POTHOVOLTAIC SYSTEM
PHOTOVOLTAIC SYSTEM CODES: CONSTRUCTION NOTES: THIS PROJECT COMPLIES WITH THE FOLLOWING: 2020 7TH EDITION FLORIDA BUILDING CODE: BUILDING CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND 2020 7TH EDITION FLORIDA BUILDING CODE: RESIDENTIAL ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS. Digitally 2020 7TH EDITION FLORIDA BUILDING CODE: MECHANICAL ALL SOLAR ENERGY SYSTEM EQUIPMENT SHALL BE SCREENED TO THE MAXIMUM EXTENT Jose signed by 2020 7TH EDITION FLORIDA BUILDING CODE: PLUMBING POSSIBLE AND SHALL BE PAINTED A COLOR SIMILAR TO THE SURFACE UPON WHICH THEY ARE Joseph J 2020 7TH EDITION FLORIDA BUILDING CODE: FUEL GAS MOUNTED. J Bravo 2020 7TH EDITION FLORIDA BUILDING CODE: ENERGY CONSERVATION Date: 2020 7TH EDITION FLORIDA BUILDING CODE: EXISTING BUILDING MODULES SHALL BE TESTED , LISTED AND INDENTIFIED WITH FIRE CLASSIFICATION IN 2022.02.09 2020 7TH EDITION FLORIDA BUILDING CODE:ACCESSIBILITY ACCORDANCE WITH UL 2703. SMOKE AND CARBON MONOXIDE ALARMS ARE REQUIRED PER Bravo 13:53:36 2020 7TH EDITION FLORIDA FIRE PREVENTION CODE (NFPA) SECTION R314 AND 315 TO BE VERIFIED AND INSPECTED BY INSPECTOR IN THE FIELD. -07'00' 2017 NATIONAL ELECTRIC CODE (NEC) DIG ALERT(811)TO BE CONTACTED AND COMPLIANCE WITH EXCAVATION SAFETY PRIOR TO ANY AS ADOPTED BY ST. LUCIE COUNTY EXCAVATION TAKING PLACE PHOTOVOLTAIC SYSTEM GROUND WILL BE TIED INTO EXISTING GROUND AT MAIN SERVICE FROM DC DISCONNECT/INVERTER AS PER 2017 NEC SEC 250.166(A). SOLAR PHOTOVOLTAIC SYSTEM EQUIPMENT WILL BE INSTALLED IN ACCORDANCE WITH VICINITY MAP: REQUIREMENTS OF ART. 690 OF THE 2017 NEC THE MAIN SERVICE PANEL WILL BE EQUIPPED WITH A GROUND ROD OR UFER UTILITY COMPANY WILL BE NOTIFIED PRIOR TO ACTIVATION OF THE SOLAR PV SYSTEM SOLAREDGE OPTIMIZERS ARE LISTED TO IEC 62109-1 (CLASS II SAFETY)AND UL 1741 STANDARDS CLIENT: ^ ROBIN DEBIE ' INSTALL CREW TO VERIFY ROOF STRUCTURE PRIOR TO COMMENCING WORK. EMT CONDUIT 6601 KENWOOD ROAD,FORT PIERCE,FL ATTACHED TO THE ROOF USING CONDUIT MOUNT. aH�sT.LUCIE COUNTY e.9M10°1—Park «e1iPvi °°•",.. « .. �a � UTILITY:FPL-FLORIDA POWER&LIGHT «.°... ,<•^ METER:ACD8649 gg PHONE:(772)461-3559 x....o°xa F 6691 RnwoP0 R4, •04c• � 5 ttre.Fl3a91 9 smxM v.n.wtapna annwme SYSTEM: a a SYSTEM SIZE(DC):62 X 290=17.980 kW w°sa°aim SYSTEM SIZE(AC):12.000 kW @ 240V am9mmamrs - "ro araa°Pka, s � MODULES:62 X REC SOLAR:REC290TP2 OPTIMIZERS:62 X SOLAREDGE P340 INVERTER 1:SOLAREDGE SE6000H-USRGM [Sill INVERTER 2:SOLAREDGE SE6000H-USRGM ' t [Sill e Canva58 UpM1lstryo \P."A a AA SITE LOCATION TABLE OF CONTENTS: PV-1 SITE LOCATION REVISIONS PV-2 SITE PLAN NO. REVISED BY DATE PV-2A ROOF PLAN WITH MODULES LAYOUT PV-2B STRUCTURAL CALCULATIONS PV-3 MOUNTING DETAILS freedom PV-3A MOUNTING DETAILS F O R E V E R PV-4 THREE LINE DIAGRAM FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800,ORLANDO, PV-4A SINGLE LINE DIAGRAM FL 32819 Tel:(800)385-1075 PV-5 CONDUCTOR CALCULATIONS GREG ALBRIGHT PV-6 EQUIPMENT&SERVICE LIST 'r PV-7 LABELS (�U PV-7A SITE PLACARD CONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR PV-8 OPTIMIZER CHART EC13008056 PV-9 SAFETY PLAN PV-10 SAFETY PLAN SITE LOCATION APPENDIX MANUFACTURER SPECIFICATION SHEETS JOB NO: DATE: I DESIGNED BY: SHEET: 121435 2/9/2022 E.C. PV-1 LEGEND: KENWOOD ROAD PROPERTY LINE OBSTRUCTION — — — — PIPE VENT Q ° ° a a MODULES d ° ° d . d ° CONDUIT a d d4 ® d SETBACK ° c AC °° d d ° DISCONNECT ° ° A M SP o d MSP L ° DRIVEWAY' FBI JUNCTION d a° 4 d BOX (N)JUNCTION BOX ° INV INVERTER (N)JUNCTION BOX s c d $ Q ° PM PRODUCTION ° d ° (N)SOLAREDGE SE6000H-USRGM [S11] METER INVERTER WITH RAPID SHUTDOWN ROOF AREA:3732.53 SQ FT ° ROOF LINE A ° (N)SOLAREDGE SE6000H-USRGM [S11] CLIENT: ° G d INVERTER WITH RAPID SHUTDOWN ROBIN DEBIE (N)COMBINER SUB PANEL 6601 KENWOOD ROAD,FORT PIERCE,FL 13'-5" 34951 N (E) MAIN SERVICE PANEL AHJ:ST.LUCIE COUNTY INV UTILITY:FPL-FLORIDA POWER&LIGHT (E) UTILITY METER METER:ACD8649 JB PHONE:(772)461-3559 (N) UTILITY DISCONNECT EATON DG223NRB A.MSF UM (OR EQUIVALENT) YSTEM: SYSTEM SIZE(DC):62 X 290=17.980 kW SYSTEM SIZE(AC):12.000 kW @ 240V MODULES:62 X REC SOLAR:REC290TP2 OPTIMIZERS:62 X SOLAREDGE P340 INVERTER 1:SOLAREDGE SE6000H-USRGM [Sill INVERTER 2:SOLAREDGE SE6000H-USRGM [Sill 0 0 14'-10" 0 (N)62 REC SOLAR: REC290TP2 m mREVISIONS NO. REVISED BY DATE . . freedom F O R E V E R FREEDOM FOREVERLLC 2619 CONSULATE DR SUITE 800,ORLANDO, FL 32819 Tel:(800)385-1075 GREG ALBRIGHT CONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 SITE PLAN 1 SCALE: 1/16" — V_On I SITE PLAN Iy 90'-7" JOB NO: DATE: I DESIGNED BY: SHEET: 121435 2/9/2022 E.C. PV-2 LEGEND: igitally signed by S. CHIMNEY S. M. Mehdl Mehdi Z morodian O PIPE VENT Zomorodian ate:2022.02.09 2 :52:27-06'00' MODULES FIRE ACCESS (N)SOLAREDGE SE6000H-USRGM [S11] PATHWAYS (N)JUNCTION BOX INVERTER CONDUIT ® (N)SOLAREDGE SE6000H-USRGM [S11] SETBACK (N)JUNCTION BOX INVERTER FA C AC DISCONNECT (N)COMBINER SUB PANEL INV PB JUNCTION BOX NV (E) MAIN SERVICE PANEL SUB (E) UTILITY METER FNV INVERTER JB (N)AC DISCONNECT ISOLATED LOAD JB MSP UM EOA IONA D NT) I SO3NRB (OR PANEL AC FM-S P MAIN SERVICE ROOF AREA:3732.53 SQ FT PANEL CLIENT: FAC FUSED AC O ROBIN DEBIE DISCONNECT 6601 KENWOOD ROAD,FORT PIERCE,FL 34951 AHJ:ST.LUCIE COUNTY UTILITY:FPL-FLORIDA POWER&LIGHT METER:ACD8649 PHONE:(772)461-3559 (N)62 REC SOLAR: REC290TP2 O SYSTEM: SYSTEM SIZE(DC):62 X 290=17.980 kW O SYSTEM SIZE(AC):12.000 kW @ 240V 0 MODULES:62 X REC SOLAR:REC290TP2 OPTIMIZERS:62 X SOLAREDGE P340 INVERTER 1:SOLAREDGE SE6000H-USRGM [Sill INVERTER 2:SOLAREDGE SE6000H-USRGM [Sill REVISIONS NO. REVISED BY DATE FIRE ACCESS PATHWAYS .Q. freedom F O R E V E R FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800,ORLANDO, FL 32819 Tel:(800)385-1075 GREG A�LhB�RIIGI HT CONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 ROOF PLAN NOTES: 1. EMT CONDUIT ATTACHED TO THE ROOF USING CONDUIT MOUNTS SCALE: 3/32" _ V-0" 2. ATTACHED CLAMPS AT 25% FROM THE EDGE AND 50% FROM THE CENTER OF THE MODULES ROOF PLAN WITH MODULES LAYOUT 3. JUNCTION BOX IS MOUNTED TO THE RAIL. JOB NO: DATE: I DESIGNED BY: SHEET: 121435 [2/9/2022 E.C. PV-2A ROOF DETAILS: TOTAL ROOF AREA: 3732.53 SQ FT ARRAY COVERAGE: 29.83% SYSTEM DISTRIBUTED WEIGHT: 2.27 LBS UNIRAC: FLASHKIT PRO POINT-LOAD: 15.9 LBS CHEMLINK: CHEM CURB W/TILT POINT-LOAD: 15.97 LBS ROOF AREA STATEMENT CLIENT: ROBIN DEBIE ROOF MODULE QUANTITY ROOF PITCH ARRAY PITCH AZIMUTH ROOF AREA ARRAY AREA 6601 KENWOOD ROAD,FORT PIERCE,FL 34951 1 7 26° 26° 180° 669.16 SQ FT 125.72 SQ FT AHJ:ST.LUCIE COUNTY UTILITY:FPL-FLORIDA POWER&LIGHT 2 6 260 260 270° 290.23 SQ FT 107.76 SQ FT METER:ACD8649 PHONE:(772)461-3559 3 9 260 260 270° 383.05 SQ FT 161.64 SQ FT 4 2 260 260 270° 231.91 SQ FT 35.92 SQ FT 5 12 260 260 90° 534.76 SQ FT 215.52 SQ FT SYSTEM: SYSTEM SIZE(DC):62 X 290=17.980 kW 6 7 260 260 90° 290.23 SQ FT 125.72 SQ FT SYSTEM SIZE X RE 1 S 2.00 OL R: E 240V MODULES:62 X C SOLAR:REC290TP2 OPTIMIZERS:62 X SOLAREDGE P340 7 6 26° 26° 0° 494.79 SQ FT 107.76 SQ FT INVERTER 1:SOLAREDGE SE6000H-USRGM [Sill 8 4 3° 13° 180° 187.8 SQ FT 71.84 SQ FT INVERTER 2:SOLAREDGE SE6000H-USRGM [Sill 9 9 3° 13° 180° 347.24 SQ FT 161.64 SQ FT REVISIONS NO. REVISED BY DATE . . freedom C' FOR E V ER FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800,ORLANDO, FL 32819 Tel:(800)385-1075 GREG A�LhB�RIIGI HT CONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 ROOF DETAILS JOB NO: DATE: DESIGNED BY: SHEET: 121435 2/9/2022 E.C. PV-213 (N)REC SOLAR: REC290TP2 UNIRAC SM LIGHT RAIL RACKING SYSTEM ROOF ATTACHMENT I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I II T I T I T I I I I I I I I I I I I I I L CLIENT: 2 FT DF#2 2X4 BLOCKING TO BE INSTALLED WHERE PV ATTACHMENTS ROBIN DEBIE 6601 2X4 TRUSS @ 24" O.C. 4' OCCUR BETWEEN HORIZONTAL TRUSSES IN ORDER TO ACHIEVE PROPER 34951KENWOOD ROAD,FORT PIERCE,FL EMBEDMENT PER RACKING MANUFACTURER. BLOCKING TO BE ATTACHED AHJ:ST.LUCIE COUNTY w/ (2) 10d NAILS EACH END MEITER:ACD864g FLORIDA POWER&LIGHT PARTIAL ROOF FRAMING PLAN PHONE:(772)461-3559 Scale: NTS SYSTEM: SYSTEM SIZE(DC):62 X 290=17.980 kW SYSTEM SIZE(AC):12.000 kW @ 240V s w. MODULES:62 X REC SOLAR:REC290TP2 OPTIMIZERS:62 X SOLAREDGE P340 v? INVERTER 1:SOLAREDGE SE6000H-USRGM [Sill INVERTER2:SOLAREDGE SE6000H-USRGM [Sill REC SOLAR:REC290TP2 y REC SOLAR:REC290TP2 UNIRAC SM LIGHT RAIL GROUNDING IEND/MID UNIRAC SM LIGHT RAIL SOLAR MOUNT RACKING SYSTEM G• (E)SINGLE LAYER OF REVISIONS UNIRAC L-FOOT A COMP SHINGLE NO. REVISED BY DATE ATTACHMENTS `ZUNIRAC CHANNEL NUT LT UNIRAC FLASHKIT PRO 2Y WITH MIN�"THREOAD UNIRAC L-FOOTEMBEDMENT,SEALED ATTACHMENTSPENETRATION f/\�/,UNIRAC FLASHKIT P ��\ freedom (E)2X4 TRUSS @ 24"O.C. R L v e R FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800,ORLANDO, FL 32819 Tel:(800)385-1075 GREG A�LhB�RIIG�HT CONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 SOLAR PV ARRAY SECTION VIEW ATTACHMENT DETAIL Scale: NTS Scale: NTS MOUNTING DETAILS JOB NO: DATE: I DESIGNED BY: SHEET: 121435 2/9/2022 E.C. PV-3 (N) REC SOLAR: REC290TP2 UNIRAC SM LIGHT RAIL RACKING SYSTEM ROOF ATTACHMENT I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I 1-4, I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I 2 FT DF#2 2X4 BLOCKING TO BE INSTALLED WHERE PV ATTACHMENTS I I I I I I I I OCCUR BETWEEN HORIZONTAL TRUSSES IN ORDER TO ACHIEVE PROPER I EMBEDMENT PER RACKING MANUFACTURER. BLOCKING TO BE ATTACHED w/ (2) 10d NAILS EACH END CLIENT: ROBIN DEBIE 6' 6601 KENWOOD ROAD,FORT PIERCE,FL 2X4 RAFTER @ 24" O.C. 34951 AHJ:ST.LUCIE COUNTY UTILITY:FPL-FLORIDA POWER&LIGHT METER:ACD864 PARTIAL ROOF FRAMING PLAN PARTIAL ROOF FRAMING PLAN PHONE:(7722)461-3559 Scale: NTS Scale: NTS SYSTEM: SYSTEM SIZE(DC):62 X 290=17.980 kW SYSTEM SIZE(AC):12.000 kW @ 