HomeMy WebLinkAboutFire Alarm System Product Submittals1349 S.W. BILTMORE STREET PORT ST_ LUCIE, FL. 34983 0 F F 10 E: 177 213 44-0 477 FAX:17721344-0478 Eire Sip_r_` ud"ir `$ Firs Alarms Fire EXIINUMS11OFS JUN 0 9 ZM ST. Lucie County;, Permitting PRODUCT SUBMITTALS FIRE ALARM SYSTEM 1 RS FILE c®p RESERVE REALTY 8401 COMMERCE CENTER DR. PORT ST LUCIE, FL ST.LUCIE COUNTY PLAN REVIEW BLDG: DATE: ELE DATE PLUMB: DATE: MECH: — DATE: State Certified Fire Protection Contractor State Certified Fire Alarm Contractor License #73406400041999 License #EF-0001037 n NAPCO StarLink � a. 333 BayvievtAveNAPCe, Ne. York 11701 Commercial Fire LTE Communicator Series For Sales and Repairs, (80D) 645-9445 For Technical Service,peose urity.0 or visit us at AHJ Submittal Package http:/!tech. n aecosec uritv.com! (Note: Technical Service is for security professionals only) Publicly traded on NASDAQ Symbol NSSC © NAPCO 2019 WI2200DLF 11/19 This package contains documents intended for submittal to the AHJ to be used in the planning and approval of commercial fire alarm installations using the NAPCO StarLink cellular fire communicator. The StarLink fire communicator models and applicable service plans referenced are fully compliant with UL 864 10th edition, NFPA 2010 and NFPA 2013, which permits its use as a sole path fire alarm communicator. To access the following information in the PDF file, simply click on the respective link: NAPCO Starl-ink Communicator Compliance Summary ...........................................................................................................................................2 Universal StarLink Cellular Fire Alarm LTE-Series Communicators..:'.......................................................................................................................5 Universal StarLink Cellular Wor IP Fire Alarm LTE-Series Communicators..............................................................................................................6 AHJ Submittal Data Sheet, SLE-LTEV-FIRE and SLE-LTEA-FIRE..........................................................................................................................7 ;;(' AHJ Submittal Data Sheet, SLE-LTEV-CFB-PS, SLE-LTEV-CFB, SLE-LTEA-CFB-PS and SLE-LTEA-CFB..........................................................9 AHJ Submittal Data Sheet, SLE-LTEVI-FIRE and SLE-LTEAI-FIRE......................................................................................................................11 AHJ Submittal Data Sheet, SLE-LTEVI-CFB-PS, SLE-LTEVI-CFB, SLE-LTEAI-CFB-PS and SLE-LTEAI-CFB....................................................13 StarLink Antenna Extension Kits: Installation Instructions......................................................................................................................................15 AHJ Testing of Communicator: Take the guesswork out of testing the fire alarm communicator, locate the NFPA revision and installed communicator model for the required step-by-step AHa test procedure: Sole Path NFPA 2010 SLE-LTE-CFB-PS Series AHJ Insp. Guide...................................................................................................................16 Sole Path NFPA 2010 SLE-LTE-FIRE and SLE-LTE-CFB Series AHJ Insp. Guide.........................................................................................18 Dual Path NFPA 2010 SLE-LTEI-CFBPS Series AHJ Insp. Guide...................................................................................................................20 Dual Path NFPA 2010 SLE-LTEI-FIRE and SLE-LTEI-CFB Series AHJ Insp. Guide.......................................................................................23 X Sole Path NFPA 2013 SLE-LTE-CFB-PS Series AHJ Insp. Guide...................................................................................................................26 Sole Path NFPA 2013 SLE-LTE-FIRE and SLE-LTE-CFB Series AHJ Insp. Guide.........................................................................................28 Dual Path NFPA 2013 SLE-LTEI-CFBPS Series AHJ Insp. Guide...................................................................................................................30 Dual Path NFPA 2013 SLE-LTEI-FIRE and SLE-LTEI-CFB Series AHJ Insp. Guide.......................................................................................33 UL864 (10th edition) Certification...........................................................................................................................................................................36 FDNY Approved Fire Alarm Control Panels with Certificate(s) of Approval............................................................................................................37 LAFDStarLink LTE Letter of Approval....................................................................................................................................................................38 California State Fire Marshal Certificate of Compliance..........................................................................................................................................39 NAPCO NOC Certificate of Compliance, UL 864, 10th Edition, UL 1635, UL 1610................................................................................................41 UL Compatibility with DSC Sur-GARD V Central Station Receiver.........................................................................................................................42 UL Compatibility with Bosch TCP/IP Protocol.........................................................................................................................................................43 NARCO StarLirik NAPCO StarLink Communicator Compliance Summary UL 864 COMMUNICATOR MODEL UL 1023 UL 985 10th Ed. UL 1610 FDNY CSFM LAFD NFPA 72 Residential Household Commercial Commercial COA Editions Burg Fire Fire Intrusion Sole Path Commercial Sole Path Fire/ SLE-LTEV-FIRE Burg Alarm Communicator ✓ ✓ ✓ �/ �/ 20, 201, SLE-LTEA-FIRE Panel Powered (12-24VDC _ _ — — — 2013, 2016, Regulated) _ (LTEA pending) 7300-0992:0144 (LTEA pending) 2019 Commercial Sole Path Fire/ SLE-LTEV-CFB-PS Burg Alarm Communicator �/ �f ,� 2007,'2010, SLE-LTEA-CFB-PS Direct 120VAC Powered or t — — 2013, 2016, Plug -In Xformer (TRF12) `W (LTEApending) 7300-0992:0144 (LTEApending) 2019 Commercial Sole Path Fire/ SLE-LTEV-CFB Burg Alarm Communicator ✓ '� V" 2007, 2010, SLE-LTEA-CFB Panel Powered (12-24VDC — -- — 2013, 2016, Regulated) (LTEA pending) 730070992:0144 (LTEA pending) 2019 Commercial Dual Path Fire (Dual Path SLE-LTEVI-FIRE IP / Cellular Alarm Communicator ✓ f ✓ ✓ ✓ does not 2007, 2010, SLE-LTEAI-FIRE — _ require 2013, 2016, i Panel Powered (12-24VDC _ _ — (LTEA pending) 7300-0992:0144 LAFD 2019 Regulated) evaluation) Commercial Dual Path Fire SLE-LTEVI-CFBPS IP / Cellular Alarm ✓ ✓ ✓ ✓ ✓ ✓ (Dual Path does not 2007, 2010, SLE-LTEAI-CFBPS Communicator require 2013, 2016, Direct 120VAC Powered or (LTEApending) 7300-0992:0144 LAFD 2019 Plug-in Xformer (TRF12) evaluation) NAPCO Security Technologies, Inc. 333 Bayview Avenue, Amityville, New York USA 11701 Telephone (800) 645-9445 (631) 842-9400 Page 1 / 3 NAPCO StarLink INTRODUCTION The StarLink- Commercial / Residential Fire and Burglary alarm capture radio communicators are fully supervised, wireless digi- tal two-way subscriber units supported by an extensive nation- wide wireless network. All models are compatible with most 12VDC alarm control panels (always adhere to the documenta- tion provided by the control panel manufacturer). The SLE- LTEV-CFB and SLE-LTEA-CFB series are compatible with most 12 or 24VDC control panels. Both can function as a backup to existing telephone lines, or as sole path primary communica- tors. In backup mode, both units will automatically switch the communication channel from the telephone line to the network when telephone line trouble is detected. See W12140 for pro- gramming information. These StarLink radios use data -capture technology that cap- tures the alarm report from the control panel and transmits the alarm signals to the SLE Control Center; the alarm signals are then forwarded to ANY central station via Contact ID or Sur - Gard System II via TCP/IP using standard line security. The SLE Control Center reports a trouble signal in the event that the network does not receive the expected supervision signal from the wireless communicator. For Commercial Burglary installations, under the armed condi- tion, any loss of communication must be treated as a Burglary Alarm at the Central Station. STARLINK RADIO REPORTING PATH The diagram below shows the transmission path of a signal from the StarLink radio to the central station. 1. Signal from a Control Panel. 2. StarLink radio receives the signal transmission (from the TIP an RING wires); sends RF signal through the GPRS network operator. 