PV Plans Stamped
PHOTOVOLTAIC SYSTEM Joseph PV SYSTEM SUMMARY: 10.150 KW CITY NOTES: I Bravo RESIDENTIAL PHOTOVOLTAIC SYSTEM THIS PROJECT COMPLIES WITH THE FOLLOWING: SYSTEM SIZE (DC) STC: 29 X 350 = 10150W DC 2020 7TH EDITION FLORIDA BUILDING CODE: BUILDING Digitally signed by 2020 7TH EDITION FLORIDA BUILDING CODE: RESIDENTIAL Joseph J Bravo PTC: 29 X 326.8 = 9477W DC 2020 7TH EDITION FLORIDA BUILDING CODE: MECHANICAL Date:2022.01.27 SYSTEM SIZE (AC) 760OW AC @ 240V 2020 7TH EDITION FLORIDA BUILDING CODE: PLUMBING 08:25:54-07'00' 2020 7TH EDITION FLORIDA BUILDING CODE: FUEL GAS MODULES 29 X LONGI SOLAR: LR4-60HPB-350M 2020 7TH EDITION FLORIDA BUILDING CODE: ENERGY CONSERVATION OPTIMIZERS 29 X SOLAR EDGE: P401 2020 7TH EDITION FLORIDA BUILDING CODE: EXISTING BUILDING 2020 7TH EDITION FLORIDA BUILDING CODE: ACCESSIBILITY INVERTER SOLAR EDGE: SE760OH-USRGM [S11] 2020 7TH EDITION FLORIDA FIRE PREVENTION CODE 2017 NATIONAL ELECTRIC CODE (NEC) TILT 18°, 18' AS ADOPTED BY CITY OF PORT ST. LUCIE AZIMUTH 180°, 90' RAFTER/TRUSS SIZE 2X4 TRUSS @ 24" O.C. ATTACHMENT TYPE UNIRAC: SFM INFINITY MICRORAIL WITH UNIRAC SFM SITE LOCATION: INFINITY RAIL-LESS MAIN SERVICE PANEL EXISTING 150 AMPS MSP WITH (E) 150 AMPS MAIN BREAKER ON TOP FED INTERCONNECTION LINE SIDE TAP 0 � OCPD RATING 40 AMPS CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM UTILITY FLORIDA POWER & LIGHT CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS. 48 Silver Oak Dr, Port St Lucie, Ff... ALL SOLAR ENERGY SYSTEM EQUIPMENT SHALL BE SCREENED TO THE MAXIMUM EXTENT POSSIBLE AND SHALL BE PAINTED A COLOR SIMILAR TABLE OF CONTENTS TO THE SURFACE UPON WHICH THEY ARE MOUNTED. PV-1 SITE LOCATION AND HOUSE AERIAL VIEW MODULES SHALL BE TESTED , LISTED AND INDENTIFIED WITH FIRE CLASSIFICATION IN PV-2 SITE PLAN ACCORDANCE WITH UL 2703. SMOKE AND CARBON MONOXIDE ALARMS ARE REQUIRED PER SECTION R314 AND 315 TO BE VERIFIED AND INSPECTED BY INSPECTOR IN THE PV-2A ROOF PLAN WITH MODULES LAYOUT FIELD. SITE LOCATION PV-3 MOUNTING DETAILS INSTALLATION NOTES: HOUSE AERIAL VIEW: PV-4 THREE LINE DIAGRAM PV-5 EXISTING SERVICE PANEL DIG ALERT(811)TO BE CONTACTED AND COMPLIANCE WITH EXCAVATION _ SAFETY PRIOR TO ANY EXCAVATION TAKING PLACE PV-6 NOTES AND EQUIPMENT LIST ? INSTALL CREW TO VERIFY ROOF STRUCTURE PRIOR TO COMMENCING WORK. PV-7 LABELS EMT CONDUIT ATTACHED TO THE ROOF USING CONDUIT MOUNT. PV-7A SITE PLACARD - PV-8 OPTIMIZER CHART _ PV-9 & 10 SAFETY PLAN t `3 .y MODULE LOCATION CLIENT: REVISIONS: TITLE: SHEET: ELECTRICAL CONTRACTOR NO: CEDRIC ALLWOOD DESCRIPTION DATE REVISION DATE: 1/27/2022 •�• freedom CERTIFIED ELECTRICAL CONTRACTOR F O R E V E R Eclsoososs 48 SILVER OAK DRIVE, AS BUILT 01/27/22 1 DESIGN JB SITE LOCATION AND FREEDOM FOREVER FLORIDA LLC GREG ALBRIGHT PORT ST. LUCIE, FL 34952 BY. HOUSE AERIAL VIEW PV_1 2619 CONSULATE DR SUITE 800,ORLANDO,FL 32819 a1 Tel:(800)385-1075 ,��� � JOB No.: F113628 ROOF AREA : 2132.68 SQ FT PV SYSTEM 10.150 kW-DC 7.600 kW-AC PROPERTY LINE ROOF LINE (N)29 LONGI SOLAR: LR4-60HPB-350M I � � 44'-10" 26'-11" LEGEND: w u OBSTRUCTION 0� 0° O PIPE VENT L0 Q MODULES — CONDUIT w DRIVEWAY > ® SETBACK i lv1 U) JUNCTION �B BOX Ac AC DISCONNECT - - - - - - — — - - - - - - - — — INv INVERTER nnsP MSP uM UTILITY METER (N) SE760OH-USRGM [S11] (N)JUNCTION BOX (N)SQUARE D D222NRB (E) UTILITY METER (E) MAIN SERVICE PANEL SITE PLAN 1 SCALE: 1/16" = V-0" CLIENT: REVISIONS: TITLE: SHEET: freedom ELECTRICAL CONTRACTOR NO: CEDRIC ALLWOOD DESCRIPTION DATE REVISION DATE: 1/27/2022 ���---✓✓✓ CERTIFIED ELECTRICAL CONTRACTOR IF O R E V E R EC13008056 48 SILVER OAK DRIVE, AS BUILT 01/27/22 1 DESIGN FREEDOM FOREVER FLORIDA LLC PORT ST. LUCIE, FL 34952 BY: JB GREG ALBRIGHT SITE PLAN PV-2 2619 CONSULATE DR SUITE 800,ORLANDO,FL 32819 Tel:(800)385-1-1075 JOB No.: F113628 r ROOF AREA STATEMENT �`"�I III/," FL ROOF AREA . 2132.68 SQ FT MODULES ARRAY SYSTEM `��.`�PN!0.YUR/q'�%� ROOF T PITCH AZIMUTH ROOF AREA ARRAY AREA V E o DISTRIBUTED ��Je ��C E N PV SYSTEM Digitally signed by 10. 1 21 18 180° 732.39 SQ FT 379.26 SQ FT 24.56% 2.31 PSF _=* * �nto VN,ian1°V�,iant° No.86261TI c=U cn=Vuriant°Vuriant° 1 ° A01410D00000116BI 50 - Yuranto 7CBF250000A7A2 7.600 kW-AC 2 8 18 90° 333.92 SQ FT 144.48 SQ FT = Raas°n:l 0OA7A Wh°of � * this d°°°me°t 1 °aci°° ''r0% STATE E O F `i Date:2001-27 06:35-06:00:00 cGORIDP 'G� ALE��`��` By Yuri at 6:34:55 AM, 1/27/2022 This item has been electronically signed and sealed by Yurianto Yurianto,SE,PE.on the date and/or time stamp shown using a digital signature. Printed copies of this document are not considered signed and sealed and the signature must be verified by a 3rd Party Certificate Authority on any electronic copy. FIRE ACCESS PATHWAYS 0- O-, LEGEND: ° 3,-1" u OBSTRUCTION O PIPE VENT �. MODULES rn — CONDUIT `L (N)29 LONGI SOLAR: LR4-60HPB-350M ® SETBACK Je JUNCTION BOX FIRE ACCESS AC AC PATHWAYS DISCONNECT INv INVERTER JIB N MSP o MSP MSP INV AC UM 0- uM UTILITY METER O•, NOTES: 1. EMT CONDUIT ATTACHED TO THE ROOF USING CONDUIT MOUNTS 2. ATTACHED CLAMPS AT 25% FROM THE EDGE AND 50% FROM THE CENTER OF THE MODULES ROOF PLAN 3. JUNCTION BOX IS MOUNTED TO SCALE: 3/32" - V-0" 1 THE RAIL. CLIENT: REVISIONS: TITLE: SHEET: freedom ELECTRICAL CONTRACTOR NO: CEDRIC ALLWOOD DESCRIPTION DATE REVISION DATE: 1/27/2022 ���---✓✓✓ CERTIFIED ELECTRICAL CONTRACTOR F O R E V E R EC13008056 48 SILVER OAK DRIVE, AS BUILT 01/27/22 1 DESIGN JB ROOF PLAN W/ FREEDOM FOREVER FLORIDA LLC PORT ST. LUCIE, FL 34952 BY. MODULES LAYOUT PV-2A GREG ALBRIGHT 2619 CONSULATE DR SUITE 800,ORLANDO,FL 32819 Tel:(800)385-1075 JOB No.: F113628 r "011111111111/ FL O 2 FT DF#2 2X4 BLOCKING TO BE INSTALLED WHERE PV ATTACHMENTS \PN� IV OCCUR BETWEEN HORIZONTAL TRUSSES IN ORDER TO ACHIEVE PROPER '*:' No.86261 *= EMBEDMENT PER RACKING MANUFACTURER. BLOCKING TO BE ATTACHED w/ (2) 10d NAILS EACH END STATE OF Or� F�ORIDP•'G��• SFM TRIMRAIL SFM MICRORAIL r"liI I111 W LONGI SOLAR: LONGI SOLAR: By Yuri of 6:34:56 AM, 112712022 LONGI SPB-350M This item has been electronically signed and sealed by LR4-60HPB-350M SFM SLIDER AND 1 Yurianto Yurianto,SE,PE.on the date and/or time I F stamp shown using a digital signature. Printed copies ATTACHMENT 1ROOF/DECK MEMBRANE of this document are not considered signed and sealed 2.5° ROOF DECK/ 5" and the signature must be verified by a 3rd Party MEMBRANE Certificate Authority on any electronic copy. 2.5"MIN.EMBED. FLASHING 2.5"MIN.EMBED. UNIRAC SLIDERS 5/16"STAINLESS STEEL LAG FLASHING BOLT OR STRUCTURAL SCREW WITH 2-1/2"MIN.EMBEDMENT 5/16"STAINLESS STEEL AND FLAT WASHER LAG BOLT OR STRUCTURALSCREW WITH 2-1/2"MIN. EMBEDMENT AND FLAT WASHER BUILDING STRUCTURE BUILDING STRUCTURE ATTACHMENT DETAIL �w Scale: NTS I Module , SFM MICRORAIL (Roof Zones) i i I Zone 1 Zone 2 i Zone 3009* 1 LONGI SOLAR. 