HomeMy WebLinkAboutCERTIFICATE OF PRODUCT RATINGSEligible for Federal Tax Credit
AHRI Certified Reference Number: 206912016 Date: 02-18-2022 Model Status : Active
AHRI Type: RCU-A-CB (Split System: Air -Cooled Condensing Unit, Coil with Blower)
Series: DAVE LENNOX SIGNATURE XC21 SERIES
Outdoor Unit Brand Name: LENNOX
Outdoor Unit Model Number (Condenser or Single Package) : XC21-048-230-12
Indoor Unit Model Number (Evaporator andlor Air Handler): CBA38MV-048-230*+TDR
Region : All (AK, AL, AR, AZ, CA, CO, CT, DC, DE, FL, GA, HI, ID, IL, IA, IN, KS, KY, LA, MA, MD, ME, ML MN, MO, MS,
MT, NC, ND, NE, NH, NJ, NM, NV, NY, OH, OK, OR, PA, RI, SC, SO, TN, TX, UT, VA, VT, WA, WV, WI, WY, U.S.
Territories)
Region Note : Central air conditioners manufactured prior to January 1, 2015 are eligible to be installed in all regions
until June 30, 2016. Beginning July 1, 2016 central air conditioners can only be installed in region(s) for
which they meet the regional efficiency requirement.
t"Active" Model Status are those chat an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being
marketed but are not yet being produced:'Produclion Stopped" Modei Status are those that an AHRI Cerfifcation Program Participant is no longer producing BUT is still
Re0ing or offering for sale.
t a that are accompanied by WASindicate an In tary t The new published rating Is sh2jj2j2U2jL the previous (i.e WASI rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes 110 representations, warranties or guarantees as to, and assumes no responsibility for,
the products) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the producins), or the
unauthorized alteration of data listed on this Certificate, Certified ratings are valid only for models and configurations listed in the
directory at www.ahrldirectory.org.
TERMS AND CONDITIONS
This Cerificate and Its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or In part, be reproduced; the copied;
din individual, entered nine Computer database; or otherwise utilized, In any form or manner or by any means, exceptAIR.CONDITIONING, HEATING,
personal and confidential reference. & REFRIGERATION INSTITUTE
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahrldirectory.org, Click on "Verify Certificate" link we make life hetteN
and enter the AHRI Certified Reference Number and the date an which the certificate was issued,
which Is listed above, and the Certificate No., which is listed at bottom right.1 132896613063474306
©2022Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.:
Job: 6601 S Indian River Drive,...
-t* wrightsofta Project Summary Date: Feb04,2022
Entire House By: Christopher Langel
Sea Coat Air Conditioning
3103Ircisual 31st Sty, Fat Piece, F134946Rh- 77246&2400
For: Robert Pru tt
6601 S Indian River Drive, Fort Pierce, FL 34982
Notes: 6601 S Indian River Drve, Fort Pierce, FL, 34982
Weather:
Winter Design Conditions
Outside db
Inside db
Design TD
vero Beach Muni, FL, US
Summer Design Conditions
43 °
F Outside db
7p OF Insided
27 OF Design TD
Daily range
Relative humidity
Moisture difference
b
Heating Summary
Structure 19663 Btuh
Ducts 4766 Btuh
Central vent (0 cfm) 0 Btuh
(none) 0 Btuh
Humidification 0 Btuh
Piping 24429 Btuh
Equipment load
Infiltration
Method
Construction quality
Fireplaces
Simpl�ed
Average
0
volumee (IV)He1895 Co1895