3. Network Operator, part of the vendor system, a section of the cellular spectrum. 4. SLE Network Operations Center, receives / routes data. 5. Central Station. FACP (1) A -- CENTRAL (5 ) STATION RF OArq StarLink Radio I (3) Network Operator (4) StarLink Network Operations Center SLE-LTEV-CFB-PS /.SLE-LTEA-CFB-PS SLE-LTEV-CFB / SLE-LTEA-CFB Commercial / Residential Fire and Burglary Series Alarm Communicators Submittal Data Sheet 3ESLE-LTEV-CFB-PS / SLE-LTEA-CFB-PS: Commercial / Resi- dential Fire and Burglary Radio in red metal housing with SLE- ULPS-R power supply and 16.5V / 20VA transformer mounted inside housing SLE-LTEV-CFB / SLE-LTEA-CFB: Commercial / Residential Fire and Burglary in red metal hous- ing. Powered directly from control panel (no power supply, no transformer, rated 12, -" input) Note: The StarLink communica- tor model naming convention includes either an "A" or "V" following the "LTE" in the model name, indicative of the carrier. "V"=Verizon carrier compatibility and "A"=AT&T carrier compati- bility. 191:72F,11WIN611010017- il1INWA These StarLink LTE Series models are compatible with most 12VDC alarm control panels equipped with a DACT that must transmit central station reports in Contact ID or 4/2 central station formats. The control panel may also trigger communication events through the use of FACP dry contacts connecting the (3) radio inputs, capa- ble of transmitting (4) distinct alarm and trouble event reports to the central station. The following features are included with mod- els that include a SLE-ULPS-R power supply: • Power limited output to the StarLink radio PC board 12V input terminals • Battery connection red and black flying leads • Monitored battery charging and Active battery test circuits • StarLink radio trouble input (from StarLink radio PC board PGM1 terminal to detect StarLink radio trouble) • Requires a sealed lead acid min 4AH / max 7AH battery for min- imum 24-hour standby time (max charge current 200mA). • Trouble relay output (C, N/O and N/C terminals) to wire to a panel zone dedicated to "LTE Trouble" (dry contacts). Remove jumper 12" to isolate common from ground • Green AC ON LED visible from the exterior housing Yellow TROUBLE LED on PC board. Flashes signify: One flash: AC fail / brownout (2 hour delay) Two flashes: Low battery Three flashes: Charging circuit trouble Four flashes: StarLink radio trouble The housing -mounted transformer (when provided) is mounted NAPCO Security Technologies, Inc., 333 Sayview Ave, Amityville, NY 11701 (800) 645-9445; Fax (631) 789-9292 A764 11/19 inside its own housing compartment with a replaceable UL Listed .5A fast blow primary fuse. 120VAC connections are to be made by a licensed electrician using suitable connectors, in accord- ance with N.E.C. and local code requirements. ADDITIONAL COMPONENTS In addition to the models listed above, the following sub- assemblies are available: SLE-ULPS-R - Power Supply. Required for installations where the control panel cannot provide the 71mA of Auxiliary power re- quired to operate the StarLink radio. Uses a standard 4AH / 12V minimum (7AH maximum) rechargeable battery to provide radio standby power. Requires connection to either the model NAP - CO TRF12/T123 (16.5V / 20VA) external plug-in transformer or the chassis -mounted 16.5VAC / 20VA transformer affixed inside the housing (see wiring diagrams further in this manual). Note: For models without the SLE-ULPS-R, connect the radio terminals 1 and 2 to the control panel Aux Power terminals (observing polarity). SLE-DLCBL - Download Cable, 6 feet SLE-ANTEXT30 - Extended antenna with 30 feet of cable SLE-ANTEXT50 - Extended antenna with 50 feet of cable SLE-ANTEXT75 - Extended antenna with 75 feet of cable SLE-ANTEXT100 - Extended antenna with 100 feet of cable (Any suitable external cellular antenna is permitted by UL). Al- ways follow the manufacturer's installation instructions. Note: Antennas are not Listed by UL. For LTE radios where an External Antenna needs to be installed outside of the room in which the radio is installed (maximum 30 meters (98 feet) in Residential applications), please use RF Transmitter Board 9SLELTEEXAPSLD available from our Customer Service Department, if not provid- ed. The 9SLELTEEXAP5LD is identified by "two red dots" located on the lower right corner of the board. See WI2239 included with the 9SLELTEEXAPSLD for the simple installation procedure. GEM-Tamperkit - Tamper switches and screws to protect metal housing SPECIFICATIONS The following specifications apply to all StarLink radio models unless otherwise stated: Electrical Ratings for 120VAC, 60Hz For Models with Power Supply • Input Voltage: 120VAC nominal Input Current: 150mA maximum Maximum Charging Current: 200mA Electrical Ratings for +12V For Models without Power Supply* • Input Voltage: 10-15VDC (power -limited output from Listed control panel). Note: Models SLE-LTEV-CFB / SLE-LTEA-CFB are rated 10-25VDC input. • Input Current for SLE-LTEV-CFB / SLE-LTEA-CFB: 10V = 90mA, 12V = 71mA, 25V = 68mA, with peak RF transmission current of 200mA. Electrical Ratings for the IN 1 Burg/Fire Input: • Input Voltage: 9-15VDC. Note: Models SLE-LTEV-CFB / SLE- LTEA-CFB are rated 9-25VDC input. • Maximum Input Current: Up to 2mA from FACP NAC circuit Electrical Ratings for IN 2 and IN 3: • Maximum Loop Voltage: 15VDC. Note: Models SLE-LTEV- CFB / SLE-LTEA-CFB are rated max 25VDC input. • Maximum Loop Current: 1.2mA • End of Line Resistor (EOLR) Value: 10K (2 req'd) Electrical Ratings for 3 PGM Outputs: • Open Collector Outputs: Maximum Voltage 3V when active; 15V maximum when not active. Note: Models SLE-LTEV- CFB / SLE-LTEA-CFB are rated max 25VDC output. • Maximum PGM Sink Current: SOmA (up to 15VDC), 25mA (15.1VDC - 25VDC) Physical (W x H x D) • Metal Housing: 11%: x 9'% x 3%" (29.2 x 24.1 x 8.9cm) • Mounting: Metal housing includes two keyhole slots for wall mounting Environmental • Operating Temperature: 0°C - 49°C (32°F -1207) • Humidity: Maximum 93% Non -Condensing • Indoor / dry location use only AGENCY LISTINGS • UL 864 Standard For Control Units and Accessories For Fire Alarm UL Systems, 10th Edition • UL 1610 Standard For Central -Station Burglar -Alarm Units • UL 985 Standard For Household Fire Warning System Units • UL 1023 Standard For Household Burglar -Alarm System Units LTEV/LTEA models are Verizon® Network Certified NOTICE TO AUTHORITIES HAVING JURISDICTION, USERS, INSTALLERS, DEALERS, AND OTHER AFFECTED PARTIES FIRE PROGRAMMING OPTION PERMITTED IN UL864? (Y/N) AVAILABLE SETTINGS REQUIRED UL 864 SETTINGS Disabled (Jumper 1 installed). Also required for Commercial / Burglary Unattended Remote Downloading No Enable / Disable installations. Note: See the Installation Instructions section "Configuration Download / Firmware Updates" for jumper instructions. IN2 and IN3 Unsupervised No Supervised / Unsuper- vised Supervised (Jumpers 4 and 5 installed) Radio Path Supervision No 200 seconds, 5 minutes, 200 seconds (UL 864 / UL 1610), 5 minutes (UL 864 9th edition), 60 60 minutes, 7 days minutes (UL 86410th edition), 7 days (UL 985 / UL 1023) 'For Commercial Fire installations, a UL Listed Fire Alarm regulated power supply or FACP regulated auxiliary output is required. IN 333 Bayview Avenue Amityville, New York 11701 FFA For Sales and e,(800)645- 440or445 StarLink SLE-LTEV-CFB-PS Fire Alarm Communicator For Technical Service, (800) 645-9440 or visit us at hftp://tech.napcosecurity.com/ Battery Calculations �7 (Note: Technical Service is for security professionals only) NAPCO Publicly traded on NASDAQ Symbol: NSSC © NAPCO 2019 W12335LF 4/19 Standby Current Calculations for the model SLE-LTEV-CFB-PS Fire Alarm Communicator: • Standby Battery Capacity: .....................................7 AH • Standby Current Draw of Communicator: ............. 85mA • De -rating Factor: ...................................................... 