Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
Shop Drawing Review Comments
w SALASO'BRIEN�, rangle Blvd., Suite 100 3501 QuadOrlando, Florida 3. Z4-7 expect a difference I 407.380.LLLJAN Ai k an.com January 10, 2022 2022 y, rmitting SHOP DRAWING REVIEW COMMENTS �^ Reference: Trane WPB SLC Morningside Library SO -Ton RTU Replacement Salas O'Brien Florida #2104402 Subject: SUBMITTAL ID: 01 Trane Equipment Submittal Reviewed By: Joseph Detig, P.E. Mahaley Vann Engineer's review is for general conformance with the design concept and contract documents. Markings or comments shall not be construed as relieving the Contractor from compliance with the project plans and specifications, nor departures therefrom. The Contractor remains responsible for details and accuracy, compliance with the Contract Documents and intent, for confirming and correcting all quantities and dimensions, for selecting appropriate fabrication processes, for techniques of assembly, and for performance of work in a safe manner. OVERALL DISPOSITION: NO EXCEPTIONS TAKEN. END OF DOCUMENT Prepared For. St Lucie County Submittal Date: December 29, 2021 Job Name: SLC - Morningside Library 50T Ipak Repl Trane U.S. Inc. is pleased to provide the following submittal for your review and approval. Product Summary Qty Product 1 Commercial Rooftop Air Conditioning Units (5,0 ton Iritellipak) Chris Cowling Trane U.S. Inc. 6965 Vista Parkway North, Suite 11 West Palm Beach, FL 33411 Office Phone: (561) 683-1521 Please Note: The attached information describes the equipment we propose to furnish for this project and is submitted for your approval. Product performance and submittal data is valid for a period of 6 months from the date of submittal generation. If six months or more has elapsed between submittal generation and equipment release, the product performance and submittal data will need to be verified. It is the customer's responsibility to obtain such verification. • Installing subcontractors and Engineer to review submittal for accuracy before order is placed. ELECTRONIC SHOP DRAWING REVIEW By: Salas O'Brien Florida, Inc. NO EXCEPTIONS TAKEN Engineer's review Is for general conformance with the design concept and contract documents. Markings or comments shall not be construed as relieving the Contractor from compliance with the project plans and specifications, nor departures therefrom. The Contractor remains responsible for details and accuracy, compliance with the Contract Documents and intent, for confirming and correcting all quantities and dimensions, for selecting appropriate fabrication processes, for techniques of assembly, and for performance of work in a safe manner. By: Joseph W. Detig 01/10/2022 © 2021 Trane Technologies All rights reserved Submittal - 50T Ipak - SLC Morningside Library 50T Ipak Repl 11 -1 1-21.docx Table of Contents ProductSummary ...........................................................................................................................................................1 - Commercial Rooftop Air Conditioning Units (Midrange) (Item Al) ...........................................................................3 TagData....................................................................................................................................................................... 3 ProductData.................................................................................................................................................................3 ProductReport..............................................................................................................................................................4 MechanicalSpecifications............................................................................................................................................ 6 DimensionalDrawings................................................................................................................................................10 FanCurve...................................................................................................................................................................13 Weight, Clearance & Rigging.....................................................................................................................................14 Accessory...................................................................................................................................................................16 Field Installed Options - Part/Order Number Summary ............................................................................................25 Commercial Rooftop Air Conditioning Units (Midrange)............................................................................................. 25 © 2021 Trane Technologies All rights reserved Submittal - 50T Ipak - SLC Morningside Library 50T Ipak Repl 11 -1 1-21.docx SLC - Morningside Library 50T Ipak Repl Tag Data - Commercial Rooftop Air Conditionings Units (Midrange) (Qtv: 11 November 11, 2021 Item Tag(s) Qt Description I Model Number Al 50T Ipak 1 20-75 Ton Packaged Industrial Rooftop (S SAHLF5040*00CZHD6El l B*W**H*BA* *6T*M86 Product Data - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak DX Cooling only, High efficiency unit R-41 QA refrigerant 50 Ton 'unit 460 Volt-60 Hertz-3 Phase 0 100%. Economizer (Outside Air damper) SS Drain Pan w Grease Lines/Filter Gauge 2 00" ;[51 mm] Spring isolators MERV 8 High efficiency:throwaway filters (1 set) eprive, Direct drive plenum`(DDP) supply fan 30 hp DpP 100% width VAV PTC) with supply VFD Programmable zonesensor (Fld,) Low' ambient damper(s)control cULus Unit disconnectswitch.with high fault SCCR_ Motors:with internal shaft grounding ring_ ; . 