DESIGN CRITERIA:
Applicable Codes, Regulations, and Standards
1. The 7th Edition (2020) Florida Building Code, specifically Chapter
16 Structural Design, Chapter 20 Aluminum, and Chapter 23 Wood.
2. AA ASM 35 and AA ADMI Specifications for Aluminum
Structures, Part 1-A of the Aluminum Design Manual prepared by
The Aluminum Association. and the AAF Guide to Aluminum
Construction in Hgh Wind Areas.
3. ASCE 7-16.
Loading Criteria
1. Live Load: 10 PSF per 7th Edition (2020) Florida Building Code,
Appendix I Section 105.1
2. Dead Load: 1 PSF
3. Wind Load:
3.1. Building Occupancy Category, Section 1604.5 and Table
1604.5: Risk Category 1.
3.2. Ultimate Design Wind Speed: V—=150 MPH, Nominal
Design Wind Speed: VAsn =116 MPH
3.3. Exposure Category, Section 1609.4.3: Exposure B
3.4. Screen Enclosure Section2002.4
4. Building Category for Aluminum Structures, Section 2002.6:
Category Type 1- Patio Cover: Non -Habitable, Unconditioned
RoofType
1. Roof Type: MONOSLOPE
2. Roof Material: 3" x 12" 0.030" Town 8c Country Industries Riser
Panel, Florida Product Approval Number FL 17638-112
Foundation Design
Existing concrete slab. No additional concrete footing or slab is
required to resist the loads imposed upon the existing slab by the
proposed construction if the existing slab is a minimum of 4" thick
and in sound condition, free from structural cracking, spalling, or
other deterioration.
Specifications
The following specifications are applicable to this project:
1. All work shall be in accordance with the 7th Edition (2020) Florida
Building Code, and any other applicable local codes and regulations.
2. Aluminum extrusions shall be 6005 T5 Alloy. Due to quality control
issues, no manufacturer substitution is acceptable without the
specific written, signed and sealed authorization of Florida
Aluminum Engineering, Inc.
3. Fasteners are required to be corrosion resistant, minimum SAE
Grade 2 or better zinc plated to ASTM B633, or coated stainless steel
series "300", or uncoated stainless steel series "400".
4. Approved concrete screw anchors to be Simpson Titen-HD or
equivalent.
5. All Self Mating Beam Sections are to be stitched with either #14
screws 6" from ends and 24" center to center or #12 screws 6" from
ends and 12" center to center.
6. Where concrete specifications are required, whether in the screen
enclosure scope or not, by one or more regulatory agency, the
following specifications are applicable:
a. Concrete shall conform to ASTM C94 for the following
components:
i. Portland Cement Type 1,- ASTM C 150
ii. Aggregates - Large Aggregate 3/4" max - ASTM C 33
iil. Air entraining +/- 1% - ASTM C 260
iv. Water reducing agent - ASTM C 494
v. Clean Potable water
vi. Other admixtures not permitted
b. Metal accessories shall conform to:
i. Reinforcing Bars - ASTM A615, grade 60
ii. Welded wire fabric - ASTM Al85
c. Concrete slump at discharge chute not less than 3" or more
than 5". Water added after batching is not permitted.
d. Prepare and place concrete per American Concrete Institute
Manual of Standard Practice, Parts 1, 2, and 3 including hot
weather recommendations.
e. Moist cure or polyethylene curing permitted.
f. Prior to placing concrete, treat the entire subsurface area for
termites in compliance with the FBC.
g. Concrete shall be placed over a polyethylene vapor barrier.
IL All aluminum components embedded within concrete shall
be coated with a bituminous paint or epoxy.
7. All flashing and weatherproofing shall be provided by the contractor.
8. Use of these plans acknowledges and accepts a limit of liability not
to exceed design and engineering fee.
WIND SPEED AND EXPOSURE HAVE
BEEN DETERMINED USING THE ADVANCED
TECHNOLOGY COUNCIL'S WEBSITE
AND GOOGLE EARTH.
3X3X0.125
0
I
A-2
2X5SMBJ
END
BEAM
A-2
S-4
A-3
2X8SM B
CROSS
2X5SMB
BEAM
4TH WALL
3"X12"X'0.030"
RISER PAN
2X8SMB
CROSS
BEAM
2X5SMB
2X5SMB
EDGE
INT
BEAM
BEAM 2X5SMB
2X5SMB
END
INT
BEAM
_BEAM
_
S-3
A-2
13'-6"
' 13'-6"
91041
File C®py
zED � zz�
BODE COMPLIANCE
ST. LUGIE COUNTY
RECEIVED
FEB 0 4 2021
St. Lucie County
Permitting
Q� 2 C) 0 O ,
o �
a W to W
V .1w 0
Uj
W
LU
Z m
W Z
J � �
Z Q Z
v
V1 N
to a W
U .l
U. O J
.
O =
tY �
a
�U�
z
Z N
Z
of'L
4 � f+l �
Z
Z HZI
Q LU w a
SS
Q LJJ Z E .