240V MODULES:62 X REC SOLAR:REC290TP2 OPTIMIZERS:62 X SOLAREDGE P340 INVERTER 1:SOLAREDGE SE6000H-USRGM [SI1] INVERTER 2:SOLAREDGE SE6000H-USRGM REC SOLAR:REC290TP2 7.5 or 5.0 [Sl1] ' M-1 Structural Sealant M-1 Structural Sealant Along Pipe Along Standoff UNIRAC SM LIGHT RAIL 1-PART Pourable Sealer or PRO PACK Pourable Sealer E � 2.0— Above 1.0 O Penetration Chem Curb UNIRAC STANDOFF CHEM LINK (E)TPO E CURB 2.0 REVISIONS ROOF NO. REVISED BY DATE Roof Surface 2X4 RAFTER @ 24"O.C. 5/16"LAG SCREWS Qr freedom WITH 2.5 MIN. M-1 Structural Sealant M-1 Structural Sealant �. F O R E V E R EMBEDMENT FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800,ORLANDO, FL 32819 Tel:(800)385-1075 GREG A�LhB�RIIG�HT CONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 SOLAR PV ARRAY SECTION VIEW ATTACHMENT DETAIL Scale: NTS Scale: NTS MOUNTING DETAILS JOB NO: DATE: DESIGNED BY: SHEET: 121435 2/9/2022 E.C. PV-3A BACKFEED BREAKER SIZING MAX. CONTINUOUS OUTPUT 50.00A @ 240V 25 X 1.25 = 31.25AMPS 35A BREAKER-OK 25 X 1.25 = 31.25AMPS 35A BREAKER-OK 50.00 X 1.25 = 62.50AMPS 70A BREAKER-OK SEE 705.12 OF 2017 NEC 200 X 1.20 = 240 240 - 200 = 40A ALLOWABLE BACKFEED (E)200A RATED OMETER )UTILITY MAIN SERVICE PANEL 7 1 PH,1201240V 60HZ (E)200A/2P CLIENT: MAIN BREAKER ROBIN DEBIE (END FED) 6601 KENWOOD ROAD,FORT PIERCE,FL 34951 AHJ:ST.LUCIE COUNTY UTILITY:FPL-FLORIDA POWER&LIGHT METER:ACD8649 PHONE:(772)461-3559 STRING-1 STRING-2 (N)LINESIDE TAP VIA UL 15 REC SOLAR:REC290TP2 16 REC SOLAR:REC290TP2 LISTED CONNECTORS (N)SOLAREDGE SE6000H-USRGM[Sill INVERTER . SYSTEM: EE E 4-#10AWG,PV WIRE SYSTEM SIZE(DC):62 X 290=17.980 kW 1-#6 AWG IN FREE AIR OR Q r 3-#8 AWG,THWN-2 (N)100A FUSED • SYSTEM SIZE(AC):12.000 kW @ 240V #8 AWG MUST BE IN EMT /�l V 1-#8 EGC,THWN-2 CONDUIT IN 3/4"OR LARGER EMT CONDUIT AC DISCONNECT MODULES:62 X REC SOLAR:REC290TP2 r —— EATON DG223NRB(OR (N)125A DEDICATED EQUIVALENT) OPTIMIZERS:62 X SOLAREDGE P340 I C LOAD CENTER 2-70 AMP FUSES INVERTER 1:SOLAREDGE SE6000H-USRGM - (N)M5A [SI1] ^/ TO UTILITY JUNCTION '.0 qj o/o OVERHEAD INVERTER 2:SOLAREDGE SE6000H-USRGM L------------ -------------- BOX ---- �J v O • FEED [SI1] ----- - -- (N)35W1 RAPID I SOLAREDGE P340 SOLAREDGE P340 SHUTDOWN I I POWER OPTIMIZERS POWER OPTIMIZERS 4-#10 AWG,THWN-2 SWITCH 1-#8 EGC,THWN-2 3-#6 AWG,THWN-2 3-#6 AWG,THWN-2 IN 3/4"OR __ 1-#8 EGC,THWN-2 IN 3/4"OR LARGER EMT CONDUIT LARGER EMT CONDUIT IN 3/4"OR LARGER EMT CONDUIT STRING-3 STRING- I L—————————- 15 REC SOLAR:REC290TP2 16 REC SOLAR:REC29GTP2 I FREE BARE COPPER (N)SOLAREDGE FREE AIR BONDED SE6000H-USRGM[Slit I EXISTING UFER TIE IN INVERTER I A TAPBOX MAY BE USED IN LIEU OF PERFORMING THE LINESIDE REVISIONS ACj I TAP r COND T HE MAIN SERVICE PANEL.THIS IS DEPENDENT UPON SITE NO. REVISED BY DATE I DC _ _ I JUNCTION I ----------------------- BOX -- ��� freedom RAPID FOREVER SOLAREDGE P340 SOLAREDGE P340 SHUTDOWN FREEDOM FOREVER LLC POWER OPTIMIZERS POWER OPTIMIZERS SWITCH 3-#B AWG,THWN-2 2619 CONSULATE DR SUITE 800,ORLANDO, 4-#10 AWG,PV WIRE 4-#10 AWG,THWN-2 1-#8 EGC,THWN-2 FL 32819 1-#6 AWG IN FREE AIR OR 1-#8 EGC,THWN-2 IN 3/4"OR LARGER EMT #8 AWG MUST BE IN EMT CONDUIT IN 3/4"OR CONDUIT Tel:(800)385-1075 LARGER EMT CONDUIT GREG ALBRIGHT CONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 NOTE: CONDUIT AND CONDUCTORS SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT THREE LINE DIAGRAM TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS JOB NO: DATE: DESIGNED BY:I SHEET: 121435 2/9/2022 E.C. PV-4 BACKFEED BREAKER SIZING MAX. CONTINUOUS OUTPUT 50.00A @ 240V 25 X 1.25 = 31.25AMPS 35A BREAKER-OK 25 X 1.25 = 31.25AMPS 35A BREAKER-OK 50.00 X 1.25 = 62.50AMPS 70A BREAKER-OK SEE 705.12 OF 2017 NEC 200 X 1.20 = 240 240 - 200 = 40A ALLOWABLE BACKFEED T)200A RATED (E)UTILITY MAIN SERVICE PANEL METER 1PH,1201240V 60HZ (E)200A/2P CLIENT: MAIN BREAKER ROBIN DEBIE (END FED) U 6601 KENWOOD ROAD,FORT PIERCE,FL 34951 AHJ:ST.LUCIE COUNTY UTILITY:FPL-FLORIDA POWER&LIGHT METER:ACD8649 PHONE:(772)461-3559 STRING-1 STRING-2 (N)LINESIDE TAP VIA UL 15 REC SOLAR:REC290TP2 16 REC SOLAR:REC290TP2 • • LISTED CONNECTORS (N)SOLAREDGE SE6000H-USRGM[SIll INVERTER SYSTEM: 4-#10 AWG,PV WIRE •� SYSTEM SIZE(DC):62 X 290=17.980 kW 1-#6 AWG IN FREE AIR OR n 3-#8 AWG,THWN-2 (N)100A FUSED !l SYSTEM SIZE(AC):12.000 kW @ 240V #8 AWG MUST BE IN EMT 1 3/ EGC,THWN-2 AC DISCONNECT • MODULES:62 X REC SOLAR:REC290TP2 CONDUIT D C IN 3/4"OR LARGER EMT CONDUIT EATON EQUIVALENT) RB(OR (N)125A DEDICATED EQUIVALENT) • OPTIMIZERS:62 X SOLAREDGE P340 LOAD CENTER 2-70 AMP FUSES • INVERTER 1:SOLAREDGE SE6000H-USRGM NI3sa2P JUNCTION ) �b 0 •�• TO UTILITY INV• OVERHEAD INVERTER 2:SOLAREDGE SE6000H-USRGM BOX ":f 0 FEED [$11] (N)35AI2P RAPID SOLAREDGE P340 SOLAREDGE P340 SHUTDOWN POWEROPTIMIZERS POWER OPTIMIZERS 4-#10 AWG,THWN-2 SWITCH 1-#8 EGC,THWN-2 3-#6 AWG,THWN-2 L 3-#6 AWG,THWN-2 IN 3/4"OR 1-#8 EGC,THWN-2 IN 3/4"OR LARGER EMT CONDUIT LARGER EMT CONDUIT IN 3/4"OR LARGER EMT CONDUIT STRING-3 STRING-4 15 REC SOLAR:REC290TP2 16 REC SOLAR:REC290TP2 (N)SOLAREDGE SE6000H-USRGM[Sill INVERTER A TAPBOX MAY BE USED IN LIEU OF PERFORMING THE LINESIDE REVISIONS ACTAP IN THE MAIN SERVICE PANEL.THIS IS DEPENDENT UPON SITE CONDITIONS. NO. REVISED BY DATE DC ILI JUNCTION BOX freedom RAPID •�• F O RE V E R SOLAREDGE P340 SOLAREDGE P340 SHUTDOWN / ] SWITCH FREEDOM FOREVER LLC POWEROPTIMIZERS POWER OPTIMIZERS 3-#8 AWG,THWN-2 2619 CONSULATE DR SUITE 800,ORLANDO, 4-#10 AWG,PV WIRE 4-#10 AWG,THWN-2 1-#8 EGC,THWN-2 1-#6 AWG IN FREE AIR OR 1-#8 EGC,THWN-2 IN 3/4"OR LARGER EMT FL 32819 #8 AWG MUST BE IN EMT CONDUIT IN 3/4"OR CONDUIT Tel:(800)385-1075 LARGER EMT CONDUIT GREG ALBRIGHT CONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 NOTE: CONDUIT AND CONDUCTORS SPECIFICATIONS ARE BASED SINGLE LINE DIAGRAM ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS JOB NO: DATE: I DESIGNED BY: SHEET: 121435 2/9/2022 1 E.C. PV-4A WIRE SCHEDULE CLIENT: ROBIN DEBIE STARTING ADJUSTMENT MAXIMUM 6601 KENWOOD ROAD,FORT PIERCE,FL STARTING TEMPERATURE ADJUSTED 34951 RACEWAY CONDUCTOR AWG ALLOWABLE CURRENT CORRECTION FACTOR FOR CONDUCTOR CURRENT AHJ:ST.LUCIE COUNTY # EQUIPMENT WIRE LOCATION QTY. WIRE AMPACITY @ 90°C FACTOR APPLIED TO MORE THAN 3 AMPACITY APPLIED TO UTILITY:FPL-FLORIDA POWER&LIGHT SIZE CONDUCTORS CONDUCTORS CONDUCTORS METER:ACD8649 310.15(B)(16) IN RACEWAY 310.15(B)(2)(a) 310.15(B)(3)(a) @ 90°C IN RACEWAY PHONE:(772)461-3559 1 DC MODULE TO OPTIMIZER ROOF/FREE-AIR 2 10 40 12.14 1 1 40.00 15.17 2 DC OPTIMIZER TO JUNCTION BOX ROOF/FREE-AIR 2 10 40 15.00 1 1 40.00 18.75 3 DC JUNCTION BOX TO INVERTER 1 EXTERIOR WALL 4 10 40 15.00 1 0.8 32.00 18.75 SYSTEM: SYSTEM SIZE(DC):62 X 290=17.980 kW 4 DC JUNCTION BOX TO INVERTER 2 EXTERIOR WALL 4 10 40 15.00 1 0.8 32.00 18.75 SYSTEM SIZE X RE 1 S 2.00 OL R: E 240V MODULES:62 X C SOLAR:REC290TP2 5 AC INVERTER 1 TO DEDICATED LOAD CENTER EXTERIOR WALL 3 8 55 25.00 1 1 55.00 31.25 OPTIMIZERS:62 X SOLAREDGE P340 INVERTER 1:SOLAREDGE SE6000H-USRGM 6 AC INVERTER 2 TO DEDICATED LOAD CENTER EXTERIOR WALL 3 8 55 25.00 1 1 55.00 31.25 [Sill INVERTER 2:SOLAREDGE SE6000H-USRGM 7 AC DEDICATED LOAD CENTER TO AC DISCONNECT EXTERIOR WALL 3 6 75 50.00 1 1 75.00 62.50 [Sill 8 AC AC DISCONNECT TO POI EXTERIOR WALL 3 6 75 50.00 1 1 75.00 62.50 REVISIONS NO. REVISED BY DATE .Q. freedom F O R E V E R FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800,ORLANDO, FL 32819 Tel:(800)385-1075 GREG A�LhB�RIIGI HT CONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 CONDUCTOR AMPACITY CALCULATIONS IN ACCORDANCE WITH NEC 690.8. CONDUCTOR CALCULATIONS JOB NO: DATE: DESIGNED BY: SHEET: 121435 2/9/2022 E.C. PV-5 BREAKER SIZES: SERVICE LIST: 70A PV BREAKER NONE 35A PV BREAKER 35A PV BREAKER MATERIAL LIST: OTY. PART PART# DESCRIPTION 62 MODULES 117-290 REC SOLAR:REC290TP2 62 OPTIMIZERS 130-340 SOLAREDGE P340 POWER OPTIMIZER-FRAME MOUNTED MODULE ADD-ON 1 JUNCTION BOX 480-276 60OVDC NEMA 3R UL LISTED JUNCTION BOX 2 CONNECTORS 240-300 STAUBLI/MULTI-CONTACT MC4 CONNECTORS(FEMALE) 2 ICONNECTORS 240-301 STAUBLI/MULTI-CONTACT MC4 CONNECTORS(MALE) 1 INVERTER 120-603 SOLAREDGE SE6000H-USRGM[Sill 240V INVERTER UL1741 SA CERTIFIED INTEGRATED ARC FAULT PROTECTION AND RAPID SHUTDOWN 1 INVERTER 120-603 SOLAREDGE SE6000H-USRGM[Sill 240V INVERTER UL1741 SA CERTIFIED INTEGRATED ARC FAULT PROTECTION AND RAPID SHUTDOWN CLIENT: 1 COMBINER PANEL 151-101 125A DEDICATED LOAD CENTER ROBIN DEBIE 6601 KENWOOD ROAD,FORT PIERCE,FL 1 AC DISCONNECT 321-101 100A RATED 240VAC NEMA 3R UL LISTED 34951 2 FUSES 330-070 70A FUSE 1 PH 240VAC AHJ:ST.LUCIE COUNTY 136 ROOF ATTACHMENT 1 241-250 UNIRAC:FLASHKIT PRO UTILITY:FPL-FLORIDA POWER&LIGHT METER:ACD8649 23 ROOF ATTACHMENT 2 520-100 CHEMLINK:CHEM CURB W/TILT PHONE:(772)461-3559 49 RAIL 1 211-100 UNIRAC SM LIGHT RAIL 168 INCH(TOTAL 582 FEET NEEDED) 53 RAIL HARDWARE 1 261-517 BND T-BOLT AND NUT SS 56 MODULE CLAMPS 1 221-101 SM MIDCLAMP PRO DIRK 56 MODULE CLAMPS 1 221-202 SM ENDCLAMP PRO W/END CLAMP SYSTEM: 19 SPLICE 1 261-600 BND SPLICE BAR PRO SERIES MILL SYSTEM SIZE(DC):62 X 290=17.980 kW 56 MLPE MOUNT 1 261-510 MICRO MNT BIND X RE S OLD TBOLT SS SYSTEM SIZE 1 : E 240V MODULES:62 X C SOLARR:RE 240V 15 ACCESSORIES 1 211-202 E-BOSS CONDUIT MOUNT COMP KIT OPTIMIZERS:62 X SOLAREDGE P340 30 ACCESSORIES 1 211-200 E-BOSS RAIL TRAY INVERTER 1:SOLAREDGE SE6000H-USRGM [Sil] 10 ACCESSORIES 1 211-206 E-BOSS BRIDGE TRAY INVERTER 2:SOLAREDGE SE6000H-USRGM 16 ACCESSORIES 1 211-207 E-BOSS BRIDGE CLIPS [SI1] 98 GROUNDING LUG 1 260-300 BURNDY GROUND WEEB-LUG 91 L-FOOT 1 241-100 UNIRAC L-FOOT SERRATED W/T-BOLT CLEAR(KIT) 9 RAIL HARDWARE 2 261-517 BND T-BOLT AND NUT SS 10 MODULE CLAMPS 2 221-101 SM MIDCLAMP PRO DIRK 10 MODULE CLAMPS 2 221-202 SM ENDCLAMP PRO W/END CLAMP 4 