HomeMy WebLinkAbout12. J-Manual - 2401 Noble Oaks - Dudley ResidenceCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-26 11:18:21 Right-Suite® Universal 2021 21.0.08 RSU27054 Page 1 ...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Load Short Form Aug 25, 2021Date:Entire House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com Project Information Oleander Model 3, Villadelta Construction Corp, LLCFor: 2401 Noble Oaks Lane, Ft Pierce, FL 34981 Design Information InfiltrationClgHtg SimplifiedMethod9041Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond EL18XCVS048-230A** AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 206221388 Efficiency 100 EFF Efficiency 12.2 EER, 17 SEER Heating input kW12.7 Sensible cooling Btuh33600 Heating output Btuh43415 Latent cooling Btuh14400 Temperature rise °F25 Total cooling Btuh48000 Actual air flow cfm1600 Actual air flow cfm1600 Air flow factor cfm/Btuh0.039 Air flow factor cfm/Btuh0.057 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.73 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Bed 2 217 3064 1776 120 101 Arrival Center 93 681 225 27 13 Laundry 83 1986 1218 78 69 Sto 12 0 0 0 0 Butlers Pantry 48 101 70 4 4 Clst 13 0 0 0 0 Bath 2 91 936 668 37 38 Foyer 72 2251 888 88 50 Den 162 2700 1680 106 95 Wtr Clst 22 544 519 21 29 Master Bath 210 4420 2477 174 140 Hers 63 1195 328 47 19 His 36 67 47 3 3 Master Bedroom 299 4913 2445 193 139 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-26 11:18:21 Right-Suite® Universal 2021 21.0.08 RSU27054 Page 2 ...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N Great Room 389 4233 4123 166 234 Bed 3 203 2056 1570 81 89 Bath 3 63 789 609 31 35 Flex Space 233 4914 2619 193 148 Hall 53 933 763 37 43 Dining 158 4361 3485 171 198 Kitchen 315 586 2712 23 154 Entire House 2832 40732 28219 1600 1600 Other equip loads 3903 2073 Equip. @ 0.95 RSM 28899 Latent cooling 11408 TOTALS 2832 44635 40307 1600 1600 2021-Aug-26 11:18:21 Right-Suite® Universal 2021 21.0.08 RSU27054 Page 1 ...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Building Analysis Aug 25, 2021Date:Entire House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com Project Information Oleander Model 3, Villadelta Construction Corp, LLCFor: 2401 Noble Oaks Lane, Ft Pierce, FL 34981 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 16.975423.1Walls 21.2944718.8Glazing 000Doors 10.044651.6Ceilings 17.980072.82.8Floors 11.350431.9Infiltration 14.06228Ducts 00Piping 00Humidification 8.73903Ventilation0Adjustments 100.044635Total Cooling Walls Glazing Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 11.735341.5Walls 29.9906618.0Glazing 000Doors 11.434401.2Ceilings 000Floors 4.413390.5Infiltration 13.84191Ducts 6.82073Ventilation 22.06650Internal gains 00Blower 0Adjustments 100.030292Total Latent Cooling Load = 11408 Btuh Overall U-value = 0.228 Btuh/ft²-°F Data entries checked. 2021-Aug-26 11:18:21 Right-Suite® Universal 2021 21.0.08 RSU27054 Page 1 ...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Component Constructions Aug 25, 2021Date:Entire House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com Project Information Oleander Model 3, Villadelta Construction Corp, LLCFor: 2401 Noble Oaks Lane, Ft Pierce, FL 34981 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Blk Wall, Stucco Ext, R-4 Rigid Foam Ins, 8" Thk, 5/8" Gyp Bd Int 3.155.00.108307n 4551.49965 10891.4923063.155.00.108733e 6471.4913713.155.00.108436s 331.49703.155.00.10822sw 10291.4921793.155.00.108692w 32541.4968903.155.00.1082190all Partitions Frm Wall, 5/8" Gyp Bd Ext, R-11 Cav Ins, 5/8" Gyp Bd Int Fnsh, 2"x4" Wd Frm, 16" OC Stud 2801.236522.8711.00.099227 Windows Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.41); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1.7 ft overhang (2 ft window ht, 1.5 ft sep.); 8 ft head ht 13811.515713.000.45012n 12311.513913.000.45011n 26011.529613.000.45023all Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.41); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 10 ft overhang (2 ft window ht, 1.5 ft sep.); 8 ft head ht 13811.515713.000.45012n Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.34); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1.7 ft overhang (6.3 ft window ht, 1.5 ft sep.); 8 ft head ht 23614.032219.100.66017n 47114.064319.100.66034n 70714.096519.100.66050all Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.27); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 10 ft overhang (8 ft window ht, 1.5 ft sep.); 8 ft head ht 4709.79101621.200.73048n Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.33); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1.7 ft overhang (3 ft window ht, 1.5 ft sep.); 8 ft head ht 63935.532418.000.62018e 2021-Aug-26 11:18:21 Right-Suite® Universal 2021 21.0.08 RSU27054 Page 2 ...