HomeMy WebLinkAboutAPPROVED, SLC DAY PERMIT CALCS AND MANUAL JProject Summary Job: : - wrightsoft@ Entire House By. QUICK CALCS, INC. 317 ST_ LUCIE LANE, FT. PIERCE, FL 34946 Phore:772-466-6799 Email: QUICKCALCS AOL.CCM Project Information For: ROBERT DAY 3175 COLUM BRINA CIRCLE, PORT ST. LUCIE, FL34952 Notes: Weather: Fort Pierce, FL, US Winter Design Conditions Outside db 42 °F Inside db 70 °F Design TD 28 °F Heating Summary Structure Ducts Central vent (0 &n) (none) Humidification Piping Equipment load Infiltration Method Construction quality Fireplaces 5799 Btuh 1340 Btu h 0 Btuh 0 Btuh 0 Btuh 7139 Btuh Simplified Average 0 Heat' Coolingg 26U Area (ft2) 26? Volume (ff3) 2080 2080 Air changes/hour 0.61 0.32 Equiv.AVF (cfm) 21 11 Heating Equipment Summary Make Daikin Trade DAIKIN Model RXB24AXVJU AHRI ref 10575515 Summer Design Conditions Outside db 90 °F Inside db 75 °F Design TD 15 °F Daily range M Relative humidity 50 % Moisture difference 61 grub Sensible Cooling Equipment Load Sizing Structure 16945 Btuh Ducts 1742 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 17752 Btuh Latent Cooling Equipment Load Sizing Structure 1263 Btuh Ducts 533 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 1796 Btuh Equipment Total Load (Sen+Lat) 19549 Btuh Req. total capacity at 0.70 SHR 2.1 ton Cooling Equipment Summary Make Daikin Trade DAIKIN Cond RXB24AXVJU Coil FTXB24AXVJU AHRI ref 10575515 Efficiency 9 HSPF Efficiency 11.0 EER, 17 SEER Heating input Sensible cooling 14840 Btuh Heating output 21200 Btuh @ 47-F Latent cooling 6360 Btuh Temperature rise 27 °F Total cooling 21200 Btuh Actual airflow 707 cfm Actual airflow 707 cfm Air flow factor 0.099 cfn/Btuh Airflawfactor 0.038 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.91 Capacity balance point -16 *F Backup: Input = 2 kW, Output= 7262 Btuh,100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed. w rightsoft- 2022-JarF31 11:30:14 — Rig7t &RuO Uriversal 2021 21.0.08 RSW8101 Page 1 ACCk...QUICMDoamerislWrighsoftHVACDAY ROB ERT.rtQ Calc=MJ8 FrortDourfaces E wrightsoft' Right-J® Worksheet Job: Entire House Date. By. QUICK CALCS, INC. 317 ST, L UCIE LANE, FT. PIERCE, FL 34946 Phone: 772-466-6799 Email:11UICKCALCS@4oL.00M 1 Room name Entire House ENLCOSED ROOM 2 Eased Aril 46.0 ft 46.0 ft 3 Room height 8.0 ft 8.0 8 heakool 4 Room dimensions 26.0 x 10.0 It 5 Room area 260.0 f 260B iF Ty Conslruttion U-value Or HTM Area (ft) Load Area (fF) Load number (Btuhl 2F) (Btuhj ) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N1P/S Heat Cool Gross N1PIS Heat I Cool 6 W 1213-0sw 0.097 n 2.72 2,34 80 80 217 187 80 80 217 187 W 1213-05w 0.097 s 2.72 2.34 60 41 111 95 80 41 ill 95 1013-w 0.600 s 16.80 12.02 19 39 324 232 19 19 324 232 `!A-clom 1270 s 35.56 34.77 20 40 711 695 20 20 7111 695 11 W 1213-0stiv 11.097 w 2.72 2.34 208 128 348 299 208 128 348 299 L—G 1 A-c1 om 1.270 w 35.56 87 % 80 12 2845 6965 80 6 2845 6965 C 17A-20zd 0.043 120 1.29 260 260 313 335 260 260 313 335 F 19A 19b* 0.049 II 11 1.08 0.58 260 I 260 280 150 4 260 260 280 150 6 c) AED exojrsion 3483 3483 Envelope fosslgain 5148 12442 5148 12442 12 a) Infiltration 651 183 651 183 b) Room ventilation 0 0 0 0 13 Internal gains' Occupants@ 230 4 920 4 920 