HomeMy WebLinkAbout13bdh CON . Envelope Leakage Test Report (Blower Door Test) R405.4.2.1 Compliance Permit # Job Information Builder: DR HORTON Community: CREEKSIDE Lot: 13 Address: 9413 POTOMAC DRIVE Unit: City: FORT PIERCE State: FL Zip: 34945 Air Leakage Test Results Passing results must be 7ACH(5O) or less 1562 x 60 _ 15720.9 = 5.9 Method for calculating building volume: CFM(SO) Building Volume ACH(50) 0 Retrieved from architectural plans software calculated Eode PASS FAIL Q Field measured and calculated When ACH(SO) is less than 3, Mechanical Ventilation installation must be verified by building department. Certification of Test Results K402.4..1.2 testing. The auflamg or aweinng unit snaii oe tested and verified as having an air leakage rate of not exceeding 7 air changes per hour in Climate Zones 1 and 2, 3 air changes per hour in Climate Zones 3 through 8. Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g. (50 Pascals). Testing shall be conducted by wither individuals as defined in Section 553.993(5) or (7), F.S. or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of of the buiidi Testing Company Company Name: SUN SEAL LLC Phone: 321-412-0035 I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected compliance path as stated above, either the Prescriptive Method or Performance Method. Date of Test: 02/09/2022 Signature of Tester: __ �, Printed Name of Tester: DANIEL MURPHY License/Certification # 5066440 Issuing Authority I