Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
AC Manual J(3)
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-27 08:07:57 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1624Job:Load Short Form 9/23/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Cialiani Residence, NisAir Air ConditioningFor: TBD Balsam Dr, Fort Pierce, FL 34982 Design Information InfiltrationClgHtg SimplifiedMethod9041Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1-041-230A** AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259425 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW10.2 Sensible cooling Btuh26950 Heating output Btuh34696 Latent cooling Btuh11550 Temperature rise °F25 Total cooling Btuh38500 Actual air flow cfm1283 Actual air flow cfm1283 Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.047 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.80 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Bed 2 164 1977 1657 84 78 Bath 72 1214 771 52 36 Bed 3 147 3968 2495 169 117 Hall 49 0 0 0 0 Kitchen 201 772 3551 33 167 Great Room 259 2624 4562 112 215 Office Foyer 218 5194 2675 221 126 Master Bed 231 4478 4287 191 202 Hers 34 764 316 33 15 His 31 39 62 2 3 Master Bath 153 2749 1404 117 66 Dining Room 119 3591 3477 153 164 Laundry 72 1659 1425 71 67 Wtr Clst 24 1066 575 45 27 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-27 08:07:57 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2 ...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N House 1772 30095 27257 1283 1283 Other equip loads 1521 808 Equip. @ 0.95 RSM 26774 Latent cooling 7044 TOTALS 1772 31616 33818 1283 1283 2021-Sep-27 08:07:57 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1624Job:Building Analysis 9/23/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Cialiani Residence, NisAir Air ConditioningFor: TBD Balsam Dr, Fort Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 18.658943.1Walls 18.5585117.8Glazing 000Doors 5.617561.0Ceilings 21.066253.73.7Floors 11.034801.8Infiltration 20.56489Ducts 00Piping 00Humidification 4.81521Ventilation0Adjustments 100.031616Total Cooling Walls Glazing CeilingsInfiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 13.036391.9Walls 23.5659020.0Glazing 000Doors 9.225921.5Ceilings 000Floors 3.59730.5Infiltration 29.28194Ducts 2.9808Ventilation 18.85270Internal gains 00Blower 0Adjustments 100.028065Total Latent Cooling Load = 7044 Btuh Overall U-value = 0.120 Btuh/ft²-°F Data entries checked. 2021-Sep-27 08:07:57 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1624Job:Component Constructions 9/23/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Cialiani Residence, NisAir Air ConditioningFor: TBD Balsam Dr, Fort Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 14083.155.10.109447ne 9012.02 4352.026803.155.10.109216se 11082.0217323.155.10.109550sw 7392.0211553.155.10.109366nw 31822.0249753.155.10.1091579all Partitions Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16" OC Stud 4561.469192.9411.00.101313 Windows Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (3.2 ft window ht, 1 ft sep.); 8 ft head ht 16922.612616.800.5807ne 21722.616116.800.58010ne 38622.628716.800.58017all Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.17 ft window ht, 1 ft sep.); 6.8 ft head ht 35122.626116.800.58016ne 48821.837716.800.58022sw 35122.626116.800.58016nw 119022.389816.800.58053all Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.16); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 10 ft overhang (1.25 ft window ht, 1 ft sep.); 6.8 ft head ht 8311.110714.200.4908se Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (2 ft window ht, 1 ft sep.); 6.8 ft head ht 15819.714418.000.6208se Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 10 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 42913.756118.000.62031se 2021-Sep-27 08:07:57 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2 ...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 15.9 ft overhang (8 ft window ht, 1 ft sep.); 6.8 ft head ht 50010.490518.800.65048se Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (3.17 ft window ht, 1 ft sep.); 6.8 ft head ht 14521.111516.800.5807sw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 6 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 42013.552516.800.58031sw 70622.652516.800.58031nw 112718.1105016.800.58062all Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 10 ft overhang (8 ft window ht, 1 ft sep.); 6.8 ft head ht 151716.0178418.800.65095nw Doors (none) Ceilings Attic, Shngls, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.0341772 25921.4617560.9930.0 Floors On Grade Depth, Tile Flr Fnsh 00662528.700.989231 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-27 08:07:57 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1624Job:Project Summary 9/23/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Cialiani Residence, NisAir Air ConditioningFor:TBD Balsam Dr, Fort Pierce, FL 34982 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh23606 Structure Btuh19063 Ducts Btuh6489 Ducts Btuh8194Central vent (48 cfm) 1521 Btuh Central vent (48 cfm) Btuh808 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh31616 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh26774 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh3021 Ducts Btuh2179Central vent (48 cfm) Btuh1844 CoolingHeating Outside air17721772Area (ft²) Equipment latent load Btuh7044 1724017240Volume (ft³)Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh33818 Equiv. AVF (cfm) 57109 Req. total capacity at 0.70 