HomeMy WebLinkAbout4MgnthashTonyPereira-MS93764FINALDESIGNStamped (1)PLAN KEY
PV-1
COVER PAGE
PV-2
SITE PLAN
PV-3
PANEL SPECIFICATION
PV-3.1
PANEL LOAD TESTING RESULTS
PV-3.2
INVERTER SPECIFICATION
PV-3.3
COMBINER BOX SPECIFICATION
PV-3.4
JUNCTION BOX SPECIFICATION
PV-3.5
ATTACHMENT DETAIL
PV-3.6
STRUCTURAL CALCULATION
PV-3.7
SEALANT SPECIFICATION
PV-4
THREE LINE DIAGRAM
PV-4.1
ELECTRICAL NOTES
PV-4.2
EQUIPMENT LABELS
PV-5
STRUCTURAL CERTIFICATION
BUILDING INFORMATION/B.O.M.
# STORIES
1/15
ROOF AREA
2054.43
P.V. AREA
559
ROOFING TYPE
CORRUGATED METAL
ROOF PITCH
18
# RAILS
15
# L-FOOT ATTACHMENTS
42
# MODULES
29
# INVERTERS
29
# SKIRTS
0
# ENPHASE COMBINER BOXES
1
EATON 60A FUSIBLE SOLAR AC
DISCONNECT
1
40AFUSES
2
125A LINE TAPS
2
SYSTEAD INFORADATION
MODULE
HANWHA Q.PEAK DUO BLK-G10+ 360
INVERTER
ENPHASE IQ7-60-2-US
RACKING
SUNMODO EZ GRIP &
ECOFASTENCLICKFITSYSTEM 2-RAIL
SYSTEM SIZE (DC)
10.44 KW
LOCATION
27.3347256,-80.3328213
J
HANWHA Q.PEAK DUO BLK-G10+ 360
360 WATT MODULE
67.6" X 41.1" X 1.26"
(SEE DATASHEET)
THIS PV SYSTEM HAS BEEN DESIGNED TO MEET THE MINIMUM DESIGN STANDARDS FOR BUILDING AND OTHER
STRUCTURES OF THE ASCE 7-16, 7TH EDITION 2020 FLORIDA RESIDENTIAL CODE, 7TH EDITION 2020 FLORIDA
BUILDING CODE, 7TH EDITION 2020 FLORIDA FIRE PREVENTION CODE, NEC 2017 AND ALL LOCAL CODES &
ORDINANCES.
ROOF SHALL HAVE NO MORE THAN TWO LAYERS OF COVERING IN ADDITION TO THE SOLAR EQUIPMENT.
INSTALLATION OF SOLAR EQUIPMENT SHALL BE FLUSH MOUNTED, PARALLEL TO AND NO MORE THAN 6-INCHES
ABOVE THE SURFACE OF THE ROOF FOR SLOPED ROOF AND NO MORE THAN 10-INCHES ABOVE THE SURFACE OF
THE ROOF FOR FLAT ROOF.
ANY PLUMBING VENTS ARE NOT TO BE CUT OR COVERED FOR SOLAR EQUIPMENT INSTALLATION. ANY
RELOCATION OR MODIFICATION OF THE VENT REQUIRES A PLUMBING PERMIT AND INSPECTION.
ALL DESIGN, CALCULATIONS ARE PERFORMED BY DANIEL DUNZIK REGISTERED ARCHITECT. FLORIDA STATE
STATUTE 471.003(3) PROVIDES THAT LICENSED ARCHITECTS ARE EXEMPTED FROM THE PROVISIONS OF
CHAPTER 471 ENGINEERING AND NOT PRECLUDED FROM PERFORMING ENGINEERING SERVICES FOR INTEGRATED
SYSTEMS AND SERVICES THAT ARE INCIDENTAL TO THE DESIGN CONSTRUCTION OR ALTERATION OF BUILDINGS
AND STRUCTURES FOR HUMAN HABITATION.
INVERTER PLACEMENT:
SYSTEM UTILIZES "ENPHASE" MICRO -INVERTERS WITH RAPID SHUTDOWN CONTROL LOCATED ON THE BACK SIDE
OF EACH MODULE.
STRUCTURAL STATEMENT:
THE EXISTING STRUCTURE IS ADEQUATE TO SUPPORT THE NEW LOADS IMPOSED BY THE PHOTOVOLTAIC MODULE
SYSTEM INCLUDING UPLIFT & SHEAR.EXISTING RAFTER SIZES & DIMENSIONS CONFORM TO 7TH EDITION 2020
FLORIDA RESIDENTIAL CODE, 7TH EDITION 2020 FLORIDA BUILDING CODE SECTION 1512 THROUGH 1525 AND
SECTION 1616 THROUGH 1626 FOR HIGH VELOCITY HURRICANE ZONES.
FSEC CERTIFICATION STATEMENT:
PER FL. STATUE 377.705 , I, MINA A. MAKAR PE# 86753, CERTIFICATE OF AUTHORIZATION #33404, AN
ENGINEER LICENSED PURSUANT TO CHAPTER 471,CERTIFY THAT THE PV ELECTRICAL SYSTEM AND ELECTRICAL
COMPONENTS ARE DESIGNED AND APPROVED USING THE STANDARDS CONTAINED IN THE MOST RECENT
VERSION OF THE FLORIDA BUILDING CODE. FBC 2020
011 momentum
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
PROFESSIONAL
ENGINEERING
A. MA
• . k '.
��P ' �CENS
No PE86753
0 STATE OF
AIL
II
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Starn
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
SOLAR CONTRACTOR
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAIOR BLVD. SUITE 307, ORLANDO FL. 32819
CUSTOMER INFORMATION
TONY PEREIRA - MS93764
409 NORTHEAST OLEANDER AVENUE
PORT ST. LUCIE, FL 34952
7724465444
PV SYSTEM INFORMATION
SYSTEM SIZE (DC): 10.44 KW
29 MODULES: HANWHA Q.PEAK DUO
BLK-G10+ 360
29 INVERTERS: ENPHASE IQ7-60-2-US
I PROJECT INFORMATION I
I INITIAL I DATE: 2/10/2022 1 DESIGNER: SN I
(REV: (DATE: (DESIGNER:
(REV: (DATE: (DESIGNER:
COVER PAGE
PV-1
LU
w
0
z
Q
ww
0
Nw
LU
0
z
RAFTER SPACING
24" O.C. (TYP)
SITE PLAN
44'-0Ilk 2"
4'-411 ,ice
4'-4" 44'-0211
56'-6"
R1
SCALE: 1/8" = 1'-0"
NOTE:
1. ROOF COVERING MATERIAL IS COMPOSED OF CORRUGATED METAL
2. EXACT ATTACHMENT LOCATION AND QUANTITY OF ATTACHMENTS ARE BASED ON EXISTING RAFTER LOCATIONS OBTAINED FROM FIELD
MEASUREMENTS.. THE LOCATION AND QUANTITY OF ATTACHMENTS MAY VARY BASED ON RAFTER LAYOUT START POINT, SPACING
VARIATIONS AND ROOFING TYPE. VERIFY IN THE FIELD ALL RAFTER LOCATIONS AND ADJUST LAYOUT AS REQUIRED. A TILE ROOF WILL
PRODUCE A STAGERED ATTACHMENT LAYOUT BECAUSE OF EXISTING STAGERED TILE JOINT LOCATIONS
3. EXISTING RESIDENCE EQUIPPED WITH SMOKE/CO DETECTOR IN AND OUTSIDE OF ALL SLEEPING ROOMS HARDWIRED AND
INTERCONNECTED AS PER FEDERAL LAW
- V\/V I V 1 1 IL 1 /-ILIIV I%J 1 1 1 JI I/- 11YV
29 180 270° 95% momentum
SOLAR
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
PROFESSIONAL
ENGINEERING
`���,• ,,�CENSF •.� �
i
No PE86753
.p 4' _
0 STATE OF
4 ON
ONAL \E?C�
►►iiii1
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
334041 on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
CLAMPING MAX SPACING IN ZONE 1 48" O.0
AND IN ZONE 2 AND ZONE 3 24" O.0
SOLAR CONTRACTOR
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
CUSTOMER INFORMATION
SYMBOL LEGEND
TONY PEREIRA - MS93764
409 NORTHEAST OLEANDER AVENUE
PORT ST. LUCIE, FL 34952
7724465444
MSP
MAIN SERVICE PANEL
®
CHIMNEY
SP
SUB -PANEL
SKYLIGHT
PV SYSTEM INFORMATION
OM
UTILITY METER
®
VENT
SYSTEM SIZE (DC): 10.44 KW
29 MODULES: HANWHA Q.PEAK DUO
BLK-GIO+ 360
29 INVERTERS: ENPHASE IQ7-60-2-US
SOLAR
AC
D15C
SOLAR AC DISCONNECT
p
PIPE VENT
UDC
UTILITY DISCONNECT
FAN
LC
LOAD CENTER
SATELLITE DISH
PROJECT INFORMATION
INITIAL
DATE: 2/10/2022
DESIGNER:SN
N3R
NEMA 3R BOX W/ ENVOY-S
®
FIRE SETBACKS
REV:
DATE:
DESIGNER:
CB
COMBINER BOX
MIN 3'x3' GROUND ACCESS
POINT
REV:
DATE:
DESIGNER:
SITE PLAN
MODULE
PITCH DIRECTION
P V - 2
WIND PRESSURE ZONE LINES
THE IDEAL SOLUTION FOR:
ctRooftoP "
'I",
residential buildings
Engineered in Germany
MECHANICAL SPECIFICATION
Format 1717mm x 1045mm x 32mm (including frame)
a2mm
0°3b
Weight 19.9 kg
Front Cover 3.2 mm thermally pre -stressed glass with
antl-reflectlon technology
}
.o,aww„s eaa..aemm
r
a.