Applianoasbther 3400 3400 Subtotal (llnes6 to 13) 5799 16945 5799 16945 Less e)dernat load 0 0 0 0 Less transfer 01 0 0 0 Redistribution 0 0 0 0 14 Subtotal 5799 16945 5799 16945 151 Dudloads 1 23% 10% 1340 1742 23% 10% 1340 1742 Total room load 7139 18687 7139 18687 Air required (drn) 707 707 707 707 Calculations aDDroved bvACCAto meet all requirements of Manual J 8th Ed. ft-- 2D22-Jan-31 11:30:14 wri hts9 RigYkSata®Uriversal202121.0.0BRSU08101 Page 1 --QUtCKVOoamertslWri hlsoR HVACDA'r; ROBERT,ri.p CaIc=MJ8 FrorB OooriacEs: E Job # Performed far. RCBERT DVV 3175CCLWBRim QRa-E PCRT ST LUCIE, FL3�2 Sheet 1 EXISTING MOBILE HOME ENLCOSED ROOM 21,200 BTU MINI SPLIT SYSTEM 707 cfrn 707 cfrn QUICK CALLS, INC. 317 ST.LUCIE LANE Fr- P IE RCE, FL 34946 Phone:772-466-6799 CJICKCALCS AOL-COM Scale: 1 : 50 Paja 1 R4tsuwDunvasd m 21.(103RSLM)B101 2322,b-0 11:3327 ---1VW j15dt I VACTW, RCBERT.w FORM R405-2020 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: ROBERT DAY Builder Name: Street: 3175 COLUMBRINA CIRCLE Permit Office: City, State, Zip: PORT ST. LUCIE, FL, Permit Number: Owner: ROBERT DAY Jurisdiction: Design Location: FL, Fort Pierce County: St. Lucie(Florida Climate Zone 2) 1. New construction or existing Addition 10. Wall Types(368.0 sqft.) Insulation Area 2. Single family or multiple family Detached a. Frame - Wood, Exterior R=11.0 368.00 ftZ b. NIA R= ft 3. Number of units, if multiple family 1 c. NIA R= ft2 4. Number of Bedrooms 0 d. NIA R= ft2 5. Is this a worst case? No 11. Ceiling Types(260,0 sgft.) Insulation Area a• Under Attic (Vented) R=19.0 260.00 ft2 6. Conditioned floor area above grade (ft) 260 b. NIA R= ft2 Conditioned floor area below grade (ft2) 0 c. NIA R= ftZ 7. Windows(119.4 sgft.) Description Area 12. Ducts, location & insulation level R ft2 a. U-Factor: Sgl, U=0.65 119.36 ftZ a. SHGC: SHGC=0.30 b. b. U-Factor: NIA ftZ c. SHGC: 13. Cooling Systems kBtulhr Efficiency c. U-Factor: NIA ftZ a. Central Unit 21.2 SEER:17.00 SHGC: Area Weighted Average Overhang Depth: 2,000 ft Area Weighted Average SHGC: 0.300 14, Heating Systems kBtu/hr Efficiency 8. Skylights Description Area a. Electric Heat Pump 21.2 HSPF:9.00 U-FactOr:(AVG) NIA NIA ft2 SHGC(AVG): NIA 15. Water Systems -None required 9. Floor Types Insulation Area Z a. 2U Ca NIA p a. Raised Floor R= 19.0 260.00 ft N/A R= ft2 b. Conservation features c. 16. Credits Pstat Glass/Floor Area:0.459 Total Proposed Modified Loads: 11.07 PASS Total Baseline Loads: 11.31 I hereby certify that the plans and specifications covered by Review of the plans and S7�2,. this calculation are in compliance with the Florida Energy specifications covered by this p'~11-1E Code. calculation indicates compliance41 with the Florida Energy Code. PREPARED BY:Q Before construction is completed Pao this building will be inspected for DATE: 1-31-2022 compliance with Section 553.908 Florida Statutes. �* , I hereby certify that this building, as designed, is in compliance Cob WE with the Florida Energy Code. OWNER/AGENT: BUILDING OFFICIAL: DATE: DATE: - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory -sealed in accordance with R403.3.2.1. - Proposed Qn of NAN exceeds the performance method default limit of 0.08 and therefore does not require duct testing. R405 .2.3 - Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires a PERFORMANCE envelope leakage test report with envelope leakage no greater than 5.00 ACH50 (R402.4.1.2). 