Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutRevisionDIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION
SECTION: 07 2100—THERMAL INSULATION
REPORT HOLDER:
DEMILEC (USA) INC.
3315 EAST DIVISION STREET
ARLINGTON, TEXAS 76011
EVALUATION SUBJECT:
SEALECTlOW 500 SPRAY -APPLIED POLYURETHANE FOAM INSULATION
ICC . ICC ICC
C PMG Isr
Look for the trusted marks of Conformity!
"2014 Recipient o Prestigious States Seismic Policy Council ti w5
P f 9 Y
(WSSPC) Award in Excellence:"
ICC ES Evahtation Reports are not to be construed as representing aesthetics or1f othe of
specifically addressed, nor are they. to be construed as an endoisemeint of the sit b1 ©,l
recommendation for its use. There is no warranty by ICC Evaluation Setvice,' LLC, �t oa•
to any finding or other matter in this report, or as to any product covered by the report.
Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved.
.mo
IMES Evaluatioh Report ESR-1172
Reissued February 2016
This report is subject to renewal February.2017.
www..lce-es.org 1 (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council®
DIVISION: 07 00 00—THERMAL AND MOISTURE
PROTECTION
Section: 0121 00—Thermal Insulation
REPORT HOLDER:
DEMILEC (USA) INC. ,
3315 EAST DIVISION STREET
ARLINGTON, TEXAS 76011
(817)IM-4900
WWWi demiiectisa.com
inf6A_dem ilecusa.com,
EVALUATION SUBJECT:
SEALECTION® 500 SPRAY -APPLIED POLYURETHANE
FOAM INSULATION
1.0 EVALUATION SCOPE
1.1 Compliance with the following codes:
0 2015, 2012 and 2009 International Building Code® (IBC)
■ 2015, 2012 and 2009 International Residential Code®
(IRC)
■ 2015, 2012 and 2009 Infernational _Energy Conservation
Code® (IECC)
■2013 Abu Dhabi Jnternational Building Code (ADIBC)t
tThe ADIBC is based on, the 2009 IBC. 2009 IBC code'sections referenced
in this report are the same sections In the ADIBC.
p Other Codes (see Section 8.0)
Properties evaluated:
■ Surface -burning characteristics
■ Physical properties
■ Thermal resistance
■ Attic and crawl space installation
■ Air permeability
■ Fire -resistance -rated construction,
■ Exterior walls in Type I through IV construction
1.2 Evaluation to the following green green standard:
■ 2008 ICC 700 National Green Building Standard"' (ICC
700-2008)
Attributes verified:
■ See Section 2.0
2.0 USES -
SEALECTION® 500 spray -applied polyurethane foam
insulation is used as a nonstructural thermal insulating
material in Type I, II, III,. IV and Type V construction under
the IBC and in dwellings under the IRC. The insulation is
for use in wall cavities, floor/ceiling assemblies, or attics
and crawl spaces when installed in accordance _with
Section 4.0. Under the IRC and the 2015 IBC, the
insulation may be used as air -impermeable insulation
when installed in accordance with Section 3.4. The
insulation may be used in nonload-bearing, fire -resistance -
rated walls when construction is in accordance with
Section 4.5.
The attributes of the insulation have been verified as
conforming to the provisions of ICC 700=2008 Section
703.2.1.1.1(c) as an air impermeable insulation. Note that
decisions on compliance for those areas rest with the user
of this report. The user is advised of the project -specific
provisions that may be contingent upon meeting specific
conditions, and the verification of those conditions is
outside the scope of this report. These codes or standards
often provide supplemental 'information as guidance.
3.0 DESCRIPTION
3.1 Materials:
SEALECTION® 500 spray -applied foam insulation is
semirigid, low -density, polyurethane foam plastic that is
installed . as a component of floor/ceiling and wall
assemblies. The insulation is a two -component spray foam
plastic with a nominal in -place density of 0.) 5 pcf (8 kg/M .
The insulation is produced in the field. by combining a
polymeric isocyanate (A-PMDI component, A -Side ISO)
with a polymeric resin (SEALECTION® 500 B-Side
component). The insulation liquid components are supplied
in 55-gallon (208 L) drums and/or 250-gallon (946 L) totes
and must be stored at temperatures between 509F (1011C)
and 100aF (38°13). The liquid components have a shelf life
of one year when stored in factory -sealed containers at
these temperatures.