SPLICE 2 261-600 BND SPLICE BAR PRO SERIES MILL 10 MLPE MOUNT 2 261-510 MICRO MNT BND TBOLT SS REVISIONS 3 ACCESSORIES 2 211-202 E-BOSS CONDUIT MOUNT COMP KIT NO. REVISED BY DATE 5 ACCESSORIES 2 211-200 E-BOSS RAIL TRAY 2 ACCESSORIES 2 211-206 E-BOSS BRIDGE TRAY 3 ACCESSORIES 2 211-207 E-BOSS BRIDGE CLIPS GROUNDING LUG 2 260-300 BURNDY GROUND WEEB-LUG 16 L-FOOT 2 L-FOOT 2 UNIRAC L-FOOT SERRATED W/T-BOLT CLEAR(KIT) '�� freedom 18 ATTACHMENT 2 241-300 "UNIRAC 4""STANDOFFS-MILL" VVV F 0 R E V E R 18 TILT KIT 2 241-050 "UNIRAC 12""ADJUSTABLE TILT KIT" FREEDOM FOREVER LLC 5 CURB KIT 2 261-600 "CHEMLINK CHEMCURB 4""CURB KIT(4 CURBS PER KIT)" 2619 CONSULATE D FIL328 IT 800,ORLANDO, 5 SPLICE BAR 2 261-600 UNIRAC:BONDING SPLICE BAR SERRATED Tel:(800)385-1075 19 T-BOLT 2 261-517 T-BOLT NUT 3/8 X 3/4 SS GREG ALBRIGHT 5 GROUND LUG 2 260-300 T-BOLT NUT 3/8 X 3/4 SS 10 T-BOLT 2 261-510 UNIRAC:MICRO MNT BND T-BOLT 1/4 X 3/4 SS 9 MOUNTING BRACKET 2 211-201 UNIRAC:E-BOSS J-BOX MOUNTING BRACKET 40 LAG BOLT 2 261-506 UNIRAC HDW LAG BOLT 5/16 X 4 CONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 EQUIPMENT&SERVICE LIST JOB NO: DATE: DESIGNED BY:I SHEET: 121435 2/9/2022 E.C. PV-6 WARNING: "WARNING" NOTES: POWER SOURCEOUTPUT DUAL POWER SOURCES 1. NEC ARTICLES 690 AND 705 AND IRC SECTION R324 Y MARKINGS SHOWN HEREON. CONNECTION • 1 SOURCE IS PHOTOVOLTAIC2. ALL MARKING SHALL CONSIST OF THE FOLLOWING: 1 • NOT RELOCATERATED AC • 1 1 1 AMPS A. UV RESISTANT SIGN MATERIAL WITH ENGRAVED OR MACHINE PRINTED LETTERS OR ELECTRO-PLATING. OVERCURRENT DEVICE. AC NORMALOPERATING VOLTAGE1 VOLTS B. RED BACKGROUND COLOR WHITE TEXT AND LINE 705.12(B)(2)(3)(b) WORK. C. ARIAL FONT. 690.54 3. ALL SIGNS SHALL BE SIZED APPROPRIATELY AND PLACED IN SOLAR PV SYSTEM EQUIPPED THE LOCATIONS SPECIFIED. SIGNAGE CANNOT BE HAND-WRITTEN. WITH RAPID SHUTDOWN 4. SIGNS SHALL BE ATTACHED TO THE SERVICE EQUIPMENT WITH POP-RIVETS OR SCREWS TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM RESPONDEREMERGENCY AND REDUCE SHOCK SOLARTHIS ■V SYSTEM ■ ■ ED HAZARD IN THE ARRAY WITH RAPID 690.56(C)(1)(A) CLIENT: ELECTRICAL SHOCK HAZARD. ROBIN DEBIE TURN RAPID SHUTDOWN6601 KENWOOD ROAD,FORT PIERCE,FL SWITCH TO THE "OFF" TERMINALS • : • 1 • ` 1 1 34951 AHJ:ST.LUCIE COUNTY POSITION. oLAPELECTaic 1 MAY - 1 • ■ POSITION. UTILITY:FPL-FLORIDA POWER&LIGHT J PVPANeLs ' METER:ACD8649 ■ ■ a ONLY CONDUCTORS INSIDE PHONE (772)461-3559 BUILDING OR OFF THE 690.13 (B) ROOF WILL SHUT DOWN SYSTEM: SYSTEM SIZE(DC):62 X 290=17.980 kW NFPA 11.12.2.1.1.1.2 MAXIMUM VOLTAGE: 480V SYSTEM SIZE(AC):12.000 kW @ 240V MAXIMUM CIRCUIT CURRENT: 16.5A MODULES:62 X REC SOLAR:REC290TP2 OPTIMIZERS:62 X SOLAREDGE P340 MAXRATED • • INVERTER 1:SOLAREDGE SE6000H-USRGM ■ V SYSTEM AC Siij Q , •NNECTTHE CONTROLLEROR DC-TO-DC INVERTER 2:SOLAREDGE SE6000H-USRGM RATED AC OUTPUT CURRENT - 50.00 AMPS CONVERTER: 15A (SI1) AC NORMAL OPERATING V• ` 1 VOLTS 690.53 690.15,690.54 ARRAY RAPID SHUTDOWN SWITCH FOR I I • � - � INVERTER � REVISIONS SYSTEM DC 4/13 NO. REVISED BY DATE 690.56(C)(3) if you have any questions about your system,please call our Customer Support Team at L EMERGENCYRESPONDER 888.557.6431 1 NEC 690.31(G)(3)&(4) '�� freedom THIS • 1 ■ ■ EQUIPPED or visit freedomforever.com/customer-service �.' F 0 R E V E R J — FREEDOM FOREVER LLC WITH RAPID ■ , , • This solar PV system was Installed by "WARNING" 2619 CONSULATE DR SUITE 800,ORLANDO, L_ - - _J — — — FL32819 treedom° PHOTOVOLTAIC POWER • ■ Tel:(800)385-1075 r e s V E s GREG ALBRIGHT •r,..e.m ran.,i..uoe..e o.„no,m.u.w.u.p.,.m.iR TURN RAPID SHUTDOWN EVERY 10'ON CONDUIT AND ENCLOSURES SWITCH TO THE "OFF" SOLAR ELECTRIC n.e. PV PANELS CONTRACTOR LICENSE: POSITION TO SHUT DOWN CERTIFIED ELECTRICAL CONTRACTOR EC13008056 ENTIRE PV SYSTEM LABELS NFPA 11.12.2.1.1.1.1 JOB NO: DATE: DESIGNED BY: SHEET: 121435 2/9/2022 E.C. PV-7 CAUTIONE POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH CLIENT: DISCONNECTS AS SHOWN ROBI34951 EBIE 6601 KENWOOD ROAD,FORT PIERCE,FL 34951 AHJ:ST.LUCIE COUNTY KENWOOD ROAD UTILITY:FPL-FLORIDAPOWER&LIGHT METER:ACD8649 JUNCTION BOX INVERTER EQUIPPED PHONE:(772)461-3559 JUNCTION BOX WITH RAPID SHUTDOWN INVERTER EQUIPPED WITH RAPID SHUTDOWN SYSTEM SIZE(DC):62 X 290=17.980 kW SYSTEM SIZE(AC):12.000 kW @ 240V SUB PANEL MODULES:62 X REC SOLAR:REC290TP2 OPTIMIZERS:62 X SOLAREDGE P340 S 1]RTER 1:SOLAREDGE SE6E6000H-USRGM UTILITY METER I INVERTER 2:SOLAREDGE SE6000H-USRGM AC DISCONNECT [SI1] 8 ® MAIN SERVICE PANEL 62 PV MODULES REVISIONS WARNING NO. REVISED BY DATE TURN OFF PHOTOVOLTAIC AC DISCONNECT PRIOR TO WORKING INSIDE PANEL . . freedom FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800,ORLANDO, FL 32819 Tel:(800)385-1075 GREG ALBRIGHT NOTES: - 1. NEC ARTICLES 690 AND 705 AND IRC SECTION R324 MARKINGS SHOWN HEREON. CONTRACTOR LICENSE: 2. ALL MARKING SHALL CONSIST OF THE FOLLOWING: CERTIFIED ELECTRICAL CONTRACTOR A. UV RESISTANT SIGN MATERIAL WITH ENGRAVED OR MACHINE PRINTED LETTERS OR ELECTRO-PLATING. EC13008056 B. RED BACKGROUND COLOR WHITE TEXT AND LINE WORK. C. AERIAL FONT. 3. ALL SIGNS SHALL BE SIZED APPROPRIATELY AND PLACED IN THE LOCATIONS SPECIFIED. SIGNAGE CANNOT BE HAND-WRITTEN. SITE PLACARD 4. SIGNS SHALL BE ATTACHED TO THE SERVICE EQUIPMENT WITH POP-RIVETS OR SCREWS. JOB NO:I DATE: DESIGNED BY: SHEET: 121435 2/9/2022 E.C. PV-7A 1 -10 11 -20 21 -30 31 -40 41 -50 51 -60 SOLAREDGE OPTIMIZER CHART 1 2 3 CLIENT: ROBIN DEB IE 6601 KENWOOD ROAD,FORT PIERCE,FL 34951 4 AHJ:ST.LUCIE COUNTY UTILITY:FPL-FLORIDA POWER&LIGHT METER:ACD8649 mPHONE:(772)461-3559 W 5 SYSTEM: SYSTEM SIZE(DC):62 X 290=17.980 kW SYSTEM SIZE(AC):12.000 kW @ 240V MODULES:62 X REC SOLAR:REC290TP2 OPTIMIZERS:62 X SOLAREDGE P340 INVERTER 1:SOLAREDGE SE6000H-USRGM 6 [SI1] INVERTER 2:SOLAREDGE SE6000H-USRGM [SI1] 7 B El m m REVISIONS 8 NO. REVISED BY DATE .Q. freedom FOREVER FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800,ORLANDO, FL 32819 Tel:(800)385-1075 GREG ALBRIGHT 10 - CONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 OPTIMIZER CHART JOB NO: DATE: DESIGNED BY: SHEET: 121435 2/9/2022 E.C. PV-8 SAFETY PLAN KENWOOD ROAD MARK UP KEY INSTRUCTIONS: 1. USE SYMBOLS IN KEY TO MARK UP THIS SHEET. O PERMANENT ANCHOR 2. SAFETY PLAN MUST BE MARKED BEFORE JOB STARTS AS PART OF THE PRE-PLAN 3. DOCUMENT ALL ADDITIONAL HAZARDS ON THIS PAGE OT TEMPORARY ANCHOR & MAKE NOTES ON THE JHA SHEET IN CASE OF EMERGENCY IL INSTALLER LADDER NEAREST HOSPITAL OR OCCUPATIONAL/INDUSTRIAL CLINIC FB] JUNCTION / COMBINER BOX NAME: IS] STUB-OUT ADDRESS: SKYLIGHT SAFETY COACH CONTACT INFORMATION z NO LADDER ACCESS (STEEP CLIENT: NAME: � ROBIN DEBIE GRADE OR GROUND LEVEL 36601 4951 NWOOD ROAD,FORT PIERCE,FL 4951 PHONE NUMBER: I OBSTRUCTIONS) AHJUTILITY:ITY:FPCIECOUNTY L-FLORIDA POWER&LIGHT m METER:ACD8649 ALL EMPLOYEES ON SITE SHALL BE MADE AWARE OF THE PHONE:(772)461-3559 F-1 SAFETY PLAN AND SIGN INDICATING THAT THEY ARE + RESTRICTED ACCESS AWARE OF THE HAZARDS ON-SITE AND THE PLAN FOR 7p , WORKING SAFELY. EEH CONDUIT SYSTEM: SYSTEM SIZE(DC):62 X 290=17.980 kW SYSTEM SIZE(AC):12.000 kW @ 240V NAME SIGNATURE I MODULES:62 X REC SOLAR:REC290TP2 GAS GAS SHUT OFF OPTIMIZERS:62 X SOLAREDGE P340 INVERTER 1:SOLAREDGE SE6000H-USRGM [SI1] INVERTER 2:SOLAREDGE SE6000H-USRGM Hzo WATER SHUT OFF [311] e B 7 SERVICE DROP 0 � m I O POWER LINES REVISIONS NO. REVISED BY DATE �Qr freedom F O R E V E R FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800,ORLANDO, FL 32819 Tel:(800)385-1075 GREG ALBRIGHT DATE: TIME: CONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 SAFETY PLAN JOB NO: DATE: DESIGNED BY: SHEET: 121435 2/9/2022 E.C. PV-9 JOB HAZARD ANALYSIS Crew leader to fill out all sections below, hold a pre-job safety meeting with all personnel, and upload this completed document and the Safety Plan to Site Capture Ladder Access • Crew leader responsible for communication with the client: Heat Related Illness Prevention NOTE ADDITIONAL HAZARDS NOT ADDRESSED ABOVE • Ladders must be inspected before each use. I I Employees shall have access to potable drinking water that is (add as many as necessary by using additional sheets) • Extension ladders must be set up on a firm and level surface at Client and public is excluded from work area by barricades (N/A, fresh, pure, and suitably cool. The water shall be located as a 4-to-1 rise to run angle(or 75 degrees)and the top must be Yes, No): close as practicable to the areas where employees are working. Define the Hazard: Method/steps to prevent incident: secured to the structure. Extension style ladders placed on Water shall be supplied in sufficient quantity at the beginning of uneven, loose or slippery surfaces must additionally have the Training and Pre-Job Safety Briefing the work shift to provide at least one quart per employee per base firmly anchored or lashed so the base will not slip out. • All employees onsite shall be made aware of the specific hazards hour for drinking for the entire shift. Employees may begin the • Extension ladders must be used with walk-through devices or of this project and review this HJA during a pre-job briefing, and shift with smaller quantities of water if they identify the location Define the Hazard: Method/steps to prevent incident: the ladder must extend 36"above the stepping off point. their signature indicates awareness of site conditions and the and have effective means for replenishment during the shift to • A-frame ladders must only be climbed with the ladder spreader plan to eliminate any hazards identified prior to and during the allow employees to drink on quart or more per hour. The bars locked in the open position;A-frame ladders shall not be project. frequent drinking of water shall be encouraged. climbed while in