0,10 volt Generic B.A.S;Module Hinged access doors BACnet Communication interface module Factory -powered 15A GFI Convenience outlet Professionally=applied Condenser coil coating Factory, Start-up 1st year Parts, Labor & Refrigerant warranty 2nd-6th,year Parts only warranty whole unit 28" tall Flat Plenum -style Vibration -isolation Roof curb w/ wind -load engineering (Fld) Equipment Submittal Page 3 of 25 SLC - Morningside Library 50T Ipak Repl November 11, 2021 Product Report - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak !Condenser Fans FLA W 1A 80 q #C mpressor 1,RLA x �a Supply Fan`FLA �u 36 60 A j Compressor 1 ,Count 2 00 Each Supply Fan Motor Count 1 C� ompressor 2'RLA 1 �Y 1910 A ether FLq Co�ripressor2Count s <2 00 Each w _... — — - Fun��_a_.ctionF:,�:,�.....v. Equipment Submittal Page 4 of 25 SLC - Morningside Library 50T Ipak Repl November 11, 2021 Product Report - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak AHRI Certiftatibn Packaged Rooftop units cooling, heating capacities and efficiencies are rated within the scope of the Air -Conditioning, Heating & Refrigeration Institute (AHRI) Certification Program and display the AHRI Certified® mark as a visual confirmation of conformance to the certification sections of AHRI Standard 340-360 (I-P) and ANSIZ21.47 and 10 CFR Part 431 pertaining to Commercial Warm Air Furnaces. Certified units may be found in the AHRI directory at www.ahridirectory.org Equipment Submittal Page 5 of 25 SLC - Morningside Library 50T Ipak Rep[ November 11, 2021 Mechanical Specifications - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak General - R410A Units shall be specifically designed for outdoor rooftop installation on a roof curb and be completely factory assembled and tested, piped, internally wired, fully charged with R-410A compressor oil and shipped in one piece. Units shall be available for direct expansion cooling only, or direct expansion cooling with natural gas, electric, hot water or steam heating. Filters, outside air system, exhaust air system, optional non -fused disconnect switches and all operating and safety controls shall be furnished factory installed. All units shall be cULus approved and factory run tested. Cooling capacity shall be rated in accordance with AHRI Standard 360. All units shall have decals and tags to aid in service and indicate caution areas. Electrical diagrams shall be printed on long life water resistant material and shall ship attached to control panel doors. Casing Exterior panels shall be zinc coated galvanized steel, phosphatized and painted with a slate grey air-dry finish durable enough to withstand a minimum of 672 hours consecutive salt spray application in accordance with standard ASTM B117. Screws shall be coated with zinc -plus -zinc chromate. Heavy gauge steel hinged access panels with tiebacks to secure door in open position shall provide access to filters and heating sections. Refrigeration components, supply air fan and compressor shall be accessible through removable panels as standard. Unit control panel, filter section, and gas heating section shall be accessible through hinged access panels as standard. Optional Double Wall Construction hinged access doors shall provide access to filters, return/exhaust air, heating and supply fan section. All access doors and panels shall have neoprene gaskets. Interior surfaces or exterior casing members shall have 1/2" fiberglass insulation. Unit base shall be watertight with heavy gauge formed load bearing members, formed recess and curb overhang. Unit lifting lugs shall accept chains or cables for rigging. Lifting lugs shall also serve as unit tiedown points. Hinged Access Doors Hinged access doors shall provide easy access to supply fan, filters, exhaust/return fan, and heating section.These access doors shall feature double wall construction with dual density insulation sandwiched between heavy gauge galvanized steel panels for strength and durability Air -Cooled Condenser Coil - R410A Condenser coils shall have all Aluminum Microchannel coils. All coils shall be leak tested at the factory to ensure pressure integrity. The condenser coil is pressure tested to 650psig Subcooling circuit(s) shall be provided as standard. Condenser Fans and Motors All condenser fans shall be vertical discharge, direct drive fans, statically balanced, with aluminum blades and zinc plated steel hubs. Condenser fan motors shall be three-phase motors with permanently lubricated ball bearings, built- in current and thermal overload protection and weathertight slingers over motor bearings. Low Ambient Low ambient dampers shall be provided on condenser fan to allow the unit. Evaporator Coil - R410A Internally enhanced copper tubing of 3/8" or 1/2" O.D. shall be mechanically bonded to heavyduty aluminum fins of configured design. All coils shall be equipped with thermal expansion valves and factory pressure and leak tested. Sloped Stainless Steel Drain Pan The double sloping stainless steel drain pan shall promote runoff of standingwater from condensation inside the unit.Two drain pipes shall be installed through the base channel on each side of the unit.The evaporator drain pan shall be constructed of 14 gauge stainless steel. On units 40 tons and larger, the intermediate drain pan shall be constructed of 16 gauge stainless steel.This shall provide protection in corrosive environments Compressors - R410A The Trane Scroll compressor shall be industrial grade, direct drive 3600 RPM maximum speed scroll type. The motor shall be suction gas-cooled hermetic design. Compressor shall have centrifugal oil pump with dirt separator, oil sight glass, and oil charging valve. Compressor shall also be provided with thermostatic motor winding temperature control to protect against excessive motor temperatures resulting from over -/under -voltage or loss of charge, high and low pressure cutouts, and reset relay. Equipment Submittal Page 6 of 25 SLC - Morningside Library SOT Ipak Repl November 11, 2021 Phase Monitor Shall protect 3-phase equipment from phase loss, phase reversal, and low voltage. Any fault condition shall produce a Failure Indicator LED, and send the unit into an emergency stop condition. cULus approved. (Standard on 20-75T units) Supply Fan Supply fan motors shall be either open drip -proof or enclosed fan cooled. All supply fans shall be dynamically balanced in factory. Supply fan shall be test run in unit and shall reach rated rpm. All 60 Hz supply fan motors meet the Energy Independence Security Act of 2007 (EISA). All 50 Hz supply fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). Variable Frequency Drive Unit shall include factory -installed and tested variable frequency drive[s] (VFD) to provide motor speed modulation. The VFD shall receive a 0-10VDC speed signal from the unit controller. The drive will respond to the signal by accelerating or decelerating to maintain the controlling set point (duct static, space pressure, etc). VFD shall also include the following features: 1. Designed, constructed, and tested in accordance with NEMA ICS, NFPA, and IEC standards and housed in a plastic IP20 enclosure. 2. DC link reactors on both the positive and negative rails of the DC bus equal to 3% impedance to minimize power line harmonics. 