to I a.o,
Back Cover Composite film
Frame Black anodised aluminium
Cell 6 x 20 monocrystalline Q.ANTUM solar half cells
Junction box 53-101mm x 32-60mm x 15-18 mm
Protection class IP67, with bypass diodes
Cable 4mm2 Solar cable;(+) a1150mm, (-) a1150mm
Connector Staubll MC4; IP68
ammlO~Ie.smm
Quality ELECTRICAL CHARACTERISTICS
Controlled PV POWER CLASS 350 355 360 365 370
MINIMUM PERFORMANCE AT STANDARD TEST CONDITIONS, STC' (POWER TOLERANCE+5 W /-0 W)
1prPVT�
Power at MPP' Paw [W] 350 355 360 365 370
www.tuv.com Short Circuit Current' Isc [A] 10.97 11.00 11.04 11.07 11.10
ID 1111232615
E Open Circuit Voltage' Vpp IV] 41.11 41.14 41.18 41.21 41.24
Current at MPP I.. [A) 10.37 10.43 10.49 10.56 10.62
MGIRMA
'MYRVoltage at MPP Vaw IV] 33.76 34.03 34.31 34.58 34.84
ST TOP BRAND PV Efficiency' n [%] >_19.5 >_19.B >2D.1 >_20.3 >_2D.6
OER �I ' MINIMUM PERFORMANCE AT NORMAL OPERATING CONDITIONS,NMOT'
1v 'aoyr Power at MPP Paw (W] 262.6 266.3 270.1 273.8 277.6
2 221 E Short Circuit Current I� [A] 8.84 8.87 8.89 8.92 8.95
Warranty Q CELLS E
,«,��sea..a°,,,�c yield sacudry - Open Circuit Voltage V_ IV] 38.77 38.80 38.83 38.86 38.90
Current at MPP I.. [A] 8.14 8.20 8.26 8.31 8.37
Voltage at MPP Vaw IV] 32.24 32.48 32.71 32.94 33.17
'Measurement tolerances Paw :3%; Iso; Vc� x5% at STC: 1000 W/m2, 25t2'C, AM 1.5 according to IEC 60904-3.2800 W/m2, NMOT, spectrum AM 1.5
BREAKING THE 20 % EFFICIENCY BARRIER O CELLS PERFORMANCE WARRANTY PERFORMANCE AT LOW IRRADIANCE
Q.ANTUM DUO Z Technology with zero gap cell layout y ----,
ii
At least 98%of nominal power dur- � i '
> x,.....� --boostsmoduleefficienc u to 20.9%. UW mgnra Thereaftermaxt93.5Y P rear.------------ degradation per year. At least 93.5%
u, of nominal power up to 10 Years. At s xao
THE MOST THOROUGH TESTING PROGRAMME IN THE INDUSTRY 3 least 86% of nominal power up to tb
�_ Q CELLS is the first solar module manufacturer to pass the most comprehen- Wo zsyears.
Q sive quality programme in the industry: The new "Quality Controlled PV" of the All data within measurement toler- p
v�r ancindependent certification institute TUV Rheinland. es. Full warranties in accordance 00
Pe with the warranty terms of the a0° t00°
Uu Q CELLS sales organisation of your 800 IRRADI-EIW/mx7
INNOVATIVE ALL-WEATHER TECHNOLOGY m YE111 respective country. Typical
�%- Optimal yields, whatever the weather with excellent oma module TCperconditions
under low irradiance conditions in
�"� ' comparison to STC conditions(25°C, 1000W/m2).
` low -light and temperature behaviour. TEMPERATURE COEFFICIENTS
Temperature Coefficient of lae a [%/K] +0.04 Temperature Coefficient of Voc D [%/K] -0.27
- ENDURING HIGH PERFORMANCE Temperature Coefficient of PaEE Y [%/K] -0.34 Nominal Module Operating Temperature NMOT [^Cl 43±3
Long-term yield security with Anti LID Technology, Anti PID
Technology', Hot -Spot Protect and Traceable Quality Tra.Q-. PROPERTIES FOR SYSTEM DESIGN
Maximum System Voltage Vsys IV] 1000 PV module classification Class 11
EXTREME WEATHER RATTING Maximum Reverse Current le [A] 20 Fire Rating based on ANSI/UL 61730 C/TYPE2
High-tech aluminium alloy frame, certified for
high snow (5400 Pa) and wind loads (4000 Pa). Max. Design Load, Push/Pull [Pa] 3600/2660 Permitted Module Temperature-40°C-+85°C
Max. Test Load, Push/Pull [Pal 5400/4000 on Continuous Duty
A RELIABLE INVESTMENT
g� Inclusive 25-year product warranty and 25-year QUALIFICATIONS AND CERTIFICATES
linear performance warranty2.
Quality Controlled pV -TUV Rheinland;
IEC 61215:2016; IEC 61730:2016.
' APT test conditions according to IEC /TS 62804-1:2015, method A(-1500V, 96h) Tni,detasheet complies ro w
2 See date sheet on rear for further information. Witt, DIN EN 50380. (\
QCPv Certification oN.irg. mxx„xxmn
Note: Installation instructions must be followed. See the installation and operating manual or contact our technical service department for further information on approved installation and
use of this product.
Menwha f3 CELLS OmbN
Sonnenallee 17-21, 06766 Bitterfeltl-Wolfen, Germany I TEL+49 (0)3494 66 99-234441 FAX +49 (0)3494 66 99-230001 EMAIL seles@q-cells.com I WEB www.q-cells.com
Q CELLS I Engineered in Germany
QCELLS
momentum
SOLAR
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
PROFESSIONAL
ENGINEERING
```xx%%IIIIII/////
.� A Mq
�P .....
%GENs
i
No PE86753
_- 06 7C 4: ,
0 STATE OF
F�ORIDP'.
ONAL \E?C�
111111
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
334041 on the Date and Time Stamr
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
SOLAR CONTRACTOR
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
CUSTOMER INFORMATION
TONY PEREIRA - MS93764
409 NORTHEAST OLEANDER AVENUE
PORT ST. LUCIE, FL 34952
7724465444
PV SYSTEM INFORMATION
SYSTEM SIZE (DC): 10.44 KW
29 MODULES: HANWHA Q.PEAK DUO
BLK-G10+ 360
29 INVERTERS: ENPHASE IQ7-60-2-US
I PROJECT INFORMATION I
I INITIAL I DATE: 2/10/2022 I DESIGNER: SN I
IREV: IDATE: IDESIGNER:
IREV: IDATE: IDESIGNER:
PANEL SPECIFICATION
PV-3
QCELLS
Document issue date: 2021-02-19
This authorization document ("Authorization Document") is issued and released by Hanwha Solutions Corporation on behalf
of the respective warrantor as named in the Hanwha Q CELLS Limited Warranty for crystalline photovoltaic modules
("Warranty").