0.80 Standby Time (Hours) = Battery Capacity x 0.80 = 65.9 Hours Communicator Current Draw Examples: 4 AH battery = (4AH / 0.085A) x 0.80 = 37.6 Hours 7 AH battery = (7AH / 0.085A) x 0.80 = 65.9 Hours n StarLinkTM SLE-LTE-CFB-PS Series 333 Bayview Avenue, Na�ye,New York 11701 Sole Path Fire Communicators For Sales and Repairs. (800) 645-9445 For Technical Service,(800)64rjty.corvisit us at NFPA 2013 AHJ Inspection Guide htto:lltech.nap casecuritV.coml (Note: Technical Service fs for security professionals only) Publicly traded an NASDAQ Symbol: NSSC © NAPCO 2019 WI2176ELF 11/19 The NAPCO SLE-LTE-CFB-PS Series Commercial Fire communicators (includes models SLE-LTEV-CFB-PS .and SLE-LTEA-CFB-PS), fully compliant with the 2013 edition of NFPA 72, are approved as fire alarm communicators. The capability of indicating and communicating signal failures to the central station within 60 minutes of an outage allows the communicators to replace existing telephone lines. The following testing guide is intended to assist with the AHJ inspection of Fire communicator installations. All required test- ing procedures are described, followed by the correct system responses. Ensure that in cases where.a communicator trou- ble output is connected to an input on the FACP, the fire control panel properly annunciates the trouble condition. Normal LED Indications With the StarLink communicator in standby mode, ensure the LEDs display as follows: LED Verify this Condition Passed? Yellow Operational LED D4 Blinks every 10 seconds (indicates normal operation). ❑ Green RF Signal LED D3 Blinks at least 2 times (indicates minimally acceptable signal strength). ❑ Red Trouble LED D5 OFF (indicates no trouble present). ❑ Yellow Trouble LED on the OFF (indicates no trouble present). ❑ SLEULPS-R AC Failure Test Remove radio AC power and observe the following SLEULPS-R power supply indications: LED Verify this Condition Passed? on the SLEULPS-R Yellow Trouble LED Blinks once. ❑ Trouble Relay Output Activates after 2 hours; check for proper trouble annunciation at FACP. ❑ Restore radio AC power: Yellow Trouble LED Turns off. ❑ Trouble Relay Output Restores; check for proper trouble restoral at FACP. ❑ No Battery / Low Battery Test Disconnect the radio battery and observe the following SLEULPS-R power supply indications: LED Verify this Condition Passed? on the SLEULPS-R Yellow Trouble LED Blinks twice. ❑ Trouble'Relay Output Activates within 200 seconds; check for proper trouble annunciation at ❑ FACP Reconnect the radio battery: Yellow Trouble LED Turns off. ❑ Trouble Relay Output Restores; check for proper trouble restoral at FACP. ❑ (continued) 26 Signal Loss Test This test ensures that the StarLink communicator will indicate a supervisory trouble condition to the FACP and central station upon loss of signal within the required time period. Remove the antenna and observe the following indications: LED Verify this Condition Passed? Red Trouble LED D5 Blinks 5 times. ❑ Yellow Trouble LED on Blinks 4 times. ❑ SLEULPS-R Trouble Relay Output on Activates within 60 minutes; check for proper trouble annunciation at ❑ SLEULPS-R FACP Supervisory signal E356 will be received by the central station within ❑ 60 minutes of the antenna being removed. Reconnect the antenna: Red Trouble LED D5 Turns off. ❑ Yellow Trouble LED on Turns off. ❑ SLEULPS-R Trouble Relay Output on Restores; check for proper trouble restoral at FACP. ❑ SLEULPS-R Supervisory restore signal R356 will be received by the central station ❑ within 60 minutes of the antenna being reconnected. Note: In cases where the radio may be located in close proximity to the cell tower, there is a possibility that the communicator may operate properly, even with the antenna removed. 27 Data Sheet Cerberus PRO 50-Point Addressable Fire Alarm Control Panel Model FC901 ARCHITECT AND ENGINEER SPECIFICATION. • Fire alarm control panel (FACP) for up to 50 addressable points that is comprised of the following three (3) system components: • Main board (Model FCM901-U3) ■ 6.5 Amps (170-Watt power supply (Model FP2011-U1) • System enclosure (Model FH901-U31 R3) System features: • Supports 50 addressable devices on one (1) 'Class A', or two (2) 'Class B' circuits • Includes one (1) 'Class A', or two (2) 'Class B' notification appliance circuits (NACs) • Built-in digital alarm communication transmitter (DACT) • Supports Carbon Monoxide (CO) detection • Downloads, prints system -event history & detector sensitivity • Supervised remote printer (Model FCA2018-U1) ■ Optional connectivity to a leased -line 1 city -tie module (Model FCI2020. • Built-in RS-485 connection for remote annunciators • A • Resettable and non-resettable 24VDC auxiliary power for manual configuration • Off -normal warning message prior to reset • Fast and easy set-up with custom -configuration tool • OUL 864 91h Edition Listed; • Supports a 182-character display FM, CSFM & NYC Fire Department Approved City of Chicago, Class 1 Approval Product Overview Main Board Model FC901 is an intelligent FACP that provides a cost-effective, feature -rich solution for small fire -alarm system applications. Small and compact in design, Model FC901 is ideal for small fire -protection applications using less than 50 addressable devices: • Retail outlets I strip malls . doctors' offices • Dry-cleaner shops . restaurants, etc. With its built-in DACT and two (2) NACs, Model FC901 is powerful enough to economically meet the needs of these applications. Each 50-point FACP has City of Chicago, Class 1 Approval, as well as being FM (43010); CSFM (,47165-0067:0259) and FDNY (46104) Approved. Specifications The Model FC901 FACP consists of a main board (Model FCM901-U3); a 170-Watt power supply (Model FP2011-U1), and a Model FH901-U3 I R3 system enclosure. The programming software for Model FC901 is held in flash electrically erasable Cerberus® PRO The Model FCM901-U3 main board provides system display and control, as well as connections for system field wiring, via removable terminal blocks. The 3.5-inch (8.9 centimeters) by 1.5" (3.8 centimeters) liquid -crystal display (LCD) screen shows all system messages and event status. Each screen supports 182 characters: seven (7) lines with 26 characters per line. Each event may have a custom message up to 40 characters that describes the event's location. The backlit LCD screen illuminates on any system event or manual key press. New, 'unacknowledged' events are indicated by a flashing exclamation point ('!'). Once 'acknowledged,' the exclamation point changes to a check mark (V '). A system -status line shows the quantity of events presently active. Since each main board contains a built-in RS-485 communication bus, Model FCM901-U3 readily supports system -status light -emitting diodes (LEDs) for Power, Alarm, Trouble, Supervisory and Ground Fault system commands. 9813 Fire Safety Products Feature -rich solution for 50-pt. addressable FACPs Specifications Main Board — (continued) There are also LEDs to indicate when audible circuits are 'active' or 'silenced.' The main board supports four (4) system -control buttons, including: Acknowledge; Alarm Silence; Unsilence, and Reset. The system offers an off -normal warning feature, alerting users when active devices are not ready for reset. These active devices may include manual stations that have not been reset; smoke detectors with smoke remaining in the optical chamber, etc. Additionally, the main board supports an alphanumeric keypad, as well as navigation keys, which are used for scrolling maintenance functions and system configuration. The main board supports connection for up to 50 addressable devices, via one (1) 'Class A', or two (2) 'Class B' circuits. The loop supports all C-NET devices, including the Cerberus PRO intelligent and Model 'H'- series devices. The main board also supports one (1) 'Class A' or two (2) 'Class B' NACs. Each NAC supports a maximum 2.5 Amps — with 2.5 Amps, max, allowed between the NACs. Each NAC can be set to a synchronized strobe, for horn -strobe devices, or for audible devices. Audible devices can be set for:. • 'STEADY' • 'ANSI Temporal T /'ANSI Temporal 4' • 'March Time 30 / 60 1120 Codes' The main board supports four (4)'Form C' relays for Alarm, Trouble, Supervisory and User Programmable events. Each relay is rated at 2 Amps at 30VDC maximum, resistive. The main board supports two (2) auxiliary 24VDC connections. Upon system reset, one (1) connection interrupts the power for five seconds for use with (4) four -wire conventional detectors. Each auxiliary -power output is 24VDC, nominal — rated at 0.75 Amps. The main board contains a built-in DACT that provides communication between Model FC901 and with the central or remote monitoring station. The built-in DACT supports two (2) separate programmable accounts, as well as two (2) connections to the public -switched telephone network. The connections support RJ31 X male connectors. (For compatibility with each Model FC901 FACP, see the Central Station Receiver Compatibility Table on the last page of this data -sheet document.) The main board contains a battery -charging circuit, providing connection to lead -acid batteries rated at 24VDC, nominal. The main board can charge up to 18 AH batteries. The main board contains a universal serial bus (USB) connector that supports connection for system configuration and module firmware upload, via the custom -configuration tool. Model FC901 can be configured using the custom - configuration tool or manually from the alphanumeric keypad on the main board. An auto -configuration feature creates a basic system configuration of all connected devices to accelerate initial system commissioning. 