3. Full rated output current continuously - 110% of rated current for 60 seconds and 160% of rated current for up to 0.5 second while starting. 4. Isolation between the Drive's power circuitry and control circuitry to ensure operator safety and to protect connected electronic control equipment from damage caused by voltage spikes, current surges, and ground loop currents. 5. Audible noise reduction through automatic adjustment of the carrier frequency and frequency avoidance. 6. Rated at 40C with a standard operating range of -10 to 50C (14 to 124F) ambient temperatures and 0 to 95% relative humidity 7. Self -diagnostics and motor protections such as: cULus listed overload, phase loss, and internal thermal overload. 8. Off/Stop and Auto/Start selector switches to start and stop the AC Drive and determine the speed reference. a. On units with bypass, an AC Drive/Off/Bypass hand selector switch shall be provided in the unit control box b. In DRIVE mode speed reference shall be provided by a 0-10 VDC analog input 9. A keypad interface which shall be programmable by language and feature multiple lines for easy reading. 10. Controlled and/or accessible points such as AC Drive Start/Stop, speed reference, and fault diagnostics. 11. Meter points such as motor power in HP, motor power in kW, motor kW-hr, motor current, motor voltage, hours run, DC link voltage, thermal load on motor, Thermal load on AC Drive and Heatsink temperature. 12. Troubleshooting features such as: a. AC Drive memory storage of the last 10 faults and related operational data b. Four simultaneous displays: frequency or speed, run time, output amps and output power c. Keypad which shall display: Reference Signal Value, Output Frequency in Hz or percent, Output Amps, Motor HP, Motor kW, kW 13. Coated circuit boards for protection against corrosive environments 14. Field readable BACnet points to allow for communication of stauts, setpoints and diagnostics to the BAS. Internal Shaft Grounding Ring Equipment Submittal Page 7 of 25 SLC - Morningside Library 50T Ipak Repl Motors shall have internal bearing protection for use with VFDs. November 11, 2021 Extended Grease Lines Lines shall be provided to allow greasing of supply and exhaust/return fan bearings through he filter access door. Two-inch Spring Isolators Supply and Exhaust/Return fan (if applicable) assemblies shall be isolated with two-inch nominal deflection to reduce transmission of vibrations 0-100 percent modulating economizer Operated through the primary temperature controls to automatically utilize OA for "free" cooling. Automatically modulated return and OA dampers shall maintain proper temperature in the conditioned space. Economizer shall be equipped with an automatic lockout when the outdoor high ambient temperature is too high for proper cooling. Minimum position control shall be standard and adjustable at the Human Interface Panel or with a remote potentiometer or through the building management system. A spring return motor shall ensure closure of OA dampers during unit shutdown or power interruption. Mechanical cooling shall be available to aid the economizer mode at any ambient. Low leak economizer dampers shall be standard with a leakage rate of 2.5 percent of nominal airflow (400 CFM/ton) at 1" wg. static pressure. Economizer Control with Dry Bulb An outdoor temperature sensor shall be included for comparing the outdoor dry bulb temperature to a locally adjustable temperature setpoint. The setpoint shall be programmed at the human interface, or remote human interface, to determine if outdoor air temperature is suitable for economizer operation. High efficiency throwaway, MERV 8 Shall be two-inch high efficiency MERV 8 media filters with average dust spot efficiency of 25-35 percent and an average arrestance in excess of 90 percent when tested in accordance with ASHRAE 52-76. Differential Pressure Gauge A factory -installed, dial -type, differential pressure gauge shall be piped to both sides of the filter to indicate status. Gauge shall maintain a +/- 5 percent accuracy within operating temperature limits of -20°F to 120°F. Gauge shall be flush -mounted with casing outer wall. Filter sections consisting of pre- and post -filters shall have a gauge for each. Unit Controller DDC microprocessor controls shall be provided to control all unit functions. The control system shall be suitable to control CV or VAV applications. The controls shall be factory -installed and mounted in the main control panel. All factory -installed controls shall be fully commissioned (run tested) at the factory. The unit shall have a Human Interface Panel with a 16 key keypad, a 2 line X 40 character clear English display as standard to provide the operator with full adjustment and display of control data functions. The unit controls shall be used as a stand-alone controller, or as part of a building management system involving multiple units. 1 The unit shall be equipped with a complete microprocessor control system. This system shall consist of temperature and pressure (thermistor and transducer) sensors, printed circuit boards (modules), and a unit mounted Humanlnterface Panel. Modules (boards) shall be individually replaceable for ease of service. All microprocessors, boards and sensors shall be factory mounted, wired and tested. The microprocessor boards shall be stand-alone DDC controls not dependent on communications with an on -site PC or a Building Management Network. The microprocessors shall be equipped with on -board diagnostics, indicating that all hardware, software and interconnecting wiring are in proper operating condition. The modules (boards) shall be protected to prevent RFI and voltage transients from affecting the board's circuits. All field wiring shall be terminated at separate, clearly marked terminal strip. Direct field wiring to the I/O boards is not acceptable. The microprocessor's memory shall be non-volatile EEPROM type requiring no battery or capacitive backup, while maintaining all data. 2 Zone sensors shall be available in several combinations with selectable features depending on sensor. 