3.2 Surface -burning Characteristics:
The insulation, at a. maximum thickness..of 6 inches
(152 mm) and a nominal density of 0.5 pcf (8 k9/m3), has a
flame -spread index of 25 or less and a smoke -developed
index of 450 or less when tested in accordance with ASTM
E84. Greater thicknesses are recognized as described in
Sections 4.3 and 4.4. SEALECTION® 500 thickness is not
limited when separated from the interior of the building by
a prescriptive thermal barrier as complying with the IBC or
IRC and as described in Section 4.3.1.
3.3 Thermal Resistance, R-values:
The insulation has thermal resistance (R-value) at a mean
temperature of 756F (24°C) as shown in Table 1.
]CC --ES Evahtarion Reports are not to be constnted as represeniiitg aesthetics or any Oder attributes not speeifically addressed, nor are they to be construed
as an endorsement of the sabjecr of the.report or a recommendation for its use. There is no warranty by ICC Evaluation Semice, LLC express or implied, as
to any finding or other matter in this report, or as to any -product covered by the report
Copyright© 2016 ICC Evaluation service; LLC. All rights reserved.
�eYa
Page 1 of 6
ESR-1172 1 Most Widely Accepted and Trusted Page 2 of 5
3.4 Air Permeability:
SEALECTION® 500 spray -applied polyurethane foam
insulation, at a minimum thickness of 3.0 inches (76 mm),
is considered air -impermeable insulation in accordance
with 2015 and 2012 IRC Section R806.5 .(2009 IRC
Section R806.4) and 2015 IBC Section 1203.3, based on
testing in accordance with ASTM E2178.
3.5 BlazelokTm IB4 Intumescent Coating:
BlazelokTM 164 intumescent coating, manufactured by
TPRZ Corporation, is a one -component, water -based liquid
coating with specific gravity of 1.3. BlazelokTm 164 is
supplied in 5-gallon (19 L) pails and/or 55-gallon (208 L)
drums and has a shelf life of one year when stored in
factory -sealed containers at temperatures between 45°F
(7°C) and 90°F (321C).
3.6 BlazelokTM TB Intumescent Coating:
BlazelokTM TB intumescent coating, manufactured by TPRZ
Corporation, is a one -component, water -based liquid
coating with specific gravity of 1.3. BlazelokTM TB is
supplied in 5-gallon (19 L) pails and/or 55-gallon (208 L)
drums and has a shelf life of one year when stored in
factory -sealed containers at temperatures between 450F
(7°C) and 90°F (32°C).
3.7 BlazelokTM TBX Intumescent Coating:
BlazelokTM TBX intumescent coating, manufactured by
TPRZ Corporation, is a one -component, water -based liquid
coating with specific gravity of 1.4. BlazelokTM TBX is
supplied in 5-gallon (19 L) pails and/or 55-gallon (208 L)
drums and has a shelf life of one year when stored in
factory -sealed containers at temperatures between 45°F
(7°C) and 90OF (320C).
3.8 Andek Firegard Intumescent Coating:
Andek Firegard intumescent coating, manufactured by
Andek Corporation, is a one -component, water -based
coating with specific gravity of 1.37. Andek Firegard is
supplied in 5-gallon (19 L) pails and has a shelf life of one
year when stored in factory -sealed containers at
temperatures between 45°F (7°C) and 90OF (320C).
3.9 No -Burn 'Plus XD Intumescent Coating:
No -Burn® Plus XD intumescent coating, manufactured by
No -Burn, Inc., is a translucent aqueous liquid in 1- and
5-gallon (3.8 and. 18.8 L) pails and 55-gallon (208 L)
drums. The coating has a shelf life of three years when
stored in a factory -sealed container at temperatures
between 40°F (4.5°C) and 90°F (321C).
3.10 DC 315 Fireproof Paint:
DC 315, manufactured by International Fireproof
Technology, Inc., is a one -component, water -based, liquid
coating with a specific gravity of 1.3. DC 315 is supplied in
5-gallon _(19 L) pails and/or 55-gallon drums and has a
shelf life of one year when stored in unopened factory -
sealed containers between 50°F (10°C) to 80°F (27°C).