1. We hereby confirm that the MODULE TYPE mounted in the CLAMP POSITION referenced in Table A, is in
compliance with the requirement of UL1703/61730, and has successfully passed a pull test load of 4000 Pa and a
max pull load of 5400 Pa in accordance with the UL 61730 standard
Table A.
OF CLAMP
TEST LOAD [Pa]
DESIGN LOAD [Pa]
MODULE TYPE
MOUNTING OPTION
POSITION [mm]
(Push /Pull)
(Push /Pull)
Q.PEAK DUO BLK-G6+/HL
Clamping at long
250 — 350
+5400 / -5400
+3600 / -3600
Q.PEAK DUO BLK-G6+/AC
modules sides
(9.84 -13.78 in)
(112.8 psf)
(75.2 psf)
Q.PEAK DUO-G6+/AC
("CL1")
NOTE:
Distance between outer edge of module and middle of the clamp
The stability of the mounting system including the clamps and fixation of the modules must be secured by a certified system
supplier.
2. As long as you adhere to the terms and conditions of this Authorization Document and the Warranty, the MODULE
TYPE, mounted and clamped as instructed in the installation manual, shall be covered by the Warranty
3. Please note that no revisions are made to the existing terms of the Warranty. The terms of the Warranty shall remain
AS IS, except as specifically referenced in this Authorization Document
4. The Warranty shall not apply to damages of the solar module backsheet and junction box caused by the mounting
subconstruction.
5. Customer may not transfer, assign or delegate any of its rights or obligation hereunder to any other person, without
the prior written consent of Hanwha Solutions Corporation
6. Any information contained in this Authorization Document is confidential and no part of this Authorization
Document may be reproduced, stored in a retrieval system or transmitted in any form or by any means, electronic,
mechanical, photocopying, recording or otherwise, without the prior written consent of Hanwha Solutions
Corporation
Q CELLS is a brand of Hanwha Solutions Corporation.
Hanwha Solutions Corporation
23F, 86 Cheonggyecheon-ro,Jung-gu, Seoul,Korea 04541
T. +82 (0)2 6049 0520, F: +82 (0)2 729 1372, W: \ w .q-cells.com
0 momentum
SOLAR
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
PROFESSIONAL
ENGINEERING
`- 0CENSF
i
No PE86753
0 STATE OF
ONAL \E?C�
/111111
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
334041 on the Date and Time Stamr
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
SOLAR CONTRACTOR
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
CUSTOMER INFORMATION
TONY PEREIRA - MS93764
409 NORTHEAST OLEANDER AVENUE
PORT ST. LUCIE, FL 34952
7724465444
PV SYSTEM INFORMATION
SYSTEM SIZE (DC): 10.44 KW
29 MODULES: HANWHA Q.PEAK DUO
BLK-G10+ 360
29 INVERTERS: ENPHASE IQ7-60-2-US
I PROJECT INFORMATION I
[INITIAL [ DATE: 2/10/2022 I DESIGNER: SN [
IREV: IDATE: IDESIGNER:
REV: IDATE: IDESIGNER:
PANEL LOAD TESTING
RESULTS
PV-3.1
Data Sheet
Enphase Microinverters
Region: AMERICAS
Enphase
IQ 7 and IQ 7+
Microinverters
V�
To learn more about Enphase offerings, visit enphase.com
The high-powered smart grid -ready
Enphase IQ 7 Micro'" and Enphase IQ 7+ MicrOTM
dramatically simplify the installation process while
achieving the highest system efficiency.
Part of the Enphase IQ System, the IQ 7 and
IQ 7+ Microinverters integrate with the Enphase
IQ Envoy', Enphase IQ Battery'", and the Enphase
Enlighten' monitoring and analysis software.
IQ Series Microinverters extend the reliability
standards set forth by previous generations and
undergo over a million hours of power -on testing,
enabling Enphase to provide an industry -leading
warranty of up to 25 years.
Easy to Install
Lightweight and simple
Faster installation with improved, lighter two -wire cabling
Built-in rapid shutdown compliant (NEC 2014 & 2017)
Productive and Reliable
Optimized for high powered 60-cell and 72-cell* modules
More than a million hours of testing
Class II double -insulated enclosure
UL listed
Smart Grid Ready
Complies with advanced grid support, voltage and
frequency ride -through requirements
Remotely updates to respond to changing
grid requirements
Configurable for varying grid profiles
Meets CA Rule 21 (UL 1741-SA)
* The IQ 7+ Micro is required to support 72-cell modules.
nENPHASE
Enphase IQ 7 and IQ 7+ Microinverters
INPUT DATA (DC)
IQ7-60-2-US / IQ7-60-B-US I07PLUS-72-2-US/I07PLUS-72-9-US
Commonly used module pairings'
235 W - 350 W + 235 W -440 W+
Module compatibility
60-cell PV modules only 60-cell and 72-cell PV modules
Maximum input DC voltage
48 V 60 V
Peak power tracking voltage
27 V - 37 V 27 V - 45 V
Operating range
16 V - 48 V 16 V - 60 V
Min/Max start voltage
22 V / 48 V 22 V / 60 V
Max DC short circuit current (module Isc)
15 A 15 A
Overvoltage class DC port
II II
DC port backfeed current
0 A 0 A
PV array configuration
1 x 1 ungrounded array; No additional DC side protection required;
AC side protection requires max 20A per branch circuit
OUTPUT DATA (AC)
IQ 7 Microinverter IQ 7+ Micrainverter
Peak output power
250 VA 295 VA
Maximum continuous output power
240 VA 290 VA
Nominal (L-L) voltage/range2
240 V / 208 V / 240 V / 208 V /
211-264 V 183-229 V 211-264 V 183-229 V
Maximum continuous output current
1.0 A (240 V) 1.15 A (208 V) 1.21 A (240 V) 1.39 A (208 V)
Nominal frequency
60 Hz 60 Hz
Extended frequency range
47 - 68 Hz 47 - 68 Hz
AC short circuit fault current over 3 cycler
5.8 Arms 5.8 Arms
Maximum units per 20 A (L-L) branch circuit'
16 (240 VAC) 13 (208 VAC) 13 (240 VAC) 11 (208 VAC)
Overvoltage class AC port
III III
AC port backfeed current
0 A 0 A
Power factor setting
1.0 1.0
Power factor (adjustable)
0.7 leading ... 0.7 lagging 0.7 leading ... 0.7 lagging
EFFICIENCY
@240 V @208 V @240 V @208 V
Peak CEC efficiency
97.6 % 97.6 % 97.5 % 97.3 %
CEC weighted efficiency
97.0 % 97.0 % 97.0 % 97.0 %
MECHANICAL DATA
Ambient temperature range
-400Cto+650C
Relative humidity range
4%to 100%(condensing)
Connector type (IQ7-60-2-US & IQ7PLUS-72-2-US) MC4 (or Amphenol H4 UTX with additional Q-DCC-5 adapter)
Connector type (IQ7-60-B-US & IQ7PLUS-72-B-US) Friends PV2 (MC4 intermateable).
Adaptors for modules with MC4 or UTX connectors:
PV2 to MC4: order ECA-S20-S22
- PV2 to UTX: order ECA-S20-S25
Dimensions (WxHxD)
212 mm x 175 mm x 30.2 mm (without bracket)
Weight
1.08 kg (2.38 Ids)
Cooling
Natural convection - No fans
Approved for wet locations
Yes
Pollution degree
PD3
Enclosure
Class II double -insulated, corrosion resistant polymeric enclosure
Environmental category / UV exposure rating
NEMA Type 6 / outdoor
FEATURES
Communication
Power Line Communication (PLC)
Monitoring
Enlighten Manager and MyEnlighten monitoring options.
Both options require installation of an Enphase IQ Envoy.
Disconnecting means
The AC and DC connectors have been evaluated and approved by UL for use as the load -break
disconnect required by NEC 690.