the closed position (ex, closed and used while • Shade shall be present when temperature exceeds 80 degrees leaned against a structure). • Crew leader(name/title): Fahrenheit. When the outdoor temperature in the work exceeds Define the Hazard: Method/steps to prevent incident: • Additional notes: 1 80 degrees Fahrenheit, employees shall have and maintain one • Crew member(name/title): or more areas with shade at all times. Mobile Equipment • New employees must be acclimatized. New employees will be • Only Qualified operators will operate equipment; operators must Crew member(name/title): monitored by their Crew Leader(site supervisor)for the first two maintain a certification on their person for the equipment being (2)weeks of employment or longer when necessary. Define the Hazard: Method/steps to prevent incident: operated. • Crew member(name/title): • Employees will be allowed and encouraged to implement • Type(s)of mobile equipment(Type/Make/Model): I scheduled breaks during each shift. Employees must take • Crew member(name/title): cool-down breaks in the shade any time they feel the need to do • Qualified operator(s): so to protect them from overheating. Supervisors are • Crew member(name/title): REQUIRED to allow employees any break period they need Material Handling and Storage during high heat conditions. CLIENT: ROBIN DEBIE • Materials will be staged/stored in a way that does not present a Airborne Contaminants: 0 Cool Vests are encouraged for all employees at all times during 6601 KENWOOD ROAD,FORT PIERCE,FL hazard to client, personnel or public. Materials stored on the • Asbestos-containing (Transite) piping (ACP)-Do not disturb periods of high heat. 34951 AHJroof will be physically protect from failing or sliding off. move, drill, cut fracture, etc. • Identify the location of the closet Occupational/industrial ational/Industrial Clinic UTILITY: ST:LUCIE COUNTY p Y Y p g g ( ) Y p UTILITY:FPL-FLORIDA POWER&LIGHT • Asbestos-containing thermal insulation (ACI)and or Hospital in case a crew member becomes ill. METER:ACD8649 Fall Protection Asbestos-containing duct wrapping (ACW)-do not disturb, no PHONE:(772)461-3559 • A site-specific plan for fall prevention and protection is required attic or crawlspace access is allowed if work to be performed What is the specific plan to provide and replenish sufficient water for prior to starting work and must remain onsite at all times until could cause exposure to personnel, client or public. all employees on site? work is complete; a fall rescue plan must be outlined and • If offsite replenish is necessary,where will you go to replenish discussed among the crew prior to work start. • If yes, list specific tasks and protection in place: water(location/address): SYSTEM: • First-person-Up (FPU) must install their anchor and connect SYSTEM SIZE(DC):62 X 290=17.980 kWSYSTEM SIZE(AC):12.000 kW @ 240V before any other task, including installing other anchors. The • Who will replenish the drinking water(name): MODULES:62 x REC SOLAR:REC290TP2 ( muse e on person on a roof OPTIMIZERS:62 X SOLAREDGEP340 Last-Person-DownLPD) t b the only p INVERTER 1:SOLAREDGE SE6000H-USRGM uninstalling fall protection. [Sill INVERTER 2:SOLAREDGE SE6000H-USRGM • FPCP(name and title): Restroom facilities [sill • Employees shall have access to restroom facilities with • FPU and LPD (name and title): hand-washing stations. Use of onsite restroom is at the client's discretion (location is annotated below). If client does not give Electrical Safety permission, location of suitable restroom facilities with • The Electrical Qualified Person (EQP)is required onsite to hand-washing stations offsite will be provided.The onsite perform electrical work. supervisor will identify location and make arrangements to • All electrical work will be performed with equipment in an ensure all employees have access at any point. electrically safe condition (de-energized)unless approval has • Restroom facilities will be(circle one): Onsite-Offsite REVISIONS NO. REVISED BY DATE been granted prior to work. Weather and Environment • If Offsite, add location name and address: • Service drops and overhead electrical hazards will be indentified • The site supervisor shall forecast the weather conditions at the and protected from contact, as neccessary. job site, prior to crew arrival, in order to mitigate any hazards Incident Reporting Procedure • EQP(name and tile): associated with inclement weather(heat, cold,wind, rain, etc.) Contact your Site Supervisor ((�� • The site supervisor will utilized a portable wind meter Name: Q* freedom Public Protection (anemometer)to verify actual onsite wind conditions, by checking F O R E V E R • The safety of the Client and Public must be maintained at all at the ground and on any elevated work surface(ex, rooftop) Phone: FREEDOM FOREVER LLC times. prior to work start, at midday and prior to solar panel staging on a 2619 CONSULATE DR SUITE 800,ORLANDO, 819 • The Client and the Public shall be prevented from entering the roof. . 80 )385- p g Contact our Manager Tel:(800)385-1075 work zone through the use of barriers and/or signage, as Elevated work involving the moving or maneuvering of solar Name: GREG ALBRIGHT required. panels shall cease at 25mph (sustained wind)until wind • Company, Client and Public property shall be protected from subsides. Phone: falling objects. Forecasted weather maximum temp(degrees f): • Pets(including dogs)shall be secured by their owners prior to Contact your Site Supervisor CONTRACTOR LICENSE: work start. Name: CERTIFIED ELECTRICAL CONTRACTOR • The Client should not leave pets,family members, or others in EC13008056 charge or care of Employees, Contractors, or Temporary Phone: Workers. With:Your full name, phone number, office location, brief description SAFETY PLAN Of what happen and when. JOB NO: DATE: DESIGNED BY: SHEET: 121435 2/9/2022 E.C. PV-10 SOLARS MOST TRUSTED OL REC REE TWINPEAK 2 SERIES _ 1675±2.5[65.94±0.1] �i,��5[1.1] 910[35.8] ss2s ns.osi �, , -- FFICIENCY YEAR PRODUCT WARRANTY RE[ - YEAR LINEAR POWER OUTPUT TWINPEAK 2 m WARRANTY 0 11±0.2 �I [0.43±0.81 TEMPERATURE RATINGS SERIES [0.720.5±0.5 e Nominal operating cell temperature(NOCT) 44.6°C(±2°C) 8±0.081 1200[471 o Temperature coefficient of PMPP 0.36%/°C 1 Temperature coefficient ofVoc -0.30%/°C PREMIUM SOLAR PANELS T--45[1.5] Temperature coefficient oflsc 0.066%/°C 100% MADE IN SINGAPORE Measurements inmm[i - 38[,.5' ELECTRICAL DATA@ STC Product Code*:RECxxxTP2 GENERALDATA REC TwinPeak Z Series solar panels feature an Nominal Power-PMPP(Wp) 275 280 285 290 295 300 $Iistype: 6stringsof20RECHCmulticrysta[linePERC innovative design with high panel efficiency and Watt Class Sorting-(W) -0/+5 -0/+s -0/+5 -0/+s 0/+5 -0/+sas: 0.13"(3.2mm)solarglasswith Nominal Power Voltage-VMPP(V) 31.5 31.7 31.9 32.1 32.3 32.5anti reflective surface treatment poweroutput,enabling customersto get the most cksheet: Highly resistant polyester Nominal Power Current IMPP(A) 8.74 8.84 8.95 9.05 9.14 9.24 of olefin construction out of the space used for the installation. � - --- - - - - - P y Open Circuit Voltage-Voc(V) 38.2 38.4 38.6 38.8 39.0 39.2 Frame: Anodized aluminum Combined with industry-leading product quality Short CircuitCurrent-IJA) 9.52 9.61 9.66 9.71 9.76 9.82 (Available in silver or black) and the reliability g of a strop and established Panel Efficiency(%) 16.5 16.8 17.1 17.4 17.7 18.0 Junction box: IP67 rated,3-part with 3 bypass diodes - - 2, -- 12AWG(4mm2)PVwire,35+47"(0.9m+1.2m) - Values at standard test conditions STC(airmass AM 1.5,irradiance 1000 W/m2,cell temperature 25°C). European brand,REC TwinPeak Z panels are ideal Atlow irradiance of200W/m'(AM 1.5 and cell temperature 25°C)at least 95%of the STC module efficiency will beachieved. Connectors: Staubli MC4 PV-KBT4/PV-KST4, 'Where xxx indicates the nominal power class(PMop)at STC above,and can be followed by the suffix BLK for black framed modules. 12 AW G(4 m m2) for residential and commercial rooftops Origins: Silicon:Made in USA&Norway worldwide. Wafer/Cell/Module:Made in Singapore ELECTRICAL oduct Code*:RECxxxTP2 MAXIMUM RATINGS r r 2 tA, NOW � NominalPower-PMPF(Wp) 206 10 214 218 223 226 Operational temperature: -40...+185°F(-40...+85°C) WITH NEW Nominal Power Voltage-VMPP(V) 29.2 29.4 29.6 29.8 30.0 30.1 Maximum system voltage: 1000V WAR A�tY� `GI/�/ Nominal Power Current-I.,(A) 7.07 7.15 7.24 7.32 7.43 7.51 Design Loads: (+)75.2lbs/ft2(3600Pa) Open Circuit Voltage VOLV (V 35.4 35.6 35.8 36.0 36.2 36.3 (-)33.4Ibs/ft2(1600Pa) • ShortCircuitCurrent-IJA) 7.52 7.59 7.68 7.75 785 7.91 Referto installation manual Nominal operating cell temperature NOCT(800 W/m�,AM 1.5,windspeed 1 m/s,ambient temperature 20°C). Oax series fuse rating: 20 A 'Wherexxx indicatesthe nominal power class(PMpp)at STC above,andcan be followed by the suffix BLK for black framed modules. Max reverse current: 20A O1 0 CERTIFICATIONS1A _ Q 20yearproductwarranty Dimensions: 65.9x39.25x1.5(1675x997x38mm) DVE e SP 25 year knear power output warranty 2 c us Area: 1798ft2(1.67m ) (Max.performance degression of 0.5%p.a.from 975%in yearly 4 UL1703,Fire Classification Type 2;IEC 61215,IEC 61730, Seewarranty conditions forfurther details. Weight: 40.8 lbs(18.5 kg) o IEC 62804(PID),IEC 62716(Ammonia),IEC 61701(Salt Mist level6), z IEC 60068-2-68(Blowing Sand),ISO 11925-2(Class E) ISO 9001:2015,1So14001:2004,OHSAS18001:2007 Note!Specifications subject to change without notice. Mr INTEGRATED MANUFACTURING IN SINGAPORE REC www.recgroup.com (("20,8MF?WAFERS CELLS OVULESSolar PowerNV•GL a w a r a w i n n e r PV MODULE RELIABILITY SCORECARD Single Phase Inverter Wit HD-Wave Tec n0 ogy for North America SE3000H-US / SE380OH-US / SE5000H-US / SE6000H-US/ Single Phase Inverter Z SE760OH-US / SE1000OH-US / SE1140OH-US SE300OH-US ,0, 00,O OUTPUT with HID-Wave TechnologyRated AC Power Output 3000 3800 @ 240V 5000 6000 @ 240V 7600 10000 11400 @ 240V VA 3300 @ 208V 5000 @ 208V 10000 @ 208V Maximum AC Power Output 3000 3800 @ 240V 5000 6000 @ 240V 7600 10000 11400 @ 240V VA for North America ;a_ 3300 @ 208V 5000 @ 208V 10000 @ 208V AC Output Voltage Min.