15 LR4-60HPB-350M FLASHING 1 SFM Components UNIRAC SLIDERS ROOF/DECK MEMBRANE C SFM Microrail 2" o SFM Splice 6.5" SFM TRIMRAIL SFM Attached Splice 8" I I I O SFM Trim Attachment 2X4 TRUSS @ 24"O.C. — SFM Trim Univ Clip © Full Trim Section Cut Trim Section EMgE� SFM SLIDER AND TRIMRAIL 25,MtN ROOF ATTACHMENT FLASHING 5/16"STAINLESS STEEL LAG MAX ATTACH M ENT SPAN - 4' BOLT OR STRUCTURAL SCREW WITH 2-1/2"MIN.EMBEDMENT AND FLAT WASHER SOLAR PV ARRAY SECTION VIEW PARTIAL ROOF FRAMING PLAN Scale: NTS Scale: NTS CLIENT: REVISIONS: TITLE: SHEET: ELECTRICAL CONTRACTOR NO: C E D R I C AL LW OO D DATE: 1/27/2022 •��\ freedom CERTIFIED ELECTRICAL CONTRACTOR DESCRIPTION DATE REVISION F o R E V E R Eclsoososs 48 SILVER OAK DRIVE, AS BUILT 01/27/22 1 DESIGN JB MOUNTING FREEDOM FOREVER FLORIDA LLC GREG ALBRIGHT PORT ST. LUCIE, FL 34952 BY: DETAILS PV-3 2619 CONSULATE DR SUITE 800,ORLANDO,FL 32819 Tel:(800)385-1075 9 �� 006 No.: F113628 BACKFEED FUSE SIZING CONDUCTOR AMPACITY DE-RATE CALCULATION MAX. CONTINUOUS OUTPUT 32A @ 240V CONDUCTOR AWG WIRE NEC FACTORS NEC FACTORS CONDUCTOR NEC FACTORS EQUIPMENT WIRE LOCATION TABLE TABLE AMPACITY TABLE 32.00 X 1.25 = 40AMPS 40A FUSES-OK QTY. SIZE 310.15(B)(16) 310.15(B)(2)(a) @90CADJ. 310.15(B)(3)(a) 1 AC INVERTER TO AC DISCONNECT EXTERIOR WALL 3 8 50 0.94 47 1.00 2 AC AC DISCONNECT TO POI EXTERIOR WALL 3 6 65 0.94 61.1 1.00 PV SYSTEM 10. 550 kW-DC 7.600 kW-AC (E)150A RATED (E)UTILITY MAIN SERVICE PANEL METER 1 PH,120/240V 60HZ (E)150A/2P STRING-1 MAIN BREAKER 15 LONGI SOLAR: (END FED) U LR4-60HPB-350M SOLAREDGE P401 POWER OPTIMIZERS 2-#10 AWG, (N)LINESIDE TAP VIA UL r_ PV WIRE LISTED CONNECTORS (N)SOLAREDGE •� SE760OH-USRGM[SI11 INVERTER • ' STRING-2 (N)60A FUSED14 LONGI SOLAR: AC DISCONNECT LR4-60HPB-350M kAC SQUARE D D222NRB •/� 2-40 AMP FUSES • I JUNCTION Qjb •" 1 TO UTILITY BOX •// �� UNDERGROUND - q_b FEED F- I 4-#10 AWG,THWN-2 SWITCH WI RAPID OWN 1-#8 EGC,THWN-2 3-#8 AWG,THWN-2 3-#6 AWG,THWN-2 I IN 3/4' O EMT CONDUIT 1-#8 EGC,THWN-2 IN 3/4"OR LARGER EMT CONDUIT IN 3/4"OR LARGER EMT CONDUIT I I L-------------- L___ J SOLAREDGE P401 1-#6 GEC,BARE COPPER POWER OPTIMIZERS FREE AIR BONDED 2-#10 AWG,PV WIRE EXISTING UFER TIE IN 1-#6 AWG IN FREE AIR OR A TAPBOX MAY BE USED IN LIEU OF PERFORMING THE LINESIDE #8 AWG MUST BE IN EMT CONDUIT TAP IN THE MAIN SERVICE PANEL.THIS IS DEPENDENT UPON SITE CONDITIONS. CONNECT TO EXISTING LIFER NOTE: CONDUIT AND CONDUCTORS SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS CLIENT: REVISIONS: TITLE: SHEET: freedom ELECTRICAL CONTRACTOR NO: CEDRIC ALLWOOD DESCRIPTION DATE REVISION DATE: 1/27/2022 ���---✓✓✓ CERTIFIED ELECTRICAL CONTRACTOR F O R E V E R EC13008056 48 SILVER OAK DRIVE, AS BUILT 01/27/22 1 DESIGN JB THREE LINE FREEDOM FOREVER FLORIDA LLC GREGALBRIGHT PORT ST. LUCIE, FL BY:34952 DIAGRAM PV-4 2619 CONSULATE DR SUITE 8 ORLANDO,FL 32819 Tel:(800)385-1-1075 JOB No.: F113628 r , s a- i •� I�oitiiei ,� _ } ,� r P j J CLIENT: REVISIONS: TITLE: SHEET: freedom ELECTRICAL CONTRACTOR NO: CEDRIC ALLWOOD DESCRIPTION DATE REVISION DATE: 1/27/2022 ���---✓✓✓ CERTIFIED ELECTRICAL CONTRACTOR IF O R E V E R EC13008056 48 SILVER OAK DRIVE, AS BUILT 01/27/22 1 DESIGN EXISTING SERVICE GREG ALBRIGHT FREEDOM FOREVER FLORIDA LLC PORT ST. LUCIE, FL 34952 BY. JB PANEL PV-5 2619 CONSULATE DR SUITE 800,ORLANDO,FL 32819 Tel:(800)385-1-1075 JOB No.: F113628 r GENERAL NOTES: 29 LONGI SOLAR WIRED AND LISTED TO UL1703 STANDARDS THE SOLAREDGE INVERTER IS INTEGRATED WITH DC DISCONNECTION AND ARC FAULT PROECTION.IT IS ATTACHED WITH SYSTEM ELECTRICAL SPECIFICATIONS W/GROUND FAULT PROTECTION&LISTED TO UL 1741 STANDARDS. PHOTOVOLTAIC SYSTEM GROUND WILL BE TIED INTO EXISTING GROUND AT MAIN SERVICE FROM DC DISCONNECT/INVERTER AS PER 2017 NEC SEC 250.166(A). SOLAR PHOTOVOLTAIC SYSTEM EQUIPMENT WILL BE INSTALLED IN ACCORDANCE WITH REQUIREMENTS OF ART.690 OF THE 2017 NEC CONDUIT ABOVE ROOF SHALL BE NO LESS THAN 1 INCH FROM TOP OF THE ROOF TO BOTTOM OF RACEWAY.TABLE NEC 310.15(B)(3)(C) PHOTOVOLTAIC DC CONDUCTORS ENTERING THE BUILDING SHALL BE INSTALLED IN METALLIC RACEWAY AND SHALL BE IDENTIFIED EVERY 10 FEET--AND WITHIN 1 FOOT ABOVE AND BELOW PENETRATIONS OF ROOF/CEILING ASSEMBLIES WALLS OR BARRIERS--WITH MINIMUM 3/8-INCH-HIGH WHITE LETTERING ON RED BACKGROUND READING:WARNING:PHOTOVOLTAIC POWER SOURCE. SYSTEM GROUNDING ELECTRODE CONDUCTOR FOR PV SYSTEM TO BE SIZED TO MEET THE REQUIREMENTS OF 2017 NEC THE EXISTING MAIN SERVICE PANEL WILL BE EQUIPPED WITH A GROUND ROD OR UFER UTILITY COMPANY WILL BE NOTIFIED PRIOR TO ACTIVIATION OF THE SOLAR PV SYSTEM TERMINALS OF THE DISCONNECTING MEANS MAY BE ENERGIZED IN THE OPEN POSITION SOLAREDGE INVERTERS ARE LISTED TO UL 1741 AND UL 1699B STANDARDS SOLAREDGE OPTIMIZERS ARE LISTED TO IEC 62109-1 (CLASS II SAFETY)AND UL 1741 STANDARDS MATERIAL LIST: QTY. PART PART# DESCRIPTION 29 MODULES 114-350 LONGI SOLAR:LR4-60HPB-350M 29 OPTIMIZERS 130-401 P401 SOLAREDGE POWER OPTIMIZER-FRAME MOUNTED MODULE ADD-ON 1 JUNCTION BOX 480-276 60OVDC NEMA 3R UL LISTED JUNCTION BOX 2 CONNECTORS 240-300 STAUBLI/MULTI-CONTACT MC4 CONNECTORS(FEMALE) BREAKER SIZES: 2 CONNECTORS 240-301 STAUBLI/MULTI-CONTACT MC4 CONNECTORS(MALE) 1 INVERTER 120-763 SE760OH-USRGM[Sill 240V INVERTER UL1741 SA CERTIFIED INTEGRATED ARC FAULT PROTECTION AND RAPID SHUTDOWN 1 AC DISCONNECT 323-065 60A RATED 240VAC NEMA 3R UL LISTED 2 FUSES 330-040 40A FUSE 1 PH 240VAC 1 FUSE REDUCER 330-530 60A-30A FUSE REDUCER 1 TAP KIT 350-111 #6-3/0 AWG INSULATED TAP 2 PORT 53 ROOF ATTACHMENT 1 261-602 UNIRAC:SFM INFINITY MICRORAIL 51 MICRORAIL 1 261-602 SFM MICRORAIL 2 INCH 21 SFM TRIM 1 241-253 FLASHKIT SFM TRIM COMP DARK 55 SFM SLIDER 1 261-603 FLASHKIT SFM SLIDER COMP DARK 16 BONDING CLAMP 1 221-100 SFM N/S BONDING CLAMP 7 BONDING CLAMP 1 241-404 SFM TRIM BONDING CLAMP 31 MOUNT ASSEMBLY 1 241-405 MLPE MOUNT ASSY 18 SFM SPLICE 1 261-604 SFM SPLICE 4 SFM ATTACHED SPLICE 1 211-101 SFM ATTACHED SPLICE 8 INCH 24 TRIMRAIL 1 261-606 SFM TRIMRAIL UNIV CLIP W/HDW 8 TRIM SPLICE 1 261-605 SFM TRIM SPLICE DIRK 13 TRIMRAIL 1 211-115 SFM TRIMRAIL UNIV DIRK 29 GROUND LUG 1 260-585 ILSCO GROUND LUG 29 TRIM END CAPS 1 UNIRAC SFM TRIM END CAPS SERVICE: CLIENT: REVISIONS: TITLE: SHEET: ELECTRICAL CONTRACTOR NO: C E D R I C AL LW OO D DATE: 1/27/2022 freedomCERTIFIED ELECTRICAL CONTRACTOR DESCRIPTION DATE REVISION F o R E V E R Eclsoososs 48 SILVER OAK DRIVE, AS BUILT 01/27/22 1 DESIGN JB NOTES AND FREEDOM FOREVER FLORIDA LLC PORT ST. LUCIE, FL 34952 BY: EQUIPMENT LIST PV-6 GREG ALBRIGHT 2619 CONSULATE DR SUITE 800,ORLANDO,FL 32819 Tel:(800)385-1075 9 � I IJOB No.: F113628 NOTES: WARNING: "WARNING" - 1. NEC ARTICLES 690 AND 705 AND NEC SECTION R324 MARKINGS SHOWN HEREON. POWER • OUTPUT DUAL POWER • - 2. ALL MARKING SHALL CONSIST OF THE FOLLOWING: Y A. UV RESISTANT SIGN MATERIAL WITH ENGRAVED OR CONNECTION SECOND SOURCE IS PHOTOVOLTAICMACHINE PRINTED LETTERS OR ELECTRO-PLATING. 