4.0 INSTALLATION
4.1 General:
SEALECTION® 500 spray -applied foam insulation must be
installed in accordance with the Center for Polyurethane
Industries Guidance on Best Practices for the Installation of
Spray Polyurethane Foam, the manufacturer's published
technical data sheet and product application guide and this
report. A copy of each document must be available at all
times on the jobsite during installation.
4.2 Application:
The SEALECTION® 500 insulation is spray -applied on the
jobsite using a volumetric positive displacement pump as
identified in the Demilec application guide. The insulation
must be applied when the ambient temperature is greater
than 23°F (-51C). The insulation must not be used in areas
that have a maximum in-service temperature greater than
180°F (821C). The foam plastic must not be used in
electrical outlet or junction boxes or in contact with water,
rain or soil. The foam plastic must not be sprayed onto a
substrate that is wet, or covered with frost or ice, loose
scales, rust, oil, or grease. The insulation must be
protected from the weather during and after application.
The insulation may be applied to the maximum thickness
in a single pass. Where insulation is used as an air -
impermeable insulation, such as in unvented attic
assemblies under 2015 and 2012 IRC Section R806.5
(2009 IRC Section R806.4) or 2015 IBC Section 1203.3,
the insulation must be installed at a minimum thickness of
3.0 inches (76 mm).
4.3 Thermal Barrier:
4.3.1 Application with a Prescriptive Thermal Barrier:
SEALECTION0 500 spray foam insulation must be
separated from the interior of the building by an approved
thermal barrier of 1/2-inch-thick (12.7 mm) gypsum
wallboard or an equivalent 15-minute thermal barrier
complying with, and installed in accordance with, IBC
Section 2603.4 or IRC Section R316.4, as applicable,
except where insulation is in an attic or crawl space as
described in Section 4.4. SEALECTION® 500 thickness is
not limited when separated from the interior of the building
by a prescriptive thermal barrier as complying with the IBC
or IRC.
4.3.2 Application without a Prescriptive Thermal
Barrier: The prescriptive 15-minute thermal barrier may be
omitted when installation is in accordance with this section
and Table 2. SEALECTION® 500 spray foam insulation
and BlazelokTm TB, BlazelokTm TBX or DC 315
intumescent coating may be spray -applied to the interior
facing of walls, the underside of roof sheathing or roof
rafters, and in crawl spaces, and may be left exposed as
an interior finish without a prescribed 15-minute thermal
barrier or ignition barrier. The foam plastic insulation
thickness must not exceed thicknesses stated in Table 2.
All foam surfaces must be covered with intumescent
coating, described in Section 3.6, at the minimum
thicknesses stated in Table 2. The intumescent coating
must be spray -applied over the insulation in accordance
with the coating manufacturer's instructions and this report
at a rate stated in Table 2 to obtain the recommended
minimum dry film thickness noted in this section.
4.4 Ignition Barrier -Attics and Crawl Spaces:
4.4.1 Application with a Prescriptive Ignition Barrier:
When SEALECTION® 500 spray foam insulation is
installed within attics or crawl spaces where entry is made
only for service of utilities, an ignition barrier must be
installed in accordance with IBC Section 2603.4.1.6 or IRC
Section R316.5.3 or R316.5.4, as applicable. The ignition
barrier must be consistent with the requirements for the
type of construction required by the applicable code, and
must be installed in a manner so the foam plastic
insulation is not exposed. SEALECTION® 500 spray -
applied foam insulation as described in this section may be
installed in unvented attics in accordance with 2015 IBC
Section 1203.3 or 2015 and 2012 IRC Section R806.5
(2009 IRC Section R806.4).
