & insulation level R ft2
a. U-Factor: Sgl, U=0.65
119.36 ftZ
a.
SHGC: SHGC=0.30
b.
b. U-Factor: NIA
ftZ
c.
SHGC:
13. Cooling Systems
kBtulhr Efficiency
c. U-Factor: NIA
ftZ
a. Central Unit
21.2 SEER:17.00
SHGC:
Area Weighted Average Overhang Depth:
2,000 ft
Area Weighted Average SHGC:
0.300
14, Heating Systems
kBtu/hr Efficiency
8. Skylights Description
Area
a. Electric Heat Pump
21.2 HSPF:9.00
U-FactOr:(AVG) NIA
NIA ft2
SHGC(AVG): NIA
15. Water Systems -None required
9. Floor Types Insulation
Area Z
a. 2U
Ca NIA
p
a. Raised Floor R= 19.0
260.00 ft
N/A R=
ft2
b. Conservation features
c.
16. Credits
Pstat
Glass/Floor Area:0.459 Total Proposed Modified Loads: 11.07
PASS
Total Baseline
Loads: 11.31
I hereby certify that the plans and specifications covered by
Review of the plans and
S7�2,.
this calculation are in compliance with the Florida
Energy
specifications covered by this
p'~11-1E
Code.
calculation indicates compliance41
with the Florida Energy Code.
PREPARED BY:Q
Before construction is completed
Pao
this building will be inspected for
DATE: 1-31-2022
compliance with Section 553.908
Florida Statutes.
�*
,
I hereby certify that this building, as designed, is in compliance
Cob WE
with the Florida Energy Code.
OWNER/AGENT:
BUILDING OFFICIAL:
DATE:
DATE:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with R403.3.2.1.
- Proposed Qn of NAN exceeds the performance method default limit of 0.08
and therefore does not require duct testing. R405 .2.3
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project
requires a PERFORMANCE envelope leakage test report with envelope leakage no greater than 5.00 ACH50 (R402.4.1.2).
11311202211:28:56 AM EnergyGaageO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
PROJECT
Title: ROBERT DAY
Addresstype- Street Address
Building Type: User
Bedrooms: 0
Lot # —
Owner: ROBERT DAY
ConditionedArea: 260
Block/SubDivision: --
Total Stories: 1
PlatBook: --
BuilderName:
Worst Case: No
Street: 3175 COLUMBRINA CIRCLE
Permit Office:
RotateAngle: 0
County: St. Lucie
Jurisdiction:
Cross Ventilation: No
City, State, Zip: PORT ST. LUCIE,
FamilyType: Detached
Whole House Fan: No
FL,
New/Existing: Addition
Terrain. Suburban
YearConstruct:
Shielding: Suburban
Comment:
CLIMATE
Design
Design Temp
Int Design Temp Heating Design Dailytemp
Location
Tmy Site 97.5% 2.5%
Winter Summer Degree Days Moisture Range
FL, Fort Pierce
FL_VERO—BEACH_MUNICIPA 39 90
70 75 299 62 Low
BLOCKS
Number Name
Area Volume
1 Entire House
260 2080
SPACES
Number Name
Area Volume Kitchen Occupants
Bedrooms Finished Cooled Heated
1 ENLCOSED ROOM
260 2080 No
Yes Yes Yes
FLOORS
(Total Exposed Area = 260 sq.ft.)
# FloorType
Space Exposed Perim PerimeterR-Value Area U-Factor JoistR-Value Tile Wood Carpet
1 Raised Floor
ENLCOSED ROOM ---
260 ft 0.051 19 0.00 1.00 0.00
ROOF
Roof Gable Roof
Rad Solar SA Emitt Emitt Deck Pitch
V# Type
Materials Area Area Color
Barr Absor. Tested Tested Insul. (deg)
1 Flat
Gravel 261 ft2 10 ft, Medium N 0.6 No 0.6 No 19 4.8
ATTIC
# Type
Ventilation Vent Ratio (1 in)
Area RBS IRCC
1 No attic
Vented 150
260 ft' N N
CEILING
(Total Exposed Area = 260 sq.ft.)
# Ceiling Type
Space R-Value Ins. Type Area U-Factor Framing Frac. Truss Type
_ 1 UnderAttic(Vented)
ENLCOSED ROOM 19.0 Blown
260.0ft2 0.065 0.00 Wood
1131/2022 11:28:56 AM EnergyGaugeO USA 7.0.00- FlaRes202O FBC7th Edition (2020) Compliant Software Page 2
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
WALLS
(Total Exposed Area = 368 sq.ft.)
