Option #1 Option #2
Installation Installation
Max. Design Pressure: -117.75 psf -206 psf
Fastener Spacing: 4" From Ends, 16" Max. O.C. 4" From Ends, 8" Max. O.C.
Min Panel Fasteners:
#10x1 ½” HiLo HWH Screw
with Weather-seal Washer
#10x1 ½” HiLo HWH Screw
with Weather-seal Washer
Fire Barrier: Where required by code, install an approved fire barrier. Refer to a current
fire directory listing for fire ratings of this roofing system assembly as well
as the location of the fire barrier within the assembly. (See note #2 below)
Note: Outside of the HVHZ, in areas with windspeeds < 170 mph, 1” round
plastic caps meeting the requirements of FBC Section 1507.1.1.1, may be
used to prevent galvanic reactions.
Underlayment: Minimum ASTM D 226 Type II, installed and anchored per FBC Section
1507.1.1.1 (min).
(or)
Any underlayment with a valid FLPA or Miami-Dade NOA
Note: Outside of the HVHZ, in areas with windspeeds < 170 mph, 1” round
plastic caps meeting the requirements of FBC Section 1507.1.1.1 may be
used to prevent galvanic reactions.
Minimum Substrate: ½’ (15/32” min) 4-ply CDX Plywood or ¾” solid wood planks (S.G. = .42
min) nailed to 2x rafters spaced 24” max. on center with 8d ring-shank
nails spaced 6” on center.
Note: The ¾” wood planking must be installed as a solid deck and must be
nailed or fastened in a manner equal to the deck above, or as specified by
a Florida licensed Architect/Engineer
Other Limitations: 1. Roof slope must meet requirements of FBC Sections 1507.4.2 or
1515.2.
2. Fire classification is not a part of this evaluation. Refer to a current
Approved Roofing Materials Directory for fire ratings of this product.
3. Design of substrate is by others and is not a part of this evaluation.