50-Point Addressable System Enclosure The Model FH901-U3 I R3 enclosure for the 50-point addressable fire system, Model FC901, supports all system modules. The enclosure also supports up to 12AH batteries. Note: For systems requiring larger than 12AH batteries, use a OUL Listed battery box. The Model FH901-U3 I R3 enclosure for the 50-point panel is comprised of a dual -mounting setup that allows the main board to be partially mounted in a lower -to -upper position. When temporarily installed in the lower position, technicians are allowed more space to install field wiring at the time of system set- up. When field -wiring installation is complete, the main board shall be moved to the upper position for standard mounting prior to applying power to the system. Additionally, 'the enclosure supports an optional battery bracket (Model FHA901-U1) that can be used to secure batteries up to 12AH. Model FHA901-U1 is required to comply with seismic certification, pursuant to ASC 1 SEI 7-05, Section 13.2.2. A flush -mount trim kit (Model FHA902-Ul I R1) is also available - for use when flush mounting Model FH901-U3 1 R3. 50-Point Power Supply The Model FCM901-U3 main board also supports connection to the system power supply. The 6.5A (170-Watt) power supply (Model FP2011-U1) incorporates a 4.OA, non-resettable slow -blow fuse on the primary input, and includes a built-in AC -line filter for surge and noise suppression. Model FP2011-U1 mounts in a standard Siemens — Fire Safety enclosure, and there are no serviceable Siemens — Fire Safety parts to be maintained. SIEMENS Industry, Inc. Building Technologies Division Cerberuse PRO Specifications — (continued) — Optional Accessories — Leased -Line / City -Tie Module The Model FC901 FACP has the capability of operating an optional leased -line, city -tie module (Model F02020-M) that provides a local -energy output for municipal call -box connection. A wiring harness, Model FCA901-U1, is required for use, and must be ordered separately. The leased -line, city -tie module is installed on the back of the main board of the Model FC901 FACP, and field wiring is connected to the main board. 50-Point Remote Annunciator The fire -system displays (FSD901-U3 / R3) are remote LED / LCD units that show the existing status of the Model FC901 FACP. The Model FSD901-1-13 I R3 optional display supports the following LEDs for system -status conditions: • Power • Alarm • Trouble • Supervisory • Ground -Fault There are also LEDs to indicate when audible circuits are 'active' or 'silenced.' The main board supports four (4) system -control buttons, including: Acknowledge; Alarm Silence; Unsilence, and Reset. For Model FSD901-U3 I R3, a LED will illuminate for any given Alarm, Supervisory and Trouble Cerberus PRO - system event. A 3.5-inch (8.9 centimeters) by 1.5" (3.8 centimeters) LCD screen will give details of the event in alphanumeric form. The display screen can be scrolled to reveal additional events. Optional remote - system -control capabilities are also available. The Remote Peripheral Module (FCA2018-U1) provides a means of connecting a Cerberus PRO 50-point addressable panel to a parallel printer for creating a hard copy of system -status events. This supervised, intelligent module contains built-in transient protection and plain -decimal addressing. When Model PAL-1 is used with the remote peripheral module, Model FCA2018-Ul supervises the printer for ON, OFF Line I POWER ON I PAPER OUT I PAPER JAM, and wiring -fault conditions, as required by OUL for NFPA 72 proprietary systems. The following are the dimensions based upon connection to a one -height -unit enclosure (1HU) for Model FC901: proximate size: 16.5" (41.9 cm.) [H]; 18.13" (46.1 cm.) [W]; 5.11" (13 cm.) [D] The weight (without operating unit or batteries) is approximately 9 pounds (4082 g]. LED Annunciator Driver: 32 Outputs 116 Inputs Model FT2007-Ul serves as the main component for allowing custom graphic annunciators to operate on Model FC901 FACPs. There are 16 inputs on each Model FT2007-Ul to accommodate user -defined system commands, which include: Reset; SilencelUnsilence; Acknowledge, and Lamp Test. Inputs can also be programmed as "Generic", which allows additional flexibility for customized functionality. Shipments of each Model FT2007-Ul driver include two (2) PC boards [PCBs]; one (1) built-in RS-485 interface, and one (1) LED driver. Additionally, one (1) ribbon cable is packaged, allowing connectivity between the two (2) PCBs. Tabular Annunciator Drivers: 16 Zones 132 Zones The Tabular Annunciators allow system events sent from Cerberus PRO 50-p0int addressable panels to be displayed remotely in real-time. The Model FT2008 series of tabular annunciators has 16 zones and the Model FT2009 series uses up to 32 zones. Additionally, no more than two (2) light -emitting diodes (LEDs) can be used per zone. A built-in RS-485 communication bus controls the operation and supervision of the 16-zone and 32- zone Tabular Annunciators, which are available in black or red. Temperature and Humidity Range Model FC901 is ©UL 864 91h Edition Listed for indoor dry locations within a temperature range of 120 +/- 30F (49 +l- 2°C) to 32 +/_ 3°F (0 +l- 2°C) and a relative humidity of 93 +/- 2% at a temperature of 90 +/- 3'F (32 +/- 20C). Related Documentation Product Data Sheet Number 170-Watt power supply 9806 Leased -Line I City -Tie Module 9810 Remote Peripheral Module 9811 50-Point Remote Annunciator 9817 LED Annunciator Driver, FT2007-U1 9824 16-Zone (FT2008-U1) 132-Zone (FT2009-1-11) Tabular Annunciators 9825 SIEMENS Industry, Inc. Building Technologies Division Cerberus° PRO Central Station Receiver Compatibility Table The following table shows a list of central station receivers that are compatible with the Cerberus PRO 50-point addressable system, Model FC901 — O o -O „~:! -0 : v O 0 coo Y� to so r`o(A Protocol co l9 y ` l9 W L(A d + so�oo to rn to ot f- F G E aXNo t lie SIA8 ✓ ✓ ✓ ✓ ✓ ✓ ✓ SIA 20 ✓ ✓ ✓ ✓ ✓ ✓ ✓ Ademco ✓ ✓ ✓ ✓ ✓ ✓ Contact ID 412 ✓ ✓ . ✓ 3/1 ✓ ✓ ✓ Note: Multiple central station receivers are compatible with the Cerberus PRO 50-point FACP, Model FC901. Although the table above illustrates central station receivers that have been verified by Siemens with the Model FC901 FACP, additional receivers and formats can also be used with each 50-point addressable system. After completing the installation, communication between the Digital Alarm Communication Transmitter (Model DACT) and Central Station Receiver must be tested and verified. Details for Ordering Model Part Description Number FCM901-U3 S54433-B101-Al Cerberus PRO Main Board {for the 50•point FACP} FH901-U3 S54433-B103-A3 System Enclosure, Black (for the 50-point FACP} FH901-R3 S54433-B103-A4 System Enclosure, Red {for the 50-point FACP} FP2011-U1 500-450222 170-Watt Power Supply SIEMENS Cerberus® PRO Siemens Industry, Inc. — Building Technologies Div. 8 Fernwood Road • Florham Park, NJ 07932 Tel: (973) 593-2600 • Fax: (908) 547-6877 Web: www.USA.Siemens.com/Cerberus-PRO Details for Ordering — (continued) — Optional Accessories — Model Part Description IFCA2018-Ul Number S54400-A65-A1 Remote Peripheral Module FCI2020-Ul S54400-A57-A1 Leased -Line / City -Tie Module Wiring Harness FCA901-Ul S54433-C106-A1 (for use with Cerberus PRO Model FC901 control panels) FHA901-Ul S54433-B107-Al Battery Bracket FHA902-Ul S54433-B106-Al Flush -Mount Trim Kit, Black FHA902-Rl S54433-B106-A2 Flush -Mount Trim Kit, Red FSD901-U3 S54433-Cl02-Al System Display, Black {specifically for the 50-point FACP} FSD901-R3 S54433-C102-A2 System Display, Red {specifically for the 50-point FACP} FT2007-Ul S54400-A142-A1 LED Annunciator Driver (32 Outputs.) 16Inputs } 16-Zone Tabular FT2008-Ul S54400-A143-A1 Annunciator, Black 16-Zone Tabular FT2008-Rl S54400-A144-A1 Annunciator, Red 32-Zone Tabular FT2009-Ul S54400-A145-A1 Annunciator, Black 32-Zone Tabular FT2009-RI S54400-A146-Al Annunciator, Red —Electronics Package — Model Part Number Description Cerberus PRO Kit for the 50-Point Addressable FACP E• 170W power supply, I Model FP2011-U1 FC901-U3 S54433-C105-Al i (Qty.1) Includes:'• System main board, ' Model FCM901-U3 (Qty. 1) NOTICE —The information contained in this data -sheet document is intended only as a summary, and is subject to change without notice. The devices described here have specific instruction sheets that cover various technical, limitation and liability information. Copies of these instruction sheets and the General Product Warning and Limitations document, which also contains important information, are provided with the product and are available from the Manufacturer. Information contained in these documents should be consulted before specifying or using the product. For further information or assistance concerning particular problems contact the Manufacturer. Building Technologies Division November 2016 — supersedes sheet dated 6/2016 (Rev. 14) SR —Fire Safety [Printed in U.S.A j Intelligent Detection Devices Photoelectric Smoke Detector Model OP921 ARCHITECT AND ENGINEER SPECIFICATIONS Data Sheet Compatible with Siemens Model'H'-series devices on the same loop (with Cerberus PRO fire -alarm control panels [FACPs] or FireFindero XLS FACPs) • Compatible with Model 8720 / DPU (device programmer / loop