1 • NOT RELOCATERATED AC • B. RED BACKGROUND COLOR WHITE TEXT AND LINE • - - DEVICE. • - OPERATING • IVOLTSWORK. C. AERIAL FONT. 705.12(B)(2)(3)(b) 3. ALL SIGNS SHALL BE SIZED APPROPRIATELY AND PLACED IN 690.54 THE LOCATIONS SPECIFIED. SIGNAGE CANNOT BE HAND-WRITTEN. SOLAR PV SYSTEM EQUIPPED 3. SIGNS SHALL BE ATTACHED TO THE SERVICE EQUIPMENT WITH WITH RAPID SHUTDOWN POP-RIVETS OR SCREWS. TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SOLARELECTRIC SHUT DOWN PV SYSTEM RRAREL= . - AND REDUCE SHOCK ELECTRICAL HAZARD IN THE ARRAY 690.56(C)(1)(A) MAY BE ENERGIZE • HAZARD. F- — — TERMINALS ON BOTH LINE AND LOAD SIDES PEN POSITION. a 690.13 (B) DISCONNECTPV SYSTEM DC VOLTAGE:MAXIMUM - :i DISCONNECTPV SYSTEM AC , MAX RATED OUTPUT CURRENT OF a THECONTROLLER OR • AC NORMAL OPERATING VOLTAGE - 240 VOLTS CONVERTER: 15A 690.15, 690.54 690.53 ARRAY RAPID SHUTDOWN SWITCH FOR SOLAR INVERTER L DC J/B 690.56(C)(3) If you have any questions about your system,please call our Customer Support Team at ■���■����I NEC 690.31(G)(3)&(4) orvisit freedomforever.00m/customer-service I I I "WARNING" Tils solar PV system Ives Ins Mel by freedom- PHOTOVOLTAIC POWER SOURCE raxcvEn ,.�e.i..l..xm..ama�m.n.ii.v,.. y�r M.b.ms.x�we.I.xM1mmwei..mMlle.m. EVERY 1U ON CONDUIT AND ENCLOSURES CLIENT: REVISIONS: TITLE: SHEET: freedom ELECTRICAL CONTRACTOR NO: CEDRIC ALLWOOD DESCRIPTION DATE REVISION DATE: 1/27/2022 ���---✓✓✓ CERTIFIED ELECTRICAL CONTRACTOR F O R E V E R Eclsooaoss 48 SILVER OAK DRIVE, AS BUILT 01/27/22 1 DESIGN FREEDOM FOREVER FLORIDA LLC GREGALBRIGHT PORT ST. LUCIE, FL 34952 BY: JB LABELS PV-7 2619 CONSULATE DR SUITE 800,ORLANDO,FL 32819 Tel:(800)38s-1-1075 JOB No.: F113628 r CAUTION: MULTIPLE SOURCES OF POWER LOCATED AS SHOWN. DANGEROUS VOLTAGE MAY BE PRESENT AT ALL TIMES Ji 0 Y Q O w J_ co F>K JUNCTION BOX MAIN SERVICE PANEL 29 PV MODULE UTILITY METER AC DISCONNECT INVERTER EQUIPPED WITH RAPID SHUTDOWN 6X8"TYP-NEC 705.10 NOTES: 1. NEC ARTICLES 690 AND 705 AND NEC SECTION R324 MARKINGS SHOWN HEREON. 2. ALL MARKING SHALL CONSIST OF THE FOLLOWING: A. UV RESISTANT SIGN MATERIAL WITH ENGRAVED OR MACHINE PRINTED LETTERS OR ELECTRO-PLATING. B. RED BACKGROUND COLOR WHITE TEXT AND LINE WORK. C. AERIAL FONT. 3. ALL SIGNS SHALL BE SIZED APPROPRIATELY AND PLACED IN THE LOCATIONS SPECIFIED. SIGNAGE CANNOT BE HAND-WRITTEN. 3. SIGNS SHALL BE ATTACHED TO THE SERVICE EQUIPMENT WITH POP-RIVETS OR SCREWS. CLIENT: REVISIONS: TITLE: SHEET: ELECTRICAL CONTRACTOR NO: C E D R I C AL LWOO D DESCRIPTION DATE REVISION DATE: 1/27/2022 freedomCERTIFIED ELECTRICAL CONTRACTOR F O R F V F R EC13008056 48 SILVER OAK DRIVE, AS BUILT 01/27/22 1 DESIGN FREEDOM FOREVER FLORIDA LLC PORT ST. LUCIE, FL 34952 BY: JB GREG ALBRIGHT SITE PLACARD PV_7A 2619 CONSULATE DR SUITE 800,ORLANDO,FL 32819 1 Tel:(800)385-1075 `f�� JOB NO.: F113628 1 -10 11 -20 21 -30 31 -40 41 -50 51 -60 SOLAREDGE OPTIMIZER CHART 1 2 3 4 5 > 0 Y Q O of ILL J U) Yi 11 8 9 10 CLIENT: REVISIONS: TITLE: SHEET: freedom ELECTRICAL CONTRACTOR NO: CEDRIC ALLWOOD DESCRIPTION DATE REVISION DATE: 1/27/2022 ���---✓✓✓ CERTIFIED ELECTRICAL CONTRACTOR F O R E V E R EC13008056 48 SILVER OAK DRIVE, AS BUILT 01/27/22 1 DESIGN FREEDOM FOREVER FLORIDA LLC PORT ST. LUCIE, FL 34952 BY: JB OPTIMIZER PV-8 2619 CONSULATE DR SUITE 800,ORLANDO,FL 32819 GREGALBRIGHT CHART Tel:(800)385-1075 JOB NO.: F113628 r SAFETY PLAN MARK UP KEY INSTRUCTIONS: 1. USE SYMBOLS IN KEY TO MARK UP THIS SHEET. O PERMANENT ANCHOR 2. SAFETY PLAN MUST BE MARKED BEFORE JOB STARTS AS PART OF THE PRE-PLAN 3. DOCUMENT ALL ADDITIONAL HAZARDS ON THIS PAGE OT TEMPORARY ANCHOR & MAKE NOTES ON THE JHA SHEET IL IN CASE OF EMERGENCY INSTALLER LADDER NEAREST HOSPITAL OR OCCUPATIONAL/INDUSTRIAL CLINIC B❑ JUNCTION / COMBINER BOX NAME: STUB-OUT ADDRESS: SKYLIGHT SAFETY COACH CONTACT INFORMATION NAME: NO LADDER ACCESS (STEEP GRADE OR GROUND LEVEL OBSTRUCTIONS) ADDRESS: uj ALL EMPLOYEES ON SITE SHALL BE MADE AWARE OF THE RESTRICTED ACCESS � SAFETY PLAN AND SIGN INDICATING THAT THEY ARE AWARE OF THE HAZARDS ON-SITE AND THE PLAN FOR Q CONDUIT WORKING SAFELY. O Lu NAME SIGNATURE > GAS SHUT OFF GAS cn HZo WATER SHUT OFF O SERVICE DROP O POWER LINES DATE: TIME: CLIENT: REVISIONS: TITLE: SHEET: � freedom ELECTRICAL CONTRACTOR NO: CEDRIC ALLWOOD DESCRIPTION DATE REVISION DATE: 1/27/2022 CERTIFIED ELECTRICAL CONTRACTOR 01 R Eclsoososs 48 SILVER OAK DRIVE, AS BUILT o��27�22 1 DESIGN FREEDOM FOREVER FLORIDA LLC PORT ST. LUCIE, FL 34952 BY: JB SAFETY PLAN GREG ALBRIGHT PV-9 2619 CONSULATE DR SUITE 800,ORLANDO,FL 32819 Tel:(800)385-1-1075 JOB NO.: F113628 JOB HAZARD ANALYSIS Crew leader to fill out all sections below, hold a pre-job safety meeting with all personnel, and upload this completed document and the Safety Plan to Site Capture Ladder Access Public Protection Weather and Environment Restroom facilities • Ladders must be inspected before each use. • The safety of the Client and the Public must be maintained at all • The site supervisor shall forecast the weather conditions at the • Employees shall have access to restroom facilities with • Extension ladders must be set up on a firm and level surface at times. job site, prior to crew arrival, in order to mitigate any hazards hand-washing stations. Use of onsite restroom is at the client's a 4-to-1 rise to run angle (or 75 degrees)and the top must be • The Client and the Public shall be prevented from entering the associated with inclement weather(heat, cold, wind, rain, etc.) discretion (location is annotated below). If client does not give secured to the structure. Extension style ladders placed on work zone through the use of barriers and/or signage, as • The site supervisor will utilized a portable wind meter permission, location of suitable restroom facilities with uneven, loose or slippery surfaces must additionally have the required. (anemometer)to verify actual onsite wind conditions, by hand-washing stations offsite will be provided. The onsite base firmly anchored or lashed so the base will not slip out. • Company, Client and Public property shall be protect from checking at the ground and on any elevated work surface (ex, supervisor will identify location and make arrangements to • Extension ladders must be used with walk-through devices or falling objects. rooftop)prior to work start, at midday and prior to solar panel ensure all employees have access at any point. the ladder must extend 36"above the stepping off point. 0 Pets (including dogs)shall be secured by their owners prior to staging on a roof. ffRestroom facilities will be circle one : Onsite-Offsite • A-frame ladders must only be climbed with the ladder spreader work start. • Elevated work involving the moving or maneuvering of solar ffsite, add location name and address: bars locked in the open position;A-frame ladders shall not be 0 The client should not leave pets,family members, or others in panels shall cease at 25mph (sustained wind)until wind climbed while in the closed position (ex, closed and used while the charge or care of Employees, Contractors, or Temporary subsides. Incident Reporting Procedure leaned against a structure). Workers. Forecasted weather maximum temp(degrees F): 0 Contact your Site Supervisor • Additional notes: 0 Crew leader responsible for communication with the client: Name: Mobile Equipment Client and public is excluded from work area by barricades(N/A, • Only Qualified operators will operate equipment; operators must Yes, No): Heat Related Illness Prevention Phone: maintain a certification on their person for the