Area 15161 15161
Archanges0.38 0.20
/hour 96 51
Equiv. AVF (chn)
Heating Equipment Summary
Make Lennox
Trade Lennox
Model 9.6 Heat Strip
AHRI ref
Efficiency
Heating Input
Heating output
Temperature rise
Actual air flow
Air flow factor
Static pressure
Space thermostat
100 EFF
8.6 kW
29418 Btuh
13 OF
2100 cfm
0.086 cfm/Btuh
0.60 in H2O
91 OF
75 °F
16 OF
50
59 gr/Ib
ible Cooling
Sens
Equipment Load Sizing
Structure 24371 Btuh
Ducts 7225 Btuh
Central vent (0 cfm) 0 Btuh
(none) wer 1707 Btuh
Blo
Use manufacturer's data n
Rate/swing multiplier 0.95
Equipment sensible load 31804 Btuh
Latent Cooling Equipment Load Sizing
Structure 11638 Btuh
Ducts 1833 Btuh
Central vent (0 cfm) 0 Btuh
(none) 13471 Btuh
Equipment latent load
Equipment Total Load (Sen+Lat) 45275 Btuh
Req. total capacity at 0. 0 SHR 3.8 ton
Cooling Equipment Summary
Make Lennox
Trade Lennox
Cond XC 21-048-230
Coil CBA38MV-048-230
AHRI ref 295821582
Efficiency 13.0 EER, 18SEER
34650 Btuh
Sensible cooling 14850 Btuh
tal cooling Latentooing 49500 Btuh
ToActual airflow 2100 cfm
flow factor 0.066 cfm/Btuh
A r tic pressure 0.60 in H2O
Sta0.71
Load sensible heat ratio
Calculations approved byACCA to meet all requirements of Manual J 8th Ed
�_-P'�1-wrightsoft" Ri¢l9iterDUnves2i371919.0.13R5U2%44 �1
�CCP. C:1Uses�avesa�DaklcjArrtiftNP CaIc=MJ6 FrtrtDariaces: E
91 OF
75 °F
16 OF
50
59 gr/Ib
ible Cooling
Sens
Equipment Load Sizing
Structure 24371 Btuh
Ducts 7225 Btuh
Central vent (0 cfm) 0 Btuh
(none) wer 1707 Btuh
Blo
Use manufacturer's data n
Rate/swing multiplier 0.95
Equipment sensible load 31804 Btuh
Latent Cooling Equipment Load Sizing
Structure 11638 Btuh
Ducts 1833 Btuh
Central vent (0 cfm) 0 Btuh
(none) 13471 Btuh
Equipment latent load
Equipment Total Load (Sen+Lat) 45275 Btuh
Req. total capacity at 0. 0 SHR 3.8 ton
Cooling Equipment Summary
Make Lennox
Trade Lennox
Cond XC 21-048-230
Coil CBA38MV-048-230
AHRI ref 295821582
Efficiency 13.0 EER, 18SEER
34650 Btuh
Sensible cooling 14850 Btuh
tal cooling Latentooing 49500 Btuh
ToActual airflow 2100 cfm
flow factor 0.066 cfm/Btuh
A r tic pressure 0.60 in H2O
Sta0.71
Load sensible heat ratio
Calculations approved byACCA to meet all requirements of Manual J 8th Ed
�_-P'�1-wrightsoft" Ri¢l9iterDUnves2i371919.0.13R5U2%44 �1
�CCP. C:1Uses�avesa�DaklcjArrtiftNP CaIc=MJ6 FrtrtDariaces: E
ible Cooling
Sens
Equipment Load Sizing
Structure 24371 Btuh
Ducts 7225 Btuh
Central vent (0 cfm) 0 Btuh
(none) wer 1707 Btuh
Blo
Use manufacturer's data n
Rate/swing multiplier 0.95
Equipment sensible load 31804 Btuh
Latent Cooling Equipment Load Sizing
Structure 11638 Btuh
Ducts 1833 Btuh
Central vent (0 cfm) 0 Btuh
(none) 13471 Btuh
Equipment latent load
Equipment Total Load (Sen+Lat) 45275 Btuh
Req. total capacity at 0. 0 SHR 3.8 ton
Cooling Equipment Summary
Make Lennox
Trade Lennox
Cond XC 21-048-230
Coil CBA38MV-048-230
AHRI ref 295821582
Efficiency 13.0 EER, 18SEER
34650 Btuh
Sensible cooling 14850 Btuh
tal cooling Latentooing 49500 Btuh
ToActual airflow 2100 cfm
flow factor 0.066 cfm/Btuh
A r tic pressure 0.60 in H2O
Sta0.71
Load sensible heat ratio
Calculations approved byACCA to meet all requirements of Manual J 8th Ed
�_-P'�1-wrightsoft" Ri¢l9iterDUnves2i371919.0.13R5U2%44 �1
�CCP. C:1Uses�avesa�DaklcjArrtiftNP CaIc=MJ6 FrtrtDariaces: E
Job: 6601 S Indian River Drive,...