-Nom.-Max. Vac 64) SE3000H-LIS / SE380OH-US / SE5000H-US / SE6000H-US / (211 AC Output Voltage Min.-Nom.-Max. � � � Vac SE760OH-LIS / SE1000OH-US / SE1140OH-US ACFre u 229) n AC Frequency(Nominal) 59.3-60-60.50I Hz Maximum Continuous Output 12 5 16 21 25 32 42 47.5 A 7 Current Conti 0 YEAR Maximum Continuous Output _ 16 24 48.5 A solarg�jtg' —HD:.,... � •� Current @208V GFDI Threshold 1 A Ln Utility Monitoring,Islanding • solar=—-- ,,,� , • Protection,Country Configurable Yes Thresholds INPUT L•1 Maximum DC Power @240V 4650 5900 1 7750 1 9300 1 11800 1 15500 1 17650 W Maximum DC Power @208V 5100 1 7750 15500 W O _ • Transformer-less,Ungrounded Yes '_• Maximum Input Voltage 480 Udc •• • • Nominal DC Input Voltage 380 400 Vdc Maximum Input Current @240VI2l 8.5 10.5 13.5 16.5 20 27 30.5 Adc • • b • Maximum Input Current @208VI2l - 9 13.5 - 27 Adc Max.Input Short Circuit Current 45 Adc O • Reverse-Polarity Protection Yes O • Ground-Fault Isolation Detection 6001m Sensitivity Maximum Inverter Efficiency 99 99.2 % CEC Weighted Efficiency 99 99 @ 240V % 98.5 @ 208V O O • • Nighttime Power Consumption <2.5 W W W ADDITIONAL FEATURES Supported Communication Interfaces RS485,Ethernet,ZigBee(optional),Cellular(optional) Revenue Grade Data,ANSI C12.20 Optionalal Rapid Shutdown-NEC 2014 and Automatic Rapid Shutdown upon AC Grid Disconnect Optimized installation with HD-Wave technology 2017690.12 STANDARD COMPLIANCE Safety UL1741,UL1741 SA,UL1699B,CSA C22.2,Canadian AFCI according to T.I.L.M-07 / Specifically designed to work with / Extremely small Grid Connection Standards IEEE1547,Rule 21,Rule 14(Ho power optimizers Emissions FCC Part15 Class B / Record-breaking efficiency / Built-in module-level monitoring INSTALLATION SPECIFICATIONS AC Output Conduit Size/AWG 3/4'minimum/14-6 AWG 3/4'minimum/14-4 AWG Range / Fixed voltage inverter for longer strings / Outdoor and indoor installation DC Input Conduit Size/#of Strings/ 3/4•minimum/1-2 strings/14-6AWG 3/4'minimum/1-3 strings/14-6 AWG AWG Range Dimensions with Safety Switch 17.7 x 14.6 x 6.8/450 x 370 x 174 21.3 x 14.6 x 7.3/540 x 370 x 185 in/ / Integrated arc fault protection and rapid shutdown for / Optional: Revenue grade data,ANSI C12.20 (HxWxD) mm NEC 2014 and 2017, per article 690.11 and 690.12 Class 0.5 (0.5%accuracy) Weight with Safety Switch 22/10 125.1/11.4 26.2/11.9 38.8/17.6 lb/kg Noise <25 <50 dBA / UL1741 SA certified,for CPUC Rule 21 grid Cooling Natural Convection compliance Operating Temperature Range -40 to+140/-25 to+6011t(-40'F/-40'C option) 'F/'C Protection Rating NEMA 4X(Inverter with Safety Switch) M For other regional settings please contact SolarEdge support solar I a r=@ " (3)A higher current source may be used;the inverter will limit its input current to the values stated cap Revenue grade inverter P/N:SExxxxH-USOOONNC2 soIaredge.comr4I For power de-rating information refer to:https://www.solaredge.com/sites/defauVfiles/se-temperature-derating-note-na.pdf rsi-40 version P/N:SExxxxH-US000NNU4 ©SolarEdge Technologies,Inc.All rights reserved.SOLAREDGE,the SolarEdge logo,OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies,Inc All Ro H S other trademarks mentioned herein are trademarks of their respective owners.Date:12/2018N01/ENG NAM.Subject to change without notice. Power Optimizer For North America ma P320 / P340 / P370 / P400 / P401 / P405 / P485 / P505 Power Optirinizer L . . O .. . . For North America ' '' power (for 72& (for high- (for high- (for higher .. .� .� . ..11 cell .. .. .. modules) P320 / P340 / P370 / P400 / P401 / P405 / P485 / P505modules) INPUT I modules) MRated Input DC Power") 320 340 370 400 405 485 505 W Absolute Maximum Input Voltage 48 60 80 60 1251zj 8312j Vdc (Voc at lowest temperature) MPPT Operating Range 8-48 8 60 8-80 8-60 12.5-105 12.5-83 Vdc Maximum Short Circuit Current 11 10.1 11.75 11 14 Adc YEAR (Isc) RRANTY O Maximum Efficiency 99.5 % Weighted Efficiency 98.8 98.6 % Overvoltage Category II OUTPUT DURING OPERATION (POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER) Maximum Output Current 15 Adc WA Maximum Output Voltage 60 85 Vdc OUTPUT DURING STANDBY(POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR SOLAREDGE INVERTER OFF) Safety Output Voltage per Power Optimizer ±0.1 Vdc STANDARD COMPLIANCE EMC FCC Part15 Class 8,IEC61000-6-2,IEC61000-6-3 - Safety IEC62109-1(class II safety),UL1741 Material UL94 V 0, Resistant RoHS Yeses INSTALLATION SPECIFICATIONS Maximum Allowed System 1000 VdC Voltage Compatible inverters All SolarEdge Single Phase and Three Phase inverters 129x153x33.5 129x153x29.5 129x162x59/ mm Dimensions(W x L x H) 129x153x27.5/5.1x6x1.1 /5.1x6x1.3 /5.1x6x1.16 129x159x49.5/5.1x6.3x1.9 5.1x6.4x2.3 /in Weight(including cables) 630/1.4 750/1.7 655/1.5 845/1.9 1064/2.3 gr/lb Input Connector MC413I Single or dual MC413I MC413xa1 Input Wire Length 0.16/0.52 Output Wire Type/Connector Double Insulated/MC4 Output Wire Length 0.9/2.95 1.2/3.9 m/ft Operating Temperature Rangelsl -40-+85/-40-+185 "C/`F Protection Rating IP68/NEMA6P PV power optimization at the module-level Relative Humidity 0-100 % (1)Rated power of the module at STC will not exceed the optimizer"Rated Input DC Power".Modules with up to+5%power tolerance are allowed (2)NEC 2017 requires max input voltage be not more than 80V Specifically designed to work with SolarEdge or Fast installation with a single bolt 3)For other connector types please contact SolarEdge (4)For dual version for parallel connection of two modules use P485-4NMDMRM.In the case of an odd number of PV modules in one string,installing one P485 dual version power optimizer connected inverters to one PV module.When connecting a single module seal the unused input connectors with the supplied pair of seals. Next generation maintenance with module- (5)For ambient temperature above+85°C/+185°F power de-rating is applied.Refer to Power Optimizers Temperature De-Rating Technical Note for more details. Up to 25% more energy level monitoring PhasePV System Design Using Single Phase Three Superior efficiency (99.5%) Meets NEC requirements for arc fault ' 08 • 277/480V grid protection (AFCI) and Photovoltaic Rapid Minimum String Length P320,P340,P370, 8 10 18 Mitigates all types of module mismatch losses, (Power Optimizers) P400,P401 g yp Shutdown System (PVRSS) P405,P485,P505 6 8 14 from manufacturing tolerance to partial Maximum String Length(Power Optimizers) 25 25 50(8) shading Module-level voltage shutdown for installer 5700(6000with Maximum Power per String SE7600-US SE11400- 5250 600010I 127501101 W and firefighter safety US) Flexible system design for maximum space Parallel Strings of Different Lengths or Orientations Yes utilization (6)For detailed string sizing information refer to:http://www.solaredge.com/sites/default/files/string-sizing-na.pdf V It is not allowed to mix P405/P485/P505 with P320/P340/P370/P400/P401 in one string (8)A string with more than 30 optimizers does not meet NEC rapid shutdown requirements;safety voltage will be above the 30V requirement (9)For 208V grid:it is allowed to install up to 7,200W per string when the maximum power difference between each string is 1,000W (10)For 277/480V grid:it is allowed to install up to 15,000W per string when the maximum power difference between each string is 2,000W T s o l a rZvi ®SolarEdge Technologies Ltd.All rights reserved.SOLAREDGE,the SolarEdge logo,OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks ofSolarEdge Technologies,Inc. RoHS soIaredge.comAll other trademarks mentioned herein are trademarks of their respective owners.Date:07/2020/V02/ENG NAM.Subject to change without notice. Intertek SOLARMOUNT no U N I RAC SOLARMOUNT is the professionals' choice for residential PV mounting applications. Every aspect of the system is designed for an easier, faster installation experience. SOLARMOUNT is a complete solution with revolutionary universal clamps, FLASHKIT PRO, full system UL 2703 certification and 25-year warranty. Not only is SOLARMOUNT easy to install, but best-in-class aesthetics make it the most attractive on any block! 