Loading...
HomeMy WebLinkAboutLetter - Wind Load Pressure Calculationse' .I RANFIELD ■--' CHITECTS 1683 N.E. JEN!�5EN 55ACH 6LVD. JEN�-5N EEAC�. FL O.RI[?A 34g57 PHONE: 7-2-203-6032 FAX: 772-283-5 50 . May 30, 2017 Project information: Islandia I 9550 S. Ocean Dr. Jensen Beach, FL Suite # 604 To whom it may concern: The following Wind Load Pressure Calculations have been performed at the aforementioned address utilizing the ASCE-7-10 (Part 4- Buildings with height of 15-80 ft) Components and Cladding pressure formulas and were performed at the request of the Contractor — Natural Flow. Building Information : Exposure D - Importance Factor #1 Height: 70 ft — 6"' Floor Wind Speed: 170 mph Minimum Required Opening Pressures: Openings that are 20 sgft to 50 : Zone 4 = +52.3 / -52.9 psf Zone 5 = +52.3 / -93.9 psf Openings that are 50 sgft to 100: Openings that are 100 sgft to 500: Zone 4 = +48.5 / -50.7 psf Zone 5 = +48.5 / -84.8 psf Zone 4 = +45.2 / -48.5 psf Zone 5 = +45.2 / -77.8 psf If there are any comments or concerns please contact me. Sincerely, Sfwra� Grr Stewart Granfield Granfield Architects PLLC ZOH-G zorl =- 15 6ra6hom k.h— b py