Project Information 10-25-18
-+ wrightsoft® Project Summary UNIT ONE Project Information For. 619 Berger Rd New Plan 619 Berger Rd, Fort Pierce, FI Notes: Job: Date: Oct 25, 2018 By: Desim Information Weather. Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 61 gr/b Heating Summary Sensible Cooling Equipment Load Sizing Structure 28425 Btuh Structure 28881 Btuh Ducts 5219 Btuh Ducts 3748 Btuh Central vent (0 chn) 0 Btuh Central vent (0 cfim) 0 Btuh (none) (none) Humidification 0 Btuh Blower 1707 Btuh Piping 0 Btuh Equipment load 33643 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 32618 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2908 Btuh Ducts 3105 Btuh Central vent (0 cfm) 0 Btuh Heatingg Cool! ngg (none) 6013 Btuh Area (ftz) 2102 2102 Equipment latent load Volume (fN) 23848 23848 Air changes/hour 0.26 103 0.14 55 Equipment Total Load�Sen+Latj Req. total capacity at 0.8 SHR 38632 h ton Equiv AVF (arm) Heating Equipment Summary Cooling Equipment Summary Make Make Goodman Mfg. Trade Trade GOODMAN Model Cond GSX160421 F AHRI ref Coil AVPTC49D14A AHRI ref 201441967 Efficiency 100 EFF Efficiency 13.0 EER,16 SEER Heating input 10.0 kW Sensible cooling 33200 Btuh Heating output 34103 Btuh Latent cooling 8300 Btuh Temperature rise 50 OF Total cooling Actual airflow 621 cfm Actual airflow 1383 Airflowfactor 0.018 cfm/Btuh Airflow.factor uh Static pressure 0 in H2O Static pressure 0.10 in H2O Space thermostat Load sensible heat ratio 0.85 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. wrigf�tsoft^ 2019-JmM 132923. ght R-Sule9Universa1201818.0.31 RSU06570 Pagel /IC:CP. F.Wransier;;uaIZ9BagwTwaPbn.rup Cab =WS Front Door faces: N +'- wrightsoft® Project Summary UNIT TWO Project Information For. 619 Berger Rd New Plan 619 Berger Rd, Fort Pierce, FI Notes: Weather. Winter Design Conditions Outside db Inside db Design TD Fort Pierce, FL, US Job: Date: Oct 25, 2018 By: Summer Design Conditions 42 OF Outside db 70 OF Inside db 28 OF Design TD Daily range Relative humidity Moisture difference Heating Summary Structure 20322 Btuh Ducts 3872 Btuh Central vent (0 ctm) 0 Btuh (none) Humidification Piping Equipment load Infiltration Method Construction quality Fireplaces 0 Btuh 0 Btuh 24194 Btuh Simplified Average 0 Co He 1335 1335 Area (ftz) Volume (fF) 16081 16081 Air changes/hour 0.31 0.17 Equiv AVF (cfm) 83 45 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 100 EFF 13.6 kW 463780 Btuh 5OF 844 din 0.035 cfm/Btuh 0 in H2O 90 OF 75 OF 15 OF 50 % 61 grAb Sensible Cooling Equipment Load Sizing Structure 27187 Btuh Ducts 2713 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 1707 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 30026 Btuh Latent Cooling Equipment Load Sizing Structure 2062 Btuh DuctCentral 2250 vent (0 cfm) BBtuh (none) Equipment latent load 4312 Btuh Equipment Total Load (Sen+Lat) 34339 Btuh Req. total capacity at 0.80 SHR 3.1 ton Cooling Equipment Summary Make Goodman Mfg. Trade GOODMAN Cond GSX16S361A Coil ASPT47D14A AHRI ref 201785534 Efficiency 13.0 EER,16 SEER Sensible cooling 28000 Btuh Latent cooling 7000 Btuh Total cooling 35000 Btuh Actual airflow 1167 cfm Air flow factor 0.039 cfmBtuh Static pressure 0.10 in H2O Load sensible heat ratio 0.88 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -01.1- wrightsoft 2019-JMM 1329:23 --- Rkht-Sti1s9Unkersa1201818.0.31 RSU06570 �2 F:1TransferWanua]J'\619BergerTwoPdn.rup Cab=W8 FrontDoorfa m N y Job: - - 1144tr{ghtl:soft" Rin