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.33); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1.7 ft overhang (5.2 ft window ht, 1.5 ft sep.); 8 ft head ht 110735.556118.000.62031e 47815.356118.000.62031s 71715.384118.000.62047s 230221.1196318.000.620109all Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.33); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 13 ft overhang (5.2 ft window ht, 1.5 ft sep.); 8 ft head ht 71715.384118.000.62047s Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.35); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 14 ft overhang (8 ft window ht, 1.5 ft sep.); 8 ft head ht 159116.6192120.000.69096s Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.27); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 11 ft overhang (8 ft window ht, 1.5 ft sep.); 8 ft head ht 33016.043821.200.73021sw Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.33); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1.7 ft overhang (4.4 ft window ht, 1.5 ft sep.); 8 ft head ht 26035.513218.000.6207w Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.33); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1.7 ft overhang (6.3 ft window ht, 1.5 ft sep.); 8 ft head ht 85735.543418.000.62024w Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.35); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 15 ft overhang (8 ft window ht, 1.5 ft sep.); 8 ft head ht 79616.696020.000.69048w Doors (none) Ceilings Attic, Metal Roof, R-20 Roof Deck Ins, 5/8" Gyp Bd Int Fnsh 21.00.3862832 34401.2144651.58 Floors On Grade Depth, Tile Flr Fnsh 00800728.700.989279 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-26 11:18:21 Right-Suite® Universal 2021 21.0.08 RSU27054 Page 1 ...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Project Summary Aug 25, 2021Date:Entire House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com Project Information Oleander Model 3, Villadelta Construction Corp, LLCFor:2401 Noble Oaks Lane, Ft Pierce, FL 34981 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh34503 Structure Btuh24028 Ducts Btuh6228 Ducts Btuh4191Central vent (122 cfm) 3903 Btuh Central vent (122 cfm) Btuh2073 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh44635 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh28899 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh4057 Ducts Btuh2618Central vent (122 cfm) Btuh4733 CoolingHeating Outside air28322832Area (ft²) Equipment latent load Btuh11408 2966929669Volume (ft³)Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh40307 Equiv. AVF (cfm) 79158 Req. total capacity at 0.70 SHR ton3.4 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOX Model Cond EL18XCVS048-230A**AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 206221388Efficiency 100 EFF Efficiency 12.2 EER, 17 SEER Heating input kW12.7 Sensible cooling Btuh33600Heating output Btuh43415 Latent cooling Btuh14400 Temperature rise °F25 Total cooling Btuh48000Actual air flow cfm1600 Actual air flow cfm1600 Air flow factor cfm/Btuh0.039 Air flow factor cfm/Btuh0.057Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.73 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-26 11:18:21Right-Suite® Universal 2021 21.0.08 RSU27054 Page 1...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Right-J® Worksheet Aug 25, 2021Date:Entire House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com 1 Room name Entire House Bed 2 2 Exposed wall 279.2 ft 30.0 ft 3 Room height 10.5 ft 10.1 heat/coolft 4 Room dimensions ft216.8x1.0 5 Room area 2832.3 ft²216.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 nn 3.153.15 1.491.49 440 307 965 455 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 12 0 157 138 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 11 0 139 123 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 12 0 157 138 0 0 0 0 11 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 17 0 322 236 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 34 0 643 471 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 nn 21.1721.17 9.799.79 48 0 1016 470 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ee 3.153.15 1.491.49 782 733 2306 1089 136 121 380 179 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 18 0 324 639 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 31 0 561 1107 16 0 280 553 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ss 3.153.15 1.491.49 657 436 1371 647 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 31 62 561 478 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 47 94 841 717 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 47 94 841 717 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ss 20.0120.01 16.5816.58 96 192 1921 1591 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 swsw 3.153.15 1.491.49 43 22 70 33 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 swsw 21.1721.17 15.9915.99 21 41 438 330 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ww 