equipment being • Employees shall have access to potable drinking water that is operated. Training and Pre-Job Safety Briefing fresh, pure, and suitably cool.The water shall be located as 0 Contact your Manager • Type(s)of mobile equipment(Type/Make/Model): • All employees onsite shall be made aware of the specific close as practicable to the areas where employees are working. hazards of this project and review this HJA during a pre-job Water shall be supplied in sufficient quantity at the beginning of Name: • Qualified operator(s): briefing, and their signature indicates awareness of site the work shift to provide at least one quart per employee per conditions and the plan to eliminate any hazards identified prior hour for drinking for the entire shift. Employees may begin the Phone: Material Handling and Storage to and during the project. shift with smaller quantities of water if they identify the location • Materials will be staged/stored in a way that does not present a and have effective means for replenishment during the shift to • Contact your Site Supervisor hazard to client, personnel or public. Materials stored on the • Crew leader(name/title): allow employees to drink on quart or more per hour.The roof will be physically protect from failing or sliding off. frequent drinking of water shall be encouraged. Name: • Crew member(name/title): 0 Shade shall be present when temperature exceeds 80 degrees Fall Protection Fahrenheit.When the outdoor temperature in the work exceeds Phone: • A site-specific plan for fall prevention and protection is required • Crew member(name/title): 80 degrees Fahrenheit, employees shall have and maintain one prior to starting work and must remain onsite at all times until or more areas with shade at all times. With:Your full name, phone number, office location, brief description work is complete; a fall rescue plan must be outlined and • Crew member(name/title): • New employees must be acclimatized. New employees will be of what happen and when. discussed among the crew prior to work start. monitored by their Crew Leader(site supervisor)for the first two • First-person-Up(FPU)must install their anchor and connect • Crew member(name/title): (2)weeks of employment or longer when necessary. NOTE ADDITIONAL HAZARDS NOT ADDRESSED ABOVE before any other task, including installing other anchors. The 0 Employees will be allowed and encouraged to implement (add as many as necessary by using additional sheets) Last-Person-Down (LPD) must be the only person on a roof • Crew member(name/title): scheduled breaks during each shift. Employees must take uninstalling fall protection. cool-down breaks in the shade any time they feel the need to do • FPCP (name and title): Airborne Contaminants: so to protect them from overheating. Supervisors are Define the Hazard: Method/steps to prevent incident: • Asbestos-containing (Transite)piping (ACP)- Do not disturb REQUIRED to allow employees any break period they need • FPU and LPD (name and title): (move, drill, cut fracture, etc.) during high heat conditions. • Asbestos-containing thermal insulation (ACI)and • Cool Vests are encouraged for all employees at all times during Electrical Safety Asbestos-containing duct wrapping (ACW)-do not disturb, no periods of high heat. • The Electrical Qualified Person (EQP)is required onsite to attic or crawlspace access is allowed if work to be performed • Identify the location of the closet Occupational/Industrial Clinic perform electrical work. could cause exposure to personnel, client or public. or Hospital in case a crew member becomes ill. Define the Hazard: Method/steps to prevent incident: • All electrical work will be performed with equipment in an electrically safe condition (de-energized)unless approval has 0 If yes, list specific tasks and protection in place: What is the specific plan to provide and replenish sufficient water for been granted prior to work. all employees on site? • Service drops and overhead electrical hazards will be • If offsite replenish is necessary,where will you go to replenish Define the Hazard: Method/steps to prevent incident: indentified and protected from contact, as neccessar . water(location/address): • EQP (name and tile): • Who will replenish the drinking water(name): Define the Hazard: Method/steps to prevent incident: CLIENT: REVISIONS: TITLE: SHEET: ELECTRICAL CONTRACTOR NO: C E D R I C AL LW OO D DATE: 1/27/2022 �\ freedom CERTIFIED ELECTRICAL CONTRACTOR DESCRIPTION DATE REVISION F o R E v E R Eclsoososs 48 SILVER OAK DRIVE, AS BUILT 01/27/22 1 DESIGN FREEDOM FOREVER FLORIDA LLC PORT ST. LUCIE, FL 34952 BY: JB SAFETY PLAN PV-10 GREG ALBRIGHT 2619 CONSULATE DR SUITE 800,ORLANDO,FL 32819 Tel:(800)385-1075 9 I I JOB No.: F113628 ' . ' : LR4-60HPB 345~370M ParametersHW04m Design(mm) Mechanical L 345~370M . W. dmmm l c3o Cell Orientation:120(6x20) Operational Temperature:AO C�+SS C ®����� . 111111111101E ❑ Junction Box:IP68,three diodes Power Output Tolerance:0-+5W � 0101110 ME t A (}9I Output Cable:4mm',1200mm in length Voc and lsc Tolerance:±3% . �� E1111111111 I _ncy e , 9.S�Q,y', (for EU DG) Maximum System Voltage:DC1000V(IEC/UL) 1������o Glass:Single glass Maximum Series Fuse Rating:20A trC with N o 3.2mm coated tempered glass Nominal Operating Cell Temperature:45±2 C �M , f w � I LID , I n.A Frame:Anodized aluminum alloy frame Safety Class:Class11 Half-cut Technologyunits:mm0wh) Weight:19.5kg Fire Rating:ULtype I or 2 toieranre: Dimension :1755x1038x35mm Length t2mm �'''''�''1RRBRR 0 997 wam:±2mm Packaging:30pcsperpallet WWIW1111111111WWIW= ME Heighe±lmm Mrm-mw±tmm 180pcs per 20'GP WII �11""" 780pcs per 40'HC M. Electrical Characteristics Test uncertainty for Pmax:±3% Model Number LR4-60HPB-345M LR4-60HPB-350M LR4-60HPB-355M LR4-60HPB-360M LR4-60HPB-365M LR4-60HPB-370M Testing Condition STC NOCT STC NOCT STC NOCT STC NOCT STC NOCT STC NOCT Maximum Power(Pmax/W) 345 257.6 350 261.4 355 265.1 360 268.8 365 272.6 370 I 276.3 12-year Warranty for Materials and Processing- Open Circuit Voltage(Voc/V) 40.2 3T7 40.4 37.9 40.6 38.1 40.8 38.2 41.0 38.4 41.2 I 38.6 25-year Warranty for Extra Linear Power Output 100% -0.55% 1 %'l Short Circuit Current(Isc/A) 11.06 8.95 11.16 9.02 11.25 9.09 11.33 9.16 11.41 9.23 11.50 9.30 25 year Polder Voltage at Maximum Power(Vmp/V) 34.2 31.8 34.4 32.0 34.6 32.2 34.8 32.4 35.0 32.6 35.2 1 32.8 Additional Val ars Warranty Annual Current at Maximum Power(Imp/A) 10.0918 9 8.09 10.1819 8.16 10.27 5 8.23 10.3519 8 8.30 10.43 20 08.36 10.5220 8.43 ue from LO Power Attenuation z 19 NGi Sol 91.2% ------------------------------- ', Linear Warr 0.55% Module Efficiency(%) 3 �tandar anty d Mo t', STC(Standard Testing Conditions):Irradiance 1000W/m2,Cell Temperature 25 C,Spectra at AM1.5 87.7% -------------------------------?