HomeMy WebLinkAboutEngineeringCONTRACTOR: The Porch F .-- , ,s-y, LLC. DES-1 CRITERIA: 1. The 5th Edition (2014) Florida Building Code, specifically Chapter 16 Structural Design, Chapter 20 Aluminum, and Chapter 23 Wood. 2. AA ASM 35 and Specifications for Aluminum Structures, Part 1-A of the Aluminum Design Manual prepared by The Aluminum Association, Inc. Washington, D.C., 2010 Edition and the Guide to Aluminum Construction in high wind areas, 2010. 3. ASCE 7-10. Wind Loads 1. Building Occupancy Category, Paragraph 1604.5 and Table 1604.5: Risk Category 1. 2. Basic Wind Speed, Figure 1609C, State of Florida Debris Region & Basic Wind Speed, Paragraph 1609.3.1 and Table 1609.3.1 Equivalent Basic Wind Speed: VuLT =150 MPH, VASD =116 MPH 3. Exposure Category, Paragraph 1609.4.3: C 4. Screen Roof Enclosure Table 2002.4 Foundation Design Existing concrete. No additional concrete footing or slab is required to resist the loads imposed by the proposed Construction if the existing slab is a minimum 4" thick with an 8" x 8" thickened slab edge and in sound condition, free from structural cracking, spalling, or other deterioration. Specifications The following specifications are applicable to this project: 1. Where concrete specifications are required, whether in the screen enclosure scope or not, by one or more regulatory agency, the following specifications are applicable: a. Concrete shall conform to ASTM C94 for the following components: i. Portland Cement Type I, ASTM C 150 ii. Aggregates - Large Aggregate 3/4" max - ASTM C 33 iii. Air entraining +/- 1% - ASTM C 260 iv.Water reducing agent - ASTM C 494 v. Clean Potable water vi. Other admixtures not permitted b. Metal accessories shall conform to: i. Reinforcing Bars - ASTM A615, grade 60 ii. Welded wire fabric - ASTM A185 c. Concrete slump at discharge chute not less than 3" or more than 5". Water added after batching is not permitted. d. Prepare and place concrete per American Concrete Institute Manual of Standard Practice, Parts 1, 2, and 3 including hot weather recommendations. e. Moist cure or polyethylene curing permitted. f. Prior to placing concrete, treat the entire subsurface area for termites in compliance with the FBC. g. Concrete shall be placed over a polyethylene vapor barrier. h. All aluminum components embedded within concrete shall be coated with a bituminous paint or epoxy. 2. Aluminum extrusions shall be 6005 T5 Alloy 3. Fasteners are required to be corrosion resistant, minimum SAE Grade 2 or better zinc plated to ASTM B633, or coated stainless steel series "300", or uncoated stainless steel series "400". 