3 The Human Interface Panel's keypad display character format shall be 40 characters x 2 lines. The character font shall be 5 x 7 dot matrix plus cursor. The display shall be Supertwist Liquid Crystal Display (LCD) with blue characters on a ray/green background which provides high visibility and ease of interface. The display format shall be in clear English. Two or three digit coded displays are not acceptable. Equipment Submittal Page 8 of 25 SLC - Morningside Library 50T Ipak Repl November 11, 2021 4 The keypad shall be equipped with 16 individual touch -sensitive membrane key switches. The switches shall be divided into four separate sections and be password protected from change by unauthorized personnel. The six main menus shall be STATUS, SETPOINTS, DIAGNOSTICS, SETUP, CONFIGURATION and SERVICE MODE. BACnet Communication Interface Module Option shall provide control and monitoring of the rooftop by Tracer SC or a 3rd party building management system utilizing BACnet protocol. Unit Interrupt Rating (High Fault Short Circuit Current Rating-SCCR) An optional 65,000 Amp rating (480V) and 25,000 Amp rating (600V) shall be applied to the unit enclosure using a non -fused circuit breaker for disconnect switch purposes. Fan motors, compressors, and electric heat circuits shall be included with protective devices that will provide the elevated level of fault protection. The unit shall be marked with approved cULus markings and will adhere to cULus regulations. Factory Powered GFI Convenience Outlet A15A, 115V Ground Fault Interrupter convenience outlet shall be factory installed. It shall be wired and powered from a factory mounted transformer. Unit -mounted, non -fused disconnect with external handle shall be furnished with factory powered outlet BAYSENS119 Programmable Zone Temperature Sensor Configured as a Variable Air Volume Unit The electronic programmable sensor shall be Auto or Manual changeover with seven day programming. Programmable sensor shall have System Off, Auto and Service LCD indicators as standard. Night setback sensor shall have up to four programs per day which can be individually configured to occupied or unoccupied. Certified AHRI Performance Packaged Rooftop units cooling, heating capacities and efficiencies are rated within the scope of the Air -Conditioning, Heating & Refrigeration Institute (AHRI) Certification Program and display the AHRI Certified® mark as a visual confirmation of conformance to the certification sections of AHRI Standard 340-360 (I-P) and ANSIZ21.47 and 10 CFR Part 431 pertaining to Commercial Warm Air Furnaces. The applications in this catalog specifically excluded from the AHRI certification program are: -Ventilation modes -Heat Recovery. -Units larger than nominal 63 tons in Cooling -Evaporative Condensers Equipment Submittal Page 9 of 25 SLC - Morningside Library 50T Ipak Repl November 11, 2021 Dimensional Drawings - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak F-O O LLN 2J OE- C = , ?FE>O gz ZD onFZzWt'Wgw�WQ�jjWZWff 2 gTOW0TOO°Z T o�F-wy°xza _ ^ zWiu�iW�LLWO� _ i m rn 0 ¢ OQW 7w^B WF- I o w J LL 7 W Q 0 F d m �3 O O J UNoO W F o W 0 D WZOOSj chi U�Uw2W�>F--,o ZO W OoOg N xF= m � �V =WzZ Q�O Foa O Or '0 v �Z� Z z�NIL 2' ZO MW wmJJ0° O ° 0ZO ZN O Z -of z O _0 m0 O0 mO ~7FM Nw>jW WrOW O W zW W W m.0Wofr� O rLL �O >ZQ� Z� NM V In � M m S O M m O z z We W O F- o Z c� ¢ W N z W �co ul Equipment Submittal Page 10 of 25 SLC - Morningside Library 50T Ipak Repl November 11, 2021 Dimensional Drawings - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak 1 TYPICAL PEDESTAL AND BASE DIMENSION DRAWING TYPICAL PEDESTALAND BASE PAN DETAIL DETAIL SHIPS FIELD GASK 3, EDESTAI ROOFCURB TYPICAL ROOF CURBAND BASE PAN DETAIL DETAIL SE _IFTING LUG V LONG Equipment Submittal Page 11 of 25 SLC - Morningside Library 50T Ipak Repl November 11, 2021 Dimensional Drawings - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak ELECTRICAL / GENERAL DATA TONS GAS HEATING - PERFORMANCE Model (Tonnage): SAHLF50 (50Ton) Heating Input: Unit Operating Voltage Range: 414-506 Heating Output: Unit Primary Voltage: 460 Capacity Steps: Unit Hertz: 60 Unit Phase: 3 HEATING -GENERAL DATA Gas inlet pressure: (in w.c.) EER: 11.0 EER Gas Pipe Connection Size: IEER: 14.5 EER COMPRESSOR ELECTRIC HEATER Compressor Count, 2.00 Each Electric Heater Kw: Compressor 1 RLA: 2020 A Electric Heater Full Load Amps: Compressor2 Count 2.00 Each Compressor2 RLA 19.10A Compressor3 Count: Value not available Compressor3 RLA: Value not available SUPPLY FAN MOTOR EXHAUST / RETURN FAN MOTOR SECTION Numberof Fans: 1.00 Each Number. Value not available NumberofMotors: 1 Horsepower (Each): Exhaust/Return fan options: None Total Horsepower: 30 hp DDP 100%width Exhaust/Return Fan MotorFLA: Value not available Supply Fan Motor Full Load Amps: 36.60A Supply Fan Efficiency: 54.34 To CONDENSER FAN MOTOR FILTERS - TYPE Number. 6 Type: Horsepower (each): 1.0 Fumished: YES Condenser Fan Motor Full Load Amps (Tote[): 10.8 Number: 20 Recommended Size: 20"x25"x 2" EVAPORATIVE CONDENSER (7) PREFILTERS Pump Horsepower: N/A Fumished: Pump Full Load Amps: NIA Number. Sump Heater Full Load Amps: NIA Recommended Size: Sump HeaterkW: REFRIGERANTTYPE FINAL FILTERS - TYPE Charge Type: R-41 DA Type: Factory Charge (Circuit91): 34.3lb Fumished: Factory Charge (Circuit 02): 32.5lb Number. Recommended Size: PREFILTERS Fumished: Number. Recommended Size: Notes: 1. LOAD 1=Current of the largest motor (compressor or fan motor); LOAD 2=Sum of the currents of all remaining motors; LOAD 3 =Current of electric heaters LOAD 4=Contml Power Transformer (20AO and 24-48 ton units add 3 FL amps for wire sizing formula, 50-75 and 59 - 89 ton units add 6 FL amps) 2. For Electric Heat MCA, MOP, RDE values, calculate for both cooling and heating modes. (When determining LOADS, the compressors do not operate when the unit is in heating mode) (On 70-89 ton single source units, heating Load 4 = 12 amps on 200,230 volt units and 9 amps on 460,575 volt units) 3. If selected Max Over Cur is less than the Min ClrAmp, then select the lowest maximum fuse size which is equal to or largerthan the Min Cir Amp, provided the selected fuse size does not exceed 800 amps. 4. If the selected Recommended Dual Element fuse size is greater than the selected Max Over Cur Protection value, then select the Recommended Dual Element fuse size value to equal the Max Over Protection value. 5. Compressor KW at AHR I rating conditions of 80/67 -95 6. Refdgerant charge is an approx. value. Fore more precise value, see unit nameplate and service instructions. 7. Sump Heater is an optional feature. 