HomeMy WebLinkAboutLetter (Civil Engineering)Paul Welch, Inc. anical * Electrical * Civil Engineering 1984 SW Biltmore St. #114 Port St. Lucie, FL, 34984 (772) 785-9888 PAUL WELCH, PE FLA REG. NO. 29945 Address: 501 W Weatherbee Rd. Permit Number: 2003-0567 Contractor: Telese Builders, LLC LIGHTING DENSITY AUDIT 2017 Florida Building Code: Energy Conservation 6th Edition Section C405 SPACE BY SPACE METHOD Table 0405.4.2(2) SPACE TYPE: Storage Area 2,640 watts / 8,472 s.f. _ .31 SPACE TYPE: Restroom 100 watts / 54 s:f. _ .54 LIGHT FIXTURES Allowable L.P.D. (watts per sq. ft.): 0.63 Provided L.P.D. (watts per sq. ft.): 0.31 Allowable L.P.D. (watts per sq. ft.): 0.90 Provided L.P.D. (watts per sq. ft.): 054 LED Flouresent Shop Lights (440 watts) each. Exhaust fan & Light (100 watts) max. EXTERIOR LIGHTING ZONES Table C405.5.1.0 ) Lighting Zone: 2 i f fviAY 2 020 i ST, Lucie County, Permitting INDIVIDUAL LIGHTING POWER ALLOWANCES FOR BUILDING EXTERIORS Table C405.5.1.(2) Base Site Allowance: (Zone 2) = 600 watts BUILDING ENTRANCES & EXITS Main Entry: (20 watts / foot of door width) 6.0' door width x 20 watts = 120 watts Other Doors: (20 watts / foot of door width) 9.0' door width x 20 watts = 180 watts Entry Canopies: (.25 watts / sq. ft.) 96.0 s.f. x .25 watts = 6.50 watts Total Exterior Power Allowance (watts): 306.5 watts MINIMUM PERFORMANCE OF WATER HEATING EQUIPMENT Table C404.2 SIZE (Input): <12kW Rating Condition: Resistance Performance Required: 0.97-0.00 132V, EF SIZE (Input): 2.OkW Rating C dition: Resistance Performance Required: 0.00 EF PAUL WELCH, PE FLA REG. NO. 29945 MAY 1, 5 2020