11311202211:28:56 AM EnergyGaageO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT PROJECT Title: ROBERT DAY Addresstype- Street Address Building Type: User Bedrooms: 0 Lot # — Owner: ROBERT DAY ConditionedArea: 260 Block/SubDivision: -- Total Stories: 1 PlatBook: -- BuilderName: Worst Case: No Street: 3175 COLUMBRINA CIRCLE Permit Office: RotateAngle: 0 County: St. Lucie Jurisdiction: Cross Ventilation: No City, State, Zip: PORT ST. LUCIE, FamilyType: Detached Whole House Fan: No FL, New/Existing: Addition Terrain. Suburban YearConstruct: Shielding: Suburban Comment: CLIMATE Design Design Temp Int Design Temp Heating Design Dailytemp Location Tmy Site 97.5% 2.5% Winter Summer Degree Days Moisture Range FL, Fort Pierce FL_VERO—BEACH_MUNICIPA 39 90 70 75 299 62 Low BLOCKS Number Name Area Volume 1 Entire House 260 2080 SPACES Number Name Area Volume Kitchen Occupants Bedrooms Finished Cooled Heated 1 ENLCOSED ROOM 260 2080 No Yes Yes Yes FLOORS (Total Exposed Area = 260 sq.ft.) # FloorType Space Exposed Perim PerimeterR-Value Area U-Factor JoistR-Value Tile Wood Carpet 1 Raised Floor ENLCOSED ROOM --- 260 ft 0.051 19 0.00 1.00 0.00 ROOF Roof Gable Roof Rad Solar SA Emitt Emitt Deck Pitch V# Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg) 1 Flat Gravel 261 ft2 10 ft, Medium N 0.6 No 0.6 No 19 4.8 ATTIC # Type Ventilation Vent Ratio (1 in) Area RBS IRCC 1 No attic Vented 150 260 ft' N N CEILING (Total Exposed Area = 260 sq.ft.) # Ceiling Type Space R-Value Ins. Type Area U-Factor Framing Frac. Truss Type _ 1 UnderAttic(Vented) ENLCOSED ROOM 19.0 Blown 260.0ft2 0.065 0.00 Wood 1131/2022 11:28:56 AM EnergyGaugeO USA 7.0.00- FlaRes202O FBC7th Edition (2020) Compliant Software Page 2 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT WALLS (Total Exposed Area = 368 sq.ft.) �# Adjacent Ornt To Wall Type Cavity Width Space R-Value Ft In Height Area U- Sheath Frm. Solar Below Ft In sq.ft. Factor R-Value Frac. Absor. Grade -1 _2 3 N Exterior Frame- Wood S Exterior Frame- Wood W Exterior Frame -Wood ENLCOSED ROOM 11.0 10.0 0 ENLCOSED ROOM 11.0 10.0 0 ENLCOSED ROOM 11.0 26.0 0 8.0 0 80.0 0.102 0 0.25 0.40 0 % 8.0 0 80.0 0.102 0 0.25 0.40 0 % 8.0 0 208.0 0.102 0 0.25 0.40 0 % WINDOWS (Total Exposed Area = 119 sq.ft.) ✓# Wall Ornt ID Frame Panes NFRC U-Factor SHGC Imp Storm Area ---Overhang---- Depth Separation InteriorShade Screening -1 S 2 Vinyl Single(Clear) _2 S 2 Vinyl Single(Clear) 3 W 3 Vinyl Single(Clear) Yes 0.65 0.30 N N 19.4ft2 Yes 0.65 0.30 N N 20.0ft2 Yes 0.65 0.30 N N 80.0ftz 2A ft 0 in 1.0 ft 4 in None None 2.0 ft 0 in 1.0 ft 4 in None None 2.0 ft0 in 1.0 ft 4 in None None INFILTRATION # Scope Method SLA CFM50 ELA EgLA ACH ACH50 Space(s) 1 Wholehouse ProposedACH(50) 0.00025 173 9.51 17.85 0.0902 5.0 All MASS # 1 Mass Type Detault(8lbs/sq.ft.) Area Thickness Furniture Fraction Space 0 ft2 0 ft 0.30 ENLCOSED ROOM HEATING SYSTEM # System TypelFl. Addition Subtype/Speed AHRI # Efficiency Capacity----GeothermalHeatPump---- Ducts Block kBtulhr Entry Power Volt