4. All Self Mating Beam Sections are to be stitched with either #14 screws 6" from ends and 24" center to center or #12 screws 6" from ends and 12" center to center. 5. Screened enclosures containing swimming pools shall comply with the applicable requirements of FBC R4501.17 Residential Swimming Barrier requirements. 6. Screen material shall be 18/14 screen. unless approved by Suncoast Aluminum Engineering, LLC. 7. Door location shall be determined by contractor in the field. 8. When installing pavers over concrete slab or footing which are supporting aluminum members, such as continuous screen tracks or upright, the pavers must be bonded to the concrete with an epoxy, thinset, or 3,000 PSI grout to ensure full positive contact with concrete. 9. All flashing and waterproofing shall be provided by the contractor. 10. Use of these plans acknowledges and accepts a limit of liability not to exceed design and engineering fee. WIND SP' _ • 4ND EXPOSURE HAVE AAI �q BEEN DETERMINED USING THE ADVANCED �ylt�Fli��� P� ��P��RS kI IAMB TECHNOLOGY COUNCIL'S WEBSITE File c® AND GOOGLE EARTHS THE HESPOP�SI6IIf�`(OP ial m �-- 9•-6-------- F C001 RAOTOR OF WiM THESE PLANNS A'ND ALL FROFOSED ORK ARE SUBJECT TO ANY CORRECTIONS REQUIRED BY MELD INSPECTORS THAT MAY BE RECEM RY.I'N ORDER- TO. COP►9PW W[TH NLL A?PLICA9"ME CODES." 1(9 ST. LUCIE COU-N.T'v n LLD7? ?G npik-SIG,_ T _UVIEVI D -0H C ti �.t ivCP, RE 1 IE iZ' %� / DATE PLANS A:ND PERMIT MIST BE KEPT ON JOD OR NO ENISPECCTION WILL BE MADE. iX2 TYP X2X Z2X2 2X2 2X2 2X2 2X2 2X2 2X2 2X2 2X2 2X2 2X2 ranNtoN N N2X2 !/�2_m A-2 N 2X2 2X2 2X2 2X2 A-2 2X2 lYP A-3 d9•-A• --_-- - - - - - - tX2 TYP ---_ m � N 2X3 ryaj Ny 213 N( 2X3 4U) 2X3 TYP NU 2X3 2X3 A-4 7-0• A-3 7-0• A-2 7•-0• A-2 7-0• i-0• 7-0• o�:J 0 10 1 ?— ; o���o ,,/// pFOFEAO;RL�S�L���\\ � ' OLLJ ui V Lii a a: I 'N a wS I U- C¢7Q z� = W ¢ ca 2X6SMB lW z N z nV Z W ¢ W I Wz �z I m LLIU I Z =7 I 2X6 — 1 W v~i LL H LL I- • nr I �Ilk c G I N N I X I� sMe Z_ U .N \ J = azWE16 � lu m g g iii QW W Ol 01 W Z !an u U Q N N Z 0 ::) Z in W .fOiu�LL LL A-3 N N W Wz v)aof 15 Ow W � a I 2 m rn OoCCr�i ti. i9NO LLLL DRAWN BY TP DATE DRAWN 05/02/17 REVISION SHEET NO: Roof Type Roof Type: HALF MANSARD A-1 N ALUMINUM MEMBERS DBUr ')NS 2 x 2: 2" x 2" x 0.046" 2 x 3: 2" x 3" x 0.050" 2 x 4: 2" x 4" x 0.050" 2x5: 2"x5"x0.050" OPEN BACK SECTIONS 1x2: 1"x2"xO.040" I x 3: 1"x 3" x 0.045" SNAP SECTIONS 2 x 2 Snap: 2" x 2" x 0.045" 2 x 3 Snap: 2" x 3" x 0.050" 2 x 4 Snap: 2" x 4" x 0.045" SELF MATING (SMB) 2 x 4 SMB: 2" x 4" x 0.044" x 0.100" 2 x 5 SMB: 2" x 5" x 0.050" x 0.100" 2 x 6 SMB: 2" x 6" x 0.050" x 0.120" 2x7SMB: 2" x 7" x 0.057" x 0. 