4.4.2 Application without a Prescriptive Ignition
Barrier:
4.4.2.1 General: SEALECTIONo 500 spray -applied foam
insulation may be installed in attics and crawl spaces,
ESR-1172 I Most Widely Accepted and Trusted Page 3 of 5
without a prescriptive ignition barrier as described in IBC
Section 2603.4.1.6 and IRC Sections R316.5.3 and
R316.5.4, in accordance with Section 4.4.2.2, 4.4.2.3,
4.4.2.4, or 4.4.2.5, when all of the following. conditions
apply:
a. Entry to the attic or crawl space is only to service
utilities, and no storage is permitted.
b. There are no interconnected attic or crawl space
areas.
c. Air in the attic or crawl space is not circulated to other
parts of the building.
d. Under -floor (crawl space) ventilation is provided when
required by 2015 IBC Section 1203.4 (2012 and 2009
IBC Section 1203.3) or IRC Section R408.1, as
applicable.
e. Attic ventilation is provided when required by IBC
Section 1203.2 or IRC Section R806, except when air -
impermeable insulation is permitted in unvented attics in
accordance with 2015 IBC Section 1203.3 or 2015 and
2012 IRC Section R806.5 (2009 IRC Section R806.4).
f. Combustion air is provided in accordance with IMC
(International Mechanical Code®) Section 701.
4.4.2.2 The insulation must be covered on all surfaces
with a fire protective coating at the minimum thickness set
forth in Table 3.
4.4.2.3 The maximum installed thickness of the insulation
must not exceed the thicknesses set forth in Table 3.
4.4.2.4 The coating must be applied over the insulation in
accordance with the coating manufacturer's instructions
and this report.
4.4.2.6 Use on Attic Floors: SEALECTION® 500 spray -
applied foam insulation may be installed at a maximum
thickness between and over the joists in attic floors as set
forth in Table 3. All exposed foam plastic surfaces must be
covered with a minimum nominal thickness of the fire
protective coatings as set forth in Table 3. The intumescent
coatings must be applied over the insulation in accordance
with the coating manufacturer's instructions and this report.
4.5 One -hour Fire -resistance -rated Wall Assemblies
(Nonload-bearing):
SEALECTION® 500 foam insulation may be used as a
component of a one -hour fire -resistance -rated, nonload-
bearing wall assembly_ as described in this section
(Section 4.5).
4.6.1 Interior and Exterior Face: One layer of 5/8-inch-
thick (16 mm); Type X gypsum wallboard complying with
ASTM C36 or ASTM C1396 is installed on the interior and
exterior side of nominally 2-by-6, No. 1, Southern yellow
pine wood studs spaced 16 inches (406 mm) on center.
The wallboard is attached with 15/8-inch-long (41 mm),
coarse -thread drywall screws located 8 inches (203 mm)
on center along the perimeter and 12 inches on center
(305 mm) in the field of the wallboard. Wallboard joints
must be taped and treated with joint compound in
accordance with ASTM C840 or GA-216. Fastener heads
must also be treated with joint compound in accordance
with ASTM C840 or GA-216.
4.5.2 Stud Cavity: A nominally 51/2-inch (140 mm)
thickness of SEALECTION® 500 foam insulation is spray -
applied in all stud cavities.
4.6 Exterior Walls of Type I, ll, III and IV Construction:
When used on exterior walls of Type I,, II, III and IV
construction, the SEALECTION® 500 foam insulation must
comply with Section 2603.5 of the IBC at a maximum
thickness of 35/8 inches (92 mm), when installed per the
manufacturer's published product application guide and
this section. The potential heat of Demilec SEALECTION®
500 spray polyurethane foam insulation is 496 Btule
(5.6 MJ/rn ) per inch of thickness when tested in
accordance with NFPA 259.
4.6.1 Nonload-bearing NFPA 285-tested Wall
Assembly:
4.6.1.1 Interior Face: One layer of 5/8-inch-thick
(16 mm), Type X gypsum wallboard complying with ASTM
C36 or ASTM C1396 is installed with the long dimension
perpendicular to 35/8-inch-deep (92 mm), 20 gage steel
studs spaced a maximum of 24 inches (609 mm) on
center. The wallboard is attached with 11/4-inch-long
(31.8 mm), bugle head screws located 8 inches (203 mm)
on center along the perimeter and 12 inches on center,
(305 mm) in the field of the wallboard. Wallboard joints
must be taped and treated with joint compound in
accordance with ASTM C840 or GA-216. Fastener heads
must also be treated with joint compound in accordance
with ASTM C840 or GA-216.