-------auleJiflearpow n er wawa NOCT(Nominal Operating Cell Temperature):Irradiance 80OW/m2,Ambient Temperature 20C,Spectra at AM1.5,Wind at 1m/S 84.5% --- -- ---- --- -- -- - 80.7% ---- --- -= - Temperature Ratings(STC) Mechanical .. ding Temperature Coefficient of Isc +0.0489/./`C Front Side Maximum Static Loading 540OPa 1 5 10 15 20 25 Temperature Coefficient of Voc -0.270%/C Rear Side Maximum Static Loading 2400Pa Complete System and Product Certifications Positive power tolerance(0 +5W)guaranteed Temperature Coefficient of Pmax -0.350%/C Hailstone Test 25mm Hailstone at the speed of 23m/s IEC 61215,IEC 61730,UL 51730 ISO9001:2008:ISO Quality Management System High module conversion efficiency(up to 20.3%) ISO 14001:2004:ISO Environment Management System Slower power degradation enabled by Low LID Mono PERC technology:first year<2%, TS62941:Guideline for module design qualification and type approval 0.55%year 2-25 Current-Voltage Curve(LR4-60HPB-360M) Power-Voltage Curve(LR4-60HPB-360M) Current-Voltage Curve(LR4-60HPB-360M) OHSA518001:2007 Occupational Health and Safety Solid PID resistance ensured by solar cell process optimization and careful module BOM 12 aoo Ce„temp=25c 12 CenT-,25C aoow/m SP® selection 10 300 -too/-' 10 TfN Incident irraa:i000w/m� 300 _��m' �,/m, g -cell Temp=25C ; 250 -400w/m' $ c us Reduced resistive loss with lower operating current <- -Cell Temp=35C � - SppN./m. c 6 -Cell Temp=45C 3 200 c 6 w -Cell Temp=55C a w •Specifications subject to technical changes and tests. Higher energy yield With lower operating temperature d 4 -cellTemp=u5c ISO q 40D-/m, LONGi Solar reserves the right of interpretation. -CellTemp=75C 100 Reduced hot spot risk with optimized electrical design and lower operating current 2 so z 2oow/m 0 0 0 0 10 20 30 40 50 0 10 20 30 40 50 0 10 20 30 40 50 Voltage(v) Voltage(v) Voltage(v) �' Room 801,Tower 3,Lujiazui Financial Plaza,No.826 Century Avenue,Pudong Shanghai,200120,China NGI Room 801,Tower 3,Lujiazui Financial Plaza,No.826 Century Avenue,Pudong Shanghai,200120,China Tel:+86-21-80162606 E-mail:module@longi-silicon.com Facebook:www.facebook.com/LONGi Solar Tel:+86-21-80162606 E-mail:module@longi-silicon.com Facebook:www.facebook.com/LONGi Solar Note:Due to continuous technical innovation,R&D and improvement,technical data above mentioned may be of modification accordingly.LONG!have the sole right to make such Note:Due to continuous technical innovation,R&D and improvement,technical data above mentioned may be of modification accordingly.LONGi have the sole right to make such modification at anytime without further notice;Demanding party shall request for the latest datasheet for such as contract need,and make it a consisting and binding part of modification at anytime without further notice;Demanding party shall request for the latest datasheet for such as contract need,and make it a consisting and binding part of lawful documentation duly signed by both parties. lawful documentation duly signed by both parties. 20200414V11 for EU DG only 20200414V11 for EU DG only Power Optimizer For North America ma P320 / P340 / P370 / P400 / P401 / P405 / P485 / P505 Power Optirinizer .Optimizer model P320 (for high- . . power For North Americacompaes) '' modules) (for high- (for high- (for higher cell voltage voltage current modules) cell .. .. modules) P320 / P340 / P370 / P400 / P401 / P405 / P485 / P505 •• INPUT Rated Input DC Power") 320 340 370 400 405 485 505 W Absolute Maximum Input Voltage 48 60 80 60 1241( 83(2( Vdc (Voc at lowest temperature) MEET Operating Range 8-48 8-60 8-80 8-60 12.5-105 12.5-83 Vdc 25 Maximum Short Circuit Current 11 10.1 11.75 11 14 Adc YEAR (Isc) .. , O Maximum Efficiency 99.5 % Weighted Efficiency 98.8 98.6 % Overvoltage Category II OUTPUT DURING OPERATION (POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER) Maximum Output Current 15 Adc Maximum Output Voltage 60 85 Vdc NT)l OUTPUT DURING STANDBY(POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR SOLAREDGE INVERTER OFF) Safety Output Voltage per Power Optimizer ±0.1 Vdc STANDARD COMPLIANCE EMC FCC Part15 Class 3,IEC61000-6-2,IEC61000-6-3 - Safety IEC62109-1(class II safety),UL1741 N Material UL94 V 0, Resistant RoHS Yeses INSTALLATION SPECIFICATIONS Maximum Allowed System 1000 Vdc Voltage Compatible inverters All SolarEdge Single Phase and Three Phase inverters 129x153x33.5 129x153x29.5 129x162x59/ mm Dimensions(W x L x H) 129x153x27.5/5.1x6x1.1 /5.1x6x1.3 /5.1x6x1.16 129x159x49.5/5.1x6.3x1.9 5.1x6.4x2.3 /in Weight(including cables) 630/1.4 750/1.7 655/1.5 845/1.9 1064/2.3 gr/lb Input Connector MC4(3( Single or dual MC40) p MC40)(4) Input Wire Length 0.16/0.52 Output Wire Type/Connector Double Insulated/MC4 Output Wire Length 0.9/2.95 1.2/3.9 Operating Temperature Range(') -40-+85/-40-+185 "C/`F Protection Rating IP68/NEMA6P PV power optimization at the module-level Relative Humidity 0-100 % (1)Rated power of the module at STC will not exceed the optimizer"Rated Input DC Power".Modules with up to+5%power tolerance are allowed (2)NEC 2017 requires max input voltage be not more than 80V Specifically designed to work with SolarEdge / Fast installation with a single bolt 3)For other connector types please contact SolarEdge (4)For dual version for parallel connection of two modules use P485-4NMDMRM.In the case of an odd number of PV modules in one string,installing one P485 dual version power optimizer connected inverters to one PV module.When connecting a single module seal the unused input connectors with the supplied pair of seals. Next generation maintenance with module- (5)For ambient temperature above+85°C/+185°F power de-rating is applied.Refer to Power Optimizers Temperature De-Rating Technical Note for more details. / Up to 25% more energy level monitoring I PV System Design Using Single Phase Three Phase for Three Phase for Superior efficiency (99.5%) / Meets NEC requirements for arc fault a SolarEdge '-Wave I Single phase 208V ' 277/480V grid protection (AFCI) and Photovoltaic Rapid Minimum String Length P320,P340,P370,p400,P401 8 10 18 / Mitigates all types of module mismatch losses, Shutdown System (PVRSS) (Power Optimizers) P405,P485,P505 6 8 14 from manufacturing tolerance to partial Maximum String Length(Power Optimizers) 25 25 50(8) shading / Module-level voltage shutdown for installer 5700(6000with Maximum Power per String SE7600-US-SE11400- 5250 6000(0) 12750(10) W and firefighter safety US) Flexible system design for maximum space Parallel Strings of Different Lengths or Orientations Yes utilization (6)For detailed string sizing information refer to:http://www.solaredge.com/sites/default/files/string-sizing-na.pdf V It is not allowed to mix P405/P485/P505 with P320/P340/P370/P400/P401 in one string (8)A string with more than 30 optimizers does not meet NEC rapid shutdown requirements;safety voltage will be above the 30V requirement (9)For 208V grid:it is allowed to install up to 7,200W per string when the maximum power difference between each string is 1,000W (10)For 277/480V grid:it is allowed to install up to 15,000W per string when the maximum power difference between each string is 2,000W soIar , , ®SolarEdge Technologies Ltd.All rights reserved.SOLAREDGE,the SolarEdge logo,OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks ofSolarEdge Technologies,Inc. AM. Ro H S sol a red g e.co m All other trademarks mentioned herein are trademarks of their respective owners.Date:07/2020NO2/ENG NAM.Subject to change without notice. Intertek Single Phase Inverter with HD-Wave Tec n0 Ogy for North America SE3000H-US / SE380OH-US / SE5000H-US / SE6000H-US/ Single Phase Inverter SE760OH-US / SE1000OH-US / SE1140OH-US with HD-Wave Technolo OUTPUT g y m Rated AC Power Output 3000 5000 7600 10000 3800 @ 240V 6000 @ 240V 11400 @240V VA 3300 @ 208V 5000 @ 208V 10000 @ 208V for North America X Maximum AC Power Output 3000 3800 @ 240V 5000 6000 @ 240V 7600 10000 11400 @240V VA 3300 @ 208V 5000 @ 208V 10000 @ 208V SE3000H-US / SE380OH-US / SE5000H-US / SE6000H-US / AC OutputVoltageMin. Nom. Max. ✓ ✓ ✓ ✓ ✓ ✓ ✓ Vac (211-240-264) AC Output Voltage Min.