8. Total Horsepower is the combined Horsepower for the Supply Fan Motors. Equipment Submittal Page 12 of 25 SLC - Morningside Library 50T Ipak Repl November 11, 2021 Fan Curve - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak Fan Details Unit Size Operating Brake 21.68 bhp Power Operating Airflow 19,000 cfm Altitude 0.00 ft Operating Static 3.940 in H2O Design Temp. 77.00 F Pressure Operating RPM 1,684 rpm ID 44 %WO 10 60 XWO 00 RPM O -240 M! ?300 M 70 76WU = 7.5 Q1 -�'20�0 i2F�tu -z-z o'F - M s0 %wo 5 �I= PM to t - PM 1400 RPM 2.5 --- -t zoo- .e .e Q. s 0 5k 10k 15k 20k airflow (cfm) Equipment Submittal Page 13 of 25 SLC - Morningside Library 50T Ipak Repi November 11, 2021 Weight, Clearance & Rigging - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak CLEARANCE I �— 72" I WI UI I Note: When 2 ormore units are to be placed side by side, the distance between the units should be increased to 150% of the recommended single unit clearance. The units should also be staggered to reduce span deflection & assure proper diffusion of exhaust air. CLEARANCE I 96" I 96" CLEARANCE RIGGING AND CLEARANCE AIR COOLED DRAWING Equipment Submittal Page 14 of 25 A SLC - Morningside Library 50T Ipak Repl Weight, Clearance & Rigging - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak Q( PL 2, X1 PL 1, X1 194 5/1 96" PL 4, X2 November 11, 2021 Center of Gravity X 17.17 ft Point load X location 1: 4.000 in Centerof Gravity Y: 4.11 it Point load X location 2: 120.000 in Point load X location 3: 236.000 in Point Load 1: 511.4 lb Point load X location 4: 332.000 in Pont Load 2: 686.0lb Point load X location 5: NIA Point Load 3: 751.6lb Point load X location 6: NIA Point Load 4: 926.3 lb Paint load X location 7: NIA Point Load 5: 991.9 lb Point load X location 8: N/A Point Load 6: 1,166.5lb Point load Y location 1: 4.000 in Point Load 7: 1,190.7lb Point load Y location 2: 87.000 in Point Load 8: 1,365.4lb Total Weight: 7,589.7 lb N otes: 1. The actual weight is stamped on the unit nameplate. 2. The weight shown represents the typical unit operating weight for the configuration selected. Estimated at +/- 10% of the nameplate weight. . 3. Design Special weights are not displayed. Any weight added through COD (Custom Order Design) will not be accounted in the +/-10% estimate 4. When 2 or mare units are to be placed side by side, the distance between the units should be increased to 150% ofthe recommended single unit clearance. The units should also be staggered to reduce span deflection & assure properdiffusion of exhaust air. PL 6, X3 PL 8, X4 PL 3, X2 PL 5, X3 CENTER OF GRAVITY AND INSTALL WEIGHT X-Y POINTS AIR COOLED DRAWING Equipment Submittal Page 15 of 25 l- SLC - Morningside Library 50T Ipak Repl November 11, 2021 Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak WARNING HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS AND FOLLOW LOCKOUT AND TAG PROCEDURES BEFORE SERVICING, INSURE THAT ALL MOTOR CAPACITORS HAVE DISCHARGED STOREDVOLTAGE. UNITS WITH VARIABLE SPEED DRIVE, REFER TO DRIVE INSTRUCTIONS FOR CAPACITOR DISCHARGE. FAILURE TO DO THE ABOVE BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY. CAUTION USE COPPER CONDUCTORS ONLYI UNITTERMINALSARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURE TO DO SO MAY CAUSE DAMAGETO THE EQUIPMENT. ATTENTION N'UTILISER QUE DES CONDUCTEURS EN CUIVREI A AVERTISSEMENT TENSION DANGEREUSE! COOPER TOUTES LES TENSIONS ET OUVRIR LES SECTIONNEURS A DISTANCE, PUIS SUIVRE LES PROCEDURES DE V ER RO U ILLAG E ET DES ETIQ U ETTES AVANT TOUTE INTERVENTION. VERIFIER QUETOUS LES CONDENSATEURS DES MOTEURS SONT DECHARGES. DANS LE CAS D'UNTTES COMPORTANT DES ENTRAINEMENTSA VITESSE VARAIBLE, SE REPORTER AUX INSTRUCTIONS DE UENTRAINEMENT POUR DECHARGER LES CONDENSATEURS. NE PAS RESPECTER CES MESURES DE PRECAUTION PEUT ENTRAINER DES BLESSURES GRAVES POUVANT ETRE MORTELLES. LES BORNES DE L'UNITE NE SONT PAS CONCUES POUR RECEVOIR D'AUTRES TYPES DE CONDUCTEURS. IMPORTANT! 00 NOT ENERGIZE UNIT UNTIL CHECK-OUT AND START-UP PROCEDURE HAS BEEN COMPLETED. L'UTILISATIONDETOUTAUTRECONDUCTEUR HEATING PEUT ENDOMMAGER L'EQUIPEMENT. SECTION �. PRECAUCI ON CONDENSER SECTION IUTILICE UNICAMENTE CONDUCTORES DE COBREI LAS TERMINALES DE LAUNIDAD NO ESTAN DISENADAS PARAACEPTAR OTROS TIPOS DE CONDUCTORES. SI NO LO HACE, PUEDE OCASIONAR DANO AL EQUIPO. DEVICE PREFIX LOCATION CODE AREA LOCATION 1 INSIDE UNIT CONTROL BOX 2 CONDENSER SECTION 3 AIR HANDLER SECTION S HEATIHGSECTION 5 EXTERNAL FIELD MOUNTED DEVICE N ote: All wiring and components shown dashed to be supplied and installed by the customer in accordance with local electrical codes. CONNECT STEAM OR HOT WATER VALVEAS ( 4 SHOWN WHEN REQUIRED �•—J 4U15 37h1 HYOROWIC HEAT 36AL BLK WHT T SPLICE SPLICE 1+1 (1 T1 T2 41 183A I _ — — 181A 1 0 ADVERTENCIA iVOLTAJE PELIGROSO! DESCONECTE TODA LA ENERGIA ELECTRICA, INCLUSO LAS DESCONEXIONES REMOTAS Y SIGALOS PROCEDIMIENTOS DE CIERREY ETIQUETADO ANTES DE PROCEDER AL SERVICIO. ASEGURESE DE QUETODOS LOS CAPACITORES DEL MOTOR HAYAN DESCARGADO EL VOLTAJEALMACENADO. PARA LAS UNIDADES CON EJE DE DIRECCION DE VELOCIDAD VARIABLE, CONSULTE LAS INSTRUCCIONES PARALA DESCARGA DEL CONDENSADOR. EL NO REALIZAR LO ANTERIORMENTE INDICADO, POORIAOCASIONAR LAIAUERTE O SERIAS LESIONES PERSONALES. CIRCUIT a2 ELECTRIC HEAT 200V1230V50 HZ UNITS ONLY 118, 1S15L2 F'T L3 I-1 CIRCUIT S1 h1AIN UNIT CONTROL 1 2 3 1TB1 OR 1S11 Ll L2 L3 Li L2 L3 L1 L2 L3 _LINE VOLTAGE _ _ LINE VOLTAGE Equipment Submittal Page 16 of 25 SLC - Morningside Library 50T Ipak Repl November 11, 2021 Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak 0 WARNING HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS AND FO LLO W LOCK OUT AND TAG PROCEDURES BEFORE SERVICING. INSURE THAT ALL MOTOR CAPACITORS HAVE DISCHARGED STORED VOLTAGE. UNITS WITH VARIABLE SPEED DRIVE, REFER TO DRIVE INSTRUCTIONS FOR CAPACITOR DISCHARGE. FAILURE TO DO THE ABOVE BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY. CAUTION USE COPPER CONDUCTORS ONLY] UNITTERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT. ATTENTION N'UTILISER QUE DES CONDUCTEURS EN CUIVREI 0 AVERTISSEMENT TENSION DANGEREUSE! COU PER TOUTES LES TENSIONS ET OUVRIR LES SECTIONNEURSADISTANCE, PUIS SUIVRE LES PROCEDURES DE VERROUILLAGE ET DES ETIQUETTESAVANT TOUTE INTERVENTION. VERIFIER QUETOUS LES CONDENSATEURS DES MOTEURS SONT DECHARGES. DANS LE CAS D'UNITES COMPORTANT DES ENTRAINEMENTSA VITESSE VARABLE, SE REPORTER AUX INSTRUCTIONS DE UENTRAINEh1ENT POUR DECHARGER LES CONDENSATEURS. NE PAS RESPECTER CES MESURES DE PRECAUTION PEUT ENTRAIN ER DES BLESSURES GRAVES POUVANT ETRE MORTELLES. LES BORNES DE L'UNITE NE SONT PAS CONCUES POUR RECEVOIR D'AUTRES TYPES DE CONDUCTEURS. UUTILISATION DETOUTAUTRE CONDUCTEUR PEUT END0MMAGER L'EQUIPEMENT. PRECAUCION IUTILICE UNICAMENTE CONDUCTORES DE COBREI LASTERMINALES DE LAUNIDAD NO ESTAN DISENADAS PARAACEPTAR OTROS TIPOS DE CO N DU CTOR ES. SI NO LO HACE, PUEDE OCASIONAR DANO AL EQUIPO. DEVICE PREFIX LOCATION CODE AREA LOCATION 1 IN SIDE UNIT CONTROL BOX 2 CONDENSER SECTION 3 AIR HANDLER SECTION 4 HEATINGSECTION 5 1 EXTERNAL FIELD MOUNTED DEVICE Note: All wiring and components shown dashed to be supplied and installed by the customer in accordance with local electrical codes. IMPORTANT! DO NOT ENERGIZE UNIT UNTIL CHECK-OUTAND START-UP PROCEDURE HAS BEEN COMPLETED. 