ht-i® Worksheet Date: Oct M 2018 UNIT ONE By: 1 2 3 4 5 Boom name Exposedwal Room height Room dime,,.:., Room area Ty Construction stu�h,M () number Cool UNITONE 190 g ft 11.3 ft 2102.0 ft mstr bed 21.0 ft 9.0 ft heat000l 10 x 2720 8 2720 f2 Area (fF) or perimeter (ft) Load (Btuh) Area (f) or perimeter (ft) Load (8tuh) Gross NIPS Heat Cool Gross N1P/S Heat Cool 0.143 1.39D 0.770 0.770 0-2W 0.143 0.770 0.143 M 70 0.770 0.770 0.770 0.770 0.770 0290 0.143 0770 0.143 im 0.770 0.770 0.143 I. 1.390 0.770 0.770 0.770 0.710 0.143 0.770 0.408 0.989 n n n n n ne no a a a a a a a a se se s s s s w w w w w w w w w rw nw - - r3&92 . 0.00 0.00 4.00 0.00 0.00 21.56 o.00 0.00 O.OD 0.00 0.00 0.00 4.00 38.92 0.00 21.56 4.00 3B.92 38.92 21.56 21.66 21.56 21.56 2 -56 21.56 4.00 21.56 1.59 27.69 2.55 20D3 2266 2266 11.31 0.00 0.00 2.65 0.00 0.00 57M 0 00 0.00 0.00 0.00 0.00 0.00 255 20.03 0.00 2266 2.55 37.88 21.73 57M 58.10 2266 57.52 22� 2266 2-55 47S6 149 ODD 402 40 6 100 21 0 0 180 0 0 10 0 0 0 0 0 ' 0 453 40 0 12 835 40 40 15 36 10 15 30 16 85 15 2102 2102 325 0 0 21 0 0 170 0 0 3 0 0 0 0 0 0 401 80 0 24 633 7 73 4 8 20 4 60 32 70 0 2102 191 1301 1557 129 216 229 0 0 681 0 0 216 0 0 0 0 0 0 1606 1557 0 259 2535 1567 1557 324 776 W4 324 � 343 280 324 3333 5287 827 8D10 1 227D 2 0 0 433 0 0 572 0 0 0 0 0 0 im 801 0 272 1611 1515 669 864 2092 864 �4 � 360 178 719 3124 0 0 0 0 0 0 0 0 0 0 0 0 0 0 188 0 0 171 40 0 155 0 10 0 0 0 272 272 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 18 0 0 101 3 0 20 0 pp 0 0 0 272 21 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 404 1557 0 324 0 0 0 0 431 582 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 257 W5 0 � 0 864 0 0 0 404 0 6 �/ L---G 1344ccs 1ODtn 4A4-2om 4A42om 91C0 13A-0ocs 4A4-2om 1M ;ocs 4A4-tom 4A4-2on, 4A4-2om 4A4-2mn 4A4-torn 4A4-2om QA4 13A-4ocs 4A4-2om 13A1tocs 10D-m 4A4-2om 4A4-2om 13A-1ocs 10Dtn 10D-m 4A4-tam 4A4-2om eaq ,Zpm 4�j� 4 �4 Zom 4A4.2om 13A-flocs 4A4 tom. 16X1 �� D Vf► L--G C F 55450 1461 6 c)A®excursion Envebpe bsslgan 25251 23880 3693 5411 a) Infiraton Room %entiiation 3174 0 911 0 307 88 0 0 12 b) Occupants @ 230 Intsmalgairs: Appian estother 3 690 3400 2 460 0 ri-3 28425 28881 4000 5959 Subbbi (Ines 6 to 13) Less eAsmal bad 0 0 0 0 0 0 0 0 Less transfer 0 0 8 7 RedWgbulbn 28425 28881 4008 5966 14 Subtotsl Ductbads 18% 13% 5219 3748 18% 130A 736 774 15 33643 32628 4744 6740 Total room bad (cfrn) 621 1383 286 Air requred Calculations approved by ACCAto meet all requirements of Manual J 8th Ed. 2019.1ar-03132923 wr!Lfgn! !r Rght-Snl@Unhmrsd201818.0.31 RSU06570 P�kp1 A F:17 n uaW'S19 r: aW'rko Pbnxup Cab = WS Front Door tames: N - + wrightsa t" Righ ONE orksheet UNIT Job: Data: Oct 25, 2018 By: W mstrbath 1 Room name 0 ft 26.0 ft 2 3 EA-edwal Fmom hebht 9.0 ft heaticool 9.0 It heaVaool 4 [Zoom di nensbns 1.15 x 14.5 R 10 x 1545 B 5 Room area 14.5 ft' 164.5 T Ty Construction LWalis Or H1M Area (T) (ft) Load (Btuh) Area (ft') or perimeter (ft) Load (Btuh) number (Btuhf F-*F) (BUIE) or perimeter Haat I Cool Gross NIPS Fleat 0001 Cross N1P/S Heat Cool 6 13A-4ots 0.143 n 4.00 255 0 0 0 0 117 101 404 257 0 10am 1.390 n 38.92 20M 0 0 0 0 0 0 0 6 0 0 0 129 M 4A4-2om M770 0.770 n n 21.56 21.56 2266 2266 0 0 0 0 0 0 10 0 216 227 11 D 4A4-tom 19D0 0.390 n 10.92 11.31 0 0 0 0 0 0 0 0 0 13A-4ocs 0.143 ne 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 4A4-2om 13A4ocs 0.770 0.143 ne a 0.00 4.00 0.00 255 0 0 0 0 0 0 0 0 0 0 1 4A4-2om 0.770 a 0.00 