Loading...
HomeMy WebLinkAboutPROJECT INFORMATIONCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-18 10:10:44 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1622Job:Load Short Form 9/21/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pellaquila Residence, NisAir Air ConditioningFor: 5302 Seagrape Dr, Fort Pierce, FL 34982 Design Information InfiltrationClgHtg SimplifiedMethod9041Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1-041-230A** AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259425 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW7.9 Sensible cooling Btuh26950 Heating output Btuh26975 Latent cooling Btuh11550 Temperature rise °F19 Total cooling Btuh38500 Actual air flow cfm1283 Actual air flow cfm1283 Air flow factor cfm/Btuh0.050 Air flow factor cfm/Btuh0.051 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.78 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Laundry 36 432 842 22 43 Bed 2 136 2421 1754 121 90 Bath 42 59 107 3 5 Bath 2 51 773 535 39 27 Hall 30 0 0 0 0 Bed 3 153 3225 2587 161 132 Bed 4 157 2507 1922 125 98 Foyer GR 426 5261 6266 263 321 Pantry 14 0 0 0 0 Kitchen DR 411 4673 7072 234 362 Master Bath 95 2084 976 104 50 Hers 20 409 161 20 8 His 9 12 21 1 1 Master Bed 222 3779 2833 189 145 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-18 10:10:44 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2 ...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N House 1801 25634 25078 1283 1283 Other equip loads 1769 939 Equip. @ 0.95 RSM 24820 Latent cooling 7383 TOTALS 1801 27403 32203 1283 1283 2021-Nov-18 10:10:44 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1622Job:Building Analysis 9/21/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pellaquila Residence, NisAir Air ConditioningFor: 5302 Seagrape Dr, Fort Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 17.046503.1Walls 13.8377717.4Glazing 000Doors 6.517851.0Ceilings 20.957343.23.2Floors 11.631842.2Infiltration 23.76504Ducts 00Piping 00Humidification 6.51769Ventilation0Adjustments 100.027403Total Cooling Walls Glazing Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 11.028671.9Walls 18.1472021.8Glazing 000Doors 12.532501.8Ceilings 000Floors 3.48900.6Infiltration 27.97251Ducts 3.6939Ventilation 23.46100Internal gains 00Blower 0Adjustments 100.026017Total Latent Cooling Load = 7383 Btuh Overall U-value = 0.104 Btuh/ft²-°F Data entries checked. 2021-Nov-18 10:10:44 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1622Job:Component Constructions 9/21/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pellaquila Residence, NisAir Air ConditioningFor: 5302 Seagrape Dr, Fort Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 11693.155.10.109371ne 7482.02 5062.027913.155.10.109251se 4592.027173.155.10.109228sw 7802.0212203.155.10.109387nw 24932.0238973.155.10.1091237all Partitions Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16" OC Stud 3741.467542.9411.00.101257 Windows Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 100121.484118.000.62047se Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 4.7 ft overhang (6.7 ft window ht, 1 ft sep.); 6.8 ft head ht 40510.167616.800.58040se Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (2.2 ft window ht, 1 ft sep.); 6.8 ft head ht 13420.311116.800.5807sw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 68121.852516.800.58031sw 70622.652516.800.58031nw 138722.2105016.800.58062all Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (2.17 ft window ht, 1 ft sep.); 6.8 ft head ht 10622.67916.800.5805nw 2021-Nov-18 10:10:44 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2 ...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 8 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 35322.626216.800.58016nw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 8 ft overhang (6.7 ft window ht, 1 ft sep.); 6.8 ft head ht 88622.075818.800.65040nw Doors (none) Ceilings Attic, Metal Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.0341801 32501.8017850.9930.0 Floors On Grade Depth, Tile Flr Fnsh 00573428.700.989200 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-18 10:10:44 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1622Job:Project Summary 9/21/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pellaquila Residence, NisAir Air ConditioningFor:5302 Seagrape Dr, Fort Pierce, FL 34982 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh19130 Structure Btuh17826 Ducts Btuh6504 Ducts Btuh7251Central vent (56 cfm) 1769 Btuh Central vent (56 cfm) Btuh939 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh27403 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh24820 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh3032 Ducts Btuh2206Central vent (56 cfm) Btuh2145 CoolingHeating Outside air18011801Area (ft²) Equipment latent load Btuh7383 1577215772Volume (ft³)Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh32203 Equiv. AVF (cfm) 53100 Req. total capacity at 0.70 SHR ton3.0 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOX Model Cond ML14XC1-041-230A**AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259425Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW7.9 Sensible cooling Btuh26950Heating output Btuh26975 Latent cooling Btuh11550 Temperature rise °F19 Total cooling Btuh38500Actual air flow cfm1283 Actual air flow cfm1283 Air flow factor cfm/Btuh0.050 Air flow factor cfm/Btuh0.051Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.78 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-18 10:10:44Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1622Job:Right-J® Worksheet 9/21/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name House Laundry 2 Exposed wall 199.9 ft 5.5 ft 3 Room height 8.8 ft 8.0 heat/coolft 4 Room dimensions ft6.5x5.5 5 Room area 1800.8 ft²35.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 371 371 1169 748 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 338 251 791 506 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 47 6 841 1001 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 10.0710.07 40 40 676 405 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 266 228 717 459 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2520.25 7 2 111 134 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 31 4 525 681 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 479 387 1220 780 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 5 0 79 106 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 31 0 525 706 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 262 353 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 40 0 758 886 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 257 257 754 374 44 44 129 64 CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 1.801.80 1801 1801 1785 3250 36 36 35 65 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 1801 200 5734 0 36 6 158 0 6 c) AED excursion 447 -30 Envelope loss/gain 15946 10836 322 98 12 a) Infiltration 3184 890 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 5 1150 0 0 Appliances/other 4950 500 Subtotal (lines 6 to 13)19130 17826 322 598 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 19130 17826 322 598 15 Duct loads 34%41%6504 7251 34%41%110 243 Total room load 25634 25078 432 842 Air required (cfm)Air required (cfm)1283 1283 22 43 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-18 10:10:44Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1622Job:Right-J® Worksheet 9/21/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 2 Bath 2 Exposed wall 24.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft135.8x1.0 ft6.0x7.0 5 Room area 135.8 ft²42.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 10.0710.07 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 84 68 216 138 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2520.25 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 16 2 262 340 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 108 108 317 158 0 0 0 0 CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 1.801.80 136 136 135 245 42 42 42 76 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 136 24 688 0 42 0 0 0 6 c) AED excursion 57 -4 Envelope loss/gain 1618 938 42 72 12 a) Infiltration 184 51 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 0 Subtotal (lines 6 to 13)1802 1240 42 72 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 4 7 2 4 14 Subtotal 1806 1247 44 76 15 Duct loads 34%41%614 507 34%41%15 31 Total room load 2421 1754 59 107 Air required (cfm)Air required (cfm)121 90 3 5 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-18 10:10:44Right-Suite® Universal 2021 21.0.10 RSU29066 Page 3...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1622Job:Right-J® Worksheet 9/21/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bath 2 Hall 2 Exposed wall 6.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.0x8.5 ft8.5x3.5 5 Room area 51.0 ft²29.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 10.0710.07 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 48 41 130 83 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2520.25 7 2 111 134 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 1.801.80 51 51 51 92 30 30 29 54 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 51 6 172 0 30 0 0 0 6 c) AED excursion 29 -3 Envelope loss/gain 464 338 29 51 12 a) Infiltration 105 29 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)569 367 29 51 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 7 13 -29 -51 14 Subtotal 577 380 0 0 15 Duct loads 34%41%196 155 34%41%0 0 Total room load 773 535 0 0 Air required (cfm)Air required (cfm)39 27 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-18 10:10:44Right-Suite® Universal 2021 21.0.10 RSU29066 Page 4...