2 New & Improved: r OPTIONAL Y AR THE PROFESSIONALS' CHOICEWARRANTY With Superior Aesthetics EL NOW FEATURING FLASHKIT PRO NOJ11TH UNIVERSAL MIDCLAMPS REVOLUTIONARY NEW ENDCLAMPS The Complete Roof Attachment Solution Accommodates 30mm-51mm module frames Concealed design and included End Caps FEATURING*FxoFasten Solar' TECHNOLOGY One tool,one-person installs are here! THE PROFESSIONALS' CHOICE FOR RESIDENTIAL RACKING BEST INSTALLATION I EXPERIENCE 1 CURB 1 APPEAL 11 COMPLETE I SOLUTION I 1 1 SUPPORT 111 SOLARMOUNT ." UNIRAC BETTER DESIGNS TRUST THE INDUSTRY'S BEST DESIGN TOOL CONCEALED UNIVERSAL o Start the design process for every project in our U-Builder on-line design tool. ENDCLAMPS It's a great way to save time and money. BETTER SYSTEMS ONE SYSTEM-MANY APPLICATIONS Quickly set modules flush to the roof on steep pitched roofs. Orient a large variety of modules in Portrait or Landscape.Tilt the system up on flat or low slow roofs. � END CAPS INCLUDED Components available in mill,clear,and dark finishes to optimize your design financials WITH EVERY ENDCLAMP and aesthetics. Lq BETTER RESULTS MAXIMIZE PROFITABILITY ON EVERY JOB Trust Unirac to help you minimize both system and labor costs from the time the job is quoted to the time yourteams get off the roof.Faster installs.Less Waste.More Profits. UNIVERSAL SELF BETTER SUPPORT STANDING MIDCLAMPS WORK WITH THE INDUSTRIES MOST EXPERIENCED TEAM Professional support for professional installers and designers. You have access to our technical support and training groups. Whatever your support needs, we've got you covered.Visit Unirac.com/solarmount for more information. - U-BUILDER ONLINE DESIGN 11i_l 1,1® TOOL SAVES TIME & MONEY o BONDING&GROUNDING �LJ CD CD CD C-D �Q��Q�� Visit design.unirac.com w 9 N MECHANICAL LOADING SYSTEM FIRE CLASSIFICATION UNIRAC CUSTOMER SERVICE MEANS THE HIGHEST LEVEL OF PRODUCT SUPPORT UNMATCHED CERTIFIED ENGINEERING BANKABLE DESIGN PERMIT EXPERIENCE QUALITY EXCELLENCE WARRANTY TOOLS DOCUMENTATION TECHNICAL SUPPORT CERTIFIED QUALITY PROVIDER BANKABLE WARRANTY Unirac's technical support team is dedicated to answering Unirac is the only PV mounting vendor with ISO certifications Dont leave your project to chance, Unirac has the financial questions & addressing issues in real time. An online for 9001:2008, 14001:2004 and OHSAS 18001:2007, strength to back our products and reduce your risk. Have library of documents including engineering reports, which means we deliver the highest standards for fit, peace of mind knowing you are providing products of stamped letters and technical data sheets greatly form, and function. These certifications demonstrate our exceptional quality.SOLARMOUNT is covered by a 25 year simplifies your permitting and project planning process. excellence and commitment to first class business practices. limited product warranty and a 5 year limited finish warranty. ENHANCE YOUR REPUTATION WITH QUALITY RACKING SOLUTIONS BACKED BY ENGINEERING EXCELLENCE AND A SUPERIOR SUPPLY CHAIN PUB2016MAY16-PRINTED UPDATE 0 NO UNIRAC FLASHKIT PRO FEATURING OO SHED&SEAL TECHNOLOGY FLASHKIT PRO is the complete attachment solution for composition shingle roofs. Featuring Unirac's patented SHED & SEAL technology, a weather proof system which provides the ultimate protection against roof leaks. Kitted in 10 packs for maximum convenience, flashings and hardware are available in Mill or Dark finishes. With FLASHKIT pro, you have everything you need for a quick, professional installation. I � tj�70 TRUSTED WATER SEAL FLASHINGS YOUR COMPLETE SOLUTION CONVENIENT 10 PACKS FEATURING 0 SHED&SEAL TECHNOLOGY Flashings,lags,continuous slot L-Feet and hardware Packaged for speed and ease of handling THE COMPLETE ROOF ATTACHMENT SOLUTION CUSTOMERFOR QUESTIONS OR FLASHKIT PRO IN INSTALLATION GUIDE FEATURING!V/SHED&SEAL TECHNOLOGY FLASHKIT PRO IS THE COMPLETE FLASHING AND ATTACHMENT SOLUTION FOR COMPOSITION ROOFS. INSTALL FLASHKIT PRO FLASHING INSTALL L-FOOT ATTACH L-FOOTTO RAIL PRE-INSTALL •Drive the lag bolt down until the L-foot is held firmly in place. It is normal for the EPDM on the underside of the stainless steel backed •Locate roof rafters and snap chalk lines to mark the installation EPDM washer to compress and expand beyond the outside edge of point for each roof attachment. the steel washer when the proper torque is applied. •Drill a 7/32" pilot hole at each roof attachment. Fill each pilot hole TIP: with sealant. •Use caution to avoid over-torqueingthe lag bolt if using an impact driver. STEP 1 INSTALL FLASHKIT PRO FLASHING •Repeat Steps 1 and 2 at each roof attachment point. •Add a U-shaped bead of roof sealant to the underside of the flashing STEP 3 ATTACH L--FOOT TO RAIL with the open side of the U pointing down the roof slope. Slide the aluminum flashing underneath the row of shingles directly up •Insert the included 3/8"-16 T-bolts into the lower slot on the Rail slope from the pilot hole as shown.Align the indicator marks on the (sold separately), spacing the bolts to match the spacing between lower end of the flashing with the chalk lines on the roof to center the roof attachments. the raised hole in the flashing over the pilot hole in the roof.When installed correctly,the flashing will extend under the two courses of •Position the Rail against the L-Foot and insert the threaded end of shingles above the pilot hole. the T-Bolt through the continuous slot in the L-Foot.Apply anti-seize to bolt threads to prevent galling of the T-bolt and included 3/8" serrated flange nut. Place the 3/8" flange nut on the T-bolt and STEP 2 INSTALL L-FOOT finger tighten.Repeat STEP 3 until all L-Feet are secured to the Rail with a T-bolt.Adjust the level and height of the Rail and torque each •Fasten L-foot and Flashing into place by passing the included lag bolt to 30ft-lbs. bolt and pre-installed stainless steel-backed EPDM washer through the L-foot EPDM grommet,and the raised hole in the flashing, into the pilot hole in the roof rafter. FASTER INSTALLATION . 25-YEAR WARRANTY. 1 ' QUESTIONS 1 ' CUSTOMER SERVICE VISIT UNIRAC.COM1 ' 1 1 Unirac Technical D- - - - ::�UNIRAC - Technical � - - - - ::� UNIRAC 2-Piece Aluminum Standoff with SolarMount-I 1-flange connection Part No. 05013C, 05014C, 05016C, 05017C 2-Piece Standoff Technical Datasheet Reference the SolarMount-I series datasheet for 1-flange connection Pub 101026-1td V1.0 October 2010 specifications. For the 1-flange connection to standoff: •2-Piece Aluminum Standoffs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Use included 1 %" EPDM washer between the 1-flangeconnection and standoff 2-Piece Aluminum Standoff with SolarMount-I 1-flange connection . . . . . . . . . . . . . . . . . . . . 2 Y Assemble with included 300 series stainless steel'/8"-16 flanged 2-Piece Aluminum Standoff with L-foot connection . . . . . . . . . . . . . . . . . . . . . . 2 Z hex head screw X Use anti-seize and tighten to 30 ft-Ibs of torque Allowable and design loads are valid when components are assembled Standoffs ,` according to authorized Unirac documents. 1-Flange connections are compatible with SolarMount-I series beams. 2-Piece Aluminum Standoffs Resistance factors and allowable loads are determined according to part 1A Part No. 310503, 310504, 310506, 310507, 310553, 310554, 310556, 310557, 310603, 310604, 310606, 310607, section 9 of the 2005 Aluminum Design Manual. 310653, 310654, 310656, 310657 NOTE: Loads are for the connection and standoff only. Check load limits Standoff and Base Material: for the lag screw or other attachment method. • One of the following extruded aluminum alloys: 6005-T5, Average Allowable Safety Design Resistance 6105-T5,6061-T6 • Ultimate tensile: 38 ksi;Yeild: 35 ksi Ultimate Load Factor, Loads Factor, Y Applied Load Direction Ibs(N) Ibs(N) FS Ibs(N) CD Clear or Dark anodized t _Z Weight: Tension,Y+ 1415(6294) 635(2825) 2.23 960(4270) 0.679 '�• X 3"Standoff(as shown): 0.522 pounds(237 g) Compression,Y- 1949(8670) 873(3883) 2.23 1320(5872) 0.677 �1 Add 0.086 pounds per inch (39 g/inch) Transverse,X-,downhill 635(2825) 313(1392) 2.03 473(2104) 0.745 Q'I © Transverse,X+, uphill 42 187 20 89 2.15 30 133 0.705 Allowable and design loads are valid for a Unirac 2-piece p ( ) ( ) ( ) aluminum standoff 559 ft Ibs 250 ft Ibs 378 ft Ibs Attach with zinc plated carbon steel or stainless steel fasteners OZ Bending,Applied Moment (758 Nm) (339 Nm) 2.24 (512 Nm) 0.676 3 MIN 1'� Resistance and safety factors are determined according to Part 1A section 9 of " 2-Piece Aluminum Standoff with L-foot connection T'MAX 0.31 the 2005 Aluminum Design Manual Reference the SolarMount datasheet for L-foot specifications. NOTE: Loads are given for the standoff only. Check load limits for lag screw or other attachment method. For the L-foot to standoff connection: • Use included 1 %" EPDM washer between the L-foot and standoff 3.75 Assemble with included 300 series stainless steel%"-16 flanged 00,36 Average hex head screw Ultimate Allowable Safety Design Resistance Use anti-seize and tighten to 30 ft-Ibs of torque 2.50' O Applied Load Load Load Factor, Load Factor, Direction Ibs(N) Ibs(N) W Ibs(N) F Y Allowable and design loads are valid when components are assembled according Z to authorized Unirac documents. 2.75 Tension/ Compression, 3266 1089 3.00 1633(7264) 0.500 X L-feet are compatible with SolarMount, SolarMount Heavy Duty, Dimensions specified in inches unless noted y+ (14528) (4844) and SunFrame rails. UZ Bending, 559 ft Ibs 250 ft Ibs 378 ft Ibs Resistance factors and allowable loads are determined according to part 1A Applied 2.24 0.676 section 9 of the 2005 Aluminum Design Manual. Moment (758 Nm) (339 Nm) (512 Nm) NOTE: Loads are for the connection and standoff only. Check load limits "Example: If the module is mounted 6"(0.5 ft)from the base of the standoff, for the lag screw or other attachment method. the allowable side load is 250 ft*lbs/0.5 ft=500 Ibs Average Allowable Safety Design Resistance Ultimate Load Factor, Loads Factor, Applied Load Direction Ibs(N) Ibs(N) FS Ibs(N) (1) Tension,Y+ 1859(8269) 707(3144) 2.63 1069(4755) 0.575 Compression,Y- 3258(14492) 1325(5893) 2.46 2004(8913) 0.615 Sliding,Z± 1766(7856) 755(3356) 2.34 1141 (5077) 0.646 Transverse,X± 486(2162) 213(949) 2.28 323(1436) 0.664 559 ft Ibs 250 ft Ibs 378 ft Ibs UZ Bending,Applied Moment (758 Nm) (339 Nm) 2.24 (512 Nm) 0.676 aDelivering • • Innovation CHEMLINK® Step 1 _ *V E-CURBr'"SYSTEM Remove all previously applied caulk, mastic, cement, Advanced Architectural Products PENETRATION SEALS asphalt, and other contaminants from penetrations with a wire brush. Clean all smooth substrates with f.. CC0V0ra,CZ&r VrOyelvv isopropyl or denatured alcohol. Brush away all gravel or loose granules. Seal the base of each penetration with M-1. Coat penetrations with M-1 to 3"above the Technical Data Guide Polyether Technology CSI Section No. 07 12 13 roof line. CHEM LINK Products, LLC Last Revision: 02/20/13 Distributed by: BEST MATERIALS ® Document No. L1350 f 1r Ph: 800-474-7570, 602-272-8128 Step 2 Fax: 602-272-8014 Hold a section of E-Curb, flat side up, and apply www.BestMaterials.com a 1/4" bead of M-1 to the entire bottom perimeter. Email: Sales@BestMaterlals.com Apply 1 additional 1/4" bead of M-1 down the center of the section. Do not tool the beads flat. Place the Product Description E-Curb section on the roof surface to form a half circle `~-r i E-Curb penetration seals replace old-style metal around the penetration(s). Press down firmly until M-1 pitch pans with versatile, precast components and extrudes from the outside edges. pourable sealants. CHEM LINK's E-Curb System can usually be installed in under 15 minutes and never requires flashing or mechanical attachment. '' E-Curbs are designed for use on granulated modified ,_:r. .