0A0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4A4-2sm 4A4-tom 0,770 0.770 a a 0.00 21.56 OLD 5722 0 0 0 0 0 0 0 0 0 0 4A4-2om 07T0 a 0.00 ODD 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4A4-2am 4A4-2om 0,770 0.770 a a 0.O 0.00 0.00 0.00 0 0 0 0 0 0 0 0 0 0 ITO 02.90 a O.t0 0.00 0 0 0 0 0 0 0 0 �, 13A4ocs 0.143 se 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 4A4-2om 13A-4ocs 0.770 0.143 se s 0.00 400 ODD 255 0 0 0 O 0 0 0 0 0 0 0 1OD-m 1.390 s 3822 20.03 0 0 0 0 0 0 0 0 0 0 0 0 0 --Ci IL-�t3 4A4-2wn 0 -2om 0.770 0.770 s s 0.00 21.58 0A0 2266 0 0 0 0 0 0 0 0 0 0 0 13AAccs 0.143 w 4.00 255 0 0 0 0 117 107 428 0 272 0 10D•m 1,390 1.390 w w 38.92 3822 37.88 21.73 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1Ot}m 4A zom 0.770 w 21.56 5752 0 0 0 0 0 0 0 0 0 0 4A42om 0.770 w 21.56 58.10 0 0 0 0 0 0 0 0 10 0 10 216 227 4A4.2orn 4A4-ZDm 0.770 0770 w w 21.56 21,56 2266 57.52 0 0 0 0 0 0 0 0 0 4W.-om 0.770 w 21.56 2266 0 0 0 0 0 0 0 0 0 0 0 0 0 4A4-2om 0.770 0.143 w 21 M 400 22.66 255 0 0 0 0 0 0 0 0 0 0 0 13A.4ocs 4A4.2om 0.770 nw nw 21.56 47 0 0 0 0 0 0 0 0 c 16X19.Omd 0.408 - 1.59 1.49 15 15 23 0 22 0 165 155 155 26 245 72D 230 0 F 2" 0.9w - 27.69 0.00 15 0 6 c)A®excursion 0 321 Envebpe bssfgait 23 21 2358 1659 12 a) Irkration 0 0 0 0 380 Oj 109 0 b) Room ven9atbn 13 Intamalgains: Occupants@ 230 0 0 0 0 0 0 Applanceslother Subtotal (fines 6 to 13) 23 21 2738 1778 LesseAsmalbad 0 0 0 0 0 0 0 0 Less transfer 0 0 0 0 Redstrbufnn 23 21 2738 1778 14 15 Subfitai Ductbads 18% 13% 4 3 18%1 130/a 503 231 Total room bad 21 24 1 3241 6D 2009 85 Air �� (�) 1 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. �` vur6ghts®¢� 2019Jan-03132923 - Rght&h0Universd201818.0.31 RSU06570 Rkp2 ACCtk F:CrmdetWmuaIJ)619E)F_Vw mFlan.rup Cab=MJB FranDoafaces; N -q- wrightsoft' Right-J@ Worksheet UNIT ONE Job: Date: Oct 25, 2018 By: 1 2 3 4 5 Room name ExQosedvvl Room h 'hat Roomdmensbns Room area m cbst 25.0 ft 9.0 ft heaticool 10 x AMft 199.5 T a/c1 0 ft 9.0 ft heaV=l 10 x i95 fir 19.5 fF Ty I Construction number U-vane (Btuhlll;"F) Or HTM (BtuhAF) Area (fP) or perimeter (ft) Load (Btuh) Area (fP) or perimeler (ft) Load (Btuh) Heat I Cool Gross NrP/S Heat Cool Gross NIPS Heat Cool 6 11 W 13A4ocs 10am 4A4-2om 4A4-2orn 11D0 13AAocs 4A4-2om 13A-4ocs 4A4.2om 4A4-2a7n 4A4-2om 4A4-2om 4A4-2om 4A4-2om 11P0 4A4-2om 10L}m 4A -2om 4A4-2om 13A-4ocs 10D•m 10D-m 4A4-2om 4A4-2om 04-2om 4A4-2om 4A4-2om 4A4-2am 13A4ocs 4A42om 16X190md 22A-V (1143 13M 0.770 0.770 0.390 0A43 0.770 0.143 CL7701 0.770 0.770 0.770 0.770 0770 0290 0.143 0.770 0.143 1.390 0.770 0.770 0.143 1.390 1.390 0.770 0.770 0.770 0.770 0.770 0.770 0.143 0.770 a408 0.9m n n n n n ne no a a a a a a a a se se s s s s w w w w w w w w w nw nw - - 4.00 38.92 21M 21.56 1092 0.00 0.00 4.00 0.00 0.00 21-% 0.00 0.00 0.00 0.00 0.00 0.00 4A0 38.92 �0.00 21.56 4.00 3892 38.92 21.56 21.56 21.56 21.55 21.56 21.66 4.00 21,56 1.59 27.69 2.55 20.03 2266 22.66 11.31 0.00 0.00 255 MOO 0.00 5722 000 000 Q.QQ 0.00 0.01) 0.00 255 20A3 0.00 2266 255 37.88 21.73 57.52 58.10 22-66 57.52 22.66 2266 255 47.86 1.49 Q.00 90 0 0 0 0 0 0 135 0 0 10 0 0 0 0 0 0 Q 0 0 0 0 0 0 0 0 0 0 0 0 0 0 200 200 90 0 0 0 0 0 0 125 0 0 1 Q 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 200 25 360 0 0 0 0 0 0 501 0 0 216 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 316 692 229 0 0 0 0 0 0 318 Q 0 572 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 296 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 