tester) Utilizes advanced microprocessor -based signal processing Extended temperature and humidity operating range Each detector is self -testing: • Self monitored for sensitivity within OUL Listed limits • Complete diagnostics performed every 10 seconds Polarity insensitive utilizing SureWireT"technology Compatible with Model DB-11—series mounting bases Tri-colordetector-status LED with 360'viewing Field -selectable application sensitivity profiles Remote sensitivity -measurement capability U� Automatic environment compensation Utilizes advanced signal processing • ®UL268A Listed [for direct air -duct use], Superior EMI / RFI immunity OULC Listed; FM ('3230, 3210) and CSFM RoHS compliant ('7272-0067:0258) Approved Product Overview The Photoelectric Smoke Detector (Model OP921) uses state-of-the-art microcontroller circuitry and surface - mount technology for maximum reliability. Model OP921 incorporates an optical sensor using a light - scattering detection principle. The device utilizes advanced software algorithms to analyze the signals, and provides highly stable and accurate smoke detection. Further, Model OP921 uses state-of-the-art microprocessor circuitry with error check; detector self - diagnostics, and supervision programs. Field -Device Programmer / Test Unit Model OP921 is compatible with the Siemens field - device programmer / test unit (Model 8720 / DPU), which is a compact, portable, menu -driven accessory for electronically programming and testing detectors easily and reliably. Cerberus® PRO Fire Safety Products Model 8720 / DPU eliminates the need for cumbersome, unreliable mechanical programming methods, such as dials or switches, and reduces installation and service costs by electronically programming and testing the detector prior to installation. For proper operation of the field -device programmer / test unit, the technician selects the accessory's program mode, and enters the desired address. In turn, Model 8720 / DPU automatically sets and verifies the address, as well as tests the detector. When in the'test' mode, Model 87201 DPU will perform a series of diagnostic tests without altering the address or other stored data, allowing technicians to determine if the detector is operating properly. Model 8720 / DPU operates on AC power or rechargeable batteries, providing flexibility and convenience in programming and testing equipment from practically any location. 99-02 Photoelectric Smoke Detector Product Overview — (continued) Model 8720 I DPU operates on AC power or rechargeable batteries, providing flexibility and convenience in programming and testing equipment from practically any location. Model OP921 is a plug-in, two -wire and addressable photoelectric smoke detector. Model OP921 is ®Underwriters' Laboratories Listed [oUL268A Listed for direct in -air duct usage]. Each detector consists of a dust -resistant photoelectric chamber and microprocessor -based electronics with a low -profile plastic housing. Every Model OP921 fire detector is shipped with a protective dust cover: Operation Model OP921 is a wide -spectrum, photoelectric smoke detector incorporating an infrared light -emitting diode (IRLED), and infrared light -sensing photodiode. Under normal conditions, light transmitted by the LED is directed away from the photodiode and scattered through the smoke chamber in a controlled pattern. The smoke chamber is designed to manage light dissipation and extraneous reflections from dust particles or other non -smoke, airborne contaminants in such a way as to maintain stable, consistent detector operation. When smoke enters the detector chamber, light emitted from the IRLED is scattered by the smoke particles, and is received by the photodiode: Sensitivity Settings Application Parameter Sets Model OP921 provides four (4) pre-programmed sensitivity parameter sets that can be selected by the FACP to match the expected application or environmental conditions: • Sensitive • Standard • Robust • Air -duct Sensitive: This application parameter set is practically suitable for areas where few misleading sources of false alarm are present, and is appropriate where priority is given to detecting open fires as soon as possible (e.g. — typically a clean application with controlled environmental conditions.) Standard: This application parameter set is practically apt for normal office, hotel -lobby -type applications, and is the default setting. Robust: This application parameter set offers improved resistance to false alarms in areas where misleading sources, such as cigarette smoke or exhaust fumes, may cause a nuisance alarm. Air -Duct: This application parameter set is used when the detector is used a oUL268A (DI) compliant direct in - air duct application without a duct housing. Model OP921 does not require a field sensitivity test. Model OP921 is ®UL Listed as a self -testing device and complies with NFPA 72 as a self monitoring detector and control panel arrangement. This parameter set is also used when Model OP921 is used in air -duct housings (Models FDBZ492 and FDBZ492-HR). The visible LED flashes green every 10 seconds to indicate communication with the FACP, and to notify Model OP921 has passed its self -test. Should Model OP921 sense a fault or failure within its system, the LED will flash aml::erl and the detector will transmit the data to the FACP. A quick visual inspection is sufficient to indicate the condition of Model OP921 at any time. If more detailed information is required, a printed report can be provided from the compatible FACP, indicating the status and settings assigned to each individual detector. When Model OP921 moves to Alarm mode, the detector will flash red and continue flashing until the system is reset at the FACP. At that same time, any user -defined, system -alarm functions programmed into the system are activated. Model OP921 contains a tri-color LED indicator, capable of flashing any one (1) of three (3) distinct colors: green, , or red. During each flash interval, the microprocessor -based detector monitors the following: SIEMENS Industry, Inc. Building Technologies Division CerberusO PRO Operation — (continued) • Smoke sensitivity is within the range indicated on the nameplate label • Smoke in its sensing chamber • Internal sensors and electronics are functional Based on the monitoring results, the LED indicator flashes the following colors based on the following conditions: Flash Flash Condition Interval Color (in seconds) Normal supervisory operation. Green*: Smoke sensitivity is within rated 10 limits. Yellow: Detector is in trouble and needs 4 replacement. 'aed Alarm condition. 1 4=>.r_: No Flash: Detector is not powered. -- * LED can be turned OFF. Please follow the corresponding description of the panel used. A quick, visual inspection is sufficient to indicate the condition of the detector at any time. If more detailed information is required, a printed report can be provided from the respective Cerberus PRO FACP that indicates the status and settings assigned to each individual detector. Installation All Model OP921 detectors use a surface -mounting base, Model DB-11 or Model DB-11E, which mounts on a 4-inch octagonal, square or single -gang electrical box. The base ,utilizes screw -clamp contacts for electrical connections and self -wiping contacts for increased reliability. The Model DB-11 base can be used with the optional Model LK 11 detector locking kit, which contains 50 detector locks and an installation tool to prevent unauthorized removal of the detector head. Model DB-11 has decorative plugs to cover the outer - mounting screw holes. Model OP921 may be installed on the same initiating circuit with the Siemens Model 'H' series detectors [when used with the Cerberus PRO FACPs1— • Model HFP-11 • Model'HMS'-series manual stations • Model'HTRI'-series interfaces • Model HCP output -control devices • Model'HZM'-series of addressable, conventional zone modules Application Data Installation of Model OP921 detectors requires a two -wire circuit. In many retrofit cases, existing wiring may be used. 7-tapping'is permitted only for Style 4 (Class B) wiring. Model OP921 is polarity insensitive, which can greatly reduce installation and debugging time. Model OP921 can be applied within the maximum 30- feet center spacing (900 sq. ft. areas), as referenced in NFPA 72. This application guideline is based on ideal conditions —specifically, smooth ceiling surfaces, minimal air movement, and no physical obstructions between potential fire sources and the actual detector. Do not mount detectors in close proximity to ventilation or heating and air-conditioning outlets. Exposed joints or beamed ceilings may also affect safe spacing limitations for detectors. Should questions arise regarding detector placement, observe NFPA 72 guidelines. Good fire -protection system engineering and common sense dictate how and when fire detectors are installed and used. Contact your local Siemens —Fire Safety distributor or sales office whenever you need assistance applying Model OP921 in unusual applications. Be sure to follow NFPA guidelines and oUL Listed I@ULC Listed installation instructions —included with every Siemens — Fire Safety detector —and local codes as for all fire - protection equipment. Technical Data Operating Temperature +320F (0°C) to 120°F (49°C) Range: Relative Humidity: 0 — 95%; non -condensing Air Pressure: No effect Air Velocity: 0— 4,000 ft. 1 min (0-20m I sec) Input Voltage Range: 16VDC — 30VDC Alarm Current (max.): 280pA Standby Current (max.): 280pA, max. (average) Maximum Spacing: 30-foot centers (900 sq. ft.), per NFPA 72 Detector Weight: 0.317 lbs. (0.144 kg.) Mechanical Protection Guard: oUL Listed I OULC Listed [with STI Guard Model STI-96041 SIEMENS Industry, Inc. Building Technologies Division CerberusO PRO Mounting Diagram Dimensions 4-13" (10-5 cm-) -.