Loading...
HomeMy WebLinkAboutPROJECT INFORMATIONCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 14:23:05 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1640Job:Load Short Form 10/12/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Dinsmore Residence, NisAir Air ConditioningFor: 1625 Easy St, Fort Pierce, FL 34982 Design Information InfiltrationClgHtg SimplifiedMethod9041Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1S042-230A** AHRI ref Coil CBA27UHE-042-230*++TDR AHRI ref 10259441 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW9.5 Sensible cooling Btuh29400 Heating output Btuh32564 Latent cooling Btuh12600 Temperature rise °F21 Total cooling Btuh42000 Actual air flow cfm1400 Actual air flow cfm1400 Air flow factor cfm/Btuh0.044 Air flow factor cfm/Btuh0.049 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.79 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Bed 2 180 2904 2072 128 102 Bath 64 985 624 43 31 Hall 32 0 0 0 0 Bed3 204 3452 2398 152 118 Kitchen 238 3328 5058 147 248 Great Room 513 3316 5226 146 256 Laundry 68 867 1032 38 51 Office 127 2529 2137 112 105 Foyer 64 897 505 40 25 Living 228 4491 2360 198 116 Wtr Clst 30 40 62 2 3 Master Bath 196 1671 967 74 47 His 36 694 432 31 21 Hers 46 60 93 3 5 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 14:23:05 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2 ...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N Master Bed 275 6498 5596 287 274 House 2299 31732 28564 1400 1400 Other equip loads 1689 897 Equip. @ 0.95 RSM 28105 Latent cooling 7816 TOTALS 2299 33421 35921 1400 1400 2021-Dec-16 14:23:05 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1640Job:Building Analysis 10/12/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Dinsmore Residence, NisAir Air ConditioningFor: 1625 Easy St, Fort Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Other Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 18.662143.1Walls 13.8459717.9Glazing 0.82543.7Doors 6.822791.0Ceilings 20.468263.03.0Floors 11.438061.8Infiltration 23.27755Ducts 00Piping 00Humidification 5.11689Ventilation0Adjustments 100.033421Total Cooling Walls Glazing Other Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 13.238741.9Walls 20.9615023.9Glazing 0.92573.7Doors 11.433641.5Ceilings 000Floors 3.410110.5Infiltration 29.38638Ducts 3.0897Ventilation 17.95270Internal gains 00Blower 0Adjustments 100.029460Total Latent Cooling Load = 7816 Btuh Overall U-value = 0.101 Btuh/ft²-°F Data entries checked. 2021-Dec-16 14:23:05 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1640Job:Component Constructions 10/12/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Dinsmore Residence, NisAir Air ConditioningFor: 1625 Easy St, Fort Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 7973.155.10.109253ne 5102.02 12242.0219133.155.10.109607se 8602.0213443.155.10.109426sw 9322.0214583.155.10.109463nw 35252.0255113.155.10.1091749all Partitions Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16" OC Stud 3491.467032.9411.00.101239 Windows Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.18); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (0.83 ft window ht, 1 ft sep.); 8 ft head ht 8817.76513.100.4505ne Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 8 ft head ht 69122.156118.000.62031ne 50922.141318.000.62023ne 120022.197418.000.62054all Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (1.33 ft window ht, 1 ft sep.); 8 ft head ht 7418.56716.800.5804se 10318.59316.800.5806se 17718.516116.800.58010all Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (4.17 ft window ht, 1 ft sep.); 8 ft head ht 37421.529216.800.58017sw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 8 ft head ht 24621.819016.800.58011sw 70622.652516.800.58031nw 95222.471416.800.58042all 2021-Dec-16 14:23:05 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2 ...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.3 ft window ht, 1 ft sep.); 8 ft head ht 25121.819316.800.58011sw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 12 ft overhang (8 ft window ht, 1 ft sep.); 8 ft head ht 89714.0120618.800.65064sw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (2.2 ft window ht, 1 ft sep.); 8 ft head ht 11622.68616.800.5805nw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 6 ft overhang (8 ft window ht, 1 ft sep.); 8 ft head ht 105822.090518.800.65048nw Doors Fbrgls Door 1793.731773.697.00.12748ne 783.73773.697.00.12721sw 2573.732543.697.00.12769all Ceilings Attic, Shngl Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.0342299 33641.4622790.9930.0 Floors On Grade Depth, Tile Flr Fnsh 00682628.700.989238 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 14:23:05 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1640Job:Project Summary 10/12/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Dinsmore Residence, NisAir Air ConditioningFor:1625 Easy St, Fort Pierce, FL 34982 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh23977 Structure Btuh19925 Ducts Btuh7755 Ducts Btuh8638Central vent (53 cfm) 1689 Btuh Central vent (53 cfm) Btuh897 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh33421 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh28105 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh3108 Ducts Btuh2660Central vent (53 cfm) Btuh2048 CoolingHeating Outside air22992299Area (ft²) Equipment latent load Btuh7816 2239322393Volume (ft³)Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh35921 Equiv. AVF (cfm) 60119 Req. total capacity at 0.70 SHR ton3.3 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOX Model Cond ML14XC1S042-230A**AHRI ref Coil CBA27UHE-042-230*++TDR AHRI ref 10259441Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW9.5 Sensible cooling Btuh29400Heating output Btuh32564 Latent cooling Btuh12600 Temperature rise °F21 Total cooling Btuh42000Actual air flow cfm1400 Actual air flow cfm1400 Air flow factor cfm/Btuh0.044 Air flow factor cfm/Btuh0.049Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.79 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 14:23:05Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1640Job:Right-J® Worksheet 10/12/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name House Bed 2 2 Exposed wall 238.0 ft 27.0 ft 3 Room height 9.7 ft 9.3 heat/coolft 4 Room dimensions ft15.0x12.0 5 Room area 2299.3 ft²180.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 360 253 797 510 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 5 0 65 88 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 31 0 561 691 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 23 0 413 509 0 0 0 0 11 DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 48 48 177 179 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 617 607 1913 1224 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 18.4918.49 4 2 67 74 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 18.4918.49 6 3 93 103 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 552 426 1344 860 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.5421.54 17 3 292 374 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 11 1 190 246 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8421.84 11 1 193 251 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 64 64 1206 897 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 swsw 3.693.69 3.733.73 21 21 77 78 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 547 463 1458 932 140 124 390 250 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 5 0 86 116 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 31 0 525 706 16 0 262 353 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 48 0 905 1058 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 239 239 703 349 112 112 328 163 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 2299 2299 2279 3364 180 180 178 263 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 2299 238 6826 0 180 27 774 0 6 c) AED excursion 1036 91 Envelope loss/gain 20171 13644 1933 1120 12 a) Infiltration 3806 1011 256 68 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 4 920 0 0 Appliances/other 4350 250 Subtotal (lines 6 to 13)23977 19925 2189 1438 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 5 8 14 Subtotal 23977 19925 2195 1446 15 Duct loads 32%43%7755 8638 32%43%710 627 Total room load 31732 28564 2904 2072 Air required (cfm)Air required (cfm)1400 1400 128 102 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 14:23:05Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1640Job:Right-J® Worksheet 10/12/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bath Hall 2 Exposed wall 8.0 ft 0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft8.0x8.0 ft8.0x4.0 5 Room area 64.0 ft²32.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 18.4918.49 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 18.4918.49 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8421.84 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 swsw 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 74 69 218 140 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 5 0 86 116 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 64 64 63 94 32 32 32 47 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 64 8 229 0 32 0 0 0 6 c) AED excursion 35 -1 Envelope loss/gain 597 384 32 45 12 a) Infiltration 136 36 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)734 420 32 45 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 11 15 -32 -45 14 Subtotal 745 435 0 0 15 Duct loads 32%43%241 189 32%43%0 0 Total room load 985 624 0 0 Air required (cfm)Air required (cfm)43 31 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 14:23:05Right-Suite® Universal 2021 21.0.10 RSU29066 Page 3...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1640Job:Right-J® Worksheet 10/12/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed3 Kitchen 2 Exposed wall 29.0 ft 26.0 ft 3 Room height 9.3 heat/coolft 10.0 heat/coolft 4 Room dimensions ft17.0x12.0 ft17.0x14.0 5 Room area 204.0 ft²238.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 120 120 378 242 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 18.4918.49 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 18.4918.49 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 112 91 285 183 140 123 386 247 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.5421.54 0 0 0 0 17 3 292 374 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8421.84 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 swsw 3.693.69 3.733.73 21 21 77 78 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 158 143 449 287 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 262 353 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 204 204 202 298 238 238 236 348 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 204 29 832 0 238 26 746 0 6 c) AED excursion 84 31 Envelope loss/gain 2108 1284 2038 1242 12 a) Infiltration 495 131 477 127 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 2 460 Appliances/other 250 1700 Subtotal (lines 6 to 13)2603 1665 2515 3529 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 5 8 0 0 14 Subtotal 2608 1673 2515 3529 15 Duct loads 32%43%844 725 32%43%813 1530 Total room load 3452 2398 3328 5058 Air required (cfm)Air required (cfm)152 118 147 248 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 14:23:05Right-Suite® Universal 2021 21.0.10 RSU29066 Page 4...