HomeMy WebLinkAboutSunroom PlanGENERAL NOTES DESIGN CRITERIA: APPLICABLE CODES, REGULATIONS & STANDARDS: 1. THE 2020 FLORIDA BUILDING CODE, 7TH EDITION SPECIFICALLY 'CHAPTER 16 STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM 2_ASCE 7-16 & SEI7 3. ACI318 CONCRETE REFRENCE MANUAL. 4. AA ASM 35 & AA ADM 1 5. AAF GUIDE TO ALUMINUM CONSTRUCTION IN HIGH WIND AREAS. WIND LOADS: 1. FBC TABLE 1604.5, RISK CATEGORY = 1 2. FBC SEC 1609.4, EXPOSURE CATEGORY = C 3. FBC SEC 1609.3, ULTIMATE DESIGN WIND SPEED = 150 MPH DESIGN NOTES: ALLOWABLE DESIGN PRESSURES UTILIZED IN THIS DOCUMENT HAVE BEEN CALCULATED PER THE REQUIREMENTS OF THE FLORIDA BUILDING CODE 7TH EDITION (2020) & ASCE 7-16 USING ALLOWABLE STRESS DESIGN METHODOLOGY WITH THE CRITERIA AS OUTLINED HEREIN. THE CONTRACTOR SHALL CONTACT THE AUTHORITY HAVING JURISDICTION TO ENSURE APPROPRIATE CRITERIA TO BE USED BEFORE CONSTRUCTION BEGINS. THE SYSTEM HAS NOT BEEN DESIGNED TO WITHSTAND CONCETRATED LOADS FROM HUMAN ACTIVITY. DRAWING INDEX SHEET NO. DESCRIPTION G01 GENERAL NOTES S01 STRUCTURAL PLAN F01 FOUNDATION PLAN D01 ROOF & PROJECTION BEAM DETAILS D02 POST & MAIN BEAM DETAILS GENERAL NOTES: 1. THIS DOCUMENT SHALL NOT BE USED OR REPRODUCED WITHOUT THE ORIGINAL SIGNATURE & RAISED SEAL OF CRAIG E. GUNDERSON, P.E. ALTERATIONS, ADDITIONS OR OTHER MARKINGS TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE OUR CERTIFICATION. PHOTOCOPIES AND UNSEALED DOCUMENTS ARE NOT TO BE ACCEPTED. 2. THIS STRUCTURE HAS BEEN DESIGNED AND SHALL BE FABRICATED IN ACCORDANCE WITH THE STRUCTURAL PROVISIONS OF THE FLORIDA BUILDING CODE SEVENTH EDITION (2020). STRUCTURE SHALL BE FABRICATED IN ACCORDANCE WITH ALL GOVERNING CODES. CONTRACTOR SHALL INVESTIGATE AND CONFORM TO ALL LOCAL BUILDING CODE AMENDMENTS WHICH MAY APPLY AND GOVERN. DESIGN CRITERIA OR SPANS BEYOND STATED HEREIN MAY REQUIRE ADDITIONAL SITE SPECIFIC SEALED ENGINEERING. 3. NO 33-1/3% INCREASE IN ALLOWABLE STRESS HAS BEEN USED IN THE DESIGN OF THIS SYSTEM. WIND LOAD DURATION FACTOR Cd=1.6 HAS BEEN USED FOR WOOD ANCHOR DESIGN. 4. THE ARCHITECT/ENGINEER OF RECORD FOR THE PROJECT SUPERSTRUCTURE WITH WHICH THIS DESIGN IS USED SHALL BE RESPONSIBLE FOR THE INTEGRITY OF ALL SUPPORTING SURFACES TO THIS DESIGN WHICH SHALL BE COORDINATED BY THE PERMITTING CONTRACTOR. 5. THE CONTRACTOR SHALL CAREFULLY CONSIDER POSSIBLE IMPOSING LOADS ON ROOF, INCLUDING BUT NOT LIMITED TO ANY CONCENTRATED LOADS WHICH MAY JUSTIFY GREATER DESIGN CRITERIA. THIS ADDITIONAL ROOF LOAD CRITERIA SHALL BE PROPERLY ANALYZED BY A LICENSED ENGINEER OR REGISTERED ARCHITECT. 6. ALL FASTENERS TO BE #12 SAE GRADE 2 OR STAINLESS STEEL 304 UNLESS NOTED OTHERWISE. FASTENERS SHALL BE CADMIUM -PLATED OR OTHERWISE CORROSION -RESISTANT MATERIAL AND SHALL COMPLY WITH "SPECIFICATIONS FOR ALUMINUM STRUCTURES" BY THE ALUMINUM ASSOCIATION, INC., & ANY APPLICABLE FEDERAL, STATE, AND/OR LOCAL CODES. 7. FOR ALUMINUM MEMBERS ALL ANCHORS SHALL BE SPACED WITH 2xDIAMETER END DISTANCE AND 2.5xDIAMETER MIN. SPACING TO ADJACENT ANCHORS, UNLESS NOTED OTHERWISE. 8. ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS. MINIMUM EMBEDMENT SHALL BE AS NOTED HEREIN. MINIMUM EMBEDMENT AND EDGE DISTANCE EXCLUDES STUCCO, FOAM, BRICK, AND OTHER WALL FINISHES. 9. ALL CONCRETE ANCHORS SHALL BE INSTALLED TO NON -CRACKED CONCRETE ONLY. 10. WOOD HOST STRUCTURE & ALL WOOD MEMBERS SHALL BE "SOUTHERN YELLOW PINE" G=0.55 OR GREATER DENSITY. 11. THE CONTRACTOR IS RESPONSIBLE TO INSULATE ALL MEMBERS FROM DISSIMILAR MATERIALS TO PREVENT ELECTROLYSIS. 12. ALL ALUMINUM SHALL BE 6005-T5 ALLOY AND TEMPER UNLESS NOTED OTHERWISE. 13. ALL STEEL ANGLES SHALL BE ASTM A1011 OR A653 GRADE 50 (Fy=50 KSI, Fu=65 KSI) OR BETTER. 14. ALL CONCRETE AND EPDXY TO REACH A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI IN 7 DAYS. 15. ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL DESIGN AS SHOWN ONLY. USE OF THIS SPECIFICATION BY CONTRACTOR, et. al. INDEMNIFIES & SAVES HARMLESS THIS ENGINEER FOR ALL COST & DAMAGES INCLUDING LEGAL FEES & APPELLATE FEES RESULTING FROM MATERIAL FABRICATION, SYSTEM ERECTION, & CONSTRUCTION PRACTICES BEYOND THAT WHICH IS CALLED FOR BY LOCAL, STATE, & FEDERAL CODES & FROM DEVIATIONS OF THIS PLAN. 16. EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL CERTIFICATIONS OR AFFIRMATIONS ARE INTENDED. 17. ALTERATIONS, ADDITIONS, HIGHLIGHTING, OR OTHER MARKINGS TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE THIS CERTIFICATION. SYSTEM NOTES: PERGOLA SHALL BE INSTALLED PER MANUFACTURER'S SPECIFICATION ISSUED BY RENAISSANCE PATIO. REFER TO AFOREMENTIONED MANUFACTURER ISSUED ASSEMBLY MANUAL FOR ALL CONNECTION DETAILS THAT ARE NOT ILLUSTRATED HEREIN. �111111111111///�� �\``\w\` �. o o 0p'• W �: - o C 00 L /'''�//llllllllr REVIEWED FOR CODE COMPLIANCE ST. LUCIIE OLI 30CC ; �z� FILE COPY -7" RENAISSANCE CLASSICO EXPOSED BEAM PATIO COVER PROJECTION BEAMS AT 24" O.C. I 9'-0" 2 II I II I Q I n n w m II Ii a II II II II z II n n II 0 0 bLu II II II 0Of II II d II II II II POST II II I� II - ------- L --- E i WALL MOUNT 3" X .024" X 1LB COMPOSITE PANELS 3003-H154 1/4"-1' SLOPE (MIN.) (FL.# 7561.1-R5) WITH INTERNAL L FAN BEAM - 24'-4" 27'-0" - 24'-4" 0 Bo 0 POST • 04 Z co C) LL 0 /_ Ld N O =0 :U c0 Lu - Q = o O N u j 12 U � p REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY BOC Z Z, 86 WD POST & BEAM SYSTEM PROJECTION BEAM = 2"X6"X0.060" MAIN BEAM = 4.875"X7"X0.125" POST = 6"X6"X0.125" 9 LE COPY SEE SECTION DETAILS ON PAGES D01 & D02 1111111I///// \\\\�olII ... 4��N'� co o 0 w � Q Z cn REVIEWED FOR Hlo CODE COMPLIANCE ST. LUCIE COUNTY BOCC J CDLo G Cl Z,��ZZ Z z p o _ U O U W =, 0 co 0) ATTACH TO CARRY BEAM RECEIVING CHANNEL WITH 6LE C®PY z W W/ #12SELF-DRILLING SCREW #12 SELF DRILLING SCREW r � �-- M � W/ 1" S WTy ASHER @ 8 ' O.C. 1" FROM ENDS TOP & v �-- � STRUCTURAL PROJECTION @6" " O WA BOTTOM OR EITHER SIDE WITH z O C TYP.SCREW THROUGH ENTIRE Q J INSULATED PANEL INTERIOR CLIP PANEL, TYP. PER SEPERATE STRUCTURAL (1) 1/4" DIA. TAPCON WITH CERTIFICATION, TYP. . INSULATED