20 20 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 20 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 31 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Q 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 29 0 yJ L--G Y---013A4ocs G T -13A4ocs �G Vd/ G C F 6 c)A®excursion 27 0 Envebpe bss/gan 2085 1443 31 29 12 a) Inflation b) Room vandatnn 365 0 105 0 0 0 0 0 13 Intemalgains: Occupants@ 230 Appfanceslolher 0 0 0 0 0 0 Sublofal (cites 6to 13) 2450 1548 31 29 14 15 Less external bad Lesstransfer Redistribution Subtotal Ductbads 18% 13%1 0 0 9 2459 4521 0 0 8 1556 2021 180/o 13% 0 0 -31 0 01 0 0 -29 0 0 Total room bad Ai required (cfm) 2911 54 1758 75 0 0 0 0 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. wrr�gh3�oft^ 2019Jan-03132923 Rbht-Suboun'eraW201618.0.31 RSU06570 PaW3 /�%K F:1TransferWanualJ�819BerXTvmPdnxup Cab=MJB FrontDoorfaces N g Job: - wreghtso UNIT ONE ol'kSFteet Date: Oct25,20W By: kind farm e 18.9 ft wal 9.0 ft heatb000l 16.0 ft heattool ht A p x 525 ft !A x 5M.0 ft tRmm enssms 525 ft2 500.0 T a Constructbn U-vatle Or HTM Area (T) (tt) (Stuh) or permetBr (tt) Load (Btuh) number (B1uWF) (BhrhlfP) or perimeter Heat Cool Gross LAPIS Heat Cool Gross NIPS Heat Cool 6 13A-0ocs 0143 n 4.00 2.55 0 0 0 0 0 0 0 0 0 0 0 0 0 0 10Din 1.390 n 38.92 20.03 0 0 0 0 0 0 0 0 0 0 4A442om OL770 n 2156 2266 0 0 0 0 0 0 0 0 4A4-2om 0,770 0.390 n n 21.56 10.92 2266 11.31 0 0 0 0 0 0 0 0 11 D W 11DO 13A-4ps 0.143 ne 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 L--G 4A4-2orn 0.770 no OAO OAD 0 0 0 0 0 0 0 0 0 0 13A-loos 0.143 a 400 255 0 0 0 0 0 0 0 0 4A4.2om 0.770 0.770 a a 0.00 O.OD 0.00 0.00 0 0 0 0 0 0 0 0 4A4-2orn 4A4 tom 0770 a 21.56 57 0 0 0 0 0 0 0 0 0 0 0 0 0 4A4-tom 0.'70 a 000 0.� 0 0 0 0 D 0 O 0 0 0 0 4A4 tom 0770 0.770 a s OOD 0.00 0.pO 0.00 0 0 0 0 0 0 0 0 D 4AA.� 11P0 0� a 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 Vp1 13A-4ocs 0.143 se 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 �-C 4AA-tom 0.770 0.143 se s 0.00 4.00 0.00 255 0 0 0 0 0 0 0 0 13A flocs IODin 1.390 s 38.92 2003 0 0 0 0 0 0 0 0 0 0 01 4A4-2om 0.770 s 0.00 0o 0 0 0 0 0 0 0 0 0 0 0 0 0' 4A4-2om 0.770 s 2156 22.66 255 0 0 0 0 304 234 937 596 13A4oas 0,143 1.390 w w 4.00 38,92 37.88 0 0 0 0 0 0 0 0 1OD-m 10D rn 1.390 w 3BD2 21.73 0 0 0 0 40 0 36 0 1557 0 869 0 4A4-2om 0.770 w 21.56 57.52 0 0 0 0 0 0 0 0 0 0 0 0 4A4_2Dm 0.770 w 21.56 58.10 0 0 0 0 0 0 0 0 4A4.2om 0.770 0,770 w w 21.56 21 BB 22.66 5752 0 0 0 0 0 0 0 0 4A4-tom 4A4-2om 0.770 w 21.56 22.66 0 0 0 0 30 30 0 648 0 681 0 4A4-tom 0.770 w 21.56 2268 0 0 0 0 0 0 0 0 0 0 0 0 0 �1 13A� 0.l43 0.770 nw nw 400 21226 255 4795 0 0 0 0 0 0 0 0 t�---G 0 4"2xn 16X19-0md 0,4W - 1.59 1.49 53 53 83 78 500 5O0 519 19 524 524 743 0 F 22A-0 0.989 - 27.69 0,00 53 0 0 0 -7 2016 6 c)A®excursion 83 71 4458 4904 Envelope loss/gain 0 0 4 142 12 a) lntitratbn 0 0 0 0 0 b) Room venth iDn 13 Irrnmalgans: Occupants@ 230 0 0 500 0 0 900 Apprancestother 83 571 4951 5946 Subtotal(ines6to13) 0 0 0 0 Less external bad 0 0 Lesstranster 14 13 0 0 Redsttutbn 98 585 4951 5946 14 SubtDW 18DAa 13% 18 76 18% 13% 909 772 15 Ductbads 112 �28 5860 6717 Total room bad F[A4�requked(cfm) 108 285 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. 2019Jan-03132923 ww rwRbht-Sub0UriwerSel201818A.31 RSUD6570 lPage4 AC F.