-,_ WStep 3 , bitumen,asphalt and coal tar B.U.R.(built up roofing). i r..w :r Apply M-1 to the second section of E-Curb as described � .; above. Place the second section of curb on the roof E-Curbs are specified for PVC, EPDM, PIB,and TPO surface to form a circle with the first section. Press single ply roofing membranes. E-Curbs are highly '* *=•''" 'r,-"r firmly in place until excess adhesive extrudes from the versatile for sealing penetrations around solar panel E-Curb System Components outside edges. Apply a bead of M-1 around the outside mounts, HVAC, Electrical, and any type of structural • E-Curb exterior rings, straights, and corners. base of the installed E-Curb,and tool to form a smooth supports. TPO Primer is required for use with TPO fillet. For non E-Curb penetrations seals, add M-1 to = �, single-ply roof membrane. • M-1 Structural Adhesive/Sealant used for bonding scarf joint surfaces and tool smooth. When installed properly,this system forms a durable, the E-Curb components, sealing and priming the waterproof rubber seal around penetrations. An penetration. extended manufacture warranty against leaks is • 1-Part"moisture cure" pourable sealer, used to Step 4 . activated with submittal of a completed warranty card. form a durable, water-tight seal around the roof Cut tip off 1-Part cartridge at widest point on plastic , ;22(t penetration. nozzle and pierce the foil seal. Insert into caulking gun Special Characteristics • Rapid installation -"Slip-fit" light weight curb design E-Curb precast form components are composed of and pump E-Curb full. When using a 1-Part pouch, 1 reduces labor significantly. light weight nylon resin. The E-Curb is 2-inches high remove cap, pour,squeeze out excess air, and reseal. Note: To provide an adequate rubber seal, maintain a _ • Excellent adhesion to most roofing materials. and is available in a variety of shapes and sizes. 1" distance between penetrations and inside edge of • No flashing or mechanical attachment required. Sizes available include: bi-sected circular pieces the E-Curb. R . •Service Temperature-40°F to 200°F(-40°C to 93°C) having inside diameters of 3,4,6,or 9 inches. Corner 3r •1-Part°accommodates movement and is suggested pieces having a 2-inch radius, and 8-inch straight for use on all granulated membranes and details pieces are also available to create larger sizes. The All properties described in this document are derived from testing conducted in laboratory conditions.Properties and performance with excessive movement. outer surface is impervious to ice, corrosion, UV will vary depending on environmental conditions and application technique.Test and evaluate to determine appropriate usage. • For sloped roof applications, substitute DuraLinkTM (ultraviolet)light and ponding water. Visit www.chemlink.com for the Material Safety Data Sheet,Technical Data Guides and full warranty for this product. non-slump adhesive/sealant for 1-Part and M-10 M-1 Structural Adhesive/Sealant is a durable, self- LIMITED WARRANTY: CHEM LINK Products, LLC warrants this product's performance, provided it is properly stored and fixturing moisture cure mastic. Cartridges of M-1 are applied within 1 year.If not satisfied,return remaining product and purchase receipt for refund or replacement of product exclusive Restrictions pp y g p p p p • Do not apply below 30°F (-1°C) supplied in each E-Curb Kit. Components are also of labor or cost of labor.This is the sole and exclusive remedy for defects or failure of this product. User must read and follow the • Do not install if rain is anticipated within 4 hours sold separately. direction of the current Technical Data Guide and MSDS prior to product use. User determines suitability of product for intended • Do not use on Hypalon or smooth APP modified 1-Part is a highly flexible, self-leveling moisture cure use and assumes all risks. Manufacturer shall not be liable for damages (including consequential or incidental damages) in bitumen membrane. For smooth APP, torch down pourable sealer that eliminates mixing. It is also excess of the purchase price,except where such exclusion or limitation is prohibited by state law.THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, WRITTEN OR ORAL, STATUTORY, EXPRESS OR IMPLIED INCLUDING ANY WARRANTY a target of granulated APP before installation. 100% solid rubber, has a very low VOC content, will OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE; except for the above express warranty given by •TPO Primer must be used for TPO applications. not melt or shrink, and is resistant to deterioration. manufacturer,the product is sold with all faults. CHEM LINK PRODUCTS,LLC SHALL NOT BE RESPONSIBLE FOR THE USE • Do not prime bonding surfaces with asphalt primer! It is supplied in 10.1-oz and 28-oz cartridges or 1/2 OF THIS PRODUCT IN A MANNER TO INFRINGE ON ANY PATENT OR ANY OTHER INTELLECTUAL PROPERTY RIGHTS • Do not use asphalt cement as a"night sealant." gallon pouches. Unused sealant can be capped and HELD BY OTHERS.This warranty gives you specific legal rights,and you may also have other rights in the U.S.which vary from Use M-1 for this purpose. reused. state to state. For warranty claim information,call 800-826-1681. • E-Curb kits are designed to contain enough 1-Part NATIONAL ' p• M to fill each curb with displacement in consideration. ROOFING CHEmbw q,L �� ASSOCIATION cry TORS ISO Refer to our penetration calculator under contractor O�D -- MEMBER iih Advanced Architectural Products M -- resources at chemlink.com to verify volumes. '"S'""`E§ sooi:zoa C&ntyactkw ID6ve#v ■■ ; SOLARMOUNT TILT LEGTILT LEG COMPONENTS : ■�■ , ■■ ; LOW & HIGH PROFILE INSTALLATION GUIDE ; PAGE -------------------------------------- ------------------------------------------------------------------------------------------------------ L-FEET NOT INCLUDED t 1/16" IN LEG KITS 1 Total Adjustable Lengths Square Tube Strut 8"to 12" I 8" 8" 18"to 30" 18" 18" 1" 26"to 44" 26" 26" 40"to 72" 40" 40" tA 3/8"DIA. 3/8-16 X 3"HEX BOLT Tilt Leg Square Tilt z 3/8 X 1-1/2"X 1/8" roperties Strut Channel Leg Tube W HD FENDER WASHER Area 0.515 0.4884 in2 l— Weight 0.57 0.56 plf H LA Width 1.625 1.82 in O Height 1.625 1.82 in Section Modulus(X-axis) 0.236 0.275 in3 Section Modulus(Y-axis) 0.261 0.275 in3 Moment of Inertia(X-axis) 0.201 0.2498 in4 1' Moment of Inertia(Y-axis) 0.213 0.2498 in4 LARadius of Gyration(X-axis) 0.625 0.7152 in 2 t— z3/8"DIA. Wrenches and Torque Wrenc lze Recommced Torque - J ®\ 3/8"Hardware I 9/16 *30 w/Anti-Seize W � � m H W 01 N O LEG STRUT STRUT NUT LEG TUBE 3/8-16 X 1-1/4"SS HEX BOLT T 3/8 x 1-1/2"x 1/8"HD T FENDER WASHER 1 13/16" 1/16" 3/8-16 STRUT NUT 3/8-16 SS FLANGE NUT 3/8"BOLT FENDER WASHER ■■ ; SOLARMOUNT TILT LEG ACCEPTABLE APPLICATIONS : �■ ; LOW & HIGH PROFILE INSTALLATION GUIDE ; PAGE --------------------------------------------------------------------------------------------------------------------------------------------- P P O O O 0 O e e PREFERRED TILT LEG ORIENTATION ACCEPTABLE TILT LEG ORIENTATION Avertical leg orientation is acceptable. but DO NOT allow the bottom of the tilt legs for any application to be angled inboard towards the front of the array. For more information on module placement please refer to the SOLARMOUNT installation guide. Remember to comply with module manufacturer clamping requirements 71* CSA � �,� CSA 2=�V Group S0Group 70131735 266909 70185553 2018-10-08 70131735 266909(266909) The grounding of the system is intended to comply with the latest edition of the National Electrical Code,to include NEC 250&690. Local codes compliance is required,in addition to national codes.All 70185553 2018-10-08 grounding/bonding connections are to be torqued in accordance with the Installation Manual and the settings used during the certification testing for the current edition of the project report. The system may employ optimizers/micro-inverters and used for grounding when installed per installation instructions. Mechanical ratings: Downward Design Load(lb/ft2) 113.4 The products listed below are eligible to bear the CSA Mark shown Upward Design Load(lb/ft2) 50.4 with adjacent indicators 'C' and 'US'for Canada and US or with adjacent Down-Slope Load(lb/ft2) 14.7 indicator 'US'for US only or without either indicator for Canada only. Conditions of acceptability: Installation is subject to acceptance of the local inspection authorities having jurisdiction.The certification of these products relates only to the methods of installation,bonding,and grounding as outlined in the Installation Manual for each product. C Dicha eL Ha ffnaq& Michael Hoffnagle Cus CLASS -C531302-POWER SUPPLIES-PHOTOVOLTAICS--PV Racking CLASS -C531382-POWER SUPPLIES-PHOTOVOLTAICS-PV