3.153.15 1.491.49 772 692 2179 1029 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 7 0 132 260 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 24 0 434 857 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ww 20.0120.01 16.5816.58 48 96 960 796 0 0 0 0 PP Frm Wall, 5/8" Gyp B 0.099Frm Wall, 5/8" Gyp B 0.099 --2.872.87 1.231.23 227 227 652 280 167 167 478 205 CC Attic, Metal Roof, R 0.386Attic, Metal Roof, R 0.386 --1.581.58 1.211.21 2832 2832 4465 3440 217 217 342 263 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 2832 279 8007 0 217 30 860 0 6 c) AED excursion 0 -7 Envelope loss/gain 29461 16039 2340 1194 12 a) Infiltration 5043 1339 255 68 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 5 1150 0 0 Appliances/other 5500 250 Subtotal (lines 6 to 13)34503 24028 2596 1512 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 34503 24028 2596 1512 15 Duct loads 18%17%6228 4191 18%17%469 264 Total room load 40732 28219 3064 1776 Air required (cfm)Air required (cfm)1600 1600 120 101 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-26 11:18:21Right-Suite® Universal 2021 21.0.08 RSU27054 Page 2...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Right-J® Worksheet Aug 25, 2021Date:Entire House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com 1 Room name Arrival Center Laundry 2 Exposed wall 7.0 ft 16.0 ft 3 Room height 10.1 heat/coolft 10.1 heat/coolft 4 Room dimensions ft92.5x1.0 ft83.0x1.0 5 Room area 92.5 ft²83.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 nn 3.153.15 1.491.49 10 10 32 15 101 84 265 125 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 11 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 17 0 322 236 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 nn 21.1721.17 9.799.79 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ee 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ss 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ss 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 swsw 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 swsw 21.1721.17 15.9915.99 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ww 3.153.15 1.491.49 0 0 0 0 61 61 191 90 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ww 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 PP Frm Wall, 5/8" Gyp B 0.099Frm Wall, 5/8" Gyp B 0.099 --2.872.87 1.231.23 61 61 174 75 0 0 0 0 CC Attic, Metal Roof, R 0.386Attic, Metal Roof, R 0.386 --1.581.58 1.211.21 93 93 146 112 83 83 131 101 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 93 7 201 0 83 16 459 0 6 c) AED excursion -19 -104 Envelope loss/gain 552 183 1367 447 12 a) Infiltration 19 5 303 80 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)571 188 1670 1028 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 5 4 13 9 14 Subtotal 576 192 1682 1037 15 Duct loads 18%17%104 33 18%17%304 181 Total room load 681 225 1986 1218 Air required (cfm)Air required (cfm)27 13 78 69 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-26 11:18:21Right-Suite® Universal 2021 21.0.08 RSU27054 Page 3...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Right-J® Worksheet Aug 25, 2021Date:Entire House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com 1 Room name Sto Butlers Pantry 2 Exposed wall 0 ft 0 ft 3 Room height 10.1 heat/coolft 10.1 heat/coolft 4 Room dimensions ft4.0x3.0 ft5.0x9.5 5 Room area 12.0 ft²47.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 nn 3.153.15 1.491.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 11 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 nn 21.1721.17 9.799.79 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ee 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ss 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ss 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 swsw 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 swsw 21.1721.17 15.9915.99 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ww 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ww 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 PP Frm Wall, 5/8" Gyp B 0.099Frm Wall, 5/8" Gyp B 0.099 --2.872.87 1.231.23 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.386Attic, Metal Roof, R 0.386 --1.581.58 1.211.21 12 12 19 15 48 48 75 58 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 12 0 0 0 48 0 0 0 6 c) AED excursion -1 -5 Envelope loss/gain 19 13 75 52 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)19 13 75 52 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -19 -13 11 7 14 Subtotal 0 0 86 60 15 Duct loads 18%17%0 0 18%17%15 10 Total room load 0 0 101 70 Air required (cfm)Air required (cfm)0 0 4 4 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-26 11:18:21Right-Suite® Universal 2021 21.0.08 RSU27054 Page 4...