\Transb WMuaIJ,619 8.MW7 °.o Phnrup Corti; = W8 Front D- farms N Job: -�- wrightsc ` Right -A Worksheet Date: oct25,2018 UNIT ONE By: Calculations approved byACCAto meet ad requirements of Manual J 8th Ed. 2018,1an-03132923 A" onscG4�B�4�nfR Rght-%i&unKwseJ201818.0.31 RSU06570 F�,W5 t ` F:\Transf,W,,,dJ'619 BeWTvwo Plan.rup cad; = MJ8 Front Door fm: N Job: weightsoft° Right-J@Worksheet Date: Oct25,2018 [UNIT ONE By: Calculations approved byACCAto meet all requirements of Manual J 8th Ed. 2019431-03132923 wva G'tsofft RAM-S boUnivmd201818.0.31 R81J08570 pb�p8 ,45ffk FRransferVManuaiJIbl9 E WTm Pk rup Cab = M JB Rmrd Door tom N N IOOgJWOl-.0 SM=qe'J dnru 1 1 668P���Nl1�Ds ll:� �j+J�jl Ld)'d oL59onsM 6£'m BIoZiamiunowe'i4Qa S;¢as a08� niw EZ6Z£L£Q-�I`6LUZ no�a suogelrr��e� -p3 Lae f lenueW jo s;uaw6An as pe 1aaw olVOOV q pa e&oz `sz 400 :tea petleVOAA Of"449M :qwr wlriightsoft° T UNITWO ®rksheet Jot: Date: Oct 25, 20 f;•8 By: 1 Room name vnerrrn 24.0ft pantry 0 ft 2 3 �� Room height 9D It heallbool 9.0 ft heatbool 4 Roomdiwnerrsnns 1.0 x 2159 R 5A x 50 R 5 Room area 215.0 W 25.0 iP Ty Construction llvabe Or HTM Area (fe) Load Area (T) Load number (BtuhWF� (BhihAP) or perimeter (ft) (Bhrh) or pertneter (ft) (Bfuh) Heat I Cool Gross wis Heat Cool Gross N/p!S Heat I Cool 6 13A4ocs 0.143 n 4.00 2.55 0 0 0 0 0 0 0 0 0 IGD.m 1.390 n 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 4A4-2Drn 4g4.2om 0.770 Q770 n n 0.00 21.56 ODD 22.66 0 0 0 0 0 0 0 0 0 0 11 1i00 0.390 n 0.00 0.00 0 0 0 0 0 0 0 0 t13A4ocs 0.143 ne 4.00 255 0 0 0 0 0 0 0 0 0 0 0 0 04-2om 13A.4ocs (1770 0. no a 21.56 4.00 47.86 255 0 153 0 97 0 38B 0 247 0 0 0 0 -G 4A4.2om 0.770 a 21.56 59.19 0 0 0 0 0 0 0 0 4p,4-2orn O.77tt a 21.66 69.19 56 5 1207 3315 0 0 0 0 4A4-2cm Q770 a 0.00 0DO 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 04.2orn 04-2om Q7 0 0.770 e a 21.56 21.58 59.10 59.19 0 0 0 0 0 0 0 0 0 04-2om 0770 a 21.56 59.56 0 0 0 0 0 0 0 0 D 11PO 0290 9 8.12 841 0 0 0 0 0 0 0 0 t13AAocs 0.143 se 4.00 2M 0 0 0 0 0 0 0 0 0 0 0 0 4A42am 0.770 se 21.56 40.33 0 0 0 0 0 0 -G 13A flocs 0.143 s 4.00 2.555 63 63 252 160 0 0 1OD4n 1.390 s 0.00 0.00 0 0 0 0 0 0 0 0 4A42wn 0.770 s 21.56 22BB 0 0 0 0 0 0 0 0 4A4-2om Q770 s 0.00 ODD 0 0 0 0 0 0 0 0 i3,44ocs 0.143 w 4.00 255 0 0 0 0 0 0 0 0 10D-m 1.390 w 0.00 0.00 0 0 0 0 0 0 0 0 1pDin 1.390 w 0.00 0.00 0 0 0 0 0 0 0 0 4A4-2orn 0.770 w 0.00 0.00 0 0 0 0 0 0 0 0 04-21om 0.770 w 0.00 0.00 0 0 0 0 0 0 0 0 4A4-2Dm 0.770 w 0.00 0.00 0 0 0 0 0 0 0 0 4/44-2om 0.770 w 0.00 0.00 0 0 0 0 0 0 0 0 0 4A4-2om 0.770 w ODD 0.00 0 0 0 0 0 0 0 4A4.2am 0.770 w 0.00 0A0 0 0 0 0 0 0 0 0 0 yd 13A.4ocs 0.143 nw 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 �--G C 4A4.2om 16X19-Cmd 0.770 0.408 MV - 0.00 1.59 O.OD 149 0 215 0 215 0 341 0 320 25 25 40 37 F 22Atpl 09fi9 - 27.69 1100 215 24 665 0 25 0 0 0 6 c)AEDexcursion 302 1 0 Fnwbpe bs. n 2853 4343 1 40 37 12 a) fri tration 351 101 0 0 0 0 b) Room vendatbn 0 0 13 Intamalgans: Occupants@ 230 0 0 0 O Applancesfother 900 Subtotal (Ines 6lo 13) 3204 5344 40 37 Lesswbrnalbad 0 0 0 0 0 0 Lesstransfer 0 13 0 12 -40 37 14 Redstrbutbn Subtotal 3217 5350 0 0 15 Ductbads 19% 10% 613 535 191/0 1000 0 0 Totalroombad 3830 5891 0 0 AF required (cfm) 134 23D 0 0 Calculations approved by ACCAto meet all requirements of Manual J 8th Ed. " eevr6�FstsoTt 2019,km-031329.23 -- - Rot-:4,WUnMNsd20l8l8.0.31 RSU06570 F ge8 ACC F.W uWjSj9WWTvwpbnrup Ceb=W8 FrontDoanfaces: N - �- wrightsoft° RIg � � orksheet Job: Date: Oct 25, 2018 By: 1 Room name n 100 ft dining 10.0 ft 2 3 Et�osedwal Room hebtrt 9.0 ft heaUcool 16.0 ft treattcool 4 Roomd'mensflstis 5.0 x 11.0 ft 1A x AeS5 It 185.5 ft 5 Room area 55.0 W Ty I Construction number U-vaUe (Btuhlft'-°F) Or HTM (etuw) Area (W) or perimeter (t>) Load (Bfuh) Area (fF) or perimeter (ft) Load (Btuh) Heat I Cool Gross NIP/S Heat cool Gross NJP/S Heat I Cooi 6 vV 13AAocs 0.143 n 4.00 2.55 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 10Drn 4A4-2orn 1.390 a770 n n 0.00 0.00 0.00 0.00 0 0 0 0 0 0 0 a 0 4A4-2pm OL770 n 21.56 2266 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 I D V�! 