�#
Adjacent
Ornt To Wall Type
Cavity Width
Space R-Value Ft In
Height Area U- Sheath Frm. Solar Below
Ft In sq.ft. Factor R-Value Frac. Absor. Grade
-1
_2
3
N Exterior Frame- Wood
S Exterior Frame- Wood
W Exterior Frame -Wood
ENLCOSED ROOM 11.0 10.0 0
ENLCOSED ROOM 11.0 10.0 0
ENLCOSED ROOM 11.0 26.0 0
8.0 0 80.0 0.102 0 0.25 0.40 0 %
8.0 0 80.0 0.102 0 0.25 0.40 0 %
8.0 0 208.0 0.102 0 0.25 0.40 0 %
WINDOWS
(Total Exposed Area = 119 sq.ft.)
✓#
Wall
Ornt ID Frame Panes
NFRC U-Factor SHGC Imp Storm Area
---Overhang----
Depth Separation InteriorShade Screening
-1 S 2 Vinyl Single(Clear)
_2 S 2 Vinyl Single(Clear)
3 W 3 Vinyl Single(Clear)
Yes 0.65 0.30 N N 19.4ft2
Yes 0.65 0.30 N N 20.0ft2
Yes 0.65 0.30 N N 80.0ftz
2A ft 0 in 1.0 ft 4 in None None
2.0 ft 0 in 1.0 ft 4 in None None
2.0 ft0 in 1.0 ft 4 in None None
INFILTRATION
#
Scope Method
SLA CFM50 ELA EgLA
ACH ACH50 Space(s)
1
Wholehouse ProposedACH(50)
0.00025 173 9.51 17.85
0.0902 5.0 All
MASS
#
1
Mass Type
Detault(8lbs/sq.ft.)
Area Thickness Furniture Fraction Space
0 ft2 0 ft 0.30 ENLCOSED ROOM
HEATING SYSTEM
#
System TypelFl. Addition Subtype/Speed AHRI # Efficiency Capacity----GeothermalHeatPump---- Ducts Block
kBtulhr Entry Power Volt Current
1
Electric Heat PumplExistinglco
Split/Single HSPF: 9.00 21.2 0.00 0.00 0.00 sys#0 1
COOLING SYSTEM
#
System Type/FI.Addition Subtype/Speed AHRI # Efficiency
Capacity Air Flow SHR Duct Block
k€3tulhr cfm
1
Central UnitlFxistinglco
Split/Single SEER:17.0 21.2 0 0.70 Ductless 1
HOT WATER SYSTEM
#
System Type Subtype
Location EF(UEF) Cap Use
SetPnt FixtureFlow, Pipe Ins. Pipelength
Recirculation RecircControl
System Type
Loop Branch Pump DWHR
length length power
Facilities Equal DWHR Other Credits
Connected Flow Eff
DUCTS
VDuct-------Supply--------------Return-----
# Location R-Value Area Location R-Value Area LeakageType
Air CFM 25 CFM 25 HVAC #
Handier TOT OUT ON RLF Heat Cool
1131 /202211:28:56 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
DUCTS(Continued)
TEMPERATURES
ProgramableThermostat: Y
Ceiling Fans: N
Cooling [ ] Jan
[] Feb
[I Mar
[ ] Apr
[] May [X] Jun [X] Jul
[X] Aug
[X] Sep
[ ] Oct
[ ] Nov
[ ] Dec
Heating [X] Jan
[Xj Feb
[X] Mar
[ ] Apr
[} May [ j Jun [I Jul
[ ] Aug
[ ] Sep
[ ] Oct
[X] Nov
[X] Dec
Venting [ ] Jan
[ ] Feb
[X] Mar
[X] Apr
[ ] May [ ] Jun [ ] Jul
[ ] Aug
(] Sep
[X] Oct
[X] Nov
I] Dec
Thermostat Schedule:
HERS 2006 Reference
Hours
Schedule Type
1
2
3 4 5 6
7
8
9
10 11
12
(WD)
AM
78
78
78 78 78 78
78
78
80
80
80
80
_Cooling
PM
80
80
78 78 78 78
78
78
78
78
78
78
Cooling (WEH)
AM
78
78
78 78 78 78
78
78
78
78
78
78
PM
78
78
78 78 78 78
78
78
76
78
78
78
Heating (WD)
AM
66
66
66 66 66 68
68
68
68
68
68
68
PM
68
68
68 68 68 68
68
68
68
68
66
66
(WEH)
AM
66
66
66 66 66 68
68
68
68
68
68
68
—Heating
PM
68
68
68 68 68 68
68
68
68
68
fib
66
1131/202211:28:56AM EnergyGauge® USA 7.0.00-FlaRes2020FBC7thEdition (2020)Compliant Software Page
2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIAa
Project Name: ROBERT DAY Builder Name:
Street: 3175 COLUMBRINA CIRCLE Permit Office:
City, State, Zip: PORT ST. LUCIE, FL, Permit Number: Y
Owner: ROBERT DAY Jurisdiction: U
Design Location: FL, Fort Pierce County: St. Lucie(Florida Climate Zone 2) _
U
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
requirements
The exteriorthermal envelope contains a continuous air barrier.
not be used as a sealing material,
Breaks orjoints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with
The insulation in any dropped ceiling/soffit
Ceiling/attic
the insulation and any gaps in the air barrier shall be sealed
shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity with
sealed.
a material having a thermal resistance of R-3 per
Knee walls shall be sealed.
inch minimum
Exteriorthermal envelope insulation forframed walls
shall be installed in substantial contact and
continuous alignmentwith the air barrier.