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Right-J® Worksheet Aug 25, 2021Date:Entire House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com 1 Room name Clst Bath 2 2 Exposed wall 0 ft 6.5 ft 3 Room height 10.1 heat/coolft 10.1 heat/coolft 4 Room dimensions ft5.0x2.5 ft6.5x14.0 5 Room area 12.5 ft²91.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 nn 3.153.15 1.491.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 11 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 nn 21.1721.17 9.799.79 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ee 3.153.15 1.491.49 0 0 0 0 66 57 178 84 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 9 0 162 319 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ss 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ss 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 swsw 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 swsw 21.1721.17 15.9915.99 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ww 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ww 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 PP Frm Wall, 5/8" Gyp B 0.099Frm Wall, 5/8" Gyp B 0.099 --2.872.87 1.231.23 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.386Attic, Metal Roof, R 0.386 --1.581.58 1.211.21 13 13 20 15 91 91 143 111 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 13 0 0 0 91 7 186 0 6 c) AED excursion -1 22 Envelope loss/gain 20 14 670 536 12 a) Infiltration 0 0 123 33 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)20 14 793 568 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -20 -14 0 0 14 Subtotal 0 0 793 568 15 Duct loads 18%17%0 0 18%17%143 99 Total room load 0 0 936 668 Air required (cfm)Air required (cfm)0 0 37 38 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-26 11:18:21Right-Suite® Universal 2021 21.0.08 RSU27054 Page 5...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Right-J® Worksheet Aug 25, 2021Date:Entire House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com 1 Room name Foyer Den 2 Exposed wall 8.5 ft 17.5 ft 3 Room height 13.1 heat/coolft 10.1 heat/coolft 4 Room dimensions ft8.5x8.5 ft161.8x1.0 5 Room area 72.3 ft²161.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 nn 3.153.15 1.491.49 111 51 162 76 116 72 226 107 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 11 0 139 123 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 12 0 157 138 0 0 0 0 11 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 34 0 643 471 GG Impact, Low-eImpact, Low-e 0.7300.730 nn 21.1721.17 9.799.79 48 0 1016 470 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ee 3.153.15 1.491.49 0 0 0 0 61 61 191 90 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ss 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ss 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 swsw 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 swsw 21.1721.17 15.9915.99 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ww 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ww 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 PP Frm Wall, 5/8" Gyp B 0.099Frm Wall, 5/8" Gyp B 0.099 --2.872.87 1.231.23 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.386Attic, Metal Roof, R 0.386 --1.581.58 1.211.21 72 72 114 88 162 162 255 196 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 72 9 244 0 162 18 502 0 6 c) AED excursion -76 -145 Envelope loss/gain 1692 696 1956 842 12 a) Infiltration 209 55 331 88 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)1901 751 2287 1430 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 7 5 0 0 14 Subtotal 1907 756 2287 1430 15 Duct loads 18%17%344 132 18%17%413 249 Total room load 2251 888 2700 1680 Air required (cfm)Air required (cfm)88 50 106 95 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-26 11:18:21Right-Suite® Universal 2021 21.0.08 RSU27054 Page 6...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Right-J® Worksheet Aug 25, 2021Date:Entire House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com 1 Room name Wtr Clst Master Bath 2 Exposed wall 4.0 ft 37.0 ft 3 Room height 10.1 heat/coolft 10.1 heat/coolft 4 Room dimensions ft4.0x5.5 ft209.8x1.0 5 Room area 22.0 ft²209.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 nn 3.153.15 1.491.49 0 0 0 0 101 89 280 132 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 12 0 157 138 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 11 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 nn 21.1721.17 9.799.79 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ee 3.153.15 1.491.49 0 0 0 0 91 91 286 135 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ss 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ss 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 swsw 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 swsw 21.1721.17 15.9915.99 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ww 3.153.15 1.491.49 40 33 104 49 182 158 496 234 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 7 