1100 13AAocs 03M 0.143 n ne 0.00 4.00 0.00 2.55 0 0 0 0 0 0 0 0 0 0 L-G 4A4-2om 0.770 0.143 ra 21.56 4.M 47BS 255 0 45 0 21 0 64 0 53 0 160 0 88 0 � 0 224 13A-4ocs 4A4-2om 0.770 a a 21.56 59.19 0 0 0 0 72 6 1552 4262 4A4-2om 0.770 a 21.56 59.19 0 0 0 0 0 0 0 0 a 0 0 0 0 4A4-2um 4A4-2orn U70 0.770 a a 0.00 21.56 0A1 58.10 a 0 a 0 0 0 0 0 0 0 0 4A4-2om 0.770 a 21.56 59.19 24 2 517 1421 0 0 0 0 0 0 0 0 G. 4A4-2om 0.770 a 21.56 59.5E 0 0 0 0 0 0 0 0 0 0 0 0 p HPO 0.290 a 8.12 8.41 0 0 0 0 0 0 Mr U---G 1344om 0.143 Q770 se se 4.00 21.56 2.55 40.33 0 0 0 0 0 0 0 0 0 0 4A4-23m 13A-4ces 0.143 s 4.00 255 45 45 180 115 0 0 0 0 101]-m 1.390 s 0.00 ODD 0 0 0 0 0 0 0 O 0 a 0 0 4A4-2r n, 0.770 s 21,56 22,66 a 0 0 0 0 0 0 0 0 0 0 0 4A4.2om 13AAocs 0.770 0.143 s w 0.00 4.00 0 2.55 0 0 0 0 0 0 0 0 1OD-m 1.390 w O.OD OAO O 0 O 0 0 0 0 0 0 0 0 0 0 1OD-m 4A4-2orn 1390 0.770 w w 0.00 0.00 0.00 0.00 0 a 0 0 0 0 0 0 0 0 0 4A4-2orn 0.770 w 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 4A4-2cm 4A4-2om 0.770 0.770 w w 0.00 ow 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 4A4-2om 0.770 w 0.00 OOO 0 0 0 0 0 0 0 0 0 0 0 0 4A4-2om 13A-0ocs 0.770 0.143 w nw O.OD 0.00 MOO 0.00 0 0 0 0 0 0 0 0 0 0 0 0 4A4.2orn 0.770 0.408 nw OAO 1.59 0.00 1.49 0 55 0 55 0 87 0 82 0 186 0 186 0 294 0 276 c F 16)(19-W 22A,40 0.9M - - 27.69 0.00 55 10 277 0 166 10 277 0 61 c)A®excursion 1 132 1 399 Envebpe bss/gait 1146 1803 2476 5161 12 a) Ir a . n 146 42 260 0 75 0 b) Room vendation 0 0 13 Intemalgains: Occupants@ 230 0 0 0 0 O App6nces/other Subtotal (Ines 6 to 13) 1292 1845 2735 5235 Less external bad 0 0 0 0 0 0 0 0 Less transfer 13 12 13 12 ReCrSH)Utim 1305 11157 2749 5248 14 Subbtal 18% 10°i6 249 185 19% 10% 524 524 T5Ductbads otalroombad 1554 541 2042 80 3272 114 5771 225 ir requFed (cfm) Calculations approved byACCAto meet all requirements of Manual J 8th Ed. wrrGgtettsotl¢- 2013,1at-03132923 Rbht-Sutc&a Unwersd201818.0.31 RSU0070 Page9 ACG� F:\Transfe V.ua18619 B.WTwo Plarr•rup Cab = MJS Front Dow faces: N Job: wrightsoftR Right-J® Worksheet Date: at26,2078 UNIT TM By: Calculations approved by ACCAto meet all requirements of Manual J 8th Ed. 2019,1ai-03132923 .1- wrGgFstsoit Rbht-SukSUniv�201818.0.31 RSU�70 10 s1CGA F;\Tramb rVJ MUWj 619 Two phnn.rup Cab = W8 Front Door faces: N Job: - 5- wrightsoft° Right-J@ Worksheet Date: Oct25, 2018 UNIT TWO By: Caiculations approved by ACCAto meet all requirements of Manual J 8th Ed. 2019,1an-031328.23 =vLig F 15s n" RbhVSUtaUnWmrsd201818D.31 RSU08570 Nge11 -Zr-K F:\Traaer muOIJ'819 BVg YTwo Ftn-P Cab = W8 Frmt Door faces: N Job: -F wrightso t` Right -A WOrksheet Date: Oct 25, 2018 UNIT TWO By: Calculations approved by ACCAto meet all requirements of Manual J 8th Ed. 2019-Jan-0313:29:23 wr@gp'tscsft" �'" Page 12 Rght-Sui�Univers�201818.0.31 RS�.106570 F..