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1640Job:Right-J® Worksheet 10/12/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Great Room Laundry 2 Exposed wall 12.5 ft 10.5 ft 3 Room height 10.0 heat/coolft 9.3 heat/coolft 4 Room dimensions ft513.0x1.0 ft8.5x8.0 5 Room area 513.0 ft²68.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 18.4918.49 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 18.4918.49 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 125 61 192 123 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8421.84 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 64 64 1206 897 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 swsw 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 98 98 287 142 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 513 513 508 750 68 68 67 99 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 513 13 359 0 68 11 301 0 6 c) AED excursion 439 -22 Envelope loss/gain 2266 2210 655 220 12 a) Infiltration 229 61 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 0 0 Appliances/other 900 500 Subtotal (lines 6 to 13)2495 3631 655 720 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 11 15 0 0 14 Subtotal 2505 3646 655 720 15 Duct loads 32%43%810 1581 32%43%212 312 Total room load 3316 5226 867 1032 Air required (cfm)Air required (cfm)146 256 38 51 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 14:23:05Right-Suite® Universal 2021 21.0.10 RSU29066 Page 5...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1640Job:Right-J® Worksheet 10/12/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Office Foyer 2 Exposed wall 17.0 ft 7.5 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft11.5x11.0 ft8.5x7.5 5 Room area 126.5 ft²63.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 110 74 233 149 75 27 85 54 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 5 0 65 88 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 31 0 561 691 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 48 48 177 179 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 30 30 95 60 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 18.4918.49 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 18.4918.49 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8421.84 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 swsw 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 30 30 88 44 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 127 127 125 185 64 64 63 93 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 127 17 488 0 64 8 215 0 6 c) AED excursion -45 -11 Envelope loss/gain 1654 1173 540 316 12 a) Infiltration 257 68 138 37 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 0 Subtotal (lines 6 to 13)1911 1491 678 352 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1911 1491 678 352 15 Duct loads 32%43%618 646 32%43%219 153 Total room load 2529 2137 897 505 Air required (cfm)Air required (cfm)112 105 40 25 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 14:23:05Right-Suite® Universal 2021 21.0.10 RSU29066 Page 6...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1640Job:Right-J® Worksheet 10/12/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Living Wtr Clst 2 Exposed wall 36.0 ft 0 ft 3 Room height 10.0 heat/coolft 9.3 heat/coolft 4 Room dimensions ft13.0x17.5 ft5.5x5.5 5 Room area 227.5 ft²30.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 175 152 479 306 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 23 0 413 509 0 0 0 0 11 DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 130 130 410 262 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 18.4918.49 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 18.4918.49 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8421.84 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 swsw 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 55 55 173 111 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 228 228 226 333 30 30 30 44 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 228 36 1033 0 30 0 0 0 6 c) AED excursion -50 -1 Envelope loss/gain 2733 1471 30 43 12 a) Infiltration 660 175 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3393 1646 30 43 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 3393 1646 30 43 15 Duct loads 32%43%1098 714 32%43%10 19 Total room load 4491 2360 40 62 Air required (cfm)Air required (cfm)198 116 2 3 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 14:23:05Right-Suite® Universal 2021 21.0.10 RSU29066 Page 7...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1640Job:Right-J® Worksheet 10/12/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Master Bath His 2 Exposed wall 13.5 ft 5.5 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft196.3x1.0 ft5.5x6.5 5 Room area 196.3 ft²35.