4.6.1.2 Stud Cavity: SEALECT►ON® 500 foam insulation,
in a maximum thickness of 35/8 inches (92_ mm), is spray -
,applied in all stud cavities.
4.6.1.3 Exterior Face: One layer of 5/9-inch-thick
(16 mrri� GP DensGlase sheathing attached to steel studs
using 1 /4-inch-long (31.8 mm), self -tapping screws spaced
8 inches (203 mm) on center along the perimeter and
12 inches on center (305 mm) in the field of the sheathing.
Details of the exterior wall covering must be provided by
the report holder, designer or specifier to the code official,
with a fire engineering analysis demonstrating that the
addition of the wall covering will not negatively affect
conformance of the assembly with the requirements of IBC
Section 2603.5.
5.0 CONDITIONS OF USE
SEALECTION® 500 spray foam insulation described in this
report complies with, or is a suitable alternative to what is
specified in, those codes listed in Section 1.0 of this report,
subject to the following conditions:
5.1 The products must be installed in accordance with the
Center for Polyurethane Industries "Guidance on Best
Practices for the Installation of Spray Polyurethane
Foam", the manufacturer's published technical data
sheet and product application guide, this evaluation
report and the applicable code. If there are any
conflicts between the manufacturer's published
installation instructions and this report, this report
governs.
5.2 The insulation must be separated from the interior of
the building by an approved 15-minute thermal
barrier, except when installation is as described in
Sections 4.3.2 or 4.4.1 through 4.4.2.5.
6.3 The insulation must not exceed the thicknesses noted
in Sections 3.2, 4.2, 4.3, 4.4. 4.5, and 4.6.
5.4 The insulation must be protected from exposure to
weather during and after application.
5.5 The insulation must be applied ,by contractors
authorized by Demilec (USA) Inc.
5.6 Use of the insulation in areas where the probability of
termite infestation is "very, heavy" must be in
accordance with IRC Section R318.4 or 2015 and
2009 IBC Section 2603.8 (2012 IBC Section 2603.9),
as applicable.
ESR-1172 I Most Widely Accepted and Trusted Page 4 of 5
5.7 When use is on exterior walls of buildings of Type I, 11,
III, and IV, construction must be as described in
Section 4.6..
5.8 See Section 4.5 for the fire -resistance -rated wall
assemblies.
5.9 Jobsite certification and labeling of the insulation must
comply with 2015 IRC Section N1101.10, 2012 IRC
Section N1101.14, 2015 or 2012 IECC Sections
C303.1, R303.1 and R401.3 [2009 IECC Section
303.1 and 401.31, as applicable.
5.10 The insulation is produced in Arlington, Texas,
under a quality -control program with inspections by
ICC-ES.
6.0 EVIDENCE SUBMITTED
6.1 Data in accordance with the ICC-ES Acceptance
Criteria for Spray -applied Foam Plastic Insulation
(AC377), dated May 2015, including reports of tests in
accordance with Appendix X.
6.2 Reports of fire propagation characteristics tests in
accordance with NFPA 285.
6.3 Reports of air leakage testing in accordance with
ASTM E283.
6.4 Reports of air permeance tests in accordance with
ASTM E2178.
6.5 Reports of room corner tests in accordance with
NFPA 286.
6.6 Reports of tests in accordance with ASTM E119.
6.7 Reports of potential heat tests in accordance with
NFPA 259.
7.0 IDENTIFICATION
Components of the spray foam insulation are identified
with the manufacturer's name (Demilec (USA) Inc.),
address and telephone number; the product name
(SEALECTION® A-PMDI or SEALECTION® 500 B-
Side); use instructions; the density; the flame -spread and
smoke -developed indices; the date of manufacture;
thermal resistance values; the evaluation report number
(ESR-1172); and the name of the inspection agency
(Intertek Testing Services NA).
Each pail of the BlazelokM I134 and the BlazelokTm TB or
BlazelokTm TBX intumescent coating is labeled with the
manufacturer's name (TPRZ Corporation), the product
name, and use instructions. Each pail of Andek
Corporations Firegard intumescent coating is labeled with
the manufacturers name (Andek Corporation) and address,
the product trade name, and use instructions.