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1622Job:Right-J® Worksheet 9/21/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 3 Bed 4 2 Exposed wall 25.5 ft 21.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft153.3x1.0 ft157.0x1.0 5 Room area 153.3 ft²157.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 64 64 202 129 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 10.0710.07 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 108 92 291 186 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2520.25 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 16 2 262 340 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 96 80 253 162 104 88 279 178 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 262 353 16 0 262 353 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 1.801.80 153 153 152 277 157 157 156 283 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 153 26 731 0 157 21 602 0 6 c) AED excursion 133 65 Envelope loss/gain 1953 1452 1501 1009 12 a) Infiltration 447 125 368 103 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 250 Subtotal (lines 6 to 13)2399 1827 1869 1362 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 7 13 2 4 14 Subtotal 2407 1839 1871 1366 15 Duct loads 34%41%818 748 34%41%636 556 Total room load 3225 2587 2507 1922 Air required (cfm)Air required (cfm)161 132 125 98 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-18 10:10:44Right-Suite® Universal 2021 21.0.10 RSU29066 Page 5...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1622Job:Right-J® Worksheet 9/21/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Foyer GR Pantry 2 Exposed wall 34.5 ft 0 ft 3 Room height 9.5 heat/coolft 8.0 heat/coolft 4 Room dimensions ft426.3x1.0 ft5.5x2.5 5 Room area 426.3 ft²13.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 223 152 478 306 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 31 4 561 668 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 10.0710.07 40 40 676 405 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2520.25 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 105 105 307 152 0 0 0 0 CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 1.801.80 426 426 423 769 14 14 14 25 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 426 35 989 0 14 0 0 0 6 c) AED excursion -76 -1 Envelope loss/gain 3435 2224 14 24 12 a) Infiltration 489 137 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 3 690 0 0 Appliances/other 1400 0 Subtotal (lines 6 to 13)3924 4451 14 24 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 2 4 -14 -24 14 Subtotal 3926 4454 0 0 15 Duct loads 34%41%1335 1812 34%41%0 0 Total room load 5261 6266 0 0 Air required (cfm)Air required (cfm)263 321 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-18 10:10:44Right-Suite® Universal 2021 21.0.10 RSU29066 Page 6...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1622Job:Right-J® Worksheet 9/21/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Kitchen DR Master Bath 2 Exposed wall 28.0 ft 19.5 ft 3 Room height 9.5 heat/coolft 8.0 heat/coolft 4 Room dimensions ft410.5x1.0 ft9.0x10.5 5 Room area 410.5 ft²94.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 71 71 224 144 72 72 227 145 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 10.0710.07 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2520.25 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 195 139 438 280 84 79 250 160 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 5 0 79 106 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 262 353 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 40 0 758 886 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 1.801.80 411 411 407 741 95 95 94 171 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 411 28 803 0 95 20 559 0 6 c) AED excursion 279 9 Envelope loss/gain 2892 2683 1209 590 12 a) Infiltration 583 163 342 96 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 0 0 Appliances/other 1700 0 Subtotal (lines 6 to 13)3475 5005 1550 686 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 12 21 5 8 14 Subtotal 3487 5027 1555 694 15 Duct loads 34%41%1186 2045 34%41%529 282 Total room load 4673 7072 2084 976 Air required (cfm)Air required (cfm)234 362 104 50 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-18 10:10:44Right-Suite® Universal 2021 21.0.10 RSU29066 Page 7...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1622Job:Right-J® Worksheet 9/21/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Hers His 2 Exposed wall 4.