0 ADVERTENCIA iVOLTAJE PELIGROSO! DE S CO NECTE TO DA LA EN ERG IA EL ECT R ICA, INCLUSO LAS DESCONEXIONES REMOTAS Y SIGALOS PROCEDIMIENTOS DE CIERREY ETIQUEfADO ANTES DE PROCEDER AL SERVICIO. ASEGURESEDEQUETODOS LOS CAPACITORES DEL MOTOR HAYAN DESCARGADO EL VOLTAJEALMACENADO. PARA LAS UNIDADES CON EJE DE DIRECCION DE VELOCIDAD VARIABLE, CONSULTE LAS INSTRUCCIONES PARALA DESCARGADELCONDENSADOR. EL NO REALIZAR LOANTERIORMENTE INDICADO, PODRIAOCASIONAR LA MUERTE 0 SERIAS LESIONES PERSONALES. NO - 498 - HEAT FAILURE COM- 499 - 499 - (-) 0.10 VOC 25 (603) NC - 500 - - 500 - (+) (A03) 26 I I I I I 1T131i\--I 1 85 496 12 � 2 486 497 13 3 487 498 14 I 4 : B8 499 15 J� I 5 636 600 16 I �r- 6 535 501 17 ,----� I I r 7 491 502 18 -r----�� r- 8 492 503 19 -(------�� 3 54910 ! II II II I --- --- -- - I I I I I l l l i I I I 22 REFRIG —495F802)E fNO 1--497- NCh1-497 I I I (r)0-`ADC I 22 ACTIVE t10 —504DIAGNOSTICS-505 {COMII I I 28 (805) NC — 506 J I I I I I SUPPLY VO — 501 - - J 221 FMI ^OM-502 I - J 502- 25 FAILURE O1 0.10 J � VDC 2b I (804) RC — 503 - - - 503 - (+) J (Aat) 24 VDC— 535-1 I I` 535 — 5 VDC 25 � 535 — 5 VDC 24 VDC— 535J I 26 E485 — 1+1 1�486 — (.) (Alt) 27 I� -191 — ly (A] 3) 27 I — (-) I�492 a9s — (-) - - '`493 (`) (AIS) 27 - - - - - - Equipment Submittal Page 17 of 25 SLC - Morningside Library 50T Ipak Repl November 11, 2021 Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak NOTES: aALL WIRING AND COM PON ENTSSHOWN DASHED TO BE SUPPLIED AND INSTALLED BY THE CUSTOMER IN ACCORDANCE WITH LOCAL ELECTRICAL CODES. aCUSTOMER CONNECTIONS -MAIN UNIT CONTROL (CIRCUIT 91)-ARE LOCATED IN THE CONDENSER SECTION FOR 20THRU 75 TON UNITS. aSEE CUSTOMER CONNECTION WIRE RANGE TABLE FOR ACCEPTABLE WIRE SIZES FOR CONNECTION TO MAIN UNIT TERMINAL BLOCK (1TB1/4TB2) OR DISCONNECT SWITCH (1Sl4/4Sl5). aWIRES TO THE OPTIONAL STEAM AND/ORHOTWATER HEAT VALVE ARE SUPPLIEDWITH THE UNIT. WIRE CONNECTIONS TO THE VALVE TO BE MADE BY THE CUSTOMER. a0 PTIONAL 5U57 REMOTE ZONE TEIVIP SENSOR IS USED FOR UNOCCUPIED HEATICOOL TEMP CONTROL SENSING. aWHEN 5U69 REMOTE ZONE TEMP SENSOR IS USED, REMOVE 51-1581NTERGRAL ZONE TEMP SENSOR ATTACHED TO TERMINALS S1 AND S2. aWIRES USE SHIELDED TWISTED PAIR WIRE. aUSE SHIELDED TWISTED PAIR WIRE. WRAP SHIELDS WITH TAPE TO PREVENT CONTACT WITH GROUND. 10 REMOVE JUMPER (lTB4-15 & 1TB4-16)AND INSTALL HIGH DUCT TEMP TSTAT /OR FIELD SUPPLIED DEVICE. 11 REMOVE JUMPER (1TB4-17 & 1TB4-18) WHEN FIELD SUPPLIED EXTERNALAUTO/STOP SWITCH (5S67) IS INSTALLED. 12 CHANGEOVER (5K87)AVAILABLE ONLY ON HYDRONIC HEAT UNITS OR MODULATING GAS HEAT UNITS. 13 ALARM OUTPUT SWITCHES ON ANY MANUAL RESET DIAGNOSTIC. 14 OPTIONAL HEAT MODULEAUX. TEM P (5RT16) IS USED FOR MORNING WARM-UP CONTROL ON UNITS WITH HEATING OPTION. 15 TERMINAL BLOCK lTB17 ANDASSOCIATED WIRING REQUIRED WITH GBAS (1U51) OPTION. DEMAND LIMIT RELAY (5K89) TO BE PROVIDED BY CUSTOMER. 16 VENTILATION OVERRIDE MODE CONTACTS RATED 12MA @ 24VDC MINIMUM (5K90 - 5K91 - 5K92 - 5K93 - 5K94) TO BE PROVIDED BY CUSTOMER. 17 WIRE NODES 533 & 534 REQUIRED WITH BAS/NETWORK COMM MODULE (1U54) OPTION. USE SHIELDEDTWISTED PAIR WIRE. 18 FIELD CONNECTIONS TO DRIVE VAV BOXES FULL OPEN DURING NIGHT SETBACK MODE. 19 15AFUSE REPLACEMENT IS REQUIRED FOR 50THRU 60TON -0 50 KVATRANSFORMER WITH 2O0V - 230V -460V OR 575V UNIT VOLTAGE. 20AFUSE REPLACEMENT IS REQUIRED FOR 50 THRU 60TON - 0.50 KVATRANSFORMER WITH 380V OR 415V UNIT VOLTAGE. 21 CONTACTS RATED 12 MA @ 24VDC MINIMUM. 22 CONNECT TO 24VAC CLASS 2 CIRCUITS ONLY. 23 REMOVE JUMPER WHEN OPTIONAL FIELD SUPPLIED OUTSIDEAIR SENSOR (3RT3) IS INSTALLEDAND THE UNIT DOES NOT HAVE ECONOMIZER. 24 FIELD SUPPLIEDAND INSTALLED OCCUPIED/UNOCCUPIED CONTACTS (5K86) FOR USE ON UNITS WITHOUT REMOTE PANEL WITH NIGHT SETBACK (51-158). 25 GBAS 0-5V OPTION CONNECTIONS. 26 GBAS 0-10V OPTION CONNECTIONS. 27 FOR GBAS INPUTS All-AI4, "GBAS 0-5V" REQUIRES 0-5V VDC AN D "G BAS 0-10V" REQ U IRES 0-10V DC. 2B "ACTIVE DIAGNOSTICS (BO5)"APPEARS WITH BOTH -GBAS 0-5V"AND "GBAS 0-10W. 29 SEE FUSE REPLACEMENT TABLE ON VFD PANEL FOR VFD POWER FUSES (1740, F41, F42). 30 SWITCH A53, LOCATED ON THE VFD, MUST BE SETTO -U" (OFF). Equipment Submittal Page 18 of 25 SLC - Morningside Library 50T Ipak Repl November 11, 2021 Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak FUSE REPLACEMENT TABLE CONDENSER FAN FUSE 1F1 THRU 1F6 CLASS RK5 UNIT VOLTAGE 200 230 380--_1 415 1 460 575 TIME DELAY 25A 25A 15A 15A 15A 15A CONTROL POWER FUSE CONTROL (1T1)TRANSFORMER RATING 0.25 KVA 0.30 KVA 0.50 KVA 0.75 KVA 1.00 KVA 1.50 KVA 1F7 CLASS CC -TYPE FNQ.-R 20-30TON 6.25A 6.25A — 10A 40 TO N 15A 20A -- 20A — — 50-60TON -- — 15A -- 20A — 7075TON -- -- -- -- 15A 20A ELECTRIC HEAT FUSE 4F19THRU 4F36, 4F46,47, 48 CLASS K5 60A COMPRESSOR PROTECTION FUSE 1F44 & 1F45 TYPE MTH 6A TRANSFORMER CIRCUIT FUSE I 11772THRU 1F74 TYPE FNQ-R 15A VFD PROTECTION FUSES (CLASS -T- FUSES) OPTIONALSUPPLY VFD 1F57 - 1F62, OPTIONAL EXHAUST I RETURN VFD 1F63-1F65 BELT DRIVE MOTOR 20-130 UNITS UNIT VOLTAGE 200V/6013 FUSE RATING 3HP 40A 5HP 60A 7.5HP BOA 10HP 100A 15 HP 150A 20HP 200A 25HP 225A 30 HP 300A 40HP 350A 50HP N/A 600V 230V/6O 3 600V 30A 45A 70A 90A 125A 175A 200A 250A 300A N/A 38OV15013 600V 15A 30A 45A 50A 90A IOOA 125A 150A 200A NIA 415V/5013 600V 15A 30A 45A 50A 90A 1DOA 125A 150A 200A NIA 460V/6013 600V 15A 25A 35A 45A 60A 90A 100A 125A 150A 200A 575VI6013 600V 15A 15A 25A 35A 50A 70A 60A t00A 125A 175A OPTIONAL DIRECT DRIVE MOTOR20-59 UNITS UNIT VOLTAGE FUSE RATING 3HP 5HP 7.5 HP 10 HP 15 HP 1K-1.6K RPM 15 HP 1.7K-2.4K RPM 20 HP 25 HP 30 HP 20OV160/3 600V 40A 60A BOA 100A 150A 150A 200A 225A 300A 23OVi60/3 600V 25A 45A 70A 90A 125A 125A 175A 200A 250A 460V/6013 600V 15A 25A 35A 45A 70A 60A 90A 100A 125A 575V/60/3 600V 15A 15A 25A 35A 50A 50A 70A 80A 100A OPTIONAL DIRECTMDIVE MOTOR M 60-89 TO N UNIT VOLTAGE FUSE RATING 10HP 15 HP 1K-1.6K RPM 15 HP 1.7K-2.4K RPM 20HP 30 HP 30 1K-1.6K 1.7-2.4K RPM HP RPM 40HP 50HP 2OOV160/3 600V 125A 175A 150A 200A 300A 150A 350A NIA 230V16013 600V 95A 150A 125A 175A 250A 250A 300A N/A 460V/60/3 600V 45A 70A 60A 90A 125A 125A 150A 200A 575V/60/3 600V 40A 60A 50A 70A 125A IOOA 125A 175A CUSTOMER CONNECTION WIRE RANGE NOTES: UNITS WITH MAIN POWER TERMINAL BLOCK (ALL VOLTAGES) BLOCK SIZE WIRE QTY CONNECTOR WIRE RANGE UNITS WITH MAIN POWER DISCONNECT SWITCH (ALL VOLTAGES) DISCONNECT SIZE WIRE CITY CONNECTOR WIRE RANGE A. BLOCK SIZE & DISCONNECT SIZE ARE CALCULATED BY SELECTING THE SIZE GREATER THAN OR EQUALTO 1.15 X (SUM OF UNIT LOADS). SEE UNIT LITERATURE FOR UNIT LOAD VALUES. 