Current 1 Electric Heat PumplExistinglco Split/Single HSPF: 9.00 21.2 0.00 0.00 0.00 sys#0 1 COOLING SYSTEM # System Type/FI.Addition Subtype/Speed AHRI # Efficiency Capacity Air Flow SHR Duct Block k€3tulhr cfm 1 Central UnitlFxistinglco Split/Single SEER:17.0 21.2 0 0.70 Ductless 1 HOT WATER SYSTEM # System Type Subtype Location EF(UEF) Cap Use SetPnt FixtureFlow, Pipe Ins. Pipelength Recirculation RecircControl System Type Loop Branch Pump DWHR length length power Facilities Equal DWHR Other Credits Connected Flow Eff DUCTS VDuct-------Supply--------------Return----- # Location R-Value Area Location R-Value Area LeakageType Air CFM 25 CFM 25 HVAC # Handier TOT OUT ON RLF Heat Cool 1131 /202211:28:56 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT DUCTS(Continued) TEMPERATURES ProgramableThermostat: Y Ceiling Fans: N Cooling [ ] Jan [] Feb [I Mar [ ] Apr [] May [X] Jun [X] Jul [X] Aug [X] Sep [ ] Oct [ ] Nov [ ] Dec Heating [X] Jan [Xj Feb [X] Mar [ ] Apr [} May [ j Jun [I Jul [ ] Aug [ ] Sep [ ] Oct [X] Nov [X] Dec Venting [ ] Jan [ ] Feb [X] Mar [X] Apr [ ] May [ ] Jun [ ] Jul [ ] Aug (] Sep [X] Oct [X] Nov I] Dec Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 (WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 _Cooling PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling (WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 76 78 78 78 Heating (WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 (WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 —Heating PM 68 68 68 68 68 68 68 68 68 68 fib 66 1131/202211:28:56AM EnergyGauge® USA 7.0.00-FlaRes2020FBC7thEdition (2020)Compliant Software Page 2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIAa Project Name: ROBERT DAY Builder Name: Street: 3175 COLUMBRINA CIRCLE Permit Office: City, State, Zip: PORT ST. LUCIE, FL, Permit Number: Y Owner: ROBERT DAY Jurisdiction: U Design Location: FL, Fort Pierce County: St. Lucie(Florida Climate Zone 2) _ U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exteriorthermal envelope contains a continuous air barrier. not be used as a sealing material, Breaks orjoints in the air barrier shall be sealed. The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit Ceiling/attic the insulation and any gaps in the air barrier shall be sealed shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity with sealed. a material having a thermal resistance of R-3 per Knee walls shall be sealed. inch minimum Exteriorthermal envelope insulation forframed walls shall be installed in substantial contact and continuous alignmentwith the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier_ Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation_ maintain permanent confactwiththe underside of above -garage subffoor decking, or floorfram ing cavity insulation andcantilevered shall be permitted to be in contactwith the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered Where provided instead of floor insulation, insulation with a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Narrowcavities Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled by insulation that on i nstallation readily conformstothe available cavity spaces. Garagesepa ration Air