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 126 122 383 245 51 46 144 92 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 18.4918.49 4 2 67 74 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 18.4918.49 0 0 0 0 6 3 93 103 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8421.84 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 swsw 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 196 196 195 287 36 36 35 52 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 196 14 387 0 36 6 158 0 6 c) AED excursion 7 29 Envelope loss/gain 1032 613 430 276 12 a) Infiltration 230 61 94 25 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1262 675 524 301 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1262 675 524 301 15 Duct loads 32%43%408 292 32%43%170 131 Total room load 1671 967 694 432 Air required (cfm)Air required (cfm)74 47 31 21 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 14:23:05Right-Suite® Universal 2021 21.0.10 RSU29066 Page 8...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1640Job:Right-J® Worksheet 10/12/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Hers Master Bed 2 Exposed wall 0 ft 45.5 ft 3 Room height 9.3 heat/coolft 10.0 heat/coolft 4 Room dimensions ft7.0x6.5 ft274.8x1.0 5 Room area 45.5 ft²274.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 160 160 504 322 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 18.4918.49 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 18.4918.49 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 175 152 480 307 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 11 1 190 246 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8421.84 0 0 0 0 11 1 193 251 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 swsw 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 120 72 227 145 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 48 0 905 1058 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 46 46 45 67 275 275 272 402 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 46 0 0 0 275 46 1305 0 6 c) AED excursion -2 451 Envelope loss/gain 45 65 4075 3182 12 a) Infiltration 0 0 835 222 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)45 65 4910 3903 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 45 65 4910 3903 15 Duct loads 32%43%15 28 32%43%1588 1692 Total room load 60 93 6498 5596 Air required (cfm)Air required (cfm)3 5 287 274 2021-Dec-16 14:23:07 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1640Job:Duct System Summary 10/12/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Dinsmore Residence, NisAir Air ConditioningFor: 1625 Easy St, Fort Pierce, FL 34982 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.488 / 0.212 in H2O in H2O0.488 / 0.212 Lowest friction rate in/100ft0.257in/100ft0.257 Actual air flow cfm1400cfm1400 Total effective length (TEL) ft273 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st2100.029.5VlFx0x04.00.3773752985hBath st2110.033.7VlFx0x07.00.3401221542904hBed 2 st2105.036.0VlFx0x07.00.3461411833452hBed3 st1100.032.5VlFx0x04.00.3683048897hFoyer st1100.041.3VlFx0x07.00.345154882613cGreat Room st2100.029.4VlFx0x06.00.377154882613cGreat Room-A st3125.054.3VlFx0x04.00.2725393cHers st3125.054.7VlFx0x04.00.2712537694hHis st2100.038.5VlFx0x08.00.3522981765058cKitchen st2100.034.2VlFx0x05.00.36361461032cLaundry st1105.043.4VlFx0x06.00.329691192245hLiving st1100.035.5VlFx0x06.00.360691192245hLiving-A st3125.059.6VlFx0x06.00.26457881671hMaster Bath st3125.065.0VlFx0x07.00.2571651723249hMaster Bed st3125.058.0VlFx0x07.00.2671651723249hMaster Bed-A st1100.034.1VlFx0x06.00.3641261342529hOffice st1105.035.5VlFx0x04.00.3474262cWtr Clst Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st3 Peak AVF 472 417 0.257 866 10.0 0x0 VinlFlx st1 st1 Peak AVF 981 868 0.257 703 16.0 0x0 VinlFlx st2 Peak AVF 699 812 0.340 759 14.0 0x0 VinlFlx Bold/italic values have been manually overridden 2021-Dec-16 14:23:07 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2 ...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb3 0x 1340 126 82.6 0.257 501 7.0 x0 0 VlFx rt1 rb7 0x 1830 141 72.7 0.292 524 8.0 x0 0 VlFx rt1 rb2 0x 1540 122 68.8 0.308 575 7.0 x0 0 VlFx rt1 rb4 0x 2380 139 0 0 0 0 x0 0 VlFx rb1 0x 5880 793 50.3 0.421 568 16.0 x0 0 VlFx rt1 rb5 0x 3840 360 0 0 0 0 x0 0 VlFx Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 1058 1181 0.257 668 18.0 0x0 VinlFlx 2021-Dec-16 14:23:07 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...ments\Wrightsoft HVAC\1625 Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1640Job:Manual S Compliance Report 10/12/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Dinsmore Residence, NisAir Air ConditioningFor: 1625 Easy St, Fort Pierce, FL 34982 Cooling Equipment Design Conditions °F76.7Entering coil DB:Btuh29460Sensible gain:°F90.4Outdoor design DB: °F63.8Entering coil WB:Btuh7816Latent gain:°F77.4Outdoor design WB: Btuh37276Total gain:°F75.0Indoor design DB: cfm1400Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: ML14XC1S042-230A**+CBA27UHE-042-230*++TDRModel:LennoxManufacturer: cfm1400Actual airflow: % of load100Btuh29400Sensible capacity: % of load161Btuh12600Latent capacity: %70SHR:% of load113Btuh42000Total capacity: Heating Equipment Design Conditions °F68.4Entering coil DB:Btuh33421Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm1400Actual airflow: °F50Temp. rise:% of load97kW9.5Output capacity: Meets all requirements of ACCA Manual S.