335AMP (1) #6-350MCM 100AMP (1) *14-1/0 760AMP (2) #4-500MGM 250AMP 840AMP (2) ;92-600MCM 400AMP (1)OR'1-BOOkcmilOR (2) 41 - 250 kcmil 600AMP (2) 250-500MGM 1000 AM P (3) 310 - 500 kcm d OPTIONAL CONVENIENCE OUTLET FUSE 1F55AND 1F56 (TIME DELAYTYPE FNQ-R FUSE) I I 20OV160/3 230V160/3 38OV15013 415V/50/3 460V/60/3 575V/60f3 12A 10A N/A N/A SA 4A Equipment Submittal Page 19 of 25 SLC - Morningside Library 50T Ipak Repl November 11, 2021 Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak A WARNING HAZARDOUS VOLTAGE! DISCONNECTALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS AND FOLLOW LOCK OUT AND TAG PROCEDURES BEFORE SERVICING. INSURETHATALL MOTOR CAPACITORS HAVE DISCHARGED STORED VOLTAGE. UNITS WITH VARIABLE SPEED DRIVE, REFER TO DRIVE INSTRUCTIONS FOR CAPACITOR DISCHARGE. FAILURE TO DO THE ABOVE BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY. CAUTION USE COPPER CONDUCTORS ONLY] UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURE TO DO SO MAY CAUSE DAMAGE TO TH E EQU IPM E NT. ATTENTION N'UTILISER QUE DES CONDUCTEURS EN CUIVREI 0 AVERTISSEMENT TENSION DANGEREUSE! COUPER TOUTES LES TENSIONS ET OUVRIR LES SECTIONNEURS A DISTANCE, PUTS SUIVRE LES PROCEDURES DE VERROUILLAGE ET DES ETIQUETTESAVANT TOUTE INTERVENTION. VERIFIER QUETOUS LES CONDENSATEURS DES MOTEURS SONT DECHARGES. DANS LE CAS D'UNITES COMPORTANT DES ENTRAINEMENTSA VITESSE VARAIBLE, SE REPORTER AUX INSTRUCTIONS DE UENTRAINEMENT POUR DECHARGER LES CONDENSATEURS. A ADVERTENCIA iVOLTAJE PELIGROSO! DESCONECTE TODA LA ENERGIA ELECTRICA, INCLUSO LAS DESCONEXIONES REMOTAS Y SIGALOS PROCEDIMIENTOS DE CIERRE Y ETIQUETADO ANTES DE PROCEDERAL SERVICIO. ASEGURESEDEQUETODOS LOS CAPACITORES DEL MOTOR HAYAN DESCARGADO ELVOLTAJEALMACENADO. PARA LAS UN IDADES CON EJE DE DIRECCION DE VELOCIDAD VARIABLE, CONSULTE LAS INSTRUCCIONES PARALA DESCARGA DEL CON DENSADOR. NE PAS RESPECTER CES MESURES DE EL NO REALIZAR LOANTERIORMENTE PRECAUTION PEUT ENTRAINER DES INDICADO, PODRIAOCASIONAR LA MUERTE BLESSURES GRAVES POUVANT ETRE 0 SERIAS LESIONES PERSONALES. MORTELLES. IMPORTANT! DO NOT ENERGIZE UNIT UNTIL CHECK-OUT AND START-UP PROCEDURE HAS BEEN COMPLETED. LES BORNES DE L'UNITE NE SONT PAS CONCUES POUR RECEVOIR D'AUTRESTYPES DE CON DU CTEU RS. L'UTILISATION DE TOUT AUTRE CONDUCTEU R PEUT ENDOMMAGER UEQUIPEMENT. PRECAUCION IUTILICE UNICAMENTE CONDUCTORES DE COBREI LASTERMINALES DE LAUNIDAD NO ESTAN DISENADAS PARAACEPTAR OTROS TIPOS DE CONDUCTORES. SI NO LO HACE, PUEDE OCASIONAR DANOAL EQUIPO. DEVICE PREFIX LOCATION CODE AREA LOCATION 1 IN SIDE UNIT CONTROL BOX 2 CONDENSER SECTION 3 AIR HANDLER SECTION 4 HEATING SECTION 5 1 EXTERNAL FIELD MOUNTED DEVICE Note: Al wiring and components shown dashed to be supplied and installed by the customer in accordance with local electrical codes. 5571 5S67 EMERGENCY EXTERNAL AUTO/STOP STOP SWITCH VAV ZONE I I SWITCH RESET OPTION r - -0�o- - 1 5U61 10 27 I I i 11�2- -I RESET I r� L J I TEMP I r - - SENSOR 435 431 434 438 I I L 425 424 I i-.---------� I I 5U57�------_----- 1TB4 REMOTE 1 1408 - rr'- ---- -- 1 408 418 2 ZONE 2 409 - 2 409 424 13 NL3 41414 _- --I J-!T SENSOR 4 412 4 35 15 0 5411 431 16Srr---r6 411 434 17 _„ Ii JIII I �----I I 413 438 1e— I— 7----I—.L� r---- r- 6 414 437 19---l----I- 9 415 537 20 I 10 416 538 21 I I 11 425 436 22 I I I - - - - - - I J - SU69 I 5668 I REMOTE I ZONE PANEL I 438 I r Z SENSORIP I I I __ I I 437 ZONE i I ' S �� I--409- I 2 COMMON I I L 5 s �° I I I I I I I I OCCUPIED! �(21 I l l'-410-- 3SACSP I U"'CCU S ` 4 HEAT? -413 -I I I —412- 4M- III COOLS 1-414 -6G SYS ON 9 1-416 —j 417- O - J 1-3 �413--7HEAT SERVCE10 1 �-dI`-8 -) -5Ufi6 -417 REMOTE J1-2 HUMAN- Si GNDit—LOOOH Ti -! - S2 COh9A (1) 12 -418-415-- INTERFACE L L _ 403 - -I J21 (*) MODULE ! I I 116- - 10 SERVICE I I 24 VAC 14 -403 I I L - 436 - - J2.2 (-) J2-3 5U58 SU59 REFTE .EL PANELREMOTS EARTH WRH F1SB GROUND - Equipment Submittal Page 20 of 25 SLC - Morningside Library 50T Ipak Repl November 11, 2021 Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak 0 WARNING HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS AND FOLLOW LOCK OUT AND TAG PROCEDURES BEFORE SERVICING. INSURE THAT ALL MOTOR CAPACITORS HAVE DISCHARGED STORED VOLTAGE. UNITS WITH VARIABLE SPEED DRIVE, REFER TO DRIVE INSTRUCTIONS FOR CAPACITOR DISCHARGE. FAILURE TO DO THE ABOVE BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY. CAUTION USE COPPER CONDUCTORS ONLYI UN IT T E RM INALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURETO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT. ATTENTION N'UTILISER QUE DES CONDUCTEURS EN CUIVREI 0 AVERTISSEMENT TENSION DANGEREUSE! COUPER TOUTES LES TENSIONS ET OUVRIR LES SECTION NEURS AD ISTAN CE, PUTS SUIVRE LES PROCEDURES DE VERROUILLAGE ET DES ETIQUETTESAVANT TOUTE INTERVENTION. VERIFIER QUETOUS LES CONDENSATEURS DES MOTEURS SONT DECHARGES. DANS LE CAS D'UNITES COMPORTANT DES ENTRAINEMENTSA VITESSE VARABLE, SE REPORTER AUX INSTRUCTIONS DE UENTRAINEMENT POUR DECHARGER LES CONDENSATEURS. NE PAS RESPECTER CES MESURES DE PRECAUTION PEUT ENTRAIN ER DES BLESSURES GRAVES POUVANT ETRE M 0 RT ELLES. LES BORNES DE L'UNITE NE SONT PAS CONCUES POUR RECEVOIR D'AUTRES TYPES DE CONDUCTEURS. L'UTILISATION DE TOUT AUTRE CONDUCTEU R PEUT ENDOMh+E RECAUCION IUTILICE UNICCAMENTE CONDUCTORES DE COBREI LAS TERMINALES DE LAUNIDAD NO ESTAN DISENADAS PARAACEPTAR OTROS TIPOS DE CONDUCTORES. SI NO LO HACE, PUEDE OCASIONAR DANO AL EQUIPO. DEVICE PREFIX LOCATION CODE AREA LOCATICH , IN SIDE UNIT CONTROL BOX 2 CONDENSER SECTION 3 AIR HANDLER SECTION 4 HEATING SECTION 5 EXTERNAL FIELD MOUNTED DEVICE Note: All wiring and components shown dashed to be supplied and installed by the customer in accordance with local electrical codes. IMPORTANT! DO NOT ENERGIZE UNIT UNTIL CHECK-0 UT API D START-UP PROCEDURE HAS BEEN COMPLETED. 0 ADVERTENCIA iVOLTAJE PELIGROSO! DESCONECTE TODA LA EN ERGIA ELECTRICA, INCLUSO LAS DESCONMONES REMOTAS Y SIGALOS PROCEDIMIENTOS DE CIERREY ETIQUETADO ANTES DE PROCEDERAL SERVICIO. ASEGURESE DE QUETODOS LOS CAPACri ORES DEL MOTOR HAYAN DESCARGADO ELVOLTAJEALMACENADO. PARA LAS UN IDADES CON EJE DE DIRECCION DE VELOCIDAD VARIABLE, CONSULTE LAS INSTRUCCIONES PARALA DESCARGA DEL CONDENSADOR. EL NO REALIZAR LOANTERIORMENTE INDICADO, PODRIAOCASIONAR LAMUERTE 0 SERIAS LESIONES PERSONALES. 