No -Burn® Plus XD intumescent coating is identified with
the manufacturer's name (No -Burn, Inc) and address, the
product trade name, and use instructions.
Each pail of DC315 is labeled with the manufacturer's
name (International Fireproof Technology Inc.), address,
product trade name and use instructions.
8.0 OTHER CODES
8.1. Evaluation Scope:
In addition to the codes referenced in Section 1.0, the
products recognized in this report have also been
evaluated in accordance with the following codes:
■ 2006 International Building Code® (2006 IBC)
■ 2006 International Residential Code® (2006 IRC)
■ 2006 International Energy Conservation Code®
(2006 IECC)
■ 2003 International Building Code (2003 IBC)
■ 2003 International Residential Code® (20031RC)
■ 2003 International Energy Conservation Code®
(2003 IECC)
8.2 Uses:
The products comply with the above -mentioned codes as
described in Sections 2.0 through 7.0 of this report except
as noted below:
■ Application with a Prescriptive Thermal Barrier: See
Section 4.3.1, except the approved thermal barrier must
be installed in accordance with Section R314.4 of the
2006 IRC or Section R314.1.12 of the 2003 IRC.
■ Application without a Prescriptive Thermal Barrier:
See Section 4.3.2.
■ Application with a Prescriptive Ignition Barrier: See
Section 4.4.1, except attics must be vented in
accordance with Section 1203.2 of the 2006 and 2003
IBC or Section R806.of the 2003 IRC, and crawl space
ventilation must be in accordance with IBC Section
1203.3 of the 2006 and 2003 IBC or IRC Section R408,
as applicable. Additionally, an ignition barrier must be
installed in accordance with Sections R314.5.3 or
R314.5.3 of the 2006 IRC or Section R314.2.3 of the
2003 IRC, as applicable.
■ Application without a Prescriptive Ignition Barrier:
See Section 4.4.2, except attics must be vented in
accordance with Section 1203.2 of the 2006 and 2003
IBC or Section R806 of the IRC, and crawl space
ventilation must be in accordance with Section 1203.3 of
the 2006 and 2003 IBC or IRC Section R408, as
applicable.
■ Protection against Termites: See Section 5.6, except
use of the insulation in areas where the probability of
termite infestation is "very heavy" must be in
accordance with Section R320.5 of the 2006 IRC or
Section R320.4 of the 2003 IRC.
■ Jobsite Certification and Labeling: See Section 5.9,
except jobsite certification and labeling must comply
with Sections 102.1.1 and 102.1.11, as applicable, of
the 2006 IECC.
ESR-1172 1 Most Widely Accepted and Trusted Page 5 of 5
TABLE 1—THERMAL RESISTANCE (124ALUES)
THICKNESS (inches)
R-VALUE ('F.ft2.h/Btu)
1
3.8
3.5
13
4
15
5.5
21
7
27
9.5
36
10
38
11.5
44
14
52
For SI: 1 inch = 25.4 mm; 1 °F.ft2.h/Btu = 0.176110 °K.0/W.
'R-values are calculated based on tested K values at 1- and 4-inch thicknesses.
TABLE 2—USE OF INSULATION WITHOUT A PRESCRIPTIVE THERMAL BARRIER
Fire Protective Coating
Maximum Insulation
Maximum Insulation
Ap illed to all Foam Surfaces
Coating
Thickness (in.)
Thickness (in.)
Minimum Coating Dry
Mnimum Coating Wet
Minimum
Minimum
Vertical Surfaces
Calling Surfaces
Film Thickness mils
Film Thickness mils
Application Rate
Blazelok TB
5 /2
10
14
25
1 al/82 ft
Blazelok TBX
7112
102
11
17
1 al/85
DC315
7 /2
11 /2
12
18
1 gaI190 ft
For SI: 1 inch= 25.4 mm; 1 gal 3.785 L; 1 ft2 = 0.093 m2.
TABLE 3—ATTIC OR CRAWL SPACE ASSEMBLIES WITHOUT A PRESCRIPTIVE IGNITION BARRIER
Maximum Insulation
Maximum Insulation
Fire Protective Coating
Coating
Thickness (in.)
Thickness (in.)