SHR ton3.2 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOX Model Cond ML14XC1-041-230A**AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259425Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW10.2 Sensible cooling Btuh26950Heating output Btuh34696 Latent cooling Btuh11550 Temperature rise °F25 Total cooling Btuh38500Actual air flow cfm1283 Actual air flow cfm1283 Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.047Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.80 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-27 08:07:57Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1624Job:Right-J® Worksheet 9/23/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name House Bed 2 2 Exposed wall 231.0 ft 14.5 ft 3 Room height 9.7 ft 9.4 heat/coolft 4 Room dimensions ft163.5x1.0 5 Room area 1772.0 ft²163.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 479 447 1408 901 136 121 381 243 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 7 0 126 169 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 10 0 161 217 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 16 0 261 351 16 0 261 351 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 311 216 680 435 0 0 0 0 GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 11.0811.08 8 8 107 83 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 19.7119.71 8 3 144 158 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 13.7413.74 31 31 561 429 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 sese 18.8518.85 10.4110.41 48 48 905 500 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 610 550 1732 1108 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.0821.08 7 1 115 145 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8121.81 22 3 377 488 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 31 31 525 420 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 508 366 1155 739 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 261 351 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 31 0 525 706 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 95 0 1784 1517 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 313 313 919 456 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 1772 1772 1756 2592 164 164 162 239 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 1772 231 6625 0 164 15 416 0 6 c) AED excursion 1055 -34 Envelope loss/gain 20127 12821 1219 799 12 a) Infiltration 3480 973 249 69 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 4 920 0 0 Appliances/other 4350 250 Subtotal (lines 6 to 13)23606 19063 1468 1119 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 83 37 14 Subtotal 23606 19063 1551 1156 15 Duct loads 27%43%6489 8194 27%43%426 501 Total room load 30095 27257 1977 1657 Air required (cfm)Air required (cfm)1283 1283 84 78 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-27 08:07:57Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1624Job:Right-J® Worksheet 9/23/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bath Bed 3 2 Exposed wall 8.5 ft 35.5 ft 3 Room height 9.4 heat/coolft 9.4 heat/coolft 4 Room dimensions ft8.5x8.5 ft147.3x1.0 5 Room area 72.3 ft²147.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 80 70 222 142 122 122 385 246 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 10 0 161 217 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 11.0811.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 19.7119.71 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 13.7413.74 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 sese 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 99 99 311 199 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 113 97 307 196 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 16 0 261 351 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 72 72 72 106 147 147 146 215 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 72 9 244 0 147 36 1018 0 6 c) AED excursion -16 78 Envelope loss/gain 698 449 2427 1286 12 a) Infiltration 146 41 609 170 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 250 Subtotal (lines 6 to 13)844 490 3036 1706 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 108 48 76 34 14 Subtotal 952 538 3112 1740 15 Duct loads 27%43%262 233 27%43%856 755 Total room load 1214 771 3968 2495 Air required (cfm)Air required (cfm)52 36 169 117 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-27 08:07:57Right-Suite® Universal 2021 21.0.08 RSU29066 Page 3...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1624Job:Right-J® Worksheet 9/23/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Hall Kitchen 2 Exposed wall 4.5 ft 7.0 ft 3 Room height 9.4 heat/coolft 10.0 heat/coolft 4 Room dimensions ft14.0x3.5 ft17.5x11.5 5 Room area 49.0 ft²201.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 11.0811.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 19.7119.71 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 13.7413.74 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 sese 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 42 42 133 85 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 70 70 206 102 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 49 49 49 72 201 201 199 294 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 49 5 129 0 201 7 201 0 6 c) AED excursion -6 -80 Envelope loss/gain 311 151 606 316 12 a) Infiltration 77 22 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 2 460 Appliances/other 0 1700 Subtotal (lines 6 to 13)388 173 606 2476 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -388 -173 0 0 14 Subtotal 0 0 606 2476 15 Duct loads 27%43%0 0 27%43%167 1075 Total room load 0 0 772 3551 Air required (cfm)Air required (cfm)0 0 33 167 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-27 08:07:57Right-Suite® Universal 2021 21.0.08 RSU29066 Page 4...