Windows, skylights
The space between window/doorjambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier_
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
(including
insulation_
maintain permanent confactwiththe underside of
above -garage
subffoor decking, or floorfram ing cavity insulation
andcantilevered
shall be permitted to be in contactwith the top side
floors)
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered
Where provided instead of floor insulation, insulation
with a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace walls.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Narrowcavities
Batts in narrow cavities shall be cut to fit, or narrow
cavities shall be filled by insulation that on
i nstallation readily conformstothe available cavity
spaces.
Garagesepa ration
Air sealing shall be provided between the garage and
conditionedspaces.
Recessed lighting
Recessed lightfixtures installed in the building thermal
Recessed light fixtures installed in the building
envelope shall be sealed to the finished surface.
thermal envelope shall be airtight and IC rated_
Plumbing and wiring
Batt insulation shall be cut neatlytoflt around wiring
and plumbing in exterior wails, or insulation that on
installation readily conforms to available space shall
extend behind piping and wiring.
Shower/tub
The air barrier installed at exterlorwalls adjacentto showers
Exterior walls adjacentto showers and tubs shall
on exteriorwall
and tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phonebox
The air barrier shall be installed behind electrical or
on extenorwalls
communication boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub -floor, wall covering
or ceiling penetrated by the boot.
Concealed
When required to be sealed, concealed fire sprinklers shall only
sprinklers
be sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
voids between fire sprin klercover plates and walls or ceilings_
a. In addition, inspection of log walls shall be in accordance with the provisions of 1CC-400.
1131 /202211:28:56 AM EnergyGaugeO USA 7.0 - RaRes2020 FBC 7th Edition (2020) Compliant Software Page 3
FORM R405-2020
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 98
The lower the EnergyPerformance Index, the more efficient the home.
3175 COLUMBRINA CIRCLE,PORT ST. LUCIE,FL,
1. New construction or existing
Addition
10.
Wall Types(368.0 sqft.)
Insulation
Area
2. Single family or multiple family
Detached
a. Frame - Wood, Exterior
R=11.0
368,00 ftz
b. NIA
R=
ft
3. Number of units, if multiple family
1
c. NIA
R=
ft2
4. Number of Bedrooms
0
d. N/A
R=
ft2
5. Is this a worst case?
No
11.
Ceiling Types(260.0 sgft.)
Insulation
Area
a. Under Attic (Vented)
R=19.0
260.00 fe
6. Conditioned floor area above grade (ft)
260
b. NIA
R
ft
Conditioned floor area below grade (ftz)
0
c. NIA
R==
ft2
7. Windows`* Description
Area
12.
Ducts, location & insulation level
R ftz
a. U-Factor: Sgl, U=0.65
119.36 ftz
a.
SHGC: SHGC=0.30
b.
b. U-Factor: NIA
ftz
C.
SHGC:
13.
Cooling Systems
kBtulhr
Efficiency
c. U-Factor: NIA
ftz
a. Central Unit
21.2 SEER:17.00
SHGC:
Area Weighted Average Overhang Depth:
2.000 ft
Area Weighted Average SHGC:
0.300
14.
Heating Systems
kBtulhr
Efficiency
8_ Skylights Description
Area
a. Electric Heat Pump
21.2
HSPF:9.00
U-Factor:(AVG) NIA
NIA ftZ
SHGC(AVG): NIA
15.
Ho Water Systems -None required
9. Floor Types Insulation
Area z
az
@
Ca NIA
p
a. Raised Floor R= 19.0
260.00 ft
b.
2
ft'
b. Conservation features
NIA R=
16.
Credits
Pstat
I certify that this home has complied with the Florida Energy Efficiency Code for Building
Construction through the above energy saving features which will be installed (or exceeded)
in this home before final inspection_ Otherwise, a new EPL Display Card will be completed
based on installed Code compliant features.
Builder Signature:
Date:
Address of New Home: 3175 COLUMBRINA CIRCLE City/FL Zip: PORT ST. LUCIE,FL,
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for
energy efficient mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the
Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
1 /31/20221 11:28:56 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1