\Tra mh-WLmuaf J`619 .amjer7Vw Pbn-rup Cab = W8 Front Dow faces N Sheet 1 Job #. Performed for. 619 Berger Rd New Phan 619 Berger Rd Fort Pierce, FI IJR Scale: 1 :141 Page 1 Right -Suite® Universal 2018 18.0.31 RSU06570 2019-Jan-0313:31:03 ...Manual J1619 Berger Two Plan.rup wrightsoft Manual S Compliance Report UNIT ONE For: 619 Berger Rd New Plan 619 Berger Rd, Fort Pierce, Ft Design Conditions Outdoor design DB: 90.0°F Sensible. gain: 34335 Btuh Outdoor design WB: 78.0°F Latent gain: 6013 40348 Btuh Btuh Indoor design DB: 75.0°F Total gam: Estimated airflow: 1383 cfnt Indoor RH: 50% Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIkAC Manufacturer: Goodman Mfg. Actual airflow: 1383 cfm Sensible capacity: 33200 Btuh Latent capacity: 8300 Btuh Total capacity: 4'1500 Btuh Design Conditions Outdoor design DB: 42.0°F Indoor design DB: 70.0°F Model: GSX160421F+AVPTC49D14A 97% of load 138% of load 103% of load SHR: 80% Heat loss: 33643 Btuh Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Elec strip Manufacturer. Model: Actual airflow: 621 c Irn Output capacity: 10.0 kW 101 % of load Meets all requirements ofACCA Manual S. Job: Date: W 25, 20'18 By: Entering cod DB: 76.4°F Entering cod WB: 63.5°F Entering coil DB: 69.5°F Temp. rise: 50 OF 2019Jm-03132925 -. wrig1}'1ltsofC' Right iaUnWsd201818A31 RSU08570 1 AN•�'ltaNfu..l.annv•.•nurwy ACM F'Rmgnwmuaijri9Lierg TvmPEm.rup cab=Ws FrmtOdorfaees: N 4+ wrightsof° (Manual S Compliance Report UNIT TWO For 619 Berger Rd New Plan 619 Berger Rd, Fort Pierce, Fl Design Conditions Outdoor design DB: 90.0°F Sensible gain: 31607 Btuh Outdoor designWB: 78.0°F Latent gain: 4312 Btuh Indoor design DB: 75.0°F Total gain: 35919 Btuh Indoor RH: 50% Estimated airflow: 1167 ch Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SWAC Manufacturer. Goodman Mfg. Actual airflow: 1167 c fm Sensible capacity: 28000 Btuh Latent capacity: 7000 Btuh Total capacity 35000 Btuh Design Conditions Model: GSX16S361A+ASPT47D14A 89% of load 162% of load 97% of load SHR: 80% Outdoor design DB: 42.0°F Heat loss: 24194 Btuh Indoor design DB: 70.0°F Manufacturer`s Performance Data atActual Design Conditions Equipment type: Elec strip Manufacturer: Model: Actual airflow: 844 cfrn Output capacity: 13.6 kW 192% of load Meets all requirements c►fACCAManual S. Job: Date: W 25, 2018 By: Entering coil DB: 76.6°F Entering coil WB: 63.5°F Entering coil DB: 69.7°F Temp. rise: 50 OF 20194M-03132925 iR !LS!i tSCIfC°' Page2 .,� Rat-SLie�Unirersa1201818.0.31 RSU06570 )m F\Ttw UWj6198wWTlwphn_p Cab=MJB FrontDoaf m N Wirightsoft Duct System Summary UNIT ONE For. 619 Berger Rd New Plan 619 Berger Rd, Fort Pierce, Fl Job: Date: Oct 25, 2018 By-, Heating CooBn Oin H2O 0.10 in H2O External static pressure 0 in H2O 0 in H2O Pressure losses 0 in H2O 0.10 in H2O Available static pressure Supply / return available pressure 0.000 / 0.000 in H2O 0.060 / 0.040 in H2O 0.025 in/100ft Lowestfriction rate 0 in/100ft 621 cfrrt 1383 ctm Actual airflow 398 ft Total effective length (TEL) Htg Clg Design Diam H x W Duct Mat Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Design Name (Btuh) (cfrn) (cfm) FIR (in) (in) 54 142 0.040 6.0 Ox 0 MFx MFx, 25.0 29.0 125.0 125.0 st2 st2 fan* c 3359 ft*-A c 3359 54 16 142 22 0.039 0.026 6.0 4.0 Ox 0 Ox 0 MFx 62.6 165.0 st6 g,etbatn c 527 6744 158 286 0.025 90 Ox 0 MFx 67.6 170.0 st6 guestrm-A When c c 3725 67 158 0.031 6.0 Ox 0 VIFx MFx 48.2 46.4 145.0 145.0 st5 sty lace, -A c 3725 67 2 158 28 0.031 0.057 6.0 4.0 Ox 0 Ox 0 VIFx 5.0 100.0 kind c 660 1758 54 75 0.042 6.0 Ox 0 VIFx 17.4 125.0 st1 m and c 2009 60 85 0.040 6.0 Ox 0 MR 24.8 125.0 st1 mstr b& mstr t o c c 3370 44 