-Nom.-Max. ✓ ✓ ✓ Vac SE760OH-US / SE10000H-US / SE1140OH-US (183-208-229) I..I..I AC Frequency(Nominal) 59.3-60-60.501 Hz Maximum Continuous Output 12.5 16 21 25 32 42 47.5 A � YEAR Current @240V solar•..: V HOwo„ Maximum Continuous Output 16 24 48.5 A Current @208V LA GFDI Threshold 1 A m solar, ,- ��I,l Utility Monitoring,Islanding Protection, Yes Country Configurable Thresholds INPUT L) Maximum DC Power @240V 4650 5900 7750 1 9300 1 11800 1 15500 1 17650 W Maximum DC Power @208V - 5100 7750 15500 W ® .b ® Transformer-less,Ungrounded Yes Maximum Input Voltage 480 Vdc I Nominal DC Input Voltage 380 400 Vdc Maximum Input Current @240VIII 8.5 10.5 13.5 16.5 20 1 27 30.5 Adc ® Maximum Input Current @208V1" - 9 13.5 - 27 Adc • �� 1— Max.Input Short Circuit Current 45 Adc q = Reverse-Polarity Protection Yes a Ground-Fault Isolation Detection 600ku Sensitivity Maximum Inverter Efficiency 99 99.2 % CEC Weighted Efficiency 99 99 @ 240V % 98.5 @ 208V a Nighttime Power Consumption <2.5 W 1W W ADDITIONAL FEATURES Supported Communication Interfaces RS485,Ethernet,ZigBee(optional),Cellular(optional) Revenue Grade Data,ANSI C12.20 OptionalM Rapid Shutdown-NEC 2014 and Automatic Rapid Shutdown upon AC Grid Disconnect Optimized installation with HD—Wave technolo 2017690.12 p 9Y STANDARD COMPLIANCE Safety UL1741,UL1741 SA,UL1699B,CSA C22.2,Canadian AFCI according to T.I.L.M-07 Specifically designed to work with Extremely small Grid Connection Standards IEEE1547,Rule 21,Rule 14(HI) power optimizers Emissions FCC Part 15 Class B INSTALLATION SPECIFICATIONS Record-breaking efficiency Built-in module-level monitoring AC Output Conduit Size/AWG Range 1"Maximum/14-6 AWG 1°Maximum/14-4AWG DC Input Conduit Size/#of Strings/ 1"Maximum/1-2 strings/14-6 AWG 1"Maximum/1-3 strings/14-6 AWG Fixed voltage inverter for longer strings Outdoor and indoor installation AWG Range Dimensions with Safety Switch 17.7 x 14.6 x 6.8 /450 x 370 x 174 21.3 x 14.6 x 7.3/540 x 370 x 185 in/ (HxWxD) mm Integrated arc fault protection and rapid shutdown for Optional: Revenue grade data, ANSI C12.20 Weight with Safety Switch 22/10 25.1/11.4 26.2/11.9 38.8/17.6 Ib/kg NEC 2014 and 2017, per article 690.11 and 690.12 Class 0.5 (0.5% accuracy) Noise <2s 1 <50 dBA Cooling Natural Convection UL1741 SA certified, for CPUC Rule 21 grid Operating Temperature Range -13 to+140/-25 to+60141(-40'F/-40°C option)1s1 °F/°C compliance Protection Rating NEMA 4X(Inverter with Safety Switch) 11 For other regional settings please contact SolarEdge support ai A higher current source may be used;the inverter will limit its input current to the values stated solar Revenue grade inverter P/N ion refer to:httNNC2 (<)For power de-rating information refer to:https://wwwsolaredge.com/sites/default/files/se-temperature-Berating-note-na.pdf solaredge.com 15)-40 version P/N:SExxxxId-US000NNU4 O SolarEdge Technologies,Inc.All rights reserved.SOLAREDGE,the SolarEdge logo,OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies,Inc.All Ro H S other trademarks mentioned herein are trademarks of their respective owners.Date,03/2019N01/ENG NAM.Subject to change without notice. It rt Address:Intertek d NY 13 11 V1t rt Address:Intertek d NY 13 11 Cortland NY 13045 Cortland NY 13045 Total Q w uty.Msui od. Telephone: 607-758-6516 Total 4 u,uty.Msui-1. Telephone: 607-758-6516 www.intertek.com www.intertek.com o SE3000A-US/SE380OA-US/SE5000A-US/SE6000A-US/SE760OA-US/SE1000OA-US/ / / Subject: ETL Evaluation of SolarEdge Products to NEC 2017 Rapid Shutdown Requirements SE1140OA-US SE3000H-US/SE380OH-US/SE5000H-US/SE6000H-US/SE760OH-US SE1000OH-US/SE1140OH-US when the following label is labeled on the side of the inverter: To,whom it may concern This letter represents the testing results of the below listed products to the requirements contained in the following standards: HOTOVOLTAIC RAPID National Electric Code, 2017,Section 690.12 requirement for rapid shutdown. SHUTDOWN SYSTEM UL 1741, UL 1741 CRD for rapid shutdown The evaluation was done on the PV Rapid Shutdown System (PVRSS),and covers installations consisting Inverter part number may be followed by a suffix of optimizers and inverters with part numbers listed below. The testing done has verified that controlled conductors are limited to: • 3-ph Inverters: o SE9KUS/SEIOKUS/SE14.4KUS/SE20KUS/SE30KUS/SE33.3KUS/SE43.2KUS/ • Not more than 30 volts and 240 voltamperes within 30 seconds of rapid shutdown initiation SE66.61KUS/SE1001KUS;when the following label is labeled on the side of the inverter: outside the array. • Not more than 80 volts and 240 voltamperes within 30 seconds of rapid shutdown initiation IBr• s inside the array. The rapid shutdown initiation is performed by either disconnecting the AC feed to the inverter,or—if HOTOVOLTAIC RAPID the inverter DC Safety switch is readily accessible—by turning off the DC Safety switch. SHUTDOWN SYSTEM Applicable products: Inverter part number may be followed by a suffix • Power optimizers: o PB followed by 001 to 350;followed by-AOB or-TFI. If there are any questions regarding the results contained in this report,or any of the other services OP followed by 001 to 500;followed by-LV,-MV, -IV or-EV. offered by Intertek, please do not hesitate to contact the undersigned. P followed by 001 to 850. SP followed by 001 to 350. *When optimizers are connected to 2 or more modules in series,the max input voltage may exceed 80V. Following the implementation of the NEC 2017 rapid shutdown value of 80V max inside of the array at the beginning of 2019, modules exceeding this combined input max voltage will be required to use optimizers with parallel inputs. • 1-ph Inverters: This information is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. This information is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement.Intertek assumes no liability to any party, Intertek's responsibility and liability are limited to the terms and conditions of the agreement.Intertek assumes no liability to any party, other than to the Client in accordance with the agreement,for any loss,expense,or damage occasioned by the use of this information. other than to the Client in accordance with the agreement,for any loss,expense,or damage occasioned by the use of this information. Any