120" 2 x 8 SMB: 2" x 8" x 0.072" x 0.124" 2 x 9 SMB: 2" x 9" x 0.072" x 0.124" 2 x 10 SMB: 2" x 10" x 0.092" x 0.398" MINIMUM FASTENER EDGE DISTANCE: 1/2" MINIMUM FASTENER SPACING: 3/4" CONCRETE SCREW ANCHOR: SIMPSON TITEN HD OR EQUIVALENT SHEET METAL SCREWS (SMS): IT W / BUILDEX OR EQUIVALENT MEMBER SIZE EDGE "C" 2X4 yv 2X5 1" 2X6-2X10 1Y" EAVE RAIL (SEE A-1 FOR SIZE) INTERNALLY SCREW THRU BEAM W/ (3) #10 x 1 1/7' SMS V x FASTEN TO EAVE RAIL W/ #10 x 1 1/2" SMS W FROM UPRIGHT & 24" O.C. (1)1/2" DIA. x 21/2" THRU BOLT W/ NYLOCK JAM NUT - IN LIEU OF NYLOCK JAM NUT, JAM NUT W/THREADLOCKER MAY BE USED INSTALLATION REQUIREMENTS: BOLT IS TO BE INSTALLED AS TO NOT DAMAGE BASE MATERIAL DO NO OVER TIGHTEN. PATENT PENDING Gm 1/9 x 2" x 2" EXTRUDED ANGLE 5052 H-32 ALLOY EA SIDE V x 7' O.B. BASE PLATE -TYP . • . •. , 1114. MIN CONC 21/4' MIN CONC < ANCHOR EMBEDMENT :ANCHOR EMBEDMENT 2 A MIN-4 v 5d MIN EDGE DISTANCE FROM SLAB / FOOTING •a v •. EXTERIOR OF COLUMN TO SEE PLAN c " OUTSIDE EDGE OF SLAB SIDE VIEW (1)1/2" DIA. THRU BOLTw/NYLOCK JAM NUT - IN LIEU OF NYLOCK JAM NUT, JAM NUTw/THREADLOCKER (1) 3/8" DIA. CONCRETE t MAY BE USED SCREWANCHORS ,, TIGHTEN TO CONTACT -DO NOT (21/4" CONC. EMBED) �� OVERTIGHTEN V x 2" BASE PLATE ANCHORED TO a a, , • v '�" a CONC W/ 1/4" CONCRETE SCREW ANCHOR (MIN. 1 1/4" EMBED) SLAB /FOOTING "'' a� a} 6" MAX EACH SIDE OF POST AND SEE PLAN ao Q; •. ,n 24" O.C. MAX FRONT VIEW B 2" x 4" OR LARGER UPRIGHT TO CONCRETE DETAIL A_2 SCALE: NTS 2"x SMB BEAM NOTCHED OVER UPRIGHT Tx PURLINS ATTACHED TO (SEE A-1 FOR SIZE) BEAM w/MIN (4) #10 x 1 1/7' SMS PLACE WASHER UNDER SCREW IN GUSSET CORNER 2" x SMB UPRIGHT (SEE A-1 FOR SIZE) UPRIGHT TO BEAM CONNECTION A-2 SCALE: NTS 3116" 5052-H32 GUSSET 1 1/4" NOTE: SEE CALL -OUT BELOW FOR # OF SCREWS. SCREWS SHOWN FOR ILLUSTRATIVE PURPOSES ONLY. DO NOT COUNT SCREWS ON DRAWING. #14 SMS @ 1 1/4" O.C. r(20 TOTAL) TYP NOTES: 1. GUSSET DIMENSIONS ARE MINIMUM (2) REQ'D - (1) EA SIDE OF BEAM - MAY BE INTERNAL OR EXTERNAL 2. AS BEAM SIZE CHANGES, ADD OR SUBTRACT SCREWS TO MAINTAIN 1 114" C/C SPACING. 