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1624Job:Right-J® Worksheet 9/23/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Great Room Office Foyer 2 Exposed wall 13.5 ft 36.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft258.8x1.0 ft218.0x1.0 5 Room area 258.8 ft²218.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 190 103 325 208 GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 11.0811.08 0 0 0 0 8 8 107 83 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 19.7119.71 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 13.7413.74 0 0 0 0 31 31 561 429 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 sese 18.8518.85 10.4110.41 0 0 0 0 48 48 905 500 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 40 40 126 81 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 135 88 276 177 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 47 0 892 759 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 130 130 382 190 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 259 259 256 379 218 218 216 319 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 259 14 387 0 218 36 1033 0 6 c) AED excursion 189 -61 Envelope loss/gain 1812 1503 3654 1749 12 a) Infiltration 246 69 419 117 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 0 0 Appliances/other 1150 0 Subtotal (lines 6 to 13)2058 3182 4074 1866 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2058 3182 4074 1866 15 Duct loads 27%43%566 1381 27%43%1120 810 Total room load 2624 4562 5194 2675 Air required (cfm)Air required (cfm)112 215 221 126 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-27 08:07:57Right-Suite® Universal 2021 21.0.08 RSU29066 Page 5...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1624Job:Right-J® Worksheet 9/23/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Master Bed Hers 2 Exposed wall 28.5 ft 7.5 ft 3 Room height 10.0 heat/coolft 9.4 heat/coolft 4 Room dimensions ft230.5x1.0 ft7.5x4.5 5 Room area 230.5 ft²33.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 11.0811.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 19.7119.71 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 13.7413.74 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 sese 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 150 128 402 257 71 71 222 142 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8121.81 22 3 377 488 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 135 88 276 177 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 47 0 892 759 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 231 231 228 337 34 34 33 49 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 231 29 817 0 34 8 215 0 6 c) AED excursion 326 -7 Envelope loss/gain 2993 2344 471 184 12 a) Infiltration 520 145 129 36 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13)3513 2990 599 220 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 3513 2990 599 220 15 Duct loads 27%43%966 1297 27%43%165 96 Total room load 4478 4287 764 316 Air required (cfm)Air required (cfm)191 202 33 15 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-27 08:07:57Right-Suite® Universal 2021 21.0.08 RSU29066 Page 6...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1624Job:Right-J® Worksheet 9/23/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name His Master Bath 2 Exposed wall 0 ft 25.0 ft 3 Room height 9.4 heat/coolft 9.4 heat/coolft 4 Room dimensions ft30.5x1.0 ft152.6x1.0 5 Room area 30.5 ft²152.6 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 85 85 267 171 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 85 77 241 154 GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 11.0811.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 19.7119.71 0 0 0 0 8 3 144 158 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 13.7413.74 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 sese 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 66 66 207 133 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 31 31 30 45 153 153 151 223 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 31 0 0 0 153 25 717 0 6 c) AED excursion -1 21 Envelope loss/gain 30 43 1727 859 12 a) Infiltration 0 0 429 120 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)30 43 2156 979 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 30 43 2156 979 15 Duct loads 27%43%8 19 27%43%593 425 Total room load 39 62 2749 1404 Air required (cfm)Air required (cfm)2 3 117 66 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-27 08:07:57Right-Suite® Universal 2021 21.0.08 RSU29066 Page 7...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1624Job:Right-J® Worksheet 9/23/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Dining Room Laundry 2 Exposed wall 22.0 ft 18.0 ft 3 Room height 10.0 heat/coolft 9.4 heat/coolft 4 Room dimensions ft9.5x12.5 ft6.0x12.0 5 Room area 118.8 ft²72.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 56 49 154 99 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 7 0 126 169 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 11.0811.