sealing shall be provided between the garage and conditionedspaces. Recessed lighting Recessed lightfixtures installed in the building thermal Recessed light fixtures installed in the building envelope shall be sealed to the finished surface. thermal envelope shall be airtight and IC rated_ Plumbing and wiring Batt insulation shall be cut neatlytoflt around wiring and plumbing in exterior wails, or insulation that on installation readily conforms to available space shall extend behind piping and wiring. Shower/tub The air barrier installed at exterlorwalls adjacentto showers Exterior walls adjacentto showers and tubs shall on exteriorwall and tubs shall separate them from the showers and tubs. be insulated. Electrical/phonebox The air barrier shall be installed behind electrical or on extenorwalls communication boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or ceiling penetrated by the boot. Concealed When required to be sealed, concealed fire sprinklers shall only sprinklers be sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids voids between fire sprin klercover plates and walls or ceilings_ a. In addition, inspection of log walls shall be in accordance with the provisions of 1CC-400. 1131 /202211:28:56 AM EnergyGaugeO USA 7.0 - RaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 FORM R405-2020 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 98 The lower the EnergyPerformance Index, the more efficient the home. 3175 COLUMBRINA CIRCLE,PORT ST. LUCIE,FL, 1. New construction or existing Addition 10. Wall Types(368.0 sqft.) Insulation Area 2. Single family or multiple family Detached a. Frame - Wood, Exterior R=11.0 368,00 ftz b. NIA R= ft 3. Number of units, if multiple family 1 c. NIA R= ft2 4. Number of Bedrooms 0 d. N/A R= ft2 5. Is this a worst case? No 11. Ceiling Types(260.0 sgft.) Insulation Area a. Under Attic (Vented) R=19.0 260.00 fe 6. Conditioned floor area above grade (ft) 260 b. NIA R ft Conditioned floor area below grade (ftz) 0 c. NIA R== ft2 7. Windows`* Description Area 12. Ducts, location & insulation level R ftz a. U-Factor: Sgl, U=0.65 119.36 ftz a. SHGC: SHGC=0.30 b. b. U-Factor: NIA ftz C. SHGC: 13. Cooling Systems kBtulhr Efficiency c. U-Factor: NIA ftz a. Central Unit 21.2 SEER:17.00 SHGC: Area Weighted Average Overhang Depth: 2.000 ft Area Weighted Average SHGC: 0.300 14. Heating Systems kBtulhr Efficiency 8_ Skylights Description Area a. Electric Heat Pump 21.2 HSPF:9.00 U-Factor:(AVG) NIA NIA ftZ SHGC(AVG): NIA 15. Ho Water Systems -None required 9. Floor Types Insulation Area z az @ Ca NIA p a. Raised Floor R= 19.0 260.00 ft b. 2 ft' b. Conservation features NIA R= 16. Credits Pstat I certify that this home has complied with the Florida Energy Efficiency Code for Building Construction through the above energy saving features which will be installed (or exceeded) in this home before final inspection_ Otherwise, a new EPL Display Card will be completed based on installed Code compliant features. Builder Signature: Date: Address of New Home: 3175 COLUMBRINA CIRCLE City/FL Zip: PORT ST. LUCIE,FL, *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 1 /31/20221 11:28:56 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1