Q Z_ ��M
t]C Ut
OZ7
m
m
J LLI
V'
o
R
W O
� U
Q U)
Q O
Z Uj
Q p OLLJ W
J Q �
CO
d�
0 Z 0 G)
fZ OLL L
TP
DATE DRAWN
11 /16/21
REVISION
A 01 /28/22
SHEET NO:
A-1
ALUMI"M MEMBERS DIMENSIONS
'HOLLOW SECTIONS
,�'C • •
.... .��
2 x 2: 2" x 2" x 0.046"
,\\ •
K%
• •
•.•• ii
2 x 3: 2" x 3" x 0.050"
#1 4 x 3/4" SMS W/ NEOPRENE
••.•'
<'')
i
2 x 4: 2" x 4" x 0.050"
FACED WASHER @ 12" O.C.
ALONG LENGTH OF ALL
t
u' 6
2 x 5: 2" x 5" X 0.050"
Z
Q
END / CROSS BEAMS
C,
OPEN BACK SECTIONS
#14 x 3/4" SMS W/
_�
0 W
H Q
1 x 2: 1" x 2" X 0.040"
NEOPRENE FACED
i N '
Q Qy
1 x 3: 1" x 3" x 0.045"
WASHER @ 4" O.C.
j Z
SECTIONS
•••
��
SNAP
i�o ••
.%• ��
2x2Snap: 2"x2"x0.045"
I I
w'y�
s,,�11��I/111
••••'••��4\\\\\
2 4 Snap: 2" 4" 0.045"
I I
x o.1 zs"
x x x
POST
SELF MATING (SMB)
2 x 4 SMB: 2" x 4" x 0.044" x 0.100"
I I
°
3
�
2 x 5 SMB: 2" x 5" x 0.050" x 0.100"
(2) 3/S DIE. CONCRETE I I
PANRISZISEEL °
LIJ
W d
2 x 6 SMB: 2" x 6" x 0.050"x 0.120"
SCREW ANCHORS
�
z
2 x 7 SMB: 2" x 7" x 0.057"x 0.120"
(3" CONC. EMBED) I I
INTERNAL/EXTERNAL
o
^ M
0 � g
2 x 8 SMB: 2" x 8" x 0.072"x 0.124"
I I
3" x 3" x 1/8" EXTRUDED
°
2" x 8"
C
2 x 9 SMB: 2" x 9" x 0.072"x 0.124"
POST BASE W/ (2) 3/8"
I I®
SMB
W z
2 x 10 SMB: 2" x 10" x 0.092" x 0.398"
I I
DIA. THRU BOLTS
t I
J w
2" x 5" SMB-Z o
Q Q z
MINIMUM FASTENER EDGE DISTANCE: 1/2"
®
z Lu
�'
MINIMUM FASTENER SPACING: 3/4"
3" x 3" x 0.125"
I I
_.
Q
N Z
POST -
N asc
CONCRETE SCREW ANCHOR:
4 •• °
' '
o
I I
1 1/2" x 21/8" x 1 1/2" x 8" x 0.125" ALUM
I V
L G J
SIMPSON TITEN HD OR EQUIVALENT
a'•,. ";. :
, " °
I
RECEIVING CHANNEL W/(7)
LL
Q Q
SHEET METAL SCREWS (SMS):
°4 '
e
#14 x 3/4" SMS EACH SIDE OF
w _
ITW / BUILDEX OR EQUIVALENT
" c ." • '
°
BEAM & (4) 3/8" DIA. THRU BOLTS
d H
INTO POST
m
B 3" x 3" POST TO CONCRETE CONNECTION
DETAIL
Z Z_ A z
A_2 SCALE: NTS
S RISER PANEL TO CORNER POST CONNECTION
z
CC %r 5 '^ W
Q
A_2
SCALE: NTS
C R' § � `"
z`� 3
1 w
Q W -,EMS
W C
;
f� Z
$ m
�,
ZLu
O o
LL o
#14 x 3/4" SMS W/ NEOPRENE
FACED WASHER @ 12" O.C.
#14 SMS x 3/4" W/ #14 x 3/4" SMS W/
NEOPRENE FACED
FLASHING
LL
#14 x 3/4" SMS W/
ALONG LENGTH OF ALL
NEOPRENE FACED
WASHER @ 12" O.C. WASHER @ 4" O.C.
NEOPRENE FACED
END / CROSS BEAMS
ALONG LENGTH
WASHER @ 4" O.C.