-- E9 Detector Compatibility Table Data Model Sheet Description Number — 6300 FireFinder@ XLS (system overview) FC901 9813 50-point panel FC922 9815 252-point system (networkable) FC924 9815 504-point system (networkable) FV922 9821 252-point intelligent voice communication system FV922 9821 504-point intelligent voice communication system SIEMENS Cerberus® PRO Siemens Industry, Inc. — Building Technologies Div 8 Fernwood Road • Florham Park, NJ 07932 Tel: (973) 593-2600 • Fax: (908) 547-6877 Web: www.USA.Siemens.com/Cerberus-PRO r� Details for Ordering Model Part Description Number OP921 S54320-F4-A2 Photoelectric Smoke Detector DB-11 500-094151 Detector Mounting Base DB-11 E 500-094151 E Detector Base (small) DB2-HR S54320-F12-A7 Relay Base Remote Alarm Indicator RL-HC 500-033230 4" octagon -box mount, red Remote Alarm Indicator: RLHW 500 033310 single -gang box mount, red FDBZ492 554319-B22-A1 Addressable Air -Duct Housing FDBZ492-HR S54319-B23-A1 Addressable Air -Duct Detector with Relay LK 11 500-695350 1 Base Locking Kit STI-9604 I -- I STI Mechanical Protection Guard See: www.STI-USA.com for further details on ordering Model STI-9604. In Canada, order: Model Part Description Number DB-11C 500-095687 Detector Mounting Base for OULC (Listed) NOTICE —The information contained in this data -sheet document is intended only as a summary, and is subject to change without notice. The devices described here have specific instruction sheets that cover various technical, limitation and liability information. Copies of these instruction sheets and the General Product Warning and Limitations document, which also contains important information, are provided with the product and, are available from the Manufacturer. Information contained in these documents should be consulted before specifying or using the product. For further information or assistance concerning particular problems contact the Manufacturer. Building Technologies Division March 2015 —Supersedes sheet dated 11/2013 (Rev. S) 5II —Fire Safety (Printed in U.S.A I SIEMENS Data Sheet Fire Safety Products Intelligent Initiating Devices HMS -Series Models HMS-D, HMS-S ARCHITECT AND ENGINEER SPECIFICATIONS • Durable design • Shock -and -vibration resistant • Single-action (Model HMS-S) and double -action (Model HMS-D) stations • Pull -down lever is down, until manually reset • Reset with Allen Key • No break rods necessary • Custom microcomputer -chip technology • Polarity insensitive via SureWireTM technology • Dynamic supervision to the fire -alarm control panel (FACP) • Device Programmer Unit (Model DPU) programs and verifies address and tests functionality of each device • Electronic -address programming (EEPROM) is easier, as well as more efficient, dependable • Surface or semi -flush installation • Two -wire operation Product Overview The Siemens intelligent manual fire -alarm boxes (Models HMS-S and HMS-D) provide the most advanced method of address programming and supervision. Each Model HMS - series manual box achieves the state of an 'intelligent - initiating device' by incorporating custom microcomputer -chip technology with sophisticated, bi-directional communication capabilities with the panel, which include Siemens 50-point, 252-point and 504-point addressable FACPs. Specifications Models HMS-S and HMS-D are constructed of durable, molded polycarbonate material that is matte finished in red with raised white lettering. The housing accommodates a'pull- down' lever, which — when operated — locks into position; indicating the fire -alarm box has been activated. The pull down lever remains down I in the 'locked' position, until the fire -alarm box is manually reset. The manual fire alarm box can only be reset by opening the hinged housing cover with an Allen key; followed by closing and locking the cover. Models HMS-S and HMS-D operate with Siemens — Fire Safety FACPs. The microcomputer chip to the manual fire -alarm box has the capacity of storing — in memory — identification and important operating -status data. Model HMS-D Dual -Action Station Model HMS-S Single -Action Station • Americans with Disabilities Act (ADA) Compliant • OUL Listed; FM (03015946 &3052621), CSFM ('7150-0067:0036) and NYC Fire Dept. e202-12E, Vol. 1) Approved Models HMS-S and HMS-D are fitted with screw terminals for connection to an addressable circuit, and can be either surface or semi -flush mounted. The Model HMS -series manual fire -alarm boxes derive their power, communicate information and receive commands over a single pair of wires. Each box is compatible on the same circuit with all Model 'H'-series detectors, interfaces or addressable, conventional zone modules. Device I Programmer Tester — Model DPU Innovative technology from Siemens — Fire Safety also allows all Model HMS -series intelligent manual fire -alarm boxes to be programmed via the Device Programmer 1 Test Unit (Model DPU). The programmer I tester is a compact, portable and menu -driven accessory that makes programming and testing of a manual fire -alarm box device faster, easier and more dependable than previous methods. Model DPU eliminates the need for mechanical -addressing mechanisms of a device because Model DPU electronically sets the address of the manual fire -alarm box into .its microcomputer chip, non-volatile memory. Therefore, Vibration, corrosion and other conditions — which can compromise the functionality of mechanical -addressing mechanisms —are no longer an issue. HMS Series Intelligent Initiating Devices 6306 SIEMENS Industry, Inc. Building Technologies Division Technical Data Electrical: Current Draw 1.4mA (Active or Standby) Indoor / Dry Conditions: Operating 32°-1000F Temperature Range (0°-38°c) Operating 0 —93%, Humidity Range non -condensing Details for Ordering Model Part Description Shipping Number Weight 500- Addressable Manual Fire 2.5 1.13 HMS-D 033400 Alarm Box, Dual Action Lbs. Oz. 500- Addressable Manual Fire 2.0 0.9 HMS-S 033200 Alarm Box, Single Action Lbs. j Oz. 500- Reset Tool Package 0.5 ? 0.23 LTP 620490 (contains two (2) tools] Lb. i Oz. SB-5R 310- Surface -Mounting Box 1.5 0.7 019860 Lbs. Oz. Mounting Diagram Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information, refer to each product's installation instructions. Fire Safety 8 Fernwood Road SIEMENS Industry, Inc. Florham Park, NJ 07932 (SH45) September 2016 Building Technologies Division Tel: (973) 593-2600 Printed in U.S.A. supersedes sheet dated 7/1015 FAX: (908) 547-6877 (Rev. 7) URL: www.usa.5iemens.com/Fire SIEMENS Data sheet Fire Safety & Security Products Intelligent Initiating Devices Intelligent Device Interface Module Model HTRI-M {STRI-M for Canada} ARCHITECT AND ENGINEER SPECIFICATIONS • Interfaces and supervises normally open (N.O.) contacts: [i.e. —fire detection] • Interfaces and supervises normally closed (N.C.) contacts: [i.e. — security detection] • Compact size allows mounting in single -gang box behind equipment • Polarity insensitive with SureWireTM technology • Innovative technology supports comprehensive system and •.;rn;_.ai i,; interface communication r-^ • Dynamic supervision ! ' • Two -wire operation ^� �� •i'n'ui:i> • Device Programmer i Test Unit programs and verifies address and test functionality siEt,;en�s • OUL Listed, OULC Listed; - w FM, CSFM and NYC Fire Department Approved Product Overview Specifications The Intelligent Interface Module (Model HTRI-M) is designed to provide the means of interfacing direct shorting devices to the Device Program / Test Unit (Model DPU) for various Siemens — Fire Safety fire -alarm control panels (FACPs). Model HTRI-M provides the most advanced method of address programming and supervision — including sophisticated FACP-communication — in the fire and life safety market. Each Model HTRI-M interface module incorporates microcomputer -chip technology, and advanced bi-directional communication capabilities with the respective FACP. Model HTRI-M is designed to monitor a N.O. or N.C. dry contact, and reports the contact status to the FACP. The