Compliance
CA Rule 21 (UL 1741-SA)
UL 62109-1, UL1741/IEEE1547, FCC Part 15 Class B, ICES-0003 Class B,
CAN/CSA-C22.2 NO. 107.1-01
This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC-2014 and
NEC-2017 section 690.12 and C22.1-2015 Rule 64-218 Rapid Shutdown of PV Systems, for AC
and DC conductors, when installed according manufacturer's instructions.
1. No enforced DC/AC ratio. See the compatibility calculator at httos://enphase.com/en-us/support/module-como�atibility.
2. Nominal voltage range can be extended beyond nominal if required by the utility.
3. Limits may vary. Refer to local requirements to define the number of microinverters per branch in your area.
To learn more about Enphase offerings, visit enphase.com n E N P H AS E
@ 2018 Enphase Energy. All rights reserved. All trademarks or brands used are the property of Enphase Energy, Inc.
2018-05-24
isino�z_l-e,
SOLAR
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
PROFESSIONAL
ENGINEERING
`��� . �r,CENSF •.� �
I
No PE86753
00 4:,
��0 STATE OF
ONAL \E?C�
/fi'111\
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
334041 on the Date and Time Staml
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
SOLAR CONTRACTOR
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
CUSTOMER INFORMATION
TONY PEREIRA - MS93764
409 NORTHEAST OLEANDER AVENUE
PORT ST. LUCIE, FL 34952
7724465444
PV SYSTEM INFORMATION
SYSTEM SIZE (DC): 10.44 KW
29 MODULES: HANWHA Q.PEAK DUO
BLK-G10+ 360
29 INVERTERS: ENPHASE IQ7-60-2-US
I PROJECT INFORMATION I
I INITIAL I DATE: 2/10/2022 I DESIGNER: SN I
IREV: IDATE: IDESIGNER:
IREV: IDATE: IDESIGNER:
INVERTER SPECIFICATION
PV-3.2
Data Sheet
Enphase Networking
Enphase
IQ Combiner 3
(X-IQ-AM1-240-3)
U�
LISTED
To learn more about Enphase offerings, visit enphase.com
The Enphase IQ Combiner 3TM with Enphase
IQ Envoy'" consolidates interconnection
equipment into a single enclosure and
streamlines PV and storage installations by
providing a consistent, pre -wired solution for
residential applications. It offers up to four
2-pole input circuits and Eaton BR series
busbar assembly.
Enphase IQ Combiner 3
MODEL NUMBER
IQ Combiner 3 IQ Combiner 3 with Enphase IQ Envoy- printed circuit board for integrated revenue grade PV
X-10-AM1-240-3 Droduction metering (ANSI C12.20+/- 0.5%) and optional* consumption monitorina (+/- 2.5%).
Enphase Mobile Connect'
CELLMODEM-03 (4G/1 2-year data plan)
Plug and play industrial grade cellular modem with data plan for systems up to 60
CELLMODEM-01 (3G/5-year data plan)
microinverters. (Available in the US, Canada, Mexico, Puerto Rico, and the US Virgin Islands,
CELLMODEM-M1 (4G based LTE-M/5-year data plan)
where there is adequate cellular service in the installation area.)
Consumption Monitoring* CT
Split core current transformers enable whole home consumption metering (+/- 2.5%).
CT-200-SPLIT
• Consumption monitoring is required for Enphase Storage Systems
Wireless USB adapter
Installed at the IQ Envoy. For communications with Enphase Encharge' storage and Enphase
COMMS-KIT-01
Enpower' smart switch. Includes USB cable for connection to IQ Envoy or Enphase IQ Combiner'"
and allows redundant wireless communication with Encharge and Enpower.
Circuit Breakers
Supports Eaton BR210, BR215, BR220, BR230, BR240, BR250, and BR260 circuit breakers.
BRK-10A-2-240
Circuit breaker, 2 pole,10A, Eaton BR210
BRK-15A-2-240
Circuit breaker, 2 pole,15A, Eaton BR215
BRK-20A-2P-240
Circuit breaker, 2 pole, 20A, Eaton BR220
EPLC-01
Power line carrier (communication bridge pair), quantity - one pair
XA-PLUG-120-3
Accessory receptacle for Power Line Carrier in IQ Combiner 3 (required for EPLC-01)
XA-ENV-PCBA-3
Replacement IQ Envoy printed circuit board (PCB) for Combiner 3
ELECTRICAL SPECIFICATIONS
Rating Continuous duty
System voltage 120/240 VAC, 60 Hz
Eaton BR series busbar rating 125 A
Max. continuous current rating (output to grid) 65 A
Max. fuse/circuit rating (output) 90 A
Branch circuits (solar and/or storage)
Up to four 2-pole Eaton BR series Distributed Generation (DG) breakers only (not included)
Smart
Max. continuous current rating (input from PV)
64 A
Includes IQ Envoy for communication
Max. total branch circuit breaker rating (input)
80A of distributed generation / 90A with IQ Envoy breaker included
and control
Production Metering CT
200 A solid core pre -installed and wired to IQ Envoy
Flexible networking supports Wi-Fi,
MECHANICAL DATA
Ethernet, or cellular
Dimensions (WxHxD)
49.5 x 37.5 x 16.8 cm (19.5" x 14.75" x 6.63"). Height is 21.06" (53.5 cm with mounting brackets).
Optional AC receptacle available for PLC
Weight
7.5 kg (16.5 Ibs)
bridge
Ambient temperature range
-40° C to+46° C (-400 to 115° F)
Provides production metering and optional
consumption monitoring
Cooling
Natural convection, plus heat shield
Enclosure environmental rating
Outdoor, NRTL-certified, NEMA type 3R, polycarbonate construction
Wire sizes 20 A to 50 A breaker inputs: 14 to 4 AWG copper conductors
Simple 60 A breaker branch input: 4 to 1/0 AWG copper conductors
Main lug combined output: 10 to 2/0 AWG copper conductors
Reduced size from previous combiner Neutral and ground: 14 to 1/0 copper conductors
Centered mounting brackets support single Always follow local code requirements for conductor sizing.
Altitude To 2000 meters (6,560 feet)
stud mounting
INTERNET CONNECTION OPTIONS
Supports back and side conduit entry
Integrated Wi-Fi 802.11b/g/n
Up to four 2-pole branch circuits for 240 VAC
plug-in breakers (not included) Ethernet Optional, 802.3, Cat5E (or Cat 6) UTP Ethernet cable (not included)
80 A total PV or storage branch circuits Cellular Optional, CELLMODEM-01 (3G) or CELLMODEM-03 (4G) or CELLMODEM-M1 (4G based LTE-M)
(not included)
COMPLIANCE
Reliable
Durable NRTL-certified NEMA type
31R enclosure
Five-year limited warranty
UL listed
Compliance, Combiner UL 1741, CAN/CSA C22.2 No. 107.1, 47 CFR, Part 15, Class B, ICES 003
Production metering: ANSI C12.20 accuracy class 0.5 (PV production)
Compliance, IQ Envoy UL 60601-1/CANCSA 22.2 No. 61010-1
To learn more about Enphase offerings, visit enphase.com
02018 Enphase Energy. All rights reserved. Enphase, the Enphase logo, IQ Combiner 3, and other trademarks or service names are the
� E N P H A S E trademarks of Enphase Energy, Inc. E N P H A S E
`/ 2019-11-04
isino�z_l-e,
SOLAR
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
PROFESSIONAL
ENGINEERING
`���,• ,,r,CENSF ••� ♦
No PE86753
0 STATE OF
ONAL \E?C�
/111111
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
334041 on the Date and Time Staml
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
SOLAR CONTRACTOR
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
CUSTOMER INFORMATION
TONY PEREIRA - MS93764
409 NORTHEAST OLEANDER AVENUE
PORT ST. LUCIE, FL 34952
7724465444
PV SYSTEM INFORMATION
SYSTEM SIZE (DC): 10.44 KW
29 MODULES: HANWHA Q.PEAK DUO
BLK-G10+ 360
29 INVERTERS: ENPHASE IQ7-60-2-US
I PROJECT INFORMATION I
I INITIAL I DATE: 2/10/2022 I DESIGNER: SN I
IREV: IDATE: IDESIGNER:
IREV: IDATE: IDESIGNER:
MBINER BOX SPECIFICATIO
PV-3.3
DESCRIPTION:
JUNCTION BOX XL FOR RAIL
DRAWN BY:
mwatkins
���������
DESCRIPTION:
JUNCTION BOX XL FOR RAIL
DRAWN BY:
mwatkins
nn
5 i1�`�i1Ora&
REVISION:
Solar Mounting Solutions
REVISION:
Solar Mounting Solutions
PART NUMBER(S):
A
595 MARKET STREET, 28TH FLOOR • SAN FRANCISCO, CA .105 USA
PART NUMBER(S):
A
585 MARKET STREET, 29TH FLOOR • SAN FRANCISCO. CA 941 OS USA
242-92120
PHONE (415) SOM900 • FAX (415) 580-6902
RE%tOWCTION,DISCLOSURE,OR USE THEREOF IS PROx131TED WITROUTTRE
EN CON—Ta SUNKN SOUTH LLC.