Racking and clamping systems-Certified to pipe in 2"and 3"diameter. US Standards Models: SM SOLARMOUNT Flush-to-Roof is an extruded aluminum rail PV racking system that is installed parallel to the roof in landscape or portrait orientations. UL 2703-1st Edition - Mounting Systems,Mounting Devices,Clamping/Retention Devices,and Ground Lugs for Use with Flat-Plate Photovoltaic Modules and Panels. The system listed is designed to provide bonding/grounding, and mechanical stability for photovoltaic modules. LTR AE-001-2012 - List of Technical Requirements for Photovoltaic Module and Panel racking Systems The system is secured to the roof with the L-Foot components through the roofing material to building structure. Modules are secured to the racking system with stainless steel or aluminum mid clamps and Aluminum end clamps. The modules are bonded to the racking system with the stainless steel bonding mid clamps with piercing points.The system is grounded with 10 AWG copper wire to bonding/grounding lugs.Fire ratings of Class A The manufacturer is required to apply the following markings: with Type 1,2,3,or 10 for steep slope. Tested at 5"interstitial gap which allows installation at any stand-off . Products shall be marked with the markings specified by the particular product standard. height. • Products certified for Canada shall have all Caution and Warning markings in both English and French. L—DQD 507 Rev.2016-02-18 Page l D D 507 Rev.2016-02-18 Page 2 P7H structura ENGINEERS January 14, 2021 Unirac 1411 Broadway Blvd. NE Albuquerque, NM 87102 Attn.: Unirac- Engineering Department Re: Engineering Certification for the Unirac U-Builder 2.0 SOLARMOUNT Flush Rail PZSE, Inc. -Structural Engineers has reviewed the Unirac SOLARMOUNT rails, proprietary mounting system constructed from modular parts which is intended for rooftop installation of solar photovoltaic(PV) panels; and has reviewed the U- builder Online tool.This U-Builder software includes analysis for the SOLARMOUNT LIGHT rail, SOLARMOUNT STANDARD rail, and SOLARMOUNT HEAVY DUTY rail with Standard and Pro Series hardware. All information, data and analysis contained within are based on, and comply with the following codes and typical specifications: 1. Minimum Design Loads for Buildings and other Structures, ASCE/SEI 7-05,ASCE/SEI 7-10, ASCE/SEI 7-16 2. 2006-2018 International Building Code, by International Code Council, Inc.w/Provisions from SEAOC PV-2 2017. 3. 2006-2018 International Residential Code, by International Code Council, Inc.w/Provisions from SEAOC PV-2 2017. 4. AC428, Acceptance Criteria for Modular Framing Systems Used to Support Photovoltaic (PV) Panels, November 1, 2012 by ICC-ES. 5. 2015 Aluminum Design Manual, by The Aluminum Association,2015 Following are typical specifications to meet the above code requirements: Design Criteria: Ground Snow Load =0- 100 (psf) Basic Wind Speed =85- 190 (mph) Roof Mean Height=0-60 (ft) Roof Pitch =0-45 (degrees) Exposure Category= B, C& D Attachment Spacing: Per U-builder Engineering report. Cantilever: Maximum cantilever length is L/3,where "L" is the span noted in the U-Builder online tool. Clearance: 2"to 10" clear from top of roof to top of PV panel. Tolerance(s): 1.0"tolerance for any specified dimension in this report is allowed for installation. Installation Orientation: See SOLARMOUNT Rail Flush Installation Guide. Landscape- PV Panel long dimension is parallel to ridge/eave line of roof and the PV panel is mounted on the long side. Portrait- PV Panel short dimension is parallel to ridge/eave line of roof and the PV panel is mounted on the short side. 1478 Stone Point Drive, Suite 190, Roseville, CA 95661 916.961.3960 F 916.961.3965 vv www.pzse.com 1 of 2 Experience I Integrity I Empowerment P7H structura ENGINEERS Components and Cladding Roof Zones: The Components and Cladding Roof Zones shall be determined based on ASCE 7-05, ASCE 7-10& 7-16 Component and Cladding design. Notes: 1) U-builder Online tool analysis is only for Unirac SM SOLARMOUNT Rail Flush systems only and do not include roof capacity check. 2) Risk Category II per ASCE 7-16. 3)Topographic factor, kzt is 1.0. 4)Array Edge Factor YE= 1.5 5)Average parapet height is 0.0 ft. 6) Wind speeds are LRFD values. 7)Attachment spacing(s) apply to a seismic design category E or less. Design Responsibility: The U-Builder design software is intended to be used under the responsible charge of a registered design professional where required by the authority having jurisdiction. In all cases, this U-builder software should be used under the direction of a design professional with sufficient structural engineering knowledge and experience to be able to: • Evaluate whether the U-Builder Software is applicable to the project, and • Understand and determine the appropriate values for all input parameters of the U-Builder software. This letter certifies that the Unirac SM SOLARMOUNT Rails Flush, when installed according to the U-Builder engineering report and the manufacture specifications, is in compliance with the above codes and loading criteria. This certification excludes evaluation of the following components: 1) The structure to support the loads imposed on the building by the array; including, but not limited to: strength and deflection of structural framing members,fastening and/or strength of roofing materials, and/or the effects of snow accumulation on the structure. 2) The attachment of the SM SOLARMOUNT Rails to the existing structure. 3) The capacity of the solar module frame to resist the loads. This requires additional knowledge of the building and is outside the scope of the certification of this racking system. DIGITAL SIGNATURE If you have any questions on the above, do not hesitate to call. ss\onal Eng. �.��FICATF, Prepared by: do PZSE, Inc.—Structural Engineers 52979 Roseville, CA PAUL K. a P S ne d gR�20NA Expires: 12-31-2023 01/15/2021 1478 Stone Point Drive, Suite 190, Roseville, CA 95661 916.961.3960 F 916.961.3965 vv www.pzse.com 2 of 2 Experience I Integrity I Empowerment to a Address:Intertek Colad NY 13 11 to ek Address:Intertek Colad NY 13 11 Cortland NY 13045 Cortland NY 13045 Total quality.Assured. Telephone: 607-758-6516 Total Quality.Assured. Telephone: 607-758-6516 www.intertek.com www.intertek.com o SE3000A-US/SE380OA-US/SE5000A-US/SE6000A-US/SE760OA-US/SE1000OA-US/ SE1140OA-US/SE3000H-US/SE380OH-US/SE5000H-US/SE6000H-US/SE760OH-US/ Subject: ETL Evaluation of SolarEdge Products to NEC 2017 Rapid Shutdown Requirements SE1000OH-US/SE1140OH-US when the following label is labeled on the side of the inverter: To,whom it may concern Ir 's This letter represents the testing results of the below listed products to the requirements contained in the following Standards: --PHOTOVOLTAIC RAPID National Electric Code, 2017,Section 690.12 requirement for rapid shutdown. SHUTDOWN SYSTEM UL 1741, UL 1741 CRD for rapid shutdown The evaluation was done on the PV Rapid Shutdown System (PVRSS),and covers installations consisting Inverter part number may be followed by a suffix of optimizers and inverters with part numbers listed below. The testing done has verified that controlled conductors are limited to: • 3-ph Inverters: o SE9KUS/SEIOKUS/SE14.4KUS/SE20KUS/SE30KUS/SE33.3KUS/SE43.2KUS/ • Not more than 30 volts and 240 voltamperes within 30 seconds of rapid shutdown initiation SE66.6KUS/SE100KUS;when the following label is labeled on the side of the inverter: outside the array. • Not more than 80 volts and 240 voltamperes within 30 seconds of rapid shutdown initiation AliblarAWI inside the array. The rapid shutdown initiation is performed by either disconnecting the AC feed to the inverter,or—if HOTOVOLTAIC RAPID the inverter DC Safety switch is readily accessible—by turning off the DC Safety switch. SHUTDOWN SYSTEM Applicable products: Inverter part number may be followed by a suffix • Power optimizers: o PB followed by 001 to 350;followed by-ACB or-TFI. If there are any questions regarding the results contained in this report,or any of the other services OP followed by 001 to 500;followed by-LV,-MV,-IV or-EV. offered by Intertek, please do not hesitate to contact the undersigned. P followed by 001 to 850. SP followed by 001 to 350. *When optimizers are connected to 2 or more modules in series,the max input voltage may exceed 80V. Following the implementation of the NEC 2017 rapid shutdown value of 80V max inside of the array at the beginning of 2019, modules exceeding this combined input max voltage will be required to use optimizers with parallel inputs. • 1-ph Inverters: This information is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. This information is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement.Intertek assumes no liability to any party, Intertek's responsibility and liability are limited to the terms and conditions of the agreement.Intertek assumes no liability to any party, other than to the Client in accordance with the agreement,for any loss,expense,or damage occasioned by the use of this information. other than to the Client in accordance with the agreement,for any loss,expense,or damage occasioned by the use of this information. Any observations and results in this report are relevant only to the sample evaluated. Only the Client is authorized to copy and Any observations and results in this report are relevant only to the sample evaluated. Only the Client is authorized to copy and distribute this information and only then in its entirety. distribute this information and only then in its entirety. ©2018 Intertek ©2018 Intertek Version:8-September-2016 Page 1 of 3 GFT-OP-110a Version:8-September-2016 Page 2 of 3 GFT-OP-10a