microcomputer chip for Model HTRI-M has the capacity of storing — in memory — identification information, as well as integral operating -status data. SIEMENS Industry, Inc. Building Technologies Division Each Model HTRI-M interface module is programmed, via Model DPU, which is a compact, portable and menu -driven accessory that makes programming and testing a given interface more accurately and efficiently than ever before. Model DPU eliminates the need for mechanical - addressing mechanisms —such as program jumpers, DIP switches or rotary dials — since Model DPU sets the interface address of Model HTRI-M into its microcomputer -chip, non-volatile memory electronically. Vibration, corrosion and other conditions that deteriorate mechanical -addressing mechanisms are no longer a cause for concern. Model HTRI-M is connected to Model DPU with the programming cable provided with the tester. This programming cable (PIN 110-694927) utilizes two (2) alligator clip connectors, to attach to the HTRI-M. Intelligent Device Interface Module 6308 Specifications — (continued) Model HTRI-M has five (5) leads [one (1) of the five (5) leads is for grounding], which are wired to the system with user -supplied wire nuts. Model HTRI-M is fully compatible on the same Model DLC circuit with all intelligent Siemens Model'H'-series detectors; Model'HMS'-series addressable, manual stations; or any other Model'H'-series addressable intelligent modules (i.e. — Model HZM or Model HCP). Electrical Hating Current Draw: 1.5mA (Active or Standby) Details for Ordering Model Number Part Number Description HTRI-M 500-034000 Single -Input Intelligent Interface Module In Canada, order: Model Number Fart Number Description STRI-M 500-034000C Single -Input Intelligent Interface Module Note: For shipping -weight considerations, each Model HTRI-series is approximately 3.5 oz. (0.1 kg). Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information, refer to each product's installation instructions. Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard SIEMENS Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario June 2013 Building Technologies Division Tel: (973) 593-2600 50.F5 L6T SE4 / Canada Supersedes sheet dated 12111 FAX: (908) 547-6877 Printed in U.S.A. Tel: (905) 799-9937 (R—a) URL: www.usa.Siemens.com/Fire FAX: (905) 799-9858 SIEMENS Data Sheet Fire Safety Products HTRI-Series Interface Modules Models HTRI-D, HTRI-R and HTRI-S (and USCG-HPLATE for Marine installs) ARCHITECT AND ENGINEER SPECIFICATIONS • Interfacing and supervising normally open (N.0) or normally closed (N.C) contacts • Integral single -pole, double -throw (SPDT) relay on Model HTRI-R (up to 4 amps) • Dual input on Model HTRI-D, using a single address • Polarity insensitive with Sure Wirer'^ technology • Dynamic supervision • Two -wire operation • Multi -color light -emitting diode (LED) indicates system status: - GREEN I Ate IDER I RED • Mounts in a 4-inch (10.2 cm.) square, 2-'/4" (5.7 cm.) deep single -gang or double -gang back box • Easy front access to programming port and wiring terminals • Comes with 5"-x- 5" (12.7-x-12.7 cm.) plastic faceplate Separate metal cover plate required for use in Marine installations • Electronic address programming is easy and dependable • Device Programmer/Tester programs and verifies address of the device and tests for proper functionality Product Overview The Siemens — Fire Safety HTRI-series Intelligent interface modules are designed to provide the means of interfacing direct shorting devices to the fire -alarm control panel (FACP) loop circuit. The HTRI-series modules provide the most advanced method of address programming and supervision on the market —combined with sophisticated control panel communication. Each HTRI-series interface module incorporates a microcomputer chip, and each interface module achieves the state of an 'intelligent device'through its microcomputer -chip technology, combined with its sophisticated, bi-directional communication capabilities with the FACP. Specifications The Siemens Mode HTRI-series intelligent interface modules are available in three (3) types: Model HTRI- D, as well as Models HTRI-S and HTRI-R, which are both designed to monitor a (N.0) or (N.C) dry contact. The interface module reports the status of the (N.0) or (N.C) contact to the control panel. Electronic address programming is easy and dependable . oUL Listed & ©ULC Listed; FM, CSFM and NYCFD Approved Model HTRI-S can only monitor and report the status of the contact, while Model HTRI-R incorporates an add ressabl e 'Form C' relay. The Model HTRI-R relay and contact device input are controlled at the same address. For the FACP, the relay and input contact can be controlled as a separate function. The relay is typically used where control or shunting of external equipment is required. The Model HTRI-D is a dual -input module that is designed to supervise and monitor two (2) sets of dry contacts. Model HTRI-D only requires one (1) address, but responds independently to each input. Model HTRI-D is ideal for monitoring a water -flow switch and its respective valve tamper switch. Model HTRI-D flashes twice — once for each address, and Model HTRI-R LED indicates a change of state in the relay. The device's microcomputer chip has the capacity of storing, in memory, identification information; as well as important operating -status data. HTRI Series Interface Modules 6304 SIEMENS Industry, Inc. Building Technologies Division Specifications (continued) Each Model HTRI device has a multi -color LED that flashes GREEN when operating in Normal; if unit is in Trouble condition, and RED to indicate a change of state. Field -Device Programmer Siemens — Fire Safety innovative technology allows HTRI-series intelligent interface modules to be programmed via the Device Programming / Test Unit: a compact, portable and menu -driven accessory that makes programming and testing an interface device faster, easier and more dependable than previous methods. The programmer / tester eliminates the need for mechanical addressing mechanisms, such as: program jumpers, DIP switches or rotary dials, since Model DPU electronically sets the HTRI-series interface address into the non-volatile memory of the interface microcomputer -chip. Vibration, corrosion and other conditions that deteriorate mechanical addressing mechanisms are no longer a cause for concern. The HTRI-series is fitted with screw terminals for connection to an addressable circuit, and is fully compatible on the same Siemens FACPs with Siemens Model'H'-series intelligent detectors; Model'HMS'-series addressable manual stations, or any other addressable intelligent modules (e.g. — Model HZM or Model HCP). Temperature and Humidity Range Model HTRI-series intelligent interface modules are oUL Listed. Environmental operating conditions for HTRI-D, HTRI-R and HTRI-S modules are 320F (0eC) to 120eF (49eC) with a relative humidity of no greater than 93%, non -condensing. Electrical Ratings Current Draw 1.3mA (Active or Standby) Relay Ratings, Model HTRI-R 4 Amps, 125 VAC Resistive: 4 Amps, 30 VDC Electrical Ratings [Leidy nau11y Z-, rvwuC-r\ - %%.v11L. M.1 3.5A, 120 VAC (0.6P.F.) 3.OA, 30 VDC (0.6P.F.) Inductive: 2.OA, 120 VAC (0.4P.F.) 2.OA, 120 VAC (0.35P.F.) 2.OA, 30 VDC (0.35P.F.) Mounting Diagram Models HTRI-S, HTRI-D and HTRI-R mount directly into a 4-inch (10.2 cm.) square, 21/4" (5.7 cm.) -deep box back box, or to a user -supplied double -gang back box. A 5" (12.7 cm.) square, off-white faceplate is included with each HTRI-series module. Note: For Marine installations, a metal cover faceplate (Model USCG-HPLATE) is available separately. The faceplate must be used to protect Siemens HTRI-series interface modules from receiving radio -frequency interference (RFI). Details for Ordering Model Part Description Number HTRI-R 500-033300 Single Input Module with Relay HTRI-D 500-033360 Dual Input Module HTRI-S 1 500-033370 Single Input Module USCG- *Metal Cover Plate for HPLATE 554319-F22-A1 HTRI Series Interface Modules *denotes for required use with Marine -only installations / applications Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information, refer to each product's installation instructions. Fire Safety Fire Safety 8 Fernwood Road 1577 North Service Road SIEMENS Industry, Inc. Florham Park, NJ 07932 East Oakville, Ontario February 2016 Tel: (973) 593-2600 5II•Fsi L6H OH61 Canada Supersedes sheet dated 6/2015 Building Technologies Division ( (Rev. hJ FAX: (908) 547-6877 Printed in U.S.A. Tel: [905] 465-8000 URL: www.USA.Slemens.com/FIRE URL: www.Siemens.CA SIEMENS Data Sheet Fire Safety & Security Products 8 Series Notification Appliances ZIP & ZR ® Strobes, Horns, & Horn / Strobes I Application: Indoor r IRE Model 'ZH' Series Product Overview — Strobes can be synchronized using the Siemens DSC sync modules, FS-250 panel, XLS panel, or PAD-3 power supply with built-in sync protocol — Selectable Continuous