242-92120
PHONE (415) 5806900 • FAX (415) 5868902
THE MFORMATOrvIN THISDMWIrvG IB CONFIDExTIuuiOOROFRIETMv. wNT
REPRODUCTION. LOSURE, ORUBE THEREOF IS PROHI&TED WITMUT THE
2.56
5.00
.80
�n
2.058011,41—
4.43
5.75
2 88
7.629
05.75 7.36
j
1
®
2.88
BOB
10.11
9.86
11.19
®�
3
10.66
10.11
10.37
4.07
1.00
3.2
1.19
74
.50
5.00
® 4 2
PARTS LIST
ITEM QTY
DESCRIPTION
1 1 SNAPNRACK, JUNCTION BOX XL (BARE)
2 2 SNAPNRACK, J BOX RAIL BRACKET
3 1 BOLT, FLANGED HEX, 5/16IN-18 X 1-1/4IN, SS
4 1 SNAPNRACK CHANNEL NUT 5/16IN-18
MATERIALS:
POLYCARBONATE, CLOSED
CELL FOAM, ALUMINUM, STAINLESS STEEL
DESIGN LOAD (LBS):
N/A
ULTIMATE LOAD (LBS):
N/A
TORQUE SPECIFICATION:
5 (CHANNEL NUT), 3 (LID) LB -FT
CERTIFICATION:
UL50/UL50E, NEMA 4X RATING
3.80
ALL DIMENSIONS IN INCHES
WEIGHT (LBS):
momentum
• •'
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, N3
(732)902-6224
MOMENTUMSOLAR.COM
PROFESSIONAL
ENGINEERING
````11111111/11/''
o
No PE86753
'0 4:
0 STATE OF 4(-
............ A�ORIDP'.•' ���
�!
'���Sis��NAL lE� ��♦
/llllll
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
SOLAR CONTRACTOR
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
CUSTOMER INFORMATION
TONY PEREIRA - MS93764
409 NORTHEAST OLEANDER AVENUE
PORT ST. LUCIE, FL 34952
7724465444
PV SYSTEM INFORMATION
SYSTEM SIZE (DC): 10.44 KW
29 MODULES: HANWHA Q.PEAK DUO
BLK-G10+ 360
29 INVERTERS: ENPHASE IQ7-60-2-US
I PROJECT INFORMATION I
I INITIAL I DATE: 2/10/2022 1 DESIGNER: SN I
ROOF JUNCTION BOX SPECIFICATION FOR LOW-SLOPE/TILE/METAL/CONCRETE ROOF REV: DATE: DESIGNER:
REV: DATE: DESIGNER:
JUNCTION BOX SPECIFICATIONI
PV-3.4
/A PUN VIEW, COMP ASSEMBLY, PO—'- MODULE
Sole: I"=1'-0"
END CAP AND CLAMP
ROOF SURFACE L FOOT
G
E
PV MODULE )
RAIL 1.l MID CLAMP
\
L13 MAX.
L
\
(` FRONT VIEW, COMP ASSEMBLY, PORTRAIT MODULE
Scale: 1"=1'-0"
(g SIDE VIEW, COMP ASSEMBLY, PORTRAIT MODULE
Scale: 1"=1'-O"
(rPVMODUUEFRAME
MID CLAMP
D DEfAI4 MID CLAMP PLAN
Scale: 6"=I'-0"
END CAP
PV MODULE FRAME
t END CLAMP
�1 DEfAI4 END CAP AND CLAMP PLAN
Scale: 6"=1'-0"
Ifl
MID CLAMP
W MODULE
FRAME
RAILS
E DET MIO CIAMP FRONT
*E"DLAMP
PV MODULE FRAME
END CAP
RAILS
(1 DEFAIL. END CAP AND CLAMP FRONT
Sole: 6"=1'-0"
IN 1/2" PLYWOOD
LOAD DIRECTION
FOS=2
FOS=3
UPLIFT
345
230
LATERAL.PERP. TO SLOT 1
1401
95
LATERAL.PARALLELTO SLOT 1
2651
175
IN 7116" OSB
LOAD DIRECTION
FOS=2
FOS=3
UPLIFT
190
125
LATERAL.PERP. TO SLOT
125
85
LATERAL.PARALLEL TO SLOT
1351
90
PORTRAIT
NOTES
Factor of Safety as shown
Torque at 3/8" T-Bolt = 15ft.lbs (20 N.m)
All loads in pounds force
Values valid only for conditons equal or better than test conditions
Values valid only when product is used in accordance with SunModo
installation instruction and other technical documentation
* The kit as shown in the BOM. For alternative configurations, contact
SunModo
4 1/4" Deck Screws in Min 7/16" OSB
B15018-001 HEX CAP SCREW 3/8-16 X 3/4
C50001-001 GASKET, EPDM, WITH ADHESIVE
B15003-001 IFLANGE NUT 318-16
B15039-001
HEX WASHER HEAD LAG BOLT 1/4X3
A50224-001
METAL ROOF DECK MOUNT
PART NUMBER
DESCRIPTION C
SEE ES
SunModo Corp.
14800 NE 65TH STREET, VANCOUVER WA 98682
P-0-i-
len�"":
Nin1°'"""°I
152ammi
°aml
Le METAL ROOF DECK MOUNT KIT
ioiisi201a
B
Awwc num aEK50532-001 STRUCTURE
SCALE: NONE SHEET 1 of 1
Company Feb 19, 2021
Designer 06.43 AM
Job Number: Checked By:_
Section Properties: Sectionl_450124 (REVX03).DXF
Section Information:
Matenal Type
= General
Shape Type
= Arbitrary
Number of Shapes
= 1
Basic Properties:
Total Width
= 1.575
in
Total Heigh
= 1.675
in
Centroid, Xo
= 0.ODO
in
Centmid, Yo
= 0.785
in
X-Bar(Right)
= 0.787
in
X-Bar(Left)
= 0.787
in
Y-Bar(Top)
= 0.788
In
Y-Bar (Sot)
= 0.786
in
Max Thick
Equivalent Properties:
Area, Ax
= 1.675
= 0.373
in
W2
Inertia, Im
= 0.151
in14
Inertia, lyy
0.100
i14
Inertia, Ixy
- -0.000
in14
Sx(TOP)
= 0.191
in-3
Six(BoU
= 0.191
in-3
BY(LeR)
= 0.126
inA3
By (Right)
= 0.128
in-3
nr
= 0.635
in
ry
= 0.518 in
Plastic Zx
= 0.222 in-3
Plastic Zy
0.180 in-3
Torsional J
- <No Cal-
AsDef
= 1.0D0
As yy Def
= 1.000
As-xz Stress
= 1.DD0
As-yy Stress
= 1.OD0
Section Diagram
C:\RISA\SectionProjecti Page 2
30 of 31
SUNM* ^:3
EZ GRIP METAL DECK MOUNT
Make your next metal roof
attachment without the
daunting task of locating the
truss. SunModo's EZ Grip Metal
Deck Mount installs into 26 gauge
sheet metal, 1/2 plywood or 7/16 OSB
roof decking material.
SunModo's EZ Grip Metal Deck Mount
installs in just minutes into sheet metal,
plywood or OSB roof decking. The four
included 1/4 x 3" Hex Washer Head Self -tapping Screws have the length to penetrate though 1-1/2
inches of insulation while still piercing completely through the roof decking. And since the four
screws are guided by the aluminum extruded base to penetrate at a 3o-degree angle, the Metal
Roof Deck Mount Kit offers superior attachment performance. 1/4-20 Self -drilling screws can be
used for attachments into 26 gauge minimum thickness metal roofs.