observations and results in this report are relevant only to the sample evaluated. Only the Client is authorized to copy and Any observations and results in this report are relevant only to the sample evaluated. Only the Client is authorized to copy and distribute this information and only then in its entirety. distribute this information and only then in its entirety. ©2018 Intertek ©2018 Intertek Version:8-September-2016 Page 1 of 3 GFT-OP-10a Version:8-September-2016 Page 2 of 3 GFT-OP-10a R (R mmUNIRAC SFM MIN INFINITY IN NoSFM INFINITY ■■■ MONO U N I RACBETTER SOLAR STARTS HERE DESIGN GUIDELINES BETTER SOLAR STARTS HERE Take your business to the next level with SFM INFINITY, UNIRAC's rail-less PV mounting system for flush While you will see advantages simply from switching to SFM INFINITY, the following guidelines will help you mount installations on comp shingle and the roofs. An advanced 3rd generation product platform in use to maximize its benefits. by top solar contractors nationwide, SFM INFINITY optimizes your operations on and off the roof, with approximately 40% less labor, 30% logistics savings, and 20% fewer roof attachments than traditional solar racking. Plus, 87% of homeowners prefer SFM INFINITY'S aesthetics. DEFAULT TO LANDSCAPE UNIRAC When possible,design in landscape orientation in order to fit more modules on the roof and minimize roof attachments. 25 r ► Y1AH_ MIX MODULE ORIENTATIONS WAHHANTY SFM INFINITY is easily configured in mixed array shapes and module orientations to maximize array density and to avoid vent pipes and other obstacles.Because mounting locations are not constrained by rails,SFM INFINITY has unmatched flexibility to enhance your projects. UNIVERSAL COMPONENTS CONSULT THE QUICK TIPS VIDEOS s FIT 32 — 40MM MODULES Visit UNIRAC's mobile-friendly library of short,topic-specific videos which answer common questions and demonstrate how simple it is to install SFM INFINITY. .r gip. Quick Tips Videos:https://unirac.com/SFM-Infinity/ INSTAIL TRIMRAIL ROOF F ��► w DESIGN IN U—BUILDER Layout your arrays in U-Builder,UNIRAC's free solar design software,to optimize SFM INFINITY's capabilities,including mixing module orientations and minimizing roof attachments.Quickly create = j layouts on Google or Bing Maps and generate project documents. SUPERIOR PERFORMANCE EASY INSTALLATION HOMEOWNER PREFERRED U-Builder:https://design.unirac.com/ Enhance your business with two installs per day Pre-assembled components,20%fewer roof attachments, More than 4 out of 5 homeowners prefer SFM INFINITY'S and 30%less cost, and level array in seconds with post height adjustment. aesthetics over a leading rail brand. Report No. 102393982LAX-002 Page 2 of 107 Issued: 11-Apr-2016 Report No. 102393982LAX-002 Page 3 of 107 Issued: 11-Apr-2016 Unirac, Inc Revised: 20-Mar-2019 Unirac, Inc Revised: 20-Mar-2019 2.0 Product Description 2.0 Product Description Product Photovoltaic Mounting System, Sun Frame Microrail- Installed Using Unirac Installation Guide, Model Similarity NA Fuse Rating: 30, Rev PUB2019MAR01 with Annex North Row Extension Installation Guide Rev PUB2019FEB20 Brand name Unirac Module Orientat a PortrF.t or Landscape The product covered by this report is the Sun Frame Micro Rail roof mounted Photovoltaic Maximum Module : ze: 1,r 98 ft2 Rack Mounting System. This system is designed to provide bonding and grounding to UL2703 Design I .c i RatV g: 33 PSF Downward, 33 PSF Upward, 10 PSF Down-Slope photovoltaic modules. The mounting system employs anodized or mill finish aluminum brackets Tested Loads-5 1 72400 'a Downward, 50psf/2400Pa Uplift, 15psf/720Pa Down Slope that are roof mounted using the slider, outlined in section 4 of this report.There are no rails Trina TSM-255P1 (;.08 anc Sunpower SPR-E20-327 used for Mechanical Loading within this product, whereas the 3" Micro Rail, Floating Splice, and 9"Attached Splice electrically bond the modules together forming the path to ground. Increased size M_.test: Maximum Modu a 1ze:22 3 ft2 The Micro Rails are installed onto the module frame by using a stainless steel bolt anodized UL2703 Design I ,c 1 RatF g: 113 PSF Downward, 50 PSF Upward, 30 PSF Down-Slope with black oxide with a stainless type 300 bonding pin,torqued to 20 ft-lbs, retaining the LG355S2W-A5 u )e for Me :hanical Loading test. modules to the bracket. The bonding pin of the Micro Rail when bolted and torqued, penetrate Mounting confic u :tion: F)ur mountings on each long side of panel with the longest span of the anodized coating of the photovoltaic module frame to contact the metal, creating a bonded 24" Description connection from module to module. UL2703 Design It-�d Ratir: g: 46.9 PSF Downward, 40 PSF Upward, 10 PSF Down-Slope Ratings LG395N2W-A5, + :ZOS2\ '-A5 and LG355S2W-A5 used for used for Mechanical Loading The grounding of the entire system is intended to be in accordance with the latest edition of the test. National Electrical Code, including NEC 250: Grounding and Bonding, and NEC 690: Solar Mounting confic u Jon: E=,x mountings for two modules used with the maximum span of Photovoltaic Systems.Any local electrical codes must be adhered in addition to the 74.5" national electrical codes. The Grounding Lug is secured to the photovoltaic module,torqued in accordance with the installation manual provided in this document. Fire Class Resist it Ratir l: -Class A for Ste( p pope A plications when using Type 1 Modules. Can be installed at any Other optional grounding includes the use of the Enphase UL2703 certified grounding system, interstitial gap. In t; ''ations lust include Trim Rail. which requires a minimum of 2 micro-inverters mounted to the same rail, and using the same -Class A for Steep pope A.plications when using Type 2 Modules. Can be installed at any engage cable. interstitial gap. In t; ''ations lust include Trim Rail. Models Unirac SFM -Class A Fire Ra-e for Loin Slope applications with Type 1 or 2 listed photovoltaic modules. This system was ex aluated ✓ith a 5"gap between the bottom of the module and the roof's surface See section 7.0 illustraction '# 1 and la for a complete list of PV modules evaluated with these racking s stems Other Ratings NA ED 16.3.15(20-Apr-17)Mandatory ED 16.3.15(20-Apr-17)Mandatory tntertek AUTHORIZATION TO MARK Total Quality.Assured. This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) TUV Rheinland PTL Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Cleftificate Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing Report. Certificate no. VJ 821600I5 V! This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be applied only at the location of the Party Authorized To Apply Mark. License Holder: Manufacturing Plant: Applicant: Unirac, Inc Manufacturer: Cixi Emeka Aluminum Co. Ltd Unirac Inc. Unirac Inc. 1411 Broadway NE 1411 Broadway NE Albuquerque NM 87102 Albuquerque NM 87102 1411 Broadway Blvd NE No. 688 ChaoSheng Road USA USA Address: Albuquerque, NM 87102 Address: Cixi City Zhejiang Province 315311 Country: USA Country: China Klaus Nicolaedis Jia Liu Test report no.: 11SA- 31440029 005 Client Reference: Tom Young Contact: Tom Young Contact: Robin Luo Tested to: UL 2703:2015 Phone: 505-462-2190 Phone: +86-15267030962 505-843-1418 +86-13621785753 FAX: NA FAX: NA klaus.nicolaedis@unirac.com om Email: toddg@unirac.com Email: ji buwan.luo@cxymj.com buwan.luo@cxymj.com Party Authorized To Apply Mark: Same as Manufacturer Certified Product: Module Rack Mounting System License Fee-Units Report Issuing Office: Lake Forest, CA U.S.A. � Model Designation: SolarMount (SM) 7 Control Number: 5003705 Authorized by: tr Max System Voltage of PV Module: 1000 VDC for Dean Davidson, Certificati irmanager Max Size of PV Module: 20. 