143 0.042 6.0 Ox 0 Ox 0 MFx MFx 21.7 13.7 120.0 155.0 st4 st4 mstr bedm-8 c 3370 44 143 1 0.035 0.042 6.0 4.01 Ox 0 MR 18.2 125.0 st1 UA-A c 24 1 Truck 1:;HtgName Type st4 PeakAVF 88 st1 PeakAVF 202 st2 PeakAVF 417 sty PeakAVF 309 s6 PeakAVF 175 Clg (dm) Design FIR Veloc Upm) Diam (in) H x W (in) Duct Material Trunk 286 0.035 647 9.0 0 x 0 VnlF1 st1 446 0.035 818 10.0 0 x 0 VinlFlx 909 0.025 514 1&0 0 x 0 VinlFlx 624 0.025 584 14.0 0 x 0 VnlFbc s't2 308 0.025 698 9.0 0 x 0 VmlFbc sty Soldlltal/c values have been manually overridden 2019-Jai-03132925 W rfghtSolrt" Page l pt ,•��.,...,�...:.rm•,w. R;�t.Suh011riwersa1201818.0.31 RSUQ8570 I C &- F:.Xrr&lsbWmualAlgeoWTvjoFbnrup ceb=W8 FrontOoorbom N Clg (dm)\ TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk Name Grille Size (in) Htg (dm) 202 175 110 134 446 308 313 316 63.2 137.4 160.0 139.4 0.064 0.029 0.025 0.029 8.18 698 573 579 10.0 9.0 10.0 10.0 Ox 0 0x 0 Ox 0 Ox 0 MR MR MR V1Fx rt3 rt1 re rb2 rbg rb8 rb10 Ox 0 0x 0 Ox 0 Ox 0 Htg (dm) Cig (ch) Design FR Veloc Upm) Diam (in) H x W (in) Duct Material Trunk Name Trunk Type 309 419 624 937 0.029 0.025 794 671 12.0 16.0 0 x 0 0 x 0 ViinlFbc VinlFbc rt1 rt3 rt1 PeakAVF PeakAVF SWerdaffc vabas have been a®nuaW GwffWden 20194wt-03132925 �+ w rights®ft- R t Suie� U fwASW 201818.0 31 RSU06570 �02 �� RMnRY IC.JJm.4uL.w/YCUMrY F.Trnaf uzjJ'619BNWTvwphrup Cab=MJB FrcntD-fww. N wrightsoft (Duct System Summary UNIT Two For. 619 Berger Rd New Plan 619 Berger Rd, Fort Pierce, FI Bxtemal static pressure Pressure losses Available static pressure Supply / return available pressure Lowest t iaion rate Actual airflow Total effective length (TEL) Heating 0 in H2O 0 in H2O 0 in H2O 0.000 / 0.000 in H2O 0 in/100ft 844 cim 379 1t Job: Date: Oct 25, 2018 By: Cooling 0.10 in H2O 0 in H2O 0.10 in H2O 0.05810.042 in H2O 0.026 in/100ft 1161 cfm Design (Btuh) Htg (drn) Clg (drn) Design FI D(a)HinW () Duct Mat Actual L ft) FnEqV L(ft) Trunk Name h 673 h 4561 c 5771 h 3493 h 582 c 5891 c 4320 c 2568 c 2042 47 208 114 140 49 134 86 11 54 26 178 225 136 23 230 169 100 80 0.058 0.057 0.032 0.031 0.026 0.027 0.037 0.040 0.027 4.0 8.0 8.0 6.0 4.0 8.0 6.0 6.0 5.0 Ox 0 Ox 0 Ox 0 Ox 0 Ox 0 Ox 0 Ox 0 Ox 0 Ox 0 VIFx VIFx VIFx VIFx VIFx VIFx VIFx VIFx VIFx 4.5 7.2 42.4 40.3 64.2 56.0 34.8 24.0 58.2 95.0 95.0 140.0 145.0 155.0 160.0 120.0 120.0 155.0 st7 st7 a st8 st3 st3 0 b02 bedrm4 dnh9 entry ebb& rM h me&rm Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (drn) (dm) FIR (fpm) (in) (in) Material Trunk st8 PeakAVF 237 332 0.026 609 10.0 0 x 0 VnlFtx st7 st7 PeakAVF 491 694 0.026 884 12.0 0 x 0 VmlFtx s13 st3 PeakAVF 589 963 0.026 1 669 16.0 0 x 0 VinlFbc Bddrdafic values have been aenua►►y ov8mdden 2019-Jan-03132925 VVrkjhtS®gyp Rght-SutoUnhwW201818.031 RWO6570 3 nvrn•tc.vm..�.�+nx���n d4Ck F1TrwrouV nuWjal9euWTmaPhn.rup cac=WS Fronto=bces: N Grille Htg Clg TEL Design Veloc Diam H x W (in) Stud/Joist Opening (in) Dud Mat Trunk Name Size (in) (dm) (cfm) (ft) FR (fpm) (in) 72.0 0.059 596 8.0 Ox 0 MR MR rb11 Ox 0 208 178 rb7 Ox 0 11 100 253 68.1 160.2 0.062 0.026 510 572 6.0 9.0 Ox 0 Ox 0 MR rl2 rb6 rb5 Ox 0 px 0 183 442 636 110.2 0.038 595 14.0 Ox 0 VIFx r12 Trunk Name Type rt2 PeakAVF Clg Design (fpm) (in) H xW (n) Duct Material Trunk Hi 889 0.026 637 16.0 0 x 0 VinlFlx 625 Solorgeffc values hate been manuafy ovenfdden 2019Ja M 132925 wrightsc t- Pdge4 ,. Rat SuI& Univ NW201818.0.31 RSU06U0 l .bl FCrrans ruMJ'619euWTYmFienrup Cab=NUB FrmtOoafeoes: N