The EZ Grip Metal Deck Mount is designed to fit
on the most popular R-Panel and U-Panel _
trapezoidal types of metal roofs. The aluminum
extruded base easily clears roof profiles 7/16"
tall by 1-1/2" wide. The EPDM gaskets on the _
washers and on the aluminum extruded base
combine to provide a water tight seal at the
roof penetration site.
Features and Benefits
• Attaches into 1/2 plywood or 7116 OSB roof decking material using four 1/4 x 3" Hex Washer
Head Self -tapping Screws
• Attaches into 26 gauge minimum thickness sheet metal using four 1/4 x 2" Hex Washer Head
Self -drilling Screws
• Angled penetrations provide superior attachment performance
• A wide variety of L-feet and attachment options are available
• Passed the High -Velocity Hurricane Zone (HVHZ)-TAS ioo(a) Wind -Driven Rain Test
SunModo Corp I Vanaouvar, WA 1360-844-0048
Document Number D10153-VO03102019 - SunModo Corp.
SOLAR
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
PROFESSIONAL
ENGINEERING
.� A
�P .....
0- • ,,�CENSF
i
No PE86753
00 4:,
0 STATE OF
F4ORI0Qa.
Sis/ONAL
0111111\
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Starn
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
SOLAR CONTRACTOR
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
CUSTOMER INFORMATION
TONY PEREIRA - MS93764
409 NORTHEAST OLEANDER AVENUE
PORT ST. LUCIE, FL 34952
7724465444
PV SYSTEM INFORMATION
SYSTEM SIZE (DC): 10.44 KW
29 MODULES: HANWHA Q.PEAK DUO
BLK-G10+ 360
29 INVERTERS: ENPHASE IQ7-60-2-US
I PROJECT INFORMATION I
I INITIAL I DATE: 2/10/2022 I DESIGNER: SN I
IREV: IDATE: IDESIGNER:
IREV: IDATE: IDESIGNER:
ATTACHMENT DETAIL
ATTACHMENT DETAIL FOR CORRUGATED METAL ROOF
PV-3.5
ALLOWABLE LOAD / ATTACHMENT 5/16" LAG SCREW W/ 3.00" EMBEDMENT INTO RAFTER
BELOW ACCORDING TO THE NATIONAL DESIGN SPECIFICIFICATION FOR WOOD
CONSTRUCTION 2015 EDITION. = W' = W X CD X CT. - PER TABLE 11.3.1 NDS
5/16" DIA. 4" LONG LAG W/ 3.00" EMBEDMENT INTO 2X ROOF RAFTER
W' = 266LB/IN (NDS11.3.1 TABLE 12.2A) FOR DF. LARCH, S.Y.P., AND S.P.F. SPECIES
CD = 1.6 (TABLE 2.3.2 2015 NDS), CT = 1.0 (TABLE 10.3.4 2015 NDS)
W' = 266LB/IN X 3.00" X 1.6 X 1.0 = 1,276.8LBS = ULTIMATE
MAX ALLOWABLE UPLIFT PRESSURE WITH 60% OF ULTIMATE CAPACITY
1,276.8LBS X 0.6 = 766.08LBS
-THREAD MUST BE EMBEDDED IN THE SIDE GRAIN OF A TRUSSES OR OTHER
STRUCTURAL MEMBER INTEGRAL WITH THE BUILDING STRUCTURE.
-LAG BOLTS MUST BE LOCATED IN THE MIDDLE THIRD OF THE STRUCTURAL MEMBER.
-THESE VALUES ARE NOT VALID FOR WET SURFACE.
-INSTALL LAG BOLTS WITH HEAD AND WASHER FLUSH TO SURFACE (NO GAP). TORQUE
AS PER MANUFACTURERS SPECIFICATIONS. DO NOT OVER -TORQUE.
-WITHDRAWAL DESIGN VALUES FOR LAG SCREW CONNECTIONS SHALL BE MULTIPLIED
BY APPLICABLE ADJUSTMENT FACTORS IF NECESSARY. SEE TABLE 10.3.1 IN THE
AMERICAN WOOD COUNCIL NDS FOR WOOD CONSTRUCTION.
WIND PRESSURE ZONE CALCULATION (ASCE FIGURE 30.4-2A, 2B)
HORIZONTAL DIMENSION A
44.0400009155273'
X 10% = 4.40400009155273'
HORIZONTAL DIMENSION B
56.599998474121'
X 10% = 5.6599998474121'
BUILDING HEIGHT
15'
X 40% = 6'
PRESSURE ZONE WIDTH
4' 4.85 "
10 % OF LEAST HORIZONTAL DIMENSION OR 40% OF THE BUILDING HEIGHT WHICHEVER IS
SMALLER BUT NOT LESS THAN EITHER 4% OF THE LEAST HORIZONTAL DIMENSION OR 3'-0"
WIND LOAD CALCULATIONS (ASCE 7-16 EQ. 29.4-7)
VELOCITY PRESSURE Qh = 0.00256 Kz*Kzt*Kd*Ke *VA 2(LB/SQFT) (EQ. 26.10-1)
DESIGN LOAD CRITERIA. AS PER ASCE 7-16 (2.4.1)
FOR THIS PARTICULAR CASE, THE "DOWNFORCE" CASE 2 AND
UPLIFT HAVE BEEN TAKEN INTO CONSIDERATION.
P (PSF) = 1xD + 1x PNET (DOWNFORCE)
P (PSF) = 0.6xD + 0.6x PNET (UPLIFT)
(P = TOTAL DESIGN LOAD)
(PNET = WIND LOAD)
(D = DEAD LOAD)
PNET HAVE BEEN CALCULATED FOLLOWING THE ALLOWABLE STRESS DESIGN METHOD.
THE MAXIMUM ABSOLUTE VALUE OF THE 2 CASES IS THE UPLIFT LOAD.
THIS 2-RAIL DESIGN IS WELL UNDER THE CAPACITY OF THE INDIVIDUAL ATTACHMENT
CAPACITIES FOR THE DESIGN. THE PHOTOVOLTAIC MODULES USED IN CONJUNCTION WITH
2-RAIL ATTACHMENT SYSTEM ADDED HAVE A DESIGN CAPACITY OF -4,000 PA., 84 PSF. THIS
DESIGN IS WITHIN THE LOADING CAPACITIES OF THE PHOTOVOLTAIC MODULE 2-RAIL DESIGN
TESTING CAPACITIES THAT HAVE BEEN PERFORMED BY INDEPENDENT TESTING BY THE PANEL
MANUFACTURERS ENGINEERS. SEE ATTACHED MANUFACTURERS TEST DATA.
WIND PRESSURE PNET IS CALCULATED BY ASCE 7-16 EQ. 29.4.7, WHERE Qh IS CALCULATED BY
EQ. 29.4-7 (PARAMETERS SHOWN IN THE TABLE).
GCp ARE CHOSEN FROM FIGURE 30.3-A-1 FOR SPECIFIC ROOF TYPE AND ROOF TILT WITH
EFFECTIVE WIND AREA EQUALS TO 10 SQFT (INTERPOLATION MAY REQUIRED).
ARRAY EDGE FACTOR rE = 1.5 FOR ARRAY EDGES UPLIFT PRESSURE IF ARRAY EDGE IS MORE
THAN 10 FEET (0.5h) TO ROOF EDGES AND MORE THAN 4 FEET TO ADJACENT ARRAY OR NEXT
ADJACENT PANEL. rE = 1.0 FOR ARRAY INTERIOR UPLIFT PRESSURE AND ALL DOWNWARD
PRESSURE AS DEFINED IN ASCE 7-16 29.4.4.
NO PANEL ARE LOCATED IN ARRAY EDGE AREA AS DEFINED BY ASCE 7-16 29.4.4. FOI
EXPOSURE B THIS PROJECT.
V (WIND SPEED) 175
MEAN HEIGHT 15.00 2-RAIL RACKING PLUS SOLAR SYSTEM DEAD LOAD
COMPONENT
WEIGHT/UNIT (LB)
#
EFFECTIVE WIND AREA (AREA OF ONE PANEL)
19.29
Kz (VELOCITY PRESSURE EXPOSURE)
0.57
MODULES
0
29
Kzt (TOPOGRAPHIC FACTOR)
1
INVERTERS
4.0
29
Kd (WIND DIRECTIONALITY)
0.85
RAILS (2-RAIL) @ 1.8LB/LF.