8 sq. ft. surface area Max Overcurrent Protection Rating of PV Module: 30 A when using the qualified grounding lugs; 20 A when using the Enphase micro inverter EGC. GISTEO US Fire Rating: Class A when installed with Type 1, Type 2, Type3, or Type 10 fire rated modules . Intertek (continued) This document supersedes all previous Authorizations to Mark for the noted Report Number. This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client.Intertek's responsibility and liability are 7 limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned Appendix: 1, 1—5 by the use of this Authorization to Mark.Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use of Intertek's Certification mark is restricted to the conditions laid out in the agreement and in this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement of the tested material,product or service must first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. Intertek Testing Services NA Inc. Licensed Test mark: Date of Issue 545 East Algonquin Road,Arlington Heights, IL 60005 (day/mo/yr) Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 2 7/0 7/2 016 Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use with Flat- Plate Photovoltaic Modules and Panels [UL 2703: 2015 Ed.1] (NU Product: Photovoltaic Mounting System, Sun Frame Microrail - Installed Using Unirac Installation Guide, Rev PUB2019MAR01 with Annex North Row Extension Installation Guide Rev PUB2019FEB20 Brand Name: Unirac Models: Unirac SFM ATM for Report 102393982LAX-002 Page 1 of 1 ATM Issued: 9-Apr-2019 TUV Rheinland PTL,LLC,1107 W.Fairmont Drive,Building A,Tempe,Arizona 85282,Tel(480)966-1700,Fax(775)314-6458 ED 16.3.15(20-Apr-17)Mandatory a a December 31, 2020 structural structural ENGINEERS ENGINEERS Unirac Components and Cladding Roof Zones: 1411 Broadway Blvd. NE The Components and Cladding Roof Zones shall be determined based on ASCE 7-05, ASCE 7-10& 7-16 Component and Albuquerque, NM 87102 Cladding design. Attn.: Unirac- Engineering Department Notes: 1) U-builder Online tool analysis is only for Unirac SFM Sunframe Microrail system only and do not include roof capacity check. Re: Engineering Certification for the Unirac Sunframe Microrail, SFM Infinity U-builder Software Version 1.0 2) Risk Category I I per ASCE 7-16. 1.0. t i k, s PZSE, Inc. -Structural Engineers has reviewed the Unirac's Sunframe Microrail, proprietary mounting system constructed 4)Array Edge Factor 3)Topographic factor, zYE= 1 from modular parts which is intended for rooftop installation of solar photovoltaic (PV) panels; and has reviewed the U- )Average parapet height is 0.0 ft. builder Online tool.This U-Builder software includes analysis for the 2" Microrail,8"Attached Splice, 6" splice, and front 5) Wind speeds are height LRF values. trimrail. All information, data and analysis contained within are based on, and comply with the following codes and 7) spacing(s)Attachments s I to a seismic designE or less. typical specifications: g( ) apply y category g y 1. Minimum Design Loads for Buildings and other Structures,ASCE/SEI 7-05,ASCE/SEI 7-10,ASCE/SEI 7-16 Design Responsibility: 2. 2020 Florida Building Code, by Florida Building Commission The U-Builder design software is intended to be used under the responsible charge of a registered design professional 3. 2006-2018 International Building Code, by International Code Council, Inc.w/Provisions from SEAOC PV-2 2017. where required by the authority having jurisdiction. In all cases, this U-builder software should be used under the 4. 2006-2018 International Residential Code, by International Code Council, Inc.w/Provisions from SEAOC PV-2 direction of a design professional with sufficient structural engineering knowledge and experience to be able to: 2017. Evaluate whether the U-Builder Software is applicable to the project, and 5. AC428,Acceptance Criteria for Modular Framing Systems Used to Support Photovoltaic (PV) Panels, November Understand and determine the appropriate values for all input parameters of the U-Builder software. 1, 2012 by ICC-ES. Following are typical specifications to meet the above code requirements: This letter certifies that the Unirac SFM Sunframe Microrail, when installed according to the U-Builder engineering report and the manufacture specifications, is in compliance with the above codes and loading criteria. Design Criteria: Ground Snow Load =0- 100 (psf) Basic Wind Speed =90- 180(mph) This certification excludes evaluation of the following components: Roof Mean Height=0-60(ft) 1) The structure to support the loads imposed on the building by the array; including, but not limited to: strength Roof Pitch =0-45 (degrees) and deflection of structural framing members,fastening and/or strength of roofing materials, and/or the effects Exposure Category= B, C& D of snow accumulation on the structure. Attachment Spacing: Per U-builder Engineering report. 2) The attachment of the SFM 2" Microrail or 8"Attached Splice to the existing structure. 3) The capacity of the solar module frame to resist the loads. Cantilever: Maximum cantilever length is L/3,where "L" is the span noted in the U-Builder online tool. This requires additional knowledge of the building and is outside the scope of the certification of this racking system. Clearance: 2"to 10" clear from top of roof to top of PV panel. If you have any questions on the above, do not hesitate to call. Tolerance(s): 1.0"tolerance for any specified dimension in this report is allowed for installation. DIGITAL SIGNATURE Prepared b Installation Orientation: See SFM Installation Guide. PZSE Roseville, Inc.CA Structural Engineers '\��\`�;*K**z*gCy,���i Landscape- PV Panel long dimension is parallel to ridge/eave line of roof and the PV ��`Q �C ENS * F panel is mounted on the long side. Portrait- PV Panel short dimension is parallel to ridge/eave line of roof and the PV panel - No. 73522 is mounted on the short side. Attachment shall be staggered where ground snow load exceeds 10 PSF. STATE �iO** EXP.02/28/2023 . .�**F�ORIOP.•*� Testing: Values were based on UTR-299 testing provided by Unirac. 1478 Stone Point Drive, Suite 190, Roseville, CA 95661 1478 Stone Point Drive, Suite 190, Roseville, CA 95661 12/31/2020 916.961.3960 916.961.3965 W www.pzse.com T 916.961.3960 F 916.961.3965 W www.pzse.com Experience I Integrity i Empowerment Experience I Integrity 1 Empowerment