5K90 VENTILATION — 5RTtfi — OVERRIDE 5K89 5K92 MODEACONTACTS OEMMJD VENTILATION HEAT 76 MAN C15 OVERRIDE t6 MODULE I 5— LA I 1 CONLACFS I ,,,DOE C CONTACTS AUX TEMP VOV IERRJDEJ 16 L J r T rY z, I I I I I 1400E D CONTACTS � r L J I f �� 14 I I 527 524 —}-- L j r I 469 490 —!— I — 527 52— 4715 4iE L 5� St0� � I I I I I I I I I I I I I I I I I is I I I I ,ras I I I I -----I— 1 469 475 11 ------i— 2 490 476 13 -------r 3 523 528 14 I I — — — — — — — — — — — — — — — 4 524 529 15— — — — — — — — — — — — — - I — — — — — — — — — I_ 5 525 530 16---------------� — — — — — — — — — — 6 526 531 17— — — — — — — — — — — — 7 527 532 18 — 8 549 533 19-------- r----- 9 550 534 20 ------ I ------ 10 427 443 21 23 r 11 426 444 22 I I I I I I I I I I I I I I I I I I I I I I I I I I 525 52I6 I 427 426 443 I 531 J �� 444 I I I 532 � I I I I I I L 1 J 5K91 tfi z3 � r L—I I I I VENTILATION I I I OVERRIDE I I 3RT3 MODE B CONTACTS I I OPTIONAL I I 12 5K87 I I I I L� I OUTSIDE CHANGEOVER AIR I Z' CONTACTS I I I vErrr'LATT 18 SENSOR I I I OVERR _ _ I h10DE ECONTACTfs I I I I I I 5U70 I I REMOTE 534 J533 MINIMUM I I POSITION I I POTENTIOMETER TRACER I � — 549 I— WHTI COMMUNICATIONS 17 II `— Equipment Submittal Page 21 of 25 SLC - Morningside Library 50T Ipak Repl November 11, 2021 Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak A WARNING HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS AND FOLLOW LOCK OUT AND TAG PROCEDURES BEFORE SERVICING. IN SU R E THAT ALL M OTO R CAPACITORS HAVE DISCHARGED STORED VOLTAGE. UNITS WITH VARIABLE SPEED DRIVE, REFER TO DRIVE INSTRUCTIONS FOR CAPACITOR DISCHARGE. FAILURE TO DO THE ABOVE BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY. CAUTION USE COPPER CONDUCTORS ONLY] UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT. ATTENTION N'UTILISER QUE DES CONDUCTEURS EN CUIVRE! Zh AVERTISSEMENT TENSION DANGEREUSE! COU PER TOUTES LES TENSIONS ET OUVRIR LES SECTIONNEURSADISTANCE, PUIS SUIVRE LES PROCEDURES DE VERROUILLAGE ET DES ETIQUETTESAVANT TOUTE INTERVENTION. VERIFIER QUETOUS LES CONDENSATEURS DES MOTEURS SONT DECHARGES. DANS LE CAS D'UNITES COMPORTANT DES ENTRAINEMENTSA VITESSE VARAIBLE, SE REPORTER AUX INSTRUCTIONS DE UENTRAINEMENT POUR DECHARGER LES CONDENSATEURS. FIE PAS RESPECTER CES MESURES DE PRECAUTION PEUT ENTRAIN ER DES BLESSURES GRAVES POUVANT ETRE MORTELLES. LES BORNES DE L'UNITE NE SONT PAS CONCUES POUR RECEVOIR D'AUTRES TYPES DE CONDUCTEURS. L'UTILISATION DE TOUT AUTRE CONDUCTEUR PELT ENDOMMAGER L'EQUIPEMENT. PRECAUCION IUTILICE UNICAMENTE CONDUCTORES DE COBREI LASTERMINALES DE LAUNIDAD NO ESTAN DISENADAS PARAACEPTAR OTROS TIPOS DE CONDUCTORES. SI NO LO HACE, PUEDE OCASIONAR DANOAL EQUIPO. DEVICE PREFIX LOCATION CODE AREA LOCATION 1 INSIDE UNIT CONTROL BOX 2 CONDENSER SECTION 3 AIR HANDLER SECTION 4 HEATING SECTION 5 EXTERNAL FIELD MOUNTED DEVICE Note: All wiring and components shown dashed to be supplied and installed by the customer in accordance with local electrical codes. IMPORTANT! DO NOT ENERGIZE UNIT UNTIL CHECK-OUT AN D START-UP PROCEDURE HAS BEEN COMPLETED. A° ADVERTENCIA iVOLTAJE PELIGROSO! DES CO N ECTE TO DA LA EN ERG IA ELECT R ICA, INCLUSO LAS DESCONEXIONES REMOTAS Y SIGALOS PROCEDIMIENTOS DE CIERREY ETIQUETADO ANTES DE PROCEDERAL SERVICIO. ASEGURESE DE QUE TODOS LOS CAPACITORES DEL MOTOR HAYAN DESCARGADO EL VO LTAJE ALMACENADO. PARA LAS UN IDADES CON EJE DE DIRECCION DE VELOCIDAD VARIABLE, CONSULTE LAS INSTRUCCIONES PARALA DESCARGA DEL CONDENSADOR. EL NO REALIZAR LOANTERIORMENTE INDICADO, PODRIAOCASIONAR LAMUERTE 0 SERIAS LESIONES PERSONALES. NO - 614 - 22 HUMIDIFICATION NC - 615 - OPA - 616 - �) 13 ALARM NO - 448 I OUTPUT ;CM - 4,19 - D I 22 (24 VAC ]AAX) NC - 450 - 1 B VAV - 445 -RELAYAY:OA1 - 446 -22 24 VAC MAX{NO NC - 447 - - I I I I 1TS16 I I - - - - - 1 507 445 12 - J I 2 508 446 13 -=J F -- - - - - - 3 509 447 14 4 541 448 15 ---- 5 542 449 16 - -J I 6 543 450 17 - _ J ---- 7 544 614 18 ----- I I (---- 8 545 615 19 - I i --- 9 546 616 20 - - - - I 10 612 21 11 613 22 I I I I I I I I I I I I I 613 = 5U10E I I (�) SPACE I 612 (+) iUMIDITYSENSOR I I I l E- 546 —PIG HEATMODE RELAY OUTPUT - 545 — COPAl (HYDRONICHEATOR MODULATING 22 - 544 —NO Jr GAS HEAT) III I �-- - - 543 — NG VO 542 — COM RELAY —NO OUTPUT I I L--509 —NC I1,- - - 508 — COIN t DIRTY 22 -- 507 —NO I (BOX) 25 I 506 (-) 0-10VDC (AO1) �26 Equipment Submittal Page 22 of 25 SLC - Morningside Library 50T Ipak Repl November 11, 2021 Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak DANFOSS VARIABLE FREQUENCY DRIVE PROGRAMMING PARAMETERS MENU PARAMETER DESCRIPTION SETTING 1-21 MOTOR POWER SET ONLY FOR APPLICATIONS USING 3HP HIGH EFFICIENCY MOTORS LOAD/MOTOR 1-22 MOTOR VOLTAGE SET ONLY FOR 200/230V60HZ 380/415V 50HZ APPLICATIONS 1-24 MOTOR CURRENT SET BASED ON MOTOR NAMEPLATE 1-25 MOTOR NOMINALSPEED 1800RPM 1-73 FLYING START ENABLED BRAKES 2-01 DC BRAKE CURRENT 0% REFERENCE/ 3-15 REFERENCE 1 SOURCE ANALOG INPUT 53 a RAMPS 3-41 IRAMP 1 RAMP UPTIME 30 SECONDS 3-42 IRAMP 1 RAMP DOWN TIME 30SECONDS LIMITS/ 4-12 MOTOR SPEED LOW LIMIT 122HZ WARNINGS 4-18 CURRENT LIMIT 100%RATED CURRENT DIGITAL 540[0] FUNCTION RELAY 1 NO ALARM IN/OUT 5-40[1] FUNCTION RELAY 2 IRUNNING 14-01 SWITCHING FREQUENCY 4.5KHZ SPECIAL 1412 FUNCTION AT MAINS IMBALANCE DERATE FUNCTIONS 14-20 RESETMODE AUTOMATIC RESET X3 14E0 FUNCTION AT OVER TEMPERATURE DERATE Equipment Submittal Page 23 of 25 SLC - Morningside Library 50T Ipak Repl November 11, 2021 Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 50T Ipak �E�IeRf�tl[Btl�R���e�u, RAYSEN119 -ZONE SENSOR PROGRAMMABLE SENSOR TEST Equipment Submittal Page 24 of 25 SLC - Morningside Library 50T Ipak Repl November 11, 2021 Field Installed Options - Part/Order Number Summary This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the 'ob. Product Family - Commercial Rooftop Air Conditioning Units (Midranael Item Tag(s) Qty Description Model Number Al 50T Ipak 1 20-75 Ton Packaged Industrial Rooftop SAHLF5040*00CZHD6El l B*W**H*BA**6T*M86 Field Installed Option Description Part/Ordering Number Programmable zone sensor Roof Curb Equipment Submittal Page 25 of 25 4.5" O 0.5' I S/A 5.5" 71 2" END VIEW L6.5"O0D ID---�--gFLANGE 2600 Industrial Ave. 3 Fort Pierce, FL 34946 SalesOCurbsfast.com 1-800-551-6606 NOTES: 1. 16 GA. GALV. STEEL CONSTRUCTION 2. LIFTING LUGS INCLUDED 3. SHIPPED FULLY ASSEMBLED 4. FULLY INSULATED 347.875" O 346.0625" I 2.375" 194.25' 29.9375"�3" � 7' .625"A 9r.. 1 95'; SIDE VIEW 42.125 I 1 150.75 341.875"ID 347.875" OD FLANGE Curb Adapters & Curbs, LLC