1.8
15.0
Ke (GROUND ELEVATION FACTOR)
1
ATTACHMENT/FLASHING
0.98
42
LF (LOAD FACTOR BASED ON ASD DESIGN)
0.6
ARRAY TOTAL AREA (SQFT)
559
Qh (VELOCITY PRESSURE)
22.98
ARRAY TOTAL WEIGHT (LB)
184
ra (SOLAR PANEL PRESSURE EQUALIZATION FACTOR)
0.69
TOTAL DEAD LOAD PER SF (LB/SQFT)
2.60
TOTAL PRESSURE AND ATTACHMENT SPACING
FOR GABLE ROOF WITH 7 to 20 DEGREE TILT
GCp
p- (LB/SQFT)
p+
(LB/SQFT)
pnet- (LB/SQFT)
pnet+
(LB/SQFT)
ATTACHMENT SPACING (INCH)
ZONE
UPLIFT
DOWNWARD
ARRAY INTERIOR
ARRAY EDGE
ARRAY INTERIOR
ARRAY EDGE
ARRAY INTERIOR
ARRAY EDGE
1
-2.00
0.30
-31.52
-47.28
4.73
-17.35
-26.81
7.33
48.00
24.00
2e
-2.00
0.30
-31.52
-47.28
4.73
-17.35
-26.81
7.33
24.00
24.00
2n
-2.59
0.30
-40.84
-61.27
4.73
-22.95
-35.20
7.33
24.00
24.00
2r
-2.59
0.30
-40.84
-61.27
4.73
-22.95
-35.20
7.33
24.00
24.00
3e
-2.59
0.30
-40.84
-61.27
4.73
-22.95
-35.20
7.33
24.00
24.00
3r
1 -3.09
1 0.30
1 -48.64
1 -72.96
1 4.73
1 -27.62
1 -42.22
1 7.33
1 24.00
1 16.00
ATTACHMENT LB
ARRAY INTERIOR
ARRAY EDGE
-195.50
-151.02
-97.75
-151.02
-129.27
-198.29
-129.27
-198.29
-129.27
-198.29
-155.61
-158.54
0 momentum
SOLAR
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
PROFESSIONAL
ENGINEERING
`\\j\111111//1///
A. MA
%CENS
No PE86753
Q STATE OF
FALORIDP' •' ���
01
II
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
SOLAR CONTRACTOR
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
CUSTOMER INFORMATION
TONY PEREIRA - MS93764
409 NORTHEAST OLEANDER AVENUE
PORT ST. LUCIE, FL 34952
7724465444
PV SYSTEM INFORMATION
SYSTEM SIZE (DC): 10.44 KW
29 MODULES: HANWHA Q.PEAK DUO
BLK-G10+ 360
29 INVERTERS: ENPHASE IQ7-60-2-US
PROJECT INFORMATION
ITIAL DATE: 2/10/2022 DESIGNER: SN
V: DATE: DESIGNER:
V: DATE: DESIGNER:
STRUCTURAL CALCULATION
PV-3.6
TOPCOAT'
LIQUID -APPLIED ROOFING
FLEXSEALm CAULK GRADE
Description
TOPCOAT® FlexSeal'" Caulk Grade is a white solvent -
based synthetic elastomeric sealant. FlexSeal" Caulk
Grade is extremely flexible and durable, but with a higher
viscosity formulation than standard viscosity FlexSeal-.
Like all solvent -based products, the surface must be
clean and completely free of moisture and residual
contaminants before application. FlexSeal'" Caulk Grade
is especially suited for use in any application where
caulk is typically used. If a more fluid viscosity is desired,
FlexSeal'" is also available in both a standard viscosity as
FlexSeal' and a low -viscosity version as FlexSeal- LV.
Uses
TOPCOAT FlexSeal" Caulk Grade is designed for use
on metal, copper, concrete, wood, asphalt shingles, SBS,
APP, EPDM, BUR, TPO, and PVC substrates. Especially
designed for use where elastomeric caulks are required,
like term bar applications or around clamping rings at
penetrations. FlexSeal- Caulk Grade may be used for
cold -weather applications provided that the material is
stored properly and the substrate is dry prior to application.
This product is easiest to apply at temperatures above
32°F (0°C). Substrate temperatures must be below 120°F
(48.9°C) when applying product.
Advantages
• Extremely flexible and durable
• Ideal for termination bar, railing, step flashings, or
edge metal
• Durable and UV resistant; will not chalk, crack, or peel
• Joint movement capability maximum ± 25%
• Bonds to multiple substrates including metal, copper,
concrete, wood, asphalt shingles, SIBS, APP, EPDM,
BUR, TPO, and PVC
• Paintable
• Limited material warranty available for up to 10 years*
• May be used in guaranteed projects up to 20 years**
• Available in 10-oz. cartridges
For Application Questions
Contact GAF Technical Services at 1-800-766-3411 or
visit gaf.com.
Applicable Standards
FlexSeal'" Caulk Grade meets ASTM D412 and D920; and
is tested in accordance with D2196 and D1475.
Application Considerations
FlexSeal'" Caulk Grade is not a structural component and
it is not intended to bridge large voids. Joint depth should
not exceed 1/2" wide by 1/2" deep (13 mm x 13 mm).
If joint exceeds 112" (13 mm) deep, the sealant depth
should be controlled by a closed cell backer rod.
The number of joints and width of joints should be
designed to accommodate a maximum of 25%
movement.
Note: Apply only as directed. Over -application may
result in slumping, dripping, or unsightly appearance.
Note: Repair leaks promptly to avoid adverse effects,
including mold growth.
"See applicable warranties and guarantees for complete coverage and restrictions.
"When used as a part of a multiply system. TOPCOA71 FlexSeai �° Caulk Grade is
a maintenance item and should be inspected periodically as a part of regular
roof maintenance.
TOPCOAT' FLEXSEAL' CAULK GRADE TECHNICAL DATA
Application Rate:
Approximately 1/4 -3/8 inch (6 - 10 mm) bead
Application Method:
Caulk gun
Application Temp (air, surface):
32°F - 120°F (0°C - 48.9°C)
Drying Time (varies by conditions):
24 - 48 hrs; skins in less than 1 hour;
full cure - approximately 48 hours
Total Solids (by weight):
77% ± 2%
Specific Gravity:
1.24 ± 0.1
Weight per Gallon:
10.3 ± 0.5 Ibs
Viscosity (75°F (23.9°C)):
1,200,000 cps ± 10%
Tensile:
>250 psi (>1.72 N/sq mm)
Storage: Recommended storage temperature range 50oF-9OoF
(10°C-32.2°C). Storage for continued periods outside
this temperature range may shorten shelf life.
Shelf Life: Approximately 1 year
Clean -Up: Mineral Spirits, Toluene, Xylene
=0
Product Data Sheets 35
SOLAR
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
PROFESSIONAL
ENGINEERING
```X11111IIII/////
�P ..... t
�� • %,%GENSF
i
No PE86753
�.0 4:,
0 STATE OF
is1ONAI. E?C�
//11111I
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Starn
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
SOLAR CONTRACTOR
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
CUSTOMER INFORMATION
TONY PEREIRA - MS93764
409 NORTHEAST OLEANDER AVENUE
PORT ST. LUCIE, FL 34952
7724465444
PV SYSTEM INFORMATION
SYSTEM SIZE (DC): 10.44 KW
29 MODULES: HANWHA Q.PEAK DUO
BLK-G10+ 360
29 INVERTERS: ENPHASE IQ7-60-2-US
I PROJECT INFORMATION I
I INITIAL I DATE: 2/10/2022 I DESIGNER: SN I
IREV: IDATE: IDESIGNER:
IREV: IDATE: IDESIGNER:
SEALANT SPECIFICATION
SEALANT SPECIFICATION FOR CORRUGATED METAL ROOFS
PV-3.7
ELECTRICAL SERVICE ELEVATION
INTERCONNECTION
DETAIL
0
#2/0 AWG SERVICE
momentum
CONDUCTOR FROM
MINUMUM BEND
RADIUS 4"
SOLAR
•
° ° METER
d RISER �
OVERHEAD FOR
HOT LINE TAPSMm
ENCLOSURE DIMENSIONS
..