A lied to all Foam Surfaces
Minimum Coating Dry
, Minimum Coating
Minimum
Vertical Surfaces and
Ceiling Surfaces
Attic Floors
Film Thickness
Wet Film Thickness
Application Rate
Blazelok 164
9 !4
11 /4
5
9
1 al/175
Andek Fire and
9 /2
11 /2.
10
20
1 al/100 ft
No -Burn Plus XD
1 9 /2
111 /2
6
10
1gal/1 60 ft
DC 315
1 7 /2
1 . 11 /2
3
4
1 al/?? fl
For SI: 1 inch= 25.4 mm; 1 gal = 3.785 L; 1 ft2 = 0.093 m2.
De►muc
SealectionO.500 is a two'component, open cell, spray applied, semi -rigid polyurethane, foam system. This product -is a fully water blown foam
system with a low in -'place density with excellent adhesion to various substrates and to itself. Sealection 50.0 incorporates the single phase
solution technology developed by Demilec for excellent shelf life and consistent processing. Sealection 500 complies with the intent of the
International Code Council's residential and commercial building codes for spray polyurethane foam plastic insulation. Sealection 500 has been
approved by the EcoLogo (formerly Environmental Choice) Program of Canada and is an NAHB Green Approved Product. Sealection 500 meets
the USDA guidelines for Incidental food contact.
.o.
ASTM D 1622
Density
0.45 - 0.5 Ib/ft'
7.2 - 8 kg/m'
ASTM C 518
.Aged Thermal Resistance (R-value @ 1 inch)
3.81 ft2h°F/BTU
0.67 Km2/W
Air Leakage (air Impermeable IAW 2006, 2009 & 20121RC, IBC & IECC requirements)
ASTM E 283
Air Permeance @ 75 Pa @ 3.5"
0.001 L/sm2
Sustained wind load for 60 minutes @ 1000 Pa (90 mph wind)
No Damage
Gust wind load test @ 3000 Pa (160 mph wind) _:
No Damage
Air Permeance @ 50 Pa @ 3.5"
0.001 Ono'
ASTM E 2178
Air Permeance @ 100 Pa @ 3.5"
0.003 L/sm2
Air Permeance @ 300 Pa @ &S5'
0.008 L/sm2
Water Vapor Permeance @ 3.5"
6.33 perms
362 ng/Pa•s•rri2
Water Vapor Permeance @ 5.5"
4.03 perms
231 ng/Pa•s•m=
ASTM E 96
Water Vapor Permeance @ 7"
3.17 perms
181 ng/Pa•s•m2
Water. Vapor Permeance @ 10:'
2.20 perms
126 ng/Pa•s•rn'
Qualifies as a Class III vapor retarder at normal installed thicknesses
ASTM E 413
Sound Transmission Class (STC) (see website for assembly specs)
49 - 51
ASTM C 423
Noise Reduction Coefficient (NRC)
75
CAN/ULC-S774-09
VOC Emissions Standard
24 hr re -occupancy time, 2 hour ventilation
period before PPE is no longer required
ASTM D 1621
Compressive'Strength
0.7•psi
4.8 kPa
ASTM D 1623.
Tensile Strength
5.6 psi
38.6 kPa
Surface Burning Characteristics, 6" thick
Class I
ASTM E 84
Flame Spread Index
21
Smoke Developed
216
Ignition Barrier _ Compliant with 2006, 2009 & 2012 IBC and IRC, and ICC-ES AC-371
Appendix X, for use in attics and crawl spaces with:
NFPA 286
Blazelok'".164 at 3 mils dry film thickness, 5 mils wet film thickness, or
Pass
Andek Firegard at'10 mils, dry film thickness,16 mils wet film thickness, or
No Burn Plus XD at 4 mils dry film thickness
NFPA 286
Thermal Barrier - Compliant with the 2006, 2009 & 2012 IBC and IRC, as an interior finish,
Pass
without a 15 minute thermal barrier with Blazelok?" TBX at 11 mils dry film thickness.
Compliant with the 2006, 2009 & 2012 IBC for exterior walls of Type 1, II, III and IV buildings of
NFPA 285
any height. See ICC-ES ESR 1172, Section 4.6-for specific -assembly. Contact the Demilec
Pass
Engineering Department for assistance with alternate assemblies.