3. GUSSET LENGTHS REMAIN CONSTANT, WIDTHS CHANGE TO MATCH BEAM SIZE. 21/2" x 1/8" x (GIRT OR PURLIN WIDTH + 112" x BEAM DEPTH OR UPRIGHT DEPTH -1 r7j ALUM BACKING PLATE 6063-T6 ALUMNINUM CHAIR RAIL MEMBER- File Copy (4) #10 x 1 1r2" SMS INTO, SCREW BOSSES . a ui .1 cr LLC, ¢ _ o Z < O ? - I U1 Qv: O V /111111�� I PROFESSIONAL SEAL . OR SELF -MATING BEAM C PURLIN OR GIRT TO BEAM OR POST DETAIL A_2 SCALE: NTS 2" x 2" 1"x 2" x 0.W' OPEN BACK FASTEN TO EAVE RAIL W/ #10 x 1 1/2" SMS SPACED 3" FROM UPRIGHT & @ 24" O.C. x PURLIN 2" x 2" x 1/8" x 3" LONG ALUM ANGLE EACH SIDE UP UPRIGHT W/ (2) #12 x 3/4" SMS INTO PURLIN (2) #12 x 3/4" SMS INTO 2" x 2" (2) #12 x 314" SMS INTO UPRIGHT (2) #12 x 3/4" SMS INTO V x 2" F SLOPED PURLIN CONNECTION DETAIL A_2 SCALE: NTS ❑ 1 OV Li; C Ld a z W a m m Iz IL ILL�w Z� z z LL C)m amin. 2 W Z Lnm Z Z Z Z W Q W Wz �z Wu u O'a Z Lu2 xu V W t; Z_ 1 J - Q z Z oo i I— zoom ILmO� � H QLu W . Of T LU mm �y z i O u i U p p Q N N I ( � C 1Z . J Z wW J Q LA US PdV� � N W I= F O w W Z_ Q 07 D_ U W Hmw- d' w a OWo n = m rn O Oo� d C) N LL LL TP DATE DRAWN 05/02/17 REVISION L\ SHEET NO: A-2 }�jT � ��"' 6"WIDE x 0.126''Z'BRACKET NOTE: 1/8"S.S. CABLE r@ EACH BEAM ATTACHED TO (2) 3/91 DIA. x 4" LAG SCREWS FOR 1/8 x 6 x 1 1/4 A36 GALV.FASCIA W/ 3/8" x 3" LAGS (3SPANS PER BRACKET) AND (1)3/8"x3" GREATER THAN 30'-0" STEEL CLIP W/ (2) 3/8" DIA x 2 3!4"EMBEDMENTLAG @ 24"O.C. AT GUTTER LAG CONCRETE SCREW(1)3l8"DIA.x4' x 2"x 0.044"OPEN BACK SCREW INTO EXISTING OVERHANG FRAMING ANCHOR1" IW/ (2) #10 x 21/2" SMS THRU BEAM INTO SCREW BOSSES OR RAFTER TAIL DBL. COMPSLEEVES IdS wL(1)#10x11/2'SMS6' N � 1-2"FROMBEAM AND24"O.C. " O�R MATING SLAB /FOOTING ELEMENT SEE PLAN • • 1/8" S.S. CABLE • • CONTRACTOR TO VERIFY Q 2"x4"FASCIA-IFLESS 1114'x5518"xlie' fY W THAN 2" x 4" FASCIA, 2" x 4' ALUM FLAT BAR 0 1/8"x2"x2"x2"ALUM • •• SUB FASCIA SHALL BE 6063-T6 ALUMINUM ULLn ANGLE W/ (4) #14 x 3!4" 5" SUPER PLACED OVER, LENGTHEN a W d SMS EACH FLANGE SIDE OF BEAM GUTTER LAG SCREWS TO FULLY I= Q c g EACH PENETRATE SUB FASCIA. IF OTHER FASCIAADD 2" x SLAB/FOOTER O C7 z 0.062" BACKING PLATE ON , 4" PT FASCIA w/ 1/2" LAG MID DEPTH m Q m INSIDE OF GUTTER BOLTS -1 1/2" INTO TRUSS +' W a 21/8" x 1 118" x .062" (MIN.) TAILS - COUNTERSINK rb' m c W Z z z z m ALUM RECEIVING CHANNEL FLUSH. WHEN INSTALLING "� W z z W/ MIN. (2) #12 x 3/4" SMS 1I2" LAG SCREWS, ffi 0 W u o w PRE -DRILL w/ 3/8" DRILL TO Z _ :3PREVENT SPLITTING. W y (2) 3/8" DIA. x 3" EMBED_�v SLAB / FOOTING CONCRETE SCREWANCHOR SEE PLAN D C7 GUTTER BRACE & MATING ELEMENT ATTACHMENT DETAIL H-1 Z o A-3 SCALE: NTS CABLE CONNECTIONS AT FOUNDATION J F A-3 SCALE: NTS J fn s F N Z o- Zmo°D �-rimog Vi N Q ui W s T -p u, �"mm O W z U "-..... U ~ n i J GUSSET PLATE SELF MATING 14 N 6 Z PER E-SERIES BEAM = Z J o N W ."'i u � 4" PURLIN MAX (9) #14 x 3/4 SMS 1/8" PLATE ON 45° ANGLE - "~ WOOD: CONTRACTOR TO INSTALL 6063-T6 ALUMINUM E #10 x 3" WOOD SCREWS, 6" (2) #14 x 2" SMS THRU BRACE r N FROM GIRT & @ 12" O.C. INTO BEAM THRU GUSSET s J W CONC: PLATE J fY I-- 0 1/4" DIA. x 3" CONCRETE • • • 0 ; w SCREW ANCHOR, 6" DETAIL#2 Z FROM GRT&@24"O.C. • / — W a �a-C-) 1 (4) #10 x 1 1/2" INTO W SCREW BOSS . OLu Z W a _ EYE BOLT FOR CABLE TENSION i 2 0] rn O OMM CC = — d C�iNOLL CONTRACTOR SHALL RUN DRAWN BY 2" OR 2" X 3" HOLLOW kkW1 1/4"THRU BOLT TO ATTACHPERIMETER FRAMING TP ECTION GIRT NYLON WASHER & STAINLESS STEEL NUT DATE DRAWN 05/02/17 xr' REVISION 1 1!2" x 5" x 1'6' (4) #12 EA MEMBER 1 5052-H32 PLATE DETAIL #1 0 SHEET NO: C-1 1X2 TO HOST STRUCTURE DETAIL H-3 ROOF BRACING CONNECTION DETAIL H-2 CABLE CONNECTION AT CORNER A-3 SCALE: NTS A-� SCALE: NTS A-3 SCALE: NTS A-3 1/8" x 2" x 2•' EXTRUDED ANGLE 5052 H-32 ALLOY SLAB / FOOTING SEE PLAN SIDE VIEW (1) 3/8" DIA. CONCRETE SCREWANCHORS (21/4" CONC. EMBED) #14 x 3/4"SMS "0 DJ x2"DJ 1" x 2" BASE PLATE ` ANCHORED TO CONC W/ 1/4•' CONCRETE SCREWANCHOR d (MIN. 1 1X' EMBED) n a d 6" MAX EACH SIDE OF POST AND 24" O.C. MAX FRONT VIEW DJ-1 DOOR JAMB TO CONCRETE DETAIL A,,,4 SCALE: NTS ��1�IIIIrI�/ le Cop ✓�� ��. LL = a' ' 0 • L o NL< o z PROFESWOfNi4SEAL n a c C. ❑ C OC Ld c 0 ui o. C CL n Lu zg LL ¢� O = c - �wm Qm u Lu UJN� = z z Z Z W W cQc LLJ z G z - z uj u = u W in ~LL i C u u M Z ., C V N o G J u J J s Q z col g k Zoom s 1"x2"O.B. FASTENEDTO CORNER LL N L Q W , N N z Al IPOSTW/#12x11/2"SMSAT5'FROM TOP & BOTTOM RAILS. TYPICALLY @ m m 0 U Z ¢ N ! 24" O.C. ,^� Z o f 1 1 Z zs:5J 1/8" x 2•' x 2" EXTRUDED ANGLE 5052 V) W ti u CORNER POST ! H-32 ALLOY EA CORNER W/ (2) #14 x 2' [ [ [ SMS INTO POST & (1) 31W DIA i 6„ CONCRETE SCREW ANCHOR INTO CONCRETE [ (2) #10 x 1 1/2" SMS — [ THRU SCREW BOSSES ? � 21/4" MW CONC ANCHOREMBEDMENT [ SLAB / FOOTING SEE PLAN ea 4 , a, ; • W i SIDE VIEW � z 1 w W {-2"� CORNER POST W/ 1"x 2" @ F (4) #14 x 3/4" SMS I BACKSIDE V m Z W i INTO POST i i i 3/8" LENGTH AS REQUIRED W O W p•[ j = m 1 x FOR 21/4" EMBED CONCRETE O o p i SCREW ANCHOR INTO = n O J d N LL LL. _ E CONCRETE 1"x 2" BASE PLATE ANCHORED TO CONC W/ 1/4" _ _ f aQ •• ; DRAWN BY CONCRETE SCREW ANCHOR °a TP (MIN. 1 EMBED) 6" MAX EACH SIDEE OF POST 'a e• a ' e � • DATE DRAWN AND 24" O.C. MAX �< : 05/02/17 REVISION 2 FRONT VIEW Q - CP-1 CORNER POST TO CONCRETE DETAIL SHEErNO: /�-4 SCALE: NTS A-4