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 19.7119.71 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 13.7413.74 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 sese 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 95 64 201 129 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 31 31 525 420 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 125 94 296 189 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 31 0 525 706 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 113 113 331 165 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 119 119 118 174 72 72 71 105 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 119 22 631 0 72 18 516 0 6 c) AED excursion 640 -34 Envelope loss/gain 2295 2259 1199 504 12 a) Infiltration 401 112 103 29 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)2696 2371 1302 1033 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 121 54 0 0 14 Subtotal 2817 2425 1302 1033 15 Duct loads 27%43%774 1052 27%38%358 392 Total room load 3591 3477 1659 1425 Air required (cfm)Air required (cfm)153 164 71 67 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-27 08:07:57Right-Suite® Universal 2021 21.0.08 RSU29066 Page 8...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1624Job:Right-J® Worksheet 9/23/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Wtr Clst 2 Exposed wall 10.5 ft 3 Room height 8.0 heat/coolft 4 Room dimensions ft23.9x1.0 5 Room area 23.9 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blk Wall, Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 .G Impact, Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 .G Impact, Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 .G Impact, Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 11 W Blk Wall, Stucco Ext 0.109 se 3.15 2.02 36 36 113 73 G Impact, Clear Low-e 0.490 se 14.21 11.08 0 0 0 0 G Impact, Clear Low-e 0.620 se 17.98 19.71 0 0 0 0 G Impact, Clear Low-e 0.620 se 17.98 13.74 0 0 0 0 G Impact, Clear Low-e 0.650 se 18.85 10.41 0 0 0 0 W Blk Wall, Stucco Ext 0.109 sw 3.15 2.02 48 41 130 83 G Impact, Clear Low-e 0.580 sw 16.82 21.08 7 1 115 145 G Impact, Clear Low-e 0.580 sw 16.82 21.81 0 0 0 0 G Impact, Clear Low-e 0.580 sw 16.82 13.48 0 0 0 0 W Blk Wall, Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 G Impact, Clear Low-e 0.650 nw 18.85 16.03 0 0 0 0 P Frm Wall, 1/2" Gyp B 0.101 -2.94 1.46 0 0 0 0 C Attic, Shngls, R-30 0.034 -0.99 1.46 24 24 24 35 F On Grade Depth, Tile 0.989 -28.68 0.00 24 11 301 0 6 c) AED excursion 39 Envelope loss/gain 683 374 12 a) Infiltration 153 43 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)836 417 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 836 417 15 Duct loads 27%38%230 158 Total room load 1066 575 Air required (cfm)45 27 2021-Sep-27 08:07:58 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1624Job:Duct System Summary 9/23/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Cialiani Residence, NisAir Air ConditioningFor: TBD Balsam Dr, Fort Pierce, FL 34982 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.440 / 0.260 in H2O in H2O0.440 / 0.260 Lowest friction rate in/100ft0.262in/100ft0.262 Actual air flow cfm1283cfm1283 Total effective length (TEL) ft267 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st4125.036.4VlFx0x05.00.27344621214hBath st1100.021.5VlFx0x06.00.362941011977hBed 2 st4125.043.0VlFx0x08.00.2621412033968hBed 3 st4125.038.4VlFx0x08.00.2701961843477cDining Room st395.022.3VlFx0x06.00.375129672281cGreat Room st395.023.3VlFx0x06.00.372129672281cGreat Room-A st2100.030.7VlFx0x04.00.3371839764hHers st2100.030.6VlFx0x04.00.3374262cHis st395.022.1VlFx0x06.00.376100201775cKitchen st395.021.6VlFx0x06.00.378100201775cKitchen-A st1100.017.7VlFx0x05.00.37480851659hLaundry st2100.036.8VlFx0x06.00.322791412749hMaster Bath st2100.041.1VlFx0x06.00.3121211152144cMaster Bed st2100.035.1VlFx0x06.00.3261211152144cMaster Bed-A 75.03.8VlFx0x06.00.559761332597hOffice Foyer st2100.034.8VlFx0x06.00.327761332597hOffice Foyer-A st2100.041.3VlFx0x05.00.31232551066hWtr Clst Bold/italic values have been manually overridden 2021-Sep-27 08:07:58 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2 ...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 449 381 0.262 823 10.0 0x0 VinlFlx st1 st1 Peak AVF 635 555 0.262 808 12.0 0x0 VinlFlx st2 Peak AVF 598 451 0.312 762 12.0 0x0 VinlFlx st3 Peak AVF 174 458 0.372 840 10.0 0x0 VinlFlx Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb4 0x 2030 141 99.1 0.262 582 8.0 x0 0 VlFx rt1 rb8 0x 1010 94 83.8 0.310 515 6.0 x0 0 VlFx rt1 rb6 0x 2700 263 0 0 0 0 x0 0 VlFx rb1 0x 9650 1042 85.5 0.304 589 18.0 x0 0 VlFx rt1 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 1269 1276 0.262 914 16.0 0x0 VinlFlx 2021-Sep-27 08:07:58 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ents\Wrightsoft HVAC\TBD Balsam Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1624Job:Manual S Compliance Report 9/23/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Cialiani Residence, NisAir Air ConditioningFor: TBD Balsam Dr, Fort Pierce, FL 34982 Cooling Equipment Design Conditions °F76.9Entering coil DB:Btuh28065Sensible gain:°F90.4Outdoor design DB: °F63.9Entering coil WB:Btuh7044Latent gain:°F77.4Outdoor design WB: Btuh35109Total gain:°F75.0Indoor design DB: cfm1283Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: ML14XC1-041-230A**+CBA27UHE-048-230*++TDRModel:LennoxManufacturer: cfm1283Actual airflow: % of load96Btuh26950Sensible capacity: % of load164Btuh11550Latent capacity: %70SHR:% of load110Btuh38500Total capacity: Heating Equipment Design Conditions °F68.4Entering coil DB:Btuh31616Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm1283Actual airflow: °F50Temp. rise:% of load110kW10.2Output capacity: Meets all requirements of ACCA Manual S.