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft4.0x5.0 ft8.9x1.0 5 Room area 20.0 ft²8.9 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 32 32 101 64 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 10.0710.07 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2520.25 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 1.801.80 20 20 20 36 9 9 9 16 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 20 4 115 0 9 0 0 0 6 c) AED excursion -6 -1 Envelope loss/gain 235 95 9 15 12 a) Infiltration 70 20 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)305 114 9 15 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 305 114 9 15 15 Duct loads 34%41%104 47 34%41%3 6 Total room load 409 161 12 21 Air required (cfm)Air required (cfm)20 8 1 1 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-18 10:10:44Right-Suite® Universal 2021 21.0.10 RSU29066 Page 8...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1622Job:Right-J® Worksheet 9/21/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Master Bed 2 Exposed wall 31.9 ft 3 Room height 8.5 heat/coolft 4 Room dimensions ft222.4x1.0 5 Room area 222.4 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blk Wall, Stucco Ext 0.109 ne 3.15 2.02 132 132 415 266 .W Blk Wall, Stucco Ext 0.109 se 3.15 2.02 115 99 312 200 .G Impact, Clear Low-e 0.620 se 17.98 21.39 16 2 280 334 .G Impact, Clear Low-e 0.580 se 16.82 10.07 0 0 0 0 11 W Blk Wall, Stucco Ext 0.109 sw 3.15 2.02 26 26 80 51 G Impact, Clear Low-e 0.580 sw 16.82 20.25 0 0 0 0 G Impact, Clear Low-e 0.580 sw 16.82 21.82 0 0 0 0 W Blk Wall, Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 G Impact, Clear Low-e 0.650 nw 18.85 22.04 0 0 0 0 P Frm Wall, 1/2" Gyp B 0.101 -2.94 1.46 0 0 0 0 C Attic, Metal Roof, R 0.034 -0.99 1.80 222 222 220 401 F On Grade Depth, Tile 0.989 -28.68 0.00 222 32 915 0 6 c) AED excursion -4 Envelope loss/gain 2224 1247 12 a) Infiltration 596 167 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 600 Subtotal (lines 6 to 13)2820 2014 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 2820 2014 15 Duct loads 34%41%959 819 Total room load 3779 2833 Air required (cfm)189 145 2021-Nov-18 10:10:45 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1622Job:Duct System Summary 9/21/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pellaquila Residence, NisAir Air ConditioningFor: 5302 Seagrape Dr, Fort Pierce, FL 34982 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.494 / 0.206 in H2O in H2O0.494 / 0.206 Lowest friction rate in/100ft0.276in/100ft0.276 Actual air flow cfm1283cfm1283 Total effective length (TEL) ft254 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st195.013.1VlFx0x04.00.45674107cBath st3120.025.2VlFx0x04.00.3403346773hBath 2 st195.012.3VlFx0x06.00.4601081452421hBed 2 st3120.029.1VlFx0x07.00.3311591943225hBed 3 st3120.024.2VlFx0x07.00.3421181512507hBed 4 st2100.032.8VlFx0x07.00.3721921583133cFoyer GR st2100.032.9VlFx0x07.00.3721921583133cFoyer GR-A st4130.048.8VlFx0x04.00.2761025409hHers st4125.044.3VlFx0x04.00.2921121cHis st2100.032.7VlFx0x07.00.3722171403536cKitchen DR-A st2100.032.4VlFx0x07.00.3732171403536cKitchen DR-B st195.013.1VlFx0x04.00.4575226842cLaundry st4125.050.7VlFx0x06.00.281601252084hMaster Bath st4125.048.5VlFx0x06.00.285871131889hMaster Bed st4125.044.1VlFx0x06.00.292871131889hMaster Bed-A Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 377 245 0.276 854 9.0 0x0 VinlFlx st2 st3 Peak AVF 391 310 0.331 884 9.0 0x0 VinlFlx st1 st1 Peak AVF 566 476 0.331 720 12.0 0x0 VinlFlx st2 Peak AVF 974 1064 0.276 762 16.0 0x0 VinlFlx Bold/italic values have been manually overridden 2021-Nov-18 10:10:45 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2 ...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb5 0x 1510 118 74.8 0.276 563 7.0 x0 0 VlFx rt1 rb6 0x 1940 159 66.5 0.310 555 8.0 x0 0 VlFx rt1 rb7 0x 1450 108 62.4 0.331 544 7.0 x0 0 VlFx rt1 rb1 0x 7980 970 62.7 0.329 549 18.0 x0 0 VlFx rt1 rb8 0x 2520 185 0 0 0 0 x0 0 VlFx Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 1287 1354 0.276 766 18.0 0x0 VinlFlx 2021-Nov-18 10:10:45 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\5302 Seagrape Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1622Job:Manual S Compliance Report 9/21/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pellaquila Residence, NisAir Air ConditioningFor: 5302 Seagrape Dr, Fort Pierce, FL 34982 Cooling Equipment Design Conditions °F76.7Entering coil DB:Btuh26017Sensible gain:°F90.4Outdoor design DB: °F63.9Entering coil WB:Btuh7383Latent gain:°F77.4Outdoor design WB: Btuh33400Total gain:°F75.0Indoor design DB: cfm1283Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: ML14XC1-041-230A**+CBA27UHE-048-230*++TDRModel:LennoxManufacturer: cfm1283Actual airflow: % of load104Btuh26950Sensible capacity: % of load156Btuh11550Latent capacity: %70SHR:% of load115Btuh38500Total capacity: Heating Equipment Design Conditions °F68.3Entering coil DB:Btuh27403Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm1283Actual airflow: °F50Temp. rise:% of load98kW7.9Output capacity: Meets all requirements of ACCA Manual S.