ASTM E 970
Sealection 500 may be left exposed on attic floors up to 14" thick.
Pass
Non load -bearing, I hour, wall assembly test. See ICC=ES ESR 1172, Section 4.5 for specific
ASTM E 119
assembly. Contact the Demilec Engineering Department for assistance with alternate
Pass
assemblies.
ASTM D 1929
Ignition Properties (spontaneous ignition temperature]
1040°F (560'C)
.o
Cream Time Gel. Time Tack Free Time End of Rise
1= 2 seconds 3 - 4 seconds . 6 -..7 seconds 6 - 7 seconds
3315 E. Division Street; Arlington, TX 76011 Sealection 500 Technical Data She_ef
Phone (817) 6404900, Toll Free (877) 336-4532 • Last Revision 9-22-16
Fax (817) 633-2000, Info@Demilec.com, www.bemilec.com Page 1 of 2
SEALECT(ONG 500
PROPERTY
APMDL,ISOCYANi4TE i ;'.
SEALECTION ,500 RESIN -
Color.,
Brown
Amber
Viscosity @ 77°F (25°C) -
180 - 220 cps
150 - 300 cps
Specific Gravity
1.24
1.08 -1.12
Shelf Life of unopened drum properly stored
12 months
12 months.
Storage Temperature
50 -100°F (10-.38°C)
50 -100°F (10 - 38°C)
Mixing Ratio (volume)
*See SDS for more Information.
O D•• O O D •
Initial Recirculating $etpoint Temperature
90 -100OF
32 - 3801C
Initial Primary. Heater Setpoint Temperature
130°F
54DC
Initial Hose Heat Setpoint Temperature
1300P
"54°C
Initial Processing Setpoint Pressure
1200 psi
8274 kPa
Substrate & Ambient Temperature
> 230F
> -5°C
Moisture Content of Substrate
_
s 19%
519%
Moisture Content of Concrete
Concrete must be cured, dry and free of dust and form release agents.
'Foam application temperatures and pressures can vary widely depending on temperature, humidity, elevation, substrate, equipment and other
factors. While processing, the applicator must continuously observe the characteristics of the sprayed foam and adjust processing temperatures.
and pressures to maintain proper cell structure, adhesion, cohesion and general foam quality. It is the sole'responsibility of the applicator to
process and apply Sealection 500 within specification.
General Requirements: Equipment must be capable of delivering the proper ratio (1:1 by volume) of polymeric isocyanate (PMDI) and polyol
blend at adequate temperatures and spray,pressures. Substrate must be at least 5 degrees above dew point, with best processing, results when
ambient humidity is below 809s. Substrate must also be free of moisture (dew or frost), grease, oil, solvents and other materials that would
adversely affect adhesion of the polyurethane foam.
Sealection 500 must be separated from the interior of the building by an approved thermal barrier or an approved finish material equivalent to a
thermal barrier in accordance -with applicable codes. Sealection 500 must be sprayed at a minimum thickness of 3" per. pass. This product must .
not be used when the continuous service temperature of the substrate or foam Is below -60'F (-51°C) or above 180°F (82°C). Sealection 500
should not be used in contact with bulk water, below grade or to cover flexible.ductwork.
Disclaimer: The information herein is to assist customers in determining whether our products are suitable for their applications. We request
that customers inspect and test our products before use and satisfy themselves as to contents and suitability. Nothing herein shall constitute a
warranty, expressed or Implied, including any warranty of merchantability or fitness, nor Is protection from any law or patent Inferred. All patent
rights are reserved. The foam prbduct.is conibustible.and must be protected in accordance with applicable codes. Protect from direct flame and
spark contact, around hot work for example. The exclusive remedy for all proven claims is replacement of our materials.
�� � RESEARCH.
CENTER'
C'hockHo US.� 91 APPROVED
-
3315 E. Division Street, Arlington, TX 76011
Phone (817) 640-4900, Toll Free (877) 336-4532
Fax (817) 633-2000, Info@Demilec.com, ww.w.Demilec.com
Sealection 500 Technical Data Sheet
Last Revision 9-22-16
Page 2 of 2
11