Horn or Temporal (Code-3) Tones with 90 or 95 dBA selectable setting (ZH) — Ceiling -mount models feature field -selectable Candela settings of 15130I75195cd and 1151177cd — Wall -mount models feature field -selectable Candela settings of 151301751110cd and 1351185cd — Base plate is protected by a disposable cover, and the appliances can quickly snap onto the base after the walls are painted — Strobes produce 1 flash per second — "Special Applications" listed with Siemens panels — EZ Mount Universal Mounting Plate (Model ZB Series) — uses single plate for ceiling and wall mount installations — EZ Mount design — with separate base plate — provides ability to pre -wire the base and test the circuit wiring before the walls are covered — ®UL Listed & OULC Listed; FM, CSFM & NYC Fire Department Approved — ADA I NFPA compliant Specifications General Audible/Visual notification appliances shall be listed for indoor use only Appliances shall be listed under oUL Standard 1971 (Standard for Safety Signaling Devices for Hearing Impaired) and ®UL Standard 464 (Fire Protective Signaling) Appliances shall use a universal back plate, which shall allow mounting to a single -gang, double -gang, 4-inch-square, 4"-octal, or a 3-112"-octal backbox — Two -wire appliance wiring shall be capable of directly connecting to the mounting back plate — Continuity check shall occur for entire NAC circuit prior to attaching any audible I visual -notification appliances — Dust cover shall fit and protect the mounting plate — Dust cover shall be easily removed when the appliance is installed over the back plate — Removal of an appliance shall result in a trouble condition by the Siemens Fire Alarm Control Panel (FACP) `08 Series Notification Appliances 2584 Specifications — (continued) Strobes — Strobe appliances shall produce a minimum flash rate of 60 flashes per minute (1 flash per second) over the Regulated Input Voltage Range, and shall incorporate a Xenon flashtube enclosed in a rugged Lexanff) lens — Strobes shall be available with two or four field -selectable settings in one unit, and shall be rated — per OUL 1971 — for up to: • 15/30/75/110cd for wall mounted • 135/185cd for wall mounted • 15130175195cd for ceiling mounted • 1151177cd for ceiling mounted — Strobes shall operate over an extended temperature range of 32•F to 120°F (0°C to 49°C), and be listed for maximum humidity of 95% RH — Strobe inputs shall be polarized for compatibility with standard reverse -polarity supervision of circuit wiring by a Siemens FACP Audible and Audible / Strobe Combinations — Horns and horn I strobes shall be listed for Indoor use under ®UL Standard 464 Horns shall be able to produce continuous synchronized output or a temporal code-3 synchronized output - Horns shall have at least 2 sound -level settings of 90 and 95 dBA Synchronization Modules The strobe portion, when synchronization is required, shall be compatible with DSC sync modules, FS-250 panel, XLS panel, or PAD-3 power supply with built-in sync protocol The strobes shall not drift out of synchronization at any time during operation — Audibles and strobes shall be able to synchronize on a 2-wire circuit with the capability to silence the audible, if required Strobes shall revert to a non -synchronized flash -rate, if the sync module or Power Supply should fail to operate (i.e. — contacts remain closed) — All notification appliances shall be listed for Special Applications: • Strobes are designed to flash at 1-flash-per-second minimum over their "Regulated Input Voltage Range" ➢ Note: NFPA-72 specifies a flash rate of 1-to-2 flashes per second, and ADA Guidelines specify a flash rate of 1-to-3 flashes per second • All candela ratings represent minimum -effective Strobe intensity, based on ®UL Standard 1971 ■ Series ZH Strobe products are listed under ®UL Standards 1971 and 464 for indoor use with a temperature range of 320F to 120•F (0°C to 49°C) and maximum humidity of 93% (± 2%) ■ Series ZH horns are listed under oUL Standard 464 for audible signal appliances (Indoor use only) CICRACRIC OnAl +r In& Mounting Diagram a.u,-._____v. a a.us _. z ya r , (Shown In Inches) Mounting Options u,t s r r:urrre -� 1 nsla rrountigp ze as saav+n in figure Ito a single ;arp, ouble•gang, A square 4' ocager, or a 3 ' o•:b e:agcn baccx wi:F:he crow oadpa head screws. T. reiio:edastcover. as:e tvimb ono index `roger on top _does c' cover a'•'. pull Of cover. 3 Ccnna.t:iold wir'ng per 6gur_5 21 an: 3 3. a.ddress v,ir_s ear9 ria backboy.. 4. =loss dust o rrer ova mounting : date to PfC:Kli ahe Grmma s whiie perorn"atg wiring ccn:inui:y-�i_.n. o. Remove dust cover be'ore snaps%n3 cr installing the s:olrncs onto t^,c mounting c•a:e per fig S. Technical Data ZH and ZH.MC Ham Reverberant dBA per Q UL464 [ZH-MC and ZH at 24V3 -16.OV 24V I 33.OV Continuous Hom High 83 87 90 Low 77 81 83 Code 3 Hom or March Time' High 79 82 86 Low T2 76 79 '.4vallable in sync mode only 0 Fi=--E ?soul (:y 5L-p S ba'as; Iniperant: A=vlosor, y has one ncJ*inng orien:atc-.1.1xv "he LP ci the base:o;he :cp of t ne device. li I Is desired tc funherse.ure th= device n the rase ;hen lino optimal screws are rrouideo. Tc install thsse screws punch c.: t-s sr -w holes Iecat=c x the tap and boron• a` :he dev ce _. To remove the = ppliance, push a small f _t•blaa:a svvidrver into .he side opening. The scre:+drrrern.rst clear the s^a-• release opening by 2:" to disengage the snap. Do no: pri =:i housing with :he screw driver. Apply [-ensure vtith scr=a drir_r, inserl=i in eit§er side opening as shct5r - =ig 4 t_•re 3se Ilia housing. Current Draw 1e-33 Voltz DC y.. Low' 0.018 FWR High, 0.075 Low' I 0.045 �O=ent amw is the same for the Cortinuous Ham. Ccce 3 Horn ; .-d fdarc• T me Settings COttrIGILIG 1„4..,4-. 1— Technical Data — (continued) Models" 19UL Listed Models and Ratings Operating ticitage, (Special Application) [per 19 UL1971] (VDCi1RW{S) , �ohage Range [pef '6 ULrr_ S526 02] (VDCA !RMS) Horn Mounting �t Candela (cd) ZR-MC '16.0-33.0 20.0-31.0 — Vlrall '151301751110 ZR-HMC 16.0-33.0 20.0-31.0 — Wall 1351185 ZR-MC-C 16.0-33.0 20.0-31.0 — Ceiling '15/30,75/95 ZR-HMC-C 16.0-33.0 20.0-31.0 — Ceiling 1151177 ZH-MC 16.0-33.0 20.0-31.0 X Wall '15130175//10 ZH-HMC '16.0-33.0 20.0-31.0 X Wall 135085 ZH-MC-C '16.0-33.0 20.0-31.0 X Ceiling 15130r75195 ZH-HMG-C '16.0-33.0 20.0-31.0 X Ceiling 1151177 ZH '16.0-33.0 20.0-3"LO X I Wall or Ceiling — — 'Available in red and White OC 16-33b'DC F'AR 116-33VRVE, DC 116-33VDC 16 -33 VRiViS 0UL Current Ratings (ZR Strobe Only) Maximum RMS Current (AMPS) MC HMC MC-C495cd HMC-C 15cd 3Dcd 75cd 110e 135cd 185cd 1Sed 3Dcd 75c115cd 177cd 0.064 0.096 0.175 0.233 0.318 0.�5 0.069 D.119 020 0.318 0.445 0.108 0.164 0.268 0.368 D4E_2 0f+64 0.117 0.160 029 0.462 0,684 Horn UL Carrell t Ra tings ZH HornIStrohe Maximum RMS Current (AMPS) Current Drmh, is the same for the Continuous Hom; Code 3:iom and March Time Setungs Details for Ordering —(Including Mounting Options & Agency Approvals) Anenry Annrovals Model Number Part Number Description Mounting Options UL ULC FM CSFM. ZH-R 500-636159 Z Horn: Red B,D,E,F X X X X ZH-W 500-635160 Z Horn: White B,D,E,F X X X X ZH-MC-R 500.636161 Z Horn: Multi Candela (Wall), Red B,D,E,F X X X X ZH-MC-W 500-636162 Z Horn: Multi Candela (Wall), White B,D,E,F X X X X ZH-HMC-R S00.636163 Z Horn: Hi Multi Candela (Wall), Red B,D,E,F X X X X ZH-HMC-W 500-636164 Z Horn: Hi Multi Candela (Wall), White B,D,E,F X X X X ZH-MC-CR 500.636165 Z Horn: Multi Candela (ceiling), Red B,D,E,F X X X X ZH-MC-CW 500-636166 Z Horn: Multi Candela (Ceiling), White B,D,E,F X X X X ZH-HMC-CR 500.536167 Z Horn: Hi Multi Candela (Ceiling), Red B,D,E,F X X X X ZH-HMC-CW 500-636168 Z Horn: Hi Multi Candela (Ceiling), White B,D,E,F X X X X ZR-MC-R 500-636169 Z Strobe: Multi Candela (Wall), Red B,D,E,F X X X X ZR-MC-W 500-636170 Z Strobe: Multi Candela (Wall), White 8,D,E,F X X X X ZR-HMC-R 500-636171 Z StrobeeHi Multi -Candela (Wall), Red B,D,E,F X X X X ZR-HMC-W 500-636172 Z Strobe: Hi Multi -Candela (Wall), White 8,D,E,F X X X X ZR-MC-CR 1 500-636173 Z Strobe: Multi Candela (Ceiling), Red B,D,E,F X X X X ZR-MC-CW 500-636174 Z Strobe: Multi Candela (Ceiling), White B,D,E,F X X X X ZR-HMC-CR 500.636175 Z Strobe: Hi Multi Candela (Ceiling), Red B,D.E,F X X X X ZR-HMC-CW SOU-636176 Z Strobe: Hi Multi Candela (Ceiling), White B,D,E,F X X X X ZB-R 500-636193 Accessory —(Includes base, dust cover, mounting screws and installation sheet) ZB-W 500-636194 Accessory —(Includes. base, dust cover, mounting screws and installation sheet) X = Listed I Approved * = Refer to data sheet 4: 2585 for detailed mounting options Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information, refer to each product's installation instructions. Fire Safety Fire Safety 6 Femwood Road 2 Kenview Boulevard SIEMENS Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario June 2012 Buildina Technaloaies Division Tel: (973) 593-2600 (511) L6T 5E41 Canada - „..