- Static Pressure and Friction Rate pate: Feb04,2022
wrightsoft'
Entire House By: Christopher Langel
Sea Coat Air Conditioning
3103IM2sirisl 31s1 Si d, FM Race, A 34946R'm T724832400
For: Robert Pruitt
6601 S Indian River Drive, Fort Pierce, FL 34982
Heating
Cooling
(in H2O)
(in H2O)
0.60
0.60
External static pressure
Pressure losses
0.10
0.10
Coil
0
0
Heat exchanger
0,03
0.03
Supply diffusers
0,03
0.03
Return grilles
0 08
0.08
Filter
0
0
Humidifier
0
0
Balancing damper
0
0
Other device
Available static pressure
0.36
0,36
Supply Retum
(ft) (10
Measured length of run -out 8
Measured length of trunk 11 0
Equivalent length of fittings 125 65
144 75
Total length 219
Total effective length
Heating Cooling
(in/100ft) (In0 064) OK
Supply Ducts 0.164 OK Return Ducts 0.164 OK 0.164 OK
Supply 11M=20,4P,D=60,11G=5,1A=35,11G=5:TotalEL=125
Return 6M=20, 5D=40,11G=5: TotalEL=65
((+�--- � WI'19h[SOi[` Ri<Jd9.itW Ultivesa1201919.0.13ft5J22694 �1
)CCIK C:Nsesav s \DWdOr\F U.rup Cac=MJs RorkD=fa : E
Job: 6601 S Indian War Drive,...
wrightsoft° Manual S Compliance Report Date: Feb04,2022
Entire House By: Christopher Langel
Sea Coat Air Conditioning
For: Robert Prum
6601 S Indian River Drive, Fort Pierce, FL 34982
Design Conditions
Outdoordesign DB: 90.5°F Sensible gain: 33303 Btuh
Outdoor designWB: 77.8°F Latent gain: 13471 Btuh
Indoor design DB: 75.0°F Total gain: 46773 Btuh
Indoor RH: 50% Estimated airflow: 2100 cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type:
SpIflAC
Manufacturer:
Lennox
Actual airflow:
2100
cfm
Sensible capacity:
34650
Btuh
Latent capacity:
14850
Btuh
Total capacity:
49500
Btuh
Design Conditions
Outdoor design DB: 43.0°F
Indoor design DB: 70.0°F
Model: XC 21-048-230+CBA38MV-048-230
104 %ofload
110% of load
106%ofload SHR: 70%
Heat loss: 24429 Btuh
Manufacturer's Performance Data at Actual Design Conditions
Equipment type:
Elec strip
Manufacturer:
Lennox Model: 9.6HeatStrip
Actual airflow:
2100 cfmOutput
capacity:
8.6 kW 120%ofload
Meets all requirements ofACCA Manual S.
Entering
coil DB:
76.7°F
Entering
coil WB:
63.3°F
Entering coil DB: 69.8°F
Temp. rise: 0 °F
d,zozzfmm n:nzsa
TF wrightsoft" RicjA3stt�UrvVesa1201919.0.13 RSU28GM �1
ACCA C:Nsesa esaDaM pw n.Np Cac=MJ6 FmA DoaNxa: E
Dining Room
243 c m
10x10
#: 6601 S Indian River Drive, Fort Pierce...
Performed by Christopher Langel for:
Robert Pmifl
6601 S Indian River Drive
Fort Pierce, FL 34982
Level 1
Sea CoatAir Conditioning
3108 Industrial 3l st Street
Fort Pierce, FL 34946
Phone: 772 466-2400
Scale: 1 : 95
Paget
RighMSuite®Universal 2019
19.0.13 RSU28644
2022-Feb-0811:44:02
C:\Use0avem a\DesktoPVruittruP
Sup Riser
1D"
Bdnn East
337 c(m
2x10
Bdrm East
#: 6601 S Indian River Drive, Fort Pier
Performed by Christopher Langel for:
Robert Pruitt
6601 S Indian River Drive
Fort Pierce, FL 34982
Level 2
Sup Riser Sup Riser
4" /10"
ATTIC
Bath 2 �
70 cfm Bdnn West
12x6 335 cfm
2x10
Stairs Bath 2
Bdrm West
HalMray
Sea CoatAir Conditioning
3108 IndusMal 31 st Street
Fort Pierce, FL 34946
Phone: 772 466-2400
Scale: 1 : 95
Page 1
Right-Suite®Universal 2019
19.0.13 RSU28644
2022-Feb-0811:44:02
C:\Use rs\aversaVesktoprpruitLrup