PANEL 2.5" EMBEDMENT INTO 3KSI PER SEPERATE OR GROUT FILLED CELLS WITH 0 < U CERTIFICATION, TYP. p p 5" MIN SPACING & 6" EDGE SCALLOP PROJECTION o . o.. p d DISTANCE @ 24" O.C, TYP. r- INTERIOR CLIP ATTACH USING POST CAP p EXISTING 0 O (2) #14 SELF -DRILLING o o CONCRETE OR CBS r p —, a-, SCREW, TYP. o p pp WALL, TYP. PROJECTION BEAM MAIN PROJECTION p d OPTIONAL (2) 1/4" DIA. TAPCON WITH BEAM BEAM o 2.5" EMBEDMENT INTO 3KSI (4) #14 SELF -DRILLING POST p OR GROUT FILLED CELLS WITH PROJECTION p p 5" MIN SPACING & 6" EDGE SCREW PER SIDE, TYP. PROJECTION • BEAM DISTANCE @ 24" O.C, TYP. INTERIOR CLIP VE TRELLIS/ PROJECTION 5 &POST CONNECTION D01 HOST CONNECTION 4 (CONCRETE OR BLOCK) D01 N co n 0 W U U N 00 M cM M T_ N U) N 0 UM z Z LL U) Q W VU Z_ LL cf)Q LLIH0� o J a 0 00 F- 0 Q 0 O F � O) Z O O a DESIGN DATE: 12/01/2021 REVISION 1: 12/01/2021 PAGE: REVISION 2: 12/01/2021 D01 ROOF & PROJECTION BEAM DETAILS SCALE: NTS MAIN BEAM INTERIOR CLIP ATTACH TO CARRY BEAM W/ #12 SELF -DRILLING SCREW 12 MAX, TYP.� �_@6" W/ 1" OD WASHER O.C, TYP. 1.5" MAX SLIDE BASE PLATE COVER OVER POST & BASE PLATE PqT(OPTIONAL) SLIDE BASE PLATE COVER OVER POST & BASE PLATE ��\1111111111//�� Qom. C4 No LL O J m Q Q /, Z I I WD POST #5 REBAR 12" LONG • :. •••• . • : THROUGH POST, TYP.cq WD POST (4) #14 SELF DRILLING Z Z Q EO SCREW PER SIDE, TYP. U 171 WD BASE PLATE (6) CONCRETE ANCHORS �J•J J O 0 (SEE PAGE 4) W LL Lo N WD BEAM (3) 3/8 X5" BOLT, ~ co .c: WASHER & NUT, TYP. Z O WD POST / Q � �N Q Q WD POST C) U 1 WD BEAM TO POST WD POST EMBEDMENT 3 ANCHOR CONNECTION D02 CONNECTION D022 D02 0(.0 O LL 'd' 0- CD 0 0 o 0 0 POST WD a a a WD POST 0.188 Lo 0 0.125 N Ll L= 4.059 WD POST CLIP 4.875 WD MAIN BEAM 'REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY EOC ?7,llz- 0(9OG FILE ropy POST & MAIN BEAM DETAILS I N O O N 00 O w U U N 00 co M M N U N O UM z Z Z LL U) QW U U Q ai W Z W LOd J -� Q Q 0 00 c OHO w Q On LL DESIGN DATE: 12/01/2021 REVISION 1: 12/01/2021 PAGE: REVISION2: 12/01/2021 DO/ SCALE: NTS _ POST BASE ANCHOR TIE - DOWN SCHEDULES: ANCHOR TYPES: (6) 1/4" DIA ITW TAPCON, 1/4" DIA. SAE GRADE WASHER, 1.75" EMBEDMENT, ANCHOR TYPE #1 2.5" SPACING, 3" MIN. EDGE DISTANCE INTO 3KSI MIN. CONCRETE (6) 1/4" DIA BLUE TAP ANCHOR WITH 2.1" EMBEDMENT, INTO 3KSI MIN. ANCHOR TYPE #2 CONCRETE 2.5" SPACING, 3" MIN. EDGE DISTANCE 1 ANCHOR SCHEDULE F01 SCALE: N. T. S 1" 2 5" u1I 00 3 g 2 ANCHORS TO BASE PLATE F01 SCALE: N. T. S #4 DOWEL @ 4O.C. MAX. & 5' FROM EDGES 6" EMBEDMENT INTO NEW SLAB & 6' MIN INTO EXISTING FOUNDATION NEW 4" SLAB 3000 PSI W/ FIBERMESH EXISTING FOUNDATION -►i- SLAB EXTENSION TYPICAL SLAB EXTENSION DETAIL SCALE: N.T.S. ,, ,, ,, ,,', ''00 ,,, ,, NEW 4" SLAB _ ,,,,,,,,,', 3000 PSI MIN. ,',',','; ,'; ,'; ; ; ,',',',',',',','; ; o Ln ,,, ,',, o ,,, ,,,,, ...................................I ,,,,,,,, ','„',', ,, ,,, 24'-4" 25'-0" FOUNDATION PLAN �� C- \ c z 'o o :z LL O I F- Z R V IED FOR CODS: COMPLIANCE ST. LUCIE COUNTY BOCC 2i�6 2 —v coon L/ z 5 yz z Flil,,,,F, COPY