•
° ° •
• ° ' '
•,
' •MSP
200AMP SERVICE
LENGTH: 21.31��
WIDTH: 10.3"
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
•
• • ••
% s ° °
r- -I s
°
DEPTH: 9.06"
(732)902-6224
MOMENTUMSOLAR.COM
• •
• • ° I ',�', • • •
Inn
PROFESSIONAL
• a
® a °
°
°• « a• °I 'I '
#2/0 AWG SERVICE
CONDUCTOR FROM
ENGINEERING
•
•'
A
• I I '%
UTILITY°,�
200AMP SERVICE
• • • .
°
•
EMPHASE
° EXISTING
° COMBINER • ' SOLAR . •
�MSP LOCATED IN SIDE
A.
•
•
• BOX oISCaN.E ' •°' •• .METE.R .: • ' :
OF STRUCTURE
�� • ',
.4
�-♦ �,,cENsF
I
No PE86753
4'
FSEC CERTIFICATION STATEMENT:
Q STATE OF
29 HANWHA Q.PEAK DUO BLK-G10+ 360 360W MODULES PAIRED WITH
PER FL. STATUE 377.705, I, MINA A. MAKAR PE# 86753, CERTIFICATE
• ' ����
•!�40RIDOF
PV SYSTEM
CURRENT 36.25 A
#33404, AN ENGINEER LICENSEDQ'
TO
���/ssIONA1.
29 ENPHASE IQ7-60-2-US MICRO -INVERTERS
CHA TER0ON 47I1 CEIR I Y THAT HE PV ELECTRICAL SYSTEM ANDANT
"1111I III``
ELECTRICAL COMPONENTS ARE DESIGNED AND APPROVED USING THE
STANDARDS CONTAINED IN THE MOST RECENT VERSION OF THE
Digitally signed by Mina A Makar.
FLORIDA BUILDING CODE. FBC 2020
BRANCH CIRCUITA
Reason : This item has been
10 MICRO -INVERTERS
EXISTING SQUARE D 150A
electronically signed and sealed by
BRANCH CIRCUIT B
MAIN SERVICE PANEL 240 V
10 MICRO -INVERTERS
[Mina A. Makar, PE 86753, COA #
BRANCH CIRCUIT C
9 MICRO -INVERTERS
+ -
-
+ - + -
- -
MAIN BREAKER: 150A
334041 on the Date and Time Stamp
ENPHASE
I SIDE
shown using a digital signature.
AC COMBINER
HOTT TAP
BOX SOLAR CIRCUIT
Printed copies of this document are
TERMINATION CAP
DISCONNECTING MEANS
150A
not considered signed and sealed
INSTALLED ON + -
+ - + -
EATON 60A FUSIBLE GRID
and the signature must be verified
END OF CABLE -
_ =
SOLAR AC DISCONNECT
on any electronic copies
4oA
SOLAR CONTRACTOR
CAMERON CHRISTENSEN
ROOF
10A/15A BREAKER
POWER UTILITY
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
INVERTERS
JUNCTION
(MANUFACTURER
40A FUSES
GROUND METER
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
CUSTOMER INFORMATION
SUPPLIED FOR
INS 1ATO 1C BOX 2A ENVOY) 3 4
RAIL SYSTEM
26 20A BREAKER (A)
2C 20A BREAKER (B)
TONY PEREIRA - MS93764
20A BREAKER (C)
409 NORTHEAST OLEANDER AVENUE
PORT ST. LUCIE, FL 34952
7724465444
PV SYSTEM INFORMATION
SYSTEM SIZE (DC): 10.44 KW
29 MODULES: HANWHA Q.PEAK DUO
Wire
Temp.
Wire
Temp.
Conduit
Derated
Inverter
NEC
Design
Ground
Ground Wire
BLK-G10+ 360
Wire Tag
Conduit
Wire Qty
Wire Type
NOC (A)
Gauge
Rating
Ampacity (A)
Derate
Fill Derate
Ampacity (A)
Qty
Correction
Current (A)
Size
Type
29 INVERTERS: ENPHASE IQ7-60-2-US
1A TO 1C
OPEN AIR
3
12 AWG
Trunk Cable
90°C
30
0.96
1
28.80
10
1
1.25
12.50
06 AWG
BARE CU
2A
10 AWG
THWN-2
75°C
35
0.96
0.8
26.88
10
1
1.25
12.50
PROJECT INFORMATION
INITIAL
DATE: 2/10/2022
DESIGNER:SN
2B
3/4" PVC
6
10 AWG
THWN-2
75°C
35
0.96
0.8
26.88
10
1
1.25
12.50
08 AWG
THWN-2
REV:
DATE:
DESIGNER:
2C
10 AWG
THWN-2
75°C
35
0.96
0.8
26.88
9
1
1.25
11.25
REV:
DATE:
DESIGNER:
3
3/4" PVC
3 + G
08 AWG
THWN-2
75'C
50
0.96
1
48.00
29
1
1.25
36.25
08 AWG
THWN-2
THREE LINE DIAGRAM
4
3/4" PVC
3 + G
06 AWG
THWN-2
75*C
65
0.96
1
62.40
29
1
1.25
36.25
THWN-2
��_
"G"
NOTE: LETTER IN WIRE QTY TAB STANDS FOR GROUNDING CONDUCTOR.
MODULE MAKE
HANWHA
MODEL
Q.PEAK DUO
BLK-G10+ 360
MAX POWER
360W
OPEN CIRCUIT VOLTAGE
41.18V
MPP VOLTAGE
34.31V
SHORT CIRCUIT CURRENT
11.04A
MPP CURRENT
10.49A
NUMBER OF MODULES
29
UL1703 COMPLIANT
YES
INVERTER MAKE ENPHASE FORMULA USED PER NEC 2014 HANDBOOK 215.2(A)(4) WHERE APPLICABLE 0
WIRE RUN VmP IMP R L (FT) VD 0/0 VO WIRE SIZE momentum
MODEL IQ7-60-2-US SOLAR:
BRANCH TO J-BOX 240.00 #NUM! 1.98 #NUM! #NUM! #NUM! 12 AWG
MAX OUTPUT POWER
CH
240W
OPEN DC VOLTAGE
48V
J-BOX TO LOAD
CENTER
240.00
NOMINAL AC VOLTAGE
240V
LOAD CENTER TO AC
DISCONNECT
240.00
MAX AC CURRENT
1A
AC DISCONNECT TO
INTERCONNECTION
240.00
CEC INVERTER EFFICIENCY
97%
NUMBER OF INVERTERS
29
WITH THE 2020
NATIONAL ELECTRICAL CODE
1703 COMPLIANT
YES
THIS SOLAR PHOTOVOLTAIC
FLORIDA BUILDING CODE
SYSTEM COMPLIES
AND THE 2017
SUB PANEL
# OF MODULES
PB
PER BRAN
BREAKER SIZE
UP TO 16
20A
0 1.24 50.00 0.000 0.00%
0 1.24 3.00 0.000 0.00%
0
1.24
10.00
0.000
0.00%
MAKE
MODEL
VOLTAGE
RATING
CONDUCTOR
RANGE MAIN
ILSCO
IPC 4020
600 V
4/0-4 AWG
ILSCO
IPC 4006
600 V
4/0-2 AWG
10 AWG
10 AWG
CONDUCTOR
RANGE TAP
6-14 AWG
2/0-6 AWG
ELECTRICAL NOTES:
1. ALL CALCULATIONS FOR VOC, VMAX, IMP AND ISC HAVE BEEN
15.
ALL CONDUCTORS MUST BE COPPER. 29.
ALL GROUNDING SHALL COMPLY WITH 690.47(A) IN THAT THE
CALCULATED USING THE MANUFACTURED STRING CALCULATOR BASED
AC MODULES WILL COMPLY WITH 250.64.
ON ASHRAE 2% HIGH AND EXTREME MINIMUM TEMPERATURE
16.
NEUTRAL AND EQUIPMENT GROUNDING CONDUCTOR BONDED AS