3" RISER
OF ALL BEAMS
PANEL
I
1 1!2" x 2 x 1 x 0
I
/
BEAM DEPTH CHANNEL W/
(4) #14 x 3/4" SMS INTO
BEAM EACH SIDE&
(4) #14 x 3/4" SMS INTO
END BEAM
o
®
I
N O
3" RISER
F
EXISTING
W U
PANEL
o 2"x5"
°
°
BUILDING
_ _
°
Q �
o SMB
2" x 8" SMB
2" x 5" SMB
� Z
o
�
Q o0�
I
2" x 5" SMB
I
1 1/2" x 21/8" x 1 1/2" x 5" x 0.126'
®I
- - - -
Wmc9WN
Z cf)O m
3" x 3" x 0.125"
POST I
ALUM RECEIVING CHANNEL W! (4)
#14 x 3/4" SMS EACH SIDE OF
I
_ - - I
I
I
w Z d• O _I
BEAM & (3) 318" DIA. THRU BOLTS
I
I
x 5
2" ' SMB
a -r
DRAWN BY
INTO POST
11/2"x21/8"x11/2"x0.125" I
END BEAM
ALUM RECEIVING CHANNEL
TP
W/ (7) #12 x 3/4" SMS EACH
SIDE OF BEAM & (4) 3/8" DIA.
DATE DRAWN
THRU BOLTS INTO THE POST
2" x 5" SMB
11 /16/21
3" x 3" x 0.125"
POST
REVISION
1 -
S-1 RISER PANEL TO CORNER POST CONNECTION
S-2 RISER PANEL TO POST CONNECTION 4TH WALL DETAIL
© _
A-2
SCALE: NTS
A_2 SCALE: NTS
S-3 INTERMEDIATE BEAM TO END BEAM ATTACHMENT
4 _
A-2 SCALE: NTS
SHEET NO:
A -2
' '•
111/111�,,I
.
�
`,,,111111111*
15-0
LL 6-
0
;�Z o
�d �W (o * W
O.
O
.
' ••. • ♦
Z
440
IIIII/IIIIIINIIII,
�
L
W Li
W fi
Z m
w Z
z az°
O
vWi
N
c%1
N Q w
W
LL J
O O
W
a
�U
zN z
Z W
r
_Z
W�e M
QW 1'Q •..�.y W
W Wa°m ¢
0 Z
z
g
OZ$ m
c
.J yJLL
#14 x 3/4" SMS W/ NEOPRENE
FACED WASHER @ 12" O.C.
3" RISER
#12x3/4"SMSW/
#14 x 3/4" SMS W/
NEOPRENE FACED
s
ALONG LENGTH OF ALL PANEL NEOPRENE FACED
WASHER 4" O.C.
WASHER @ 4" O.C.
END/CROSSBEAMS
@
3" RISER
PANEL
2" x SMB
1 1/2" x 21/8" x 1 1/2" x 0.125"
1 1/2" x 21/8" x 1 1/2" x 0.125"
EDGE BEAM
BEAM DEPTH CHANNEL W/
BEAM DEPTH CHANNEL W/
(4) #14 x 3/4" SMS INTO (4),114 x 3/4" SMS INTO
BEAM EACH SIDE&
BEAM EACH SIDE&
-- --
(4) #14 x 3/4" SMS INTO
(4) #14 x 3/4" SMS INTO
12' MAX
END BEAM
END BEAM
OVERHANG
LU O
f
---
o •
I
I
o• o I
I o o•
0�
2" x 5" SMB
2" x 5" SMB
e o
2" x SMB
o o
\ I
\
I /
Q Z
Q
• o
EDGE BEAM
\ \ I
I
�j
o a3
11/2"x21/8"x11/2"x
\ \
\ \ I
I / /
m W N
0.062" x 3" LONG ALUM
\ \
\
\
/ /
— —
'
— —
RECEIVING CHANNEL W/ (3)
\ \ I
I
\ \ I
I / /
Z 0 �
O Z
#12 x 3/4" SMS EA. FACE &
(3) #12 x 3/4" INTO BEAM
\ 12"
\
I
\ \ I
12 I / /
J � �
2"
x 3" x 0.045" \
\
3' x 3" x 0.125"
2" x 3" x 0.045"
\ \
/ 2" x 3" x 0.045"
CL r O U-
42"
KNEE BRACE
\
POST
KNEE BRACE \ I
I / KNEE BRACE
DRAWN BY
TP
DATE DRAWN
x 8" SMB
11/2"x21/8"x11/2"x I
1 1/2" x 2 1 /8" x 1 1/2" x
1 1/2" x 2 1/8" x 1 1/2" x
CROSS BEAM
0.062" x 3"LONG ALUM I
RECEIVING CHANNEL W/ (3)
0.082" x 3" LONG ALUM
RECEIVING CHANNEL W/ (3)
0.062" x 3" LONG ALUM
RECEIVING CHANNEL W/ (3)
11 /16/21
#12 x 3/4" SMS EA. FACE &
#12 x 3/4" SMS EA. FACE &
#12 x 3/4" SMS EA. FACE &
REVISION
(3) #12 x 3/4" INTO POST I
I
(3) #12 x 3/4" INTO POST I
(3) #12 x 3/4" INTO POST
-
I
3" x 3" x 0.125"
POST
S-4 INTERMEDIATE BEAM TO CROSS BEAM ATTACHMENT
S-5 KNEE BRACE CONNECTION DETAIL
S-6 KNEE BRACE CONNECTION DETAIL
4 -
SHEEP NO:
A-� SCALE: NTS
A 3 SCALE: NTS
A-3
SCALE: NTS
A- 3
w
�9
c
cq
9)