0 132 260 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 24 0 434 857 GG Impact, Low-eImpact, Low-e 0.6900.690 ww 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 PP Frm Wall, 5/8" Gyp B 0.099Frm Wall, 5/8" Gyp B 0.099 --2.872.87 1.231.23 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.386Attic, Metal Roof, R 0.386 --1.581.58 1.211.21 22 22 35 27 210 210 331 255 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 22 4 115 0 210 37 1061 0 6 c) AED excursion 86 172 Envelope loss/gain 385 422 3045 1923 12 a) Infiltration 76 20 700 186 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)461 442 3745 2109 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 461 442 3745 2109 15 Duct loads 18%17%83 77 18%17%676 368 Total room load 544 519 4420 2477 Air required (cfm)Air required (cfm)21 29 174 140 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-26 11:18:21Right-Suite® Universal 2021 21.0.08 RSU27054 Page 7...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Right-J® Worksheet Aug 25, 2021Date:Entire House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com 1 Room name Hers His 2 Exposed wall 11.5 ft 0 ft 3 Room height 10.1 heat/coolft 10.1 heat/coolft 4 Room dimensions ft11.5x5.5 ft6.0x6.0 5 Room area 63.3 ft²36.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 nn 3.153.15 1.491.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 11 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 nn 21.1721.17 9.799.79 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ee 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ss 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ss 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 swsw 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 swsw 21.1721.17 15.9915.99 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ww 3.153.15 1.491.49 116 116 365 173 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ww 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 PP Frm Wall, 5/8" Gyp B 0.099Frm Wall, 5/8" Gyp B 0.099 --2.872.87 1.231.23 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.386Attic, Metal Roof, R 0.386 --1.581.58 1.211.21 63 63 100 77 36 36 57 44 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 63 12 330 0 36 0 0 0 6 c) AED excursion -28 -4 Envelope loss/gain 795 221 57 40 12 a) Infiltration 217 58 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1013 279 57 40 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1013 279 57 40 15 Duct loads 18%17%183 49 18%17%10 7 Total room load 1195 328 67 47 Air required (cfm)Air required (cfm)47 19 3 3 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-26 11:18:21Right-Suite® Universal 2021 21.0.08 RSU27054 Page 8...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Right-J® Worksheet Aug 25, 2021Date:Entire House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com 1 Room name Master Bedroom Great Room 2 Exposed wall 35.5 ft 16.0 ft 3 Room height 11.1 heat/coolft 11.1 heat/coolft 4 Room dimensions ft299.0x1.0 ft389.3x1.0 5 Room area 299.0 ft²389.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 nn 3.153.15 1.491.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 11 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 nn 21.1721.17 9.799.79 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ee 3.153.15 1.491.49 50 50 157 74 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ss 3.153.15 1.491.49 178 131 412 194 178 82 257 121 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 47 47 841 717 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ss 20.0120.01 16.5816.58 0 0 0 0 96 96 1921 1591 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 swsw 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 swsw 21.1721.17 15.9915.99 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ww 3.153.15 1.491.49 167 167 524 247 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ww 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 PP Frm Wall, 5/8" Gyp B 0.099Frm Wall, 5/8" Gyp B 0.099 --2.872.87 1.231.23 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.386Attic, Metal Roof, R 0.386 --1.581.58 1.211.21 299 299 471 363 389 389 614 473 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 299 36 1018 0 389 16 459 0 6 c) AED excursion -211 -355 Envelope loss/gain 3424 1386 3250 1830 12 a) Infiltration 738 196 333 88 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 3 690 Appliances/other 500 900 Subtotal (lines 6 to 13)4161 2081 3583 3509 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 3 2 14 Subtotal 4161 2081 3586 3511 15 Duct loads 18%17%751 363 18%17%647 612 Total room load 4913 2445 4233 4123 Air required (cfm)Air required (cfm)193 139 166 234 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-26 11:18:21Right-Suite® Universal 2021 21.0.08 RSU27054 Page 9...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Right-J® Worksheet Aug 25, 2021Date:Entire House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com 1 Room name Bed 3 Bath 3 2 Exposed wall 15.0 ft 5.5 ft 3 Room height 10.1 heat/coolft 10.1 heat/coolft 4 Room dimensions ft202.5x1.0 ft62.5x1.0 5 Room area 202.5 ft²62.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 nn 3.153.15 1.491.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 11 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 nn 21.1721.17 9.799.79 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ee 3.153.15 1.491.49 152 136 428 202 56 47 146 69 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 9 0 162 319 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 16 0 280 553 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ss 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ss 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 swsw 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 swsw 21.1721.17 15.9915.99 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ww 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ww 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 PP Frm Wall, 5/8" Gyp B 0.099Frm Wall, 5/8" Gyp B 0.099 --2.872.87 1.231.23 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.386Attic, Metal Roof, R 0.386 --1.581.58 1.211.21 203 203 319 246 63 63 99 76 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 203 15 430 0 63 6 158 0 6 c) AED excursion 11 27 Envelope loss/gain 1458 1012 565 491 12 a) Infiltration 284 75 104 28 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 0 Subtotal (lines 6 to 13)1741 1337 669 519 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1741 1337 669 519 15 Duct loads 18%17%314 233 18%17%121 90 Total room load 2056 1570 789 609 Air required (cfm)Air required (cfm)81 89 31 35 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-26 11:18:21Right-Suite® Universal 2021 21.0.08 RSU27054 Page 10...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Right-J® Worksheet Aug 25, 2021Date:Entire House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com 1 Room name Flex Space Hall 2 Exposed wall 42.0 ft 4.2 ft 3 Room height 10.1 heat/coolft 10.1 heat/coolft 4 Room dimensions ft232.5x1.0 ft53.0x1.0 5 Room area 232.5 ft²53.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 nn 3.153.15 1.491.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 11 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 nn 21.1721.17 9.799.79 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ee 3.153.15 1.491.49 172 172 540 255 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ss 3.153.15 1.491.49 152 120 379 179 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 31 31 561 478 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ss 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 swsw 3.153.15 1.491.49 0 0 0 0 43 22 70 33 GG Impact, Low-eImpact, Low-e 0.7300.730 swsw 21.1721.17 15.9915.99 0 0 0 0 21 21 438 330 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ww 3.153.15 1.491.49 101 101 318 150 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ww 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 PP Frm Wall, 5/8" Gyp B 0.099Frm Wall, 5/8" Gyp B 0.099 --2.872.87 1.231.23 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.386Attic, Metal Roof, R 0.386 --1.581.58 1.211.21 233 233 367 282 53 53 84 64 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 233 42 1205 0 53 4 120 0 6 c) AED excursion -226 201 Envelope loss/gain 3369 1119 710 629 12 a) Infiltration 794 211 80 21 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 900 0 Subtotal (lines 6 to 13)4163 2230 791 650 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 4163 2230 791 650 15 Duct loads 18%17%751 389 18%17%143 113 Total room load 4914 2619 933 763 Air required (cfm)Air required (cfm)193 148 37 43 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-26 11:18:21Right-Suite® Universal 2021 21.0.08 RSU27054 Page 11...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Right-J® Worksheet Aug 25, 2021Date:Entire House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com 1 Room name Dining Kitchen 2 Exposed wall 23.0 ft 0 ft 3 Room height 11.1 heat/coolft 10.1 heat/coolft 4 Room dimensions ft158.3x1.0 ft315.0x1.0 5 Room area 158.3 ft²315.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 nn 3.153.15 1.491.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.4500.450 nn 13.0513.05 11.4911.49 0 0 0 0 0 0 0 0 11 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6600.660 nn 19.1419.14 14.0214.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 nn 21.1721.17 9.799.79 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ee 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ee 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ss 3.153.15 1.491.49 150 103 324 153 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ss 17.9817.98 15.3215.32 47 47 841 717 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ss 20.0120.01 16.5816.58 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 swsw 3.153.15 1.491.49 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.7300.730 swsw 21.1721.17 15.9915.99 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.108Blk Wall, Stucco Ext 0.108 ww 3.153.15 1.491.49 105 57 181 85 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6200.620 ww 17.9817.98 35.4735.47 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.6900.690 ww 20.0120.01 16.5816.58 48 48 960 796 0 0 0 0 PP Frm Wall, 5/8" Gyp B 0.099Frm Wall, 5/8" Gyp B 0.099 --2.872.87 1.231.23 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.386Attic, Metal Roof, R 0.386 --1.581.58 1.211.21 158 158 249 192 315 315 497 383 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 158 23 660 0 315 0 0 0 6 c) AED excursion 897 -234 Envelope loss/gain 3216 2841 497 149 12 a) Infiltration 478 127 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 2 460 Appliances/other 0 1700 Subtotal (lines 6 to 13)3694 2968 497 2309 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 3694 2968 497 2309 15 Duct loads 18%17%667 518 18%17%90 403 Total room load 4361 3485 586 2712 Air required (cfm)Air required (cfm)171 198 23 154 2021-Aug-26 11:18:23 Right-Suite® Universal 2021 21.0.08 RSU27054 Page 1 ...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Duct System Summary Aug 25, 2021Date:Entire House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com Project Information Oleander Model 3, Villadelta Construction Corp, LLCFor: 2401 Noble Oaks Lane, Ft Pierce, FL 34981 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.442 / 0.258 in H2O in H2O0.442 / 0.258 Lowest friction rate in/100ft0.119in/100ft0.119 Actual air flow cfm1600cfm1600 Total effective length (TEL) ft589 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st2200.017.4VlFx0x04.00.2031327681hArrival Center st3200.029.9VlFx0x04.00.1921918334cBath 2 st3200.035.0VlFx0x04.00.1881918334cBath 2-A st5300.054.2VlFx0x04.00.1253531609cBath 3 st3200.033.4VlFx0x07.00.1891011203064hBed 2 st3200.032.0VlFx0x06.00.19189811570cBed 3 st3200.033.5VlFx0x04.00.1894470cButlers Pantry st1205.041.4VlFx0x06.00.179951062700hDen st5300.052.3VlFx0x09.00.1251981713485cDining st5300.056.4VlFx0x09.00.1241481934914hFlex Space-A st1205.040.5VlFx0x06.00.18050882251hFoyer st1205.048.3VlFx0x07.00.174117832062cGreat Room st1205.037.5VlFx0x07.00.182117832062cGreat Room-A st5300.049.3VlFx0x04.00.1274337763cHall st4305.056.6VlFx0x04.00.12219471195hHers st4305.056.9VlFx0x04.00.1223347cHis st3200.030.3VlFx0x07.00.192154232712cKitchen st2200.016.4VlFx0x05.00.20469781986hLaundry st4305.061.8VlFx0x08.00.1201401744420hMaster Bath st4305.066.9VlFx0x09.00.1191391934913hMaster Bedroom st4305.055.4VlFx0x04.00.1232921519cWtr Clst Bold/italic values have been manually overridden 2021-Aug-26 11:18:23 Right-Suite® Universal 2021 21.0.08 RSU27054 Page 2 ...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 438 330 0.119 557 12.0 0x0 VinlFlx st1 st1 Peak AVF 798 709 0.119 572 16.0 0x0 VinlFlx st2 Peak AVF 105 82 0.203 533 6.0 0x0 VinlFlx st5 Peak AVF 432 424 0.124 550 12.0 0x0 VinlFlx st3 st3 Peak AVF 697 809 0.124 757 14.0 0x0 VinlFlx Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb8 0x 2430 160 216.0 0.119 549 9.0 x0 0 VlFx rt2 rb7 0x 1060 95 211.2 0.122 397 7.0 x0 0 VlFx rt2 rb5 0x 810 89 208.2 0.124 333 7.0 x0 0 VlFx rt3 rb4 0x 1930 148 217.2 0.119 437 9.0 x0 0 VlFx rt3 rb6 0x 1200 101 82.6 0.313 450 7.0 x0 0 VlFx rt1 rb3 0x 8570 1007 78.8 0.328 570 18.0 x0 0 VlFx rt1 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt2 Peak AVF 349 255 0.119 444 12.0 0x0 VinlFlx rt1 rt3 Peak AVF 274 238 0.119 502 10.0 0x0 VinlFlx rt1 rt1 Peak AVF 1600 1600 0.119 905 18.0 0x0 VinlFlx 2021-Aug-26 11:18:23 Right-Suite® Universal 2021 21.0.08 RSU27054 Page 1 ...ocuments\Wrightsoft HVAC\2401 Noble Oaks Ln.rup Calc = MJ8 Front Door faces: N 1604Job:Manual S Compliance Report Aug 25, 2021Date:Entire House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Web: www.aircalcs.com Project Information Oleander Model 3, Villadelta Construction Corp, LLCFor: 2401 Noble Oaks Lane, Ft Pierce, FL 34981 Cooling Equipment Design Conditions °F76.4Entering coil DB:Btuh30292Sensible gain:°F90.4Outdoor design DB: °F64.3Entering coil WB:Btuh11408Latent gain:°F77.4Outdoor design WB: Btuh41700Total gain:°F75.0Indoor design DB: cfm1600Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: EL18XCVS048-230A**+CBA27UHE-048-230*++TDRModel:LennoxManufacturer: cfm1600Actual airflow: % of load111Btuh33600Sensible capacity: % of load126Btuh14400Latent capacity: %70SHR:% of load115Btuh48000Total capacity: Heating Equipment Design Conditions °F67.5Entering coil DB:Btuh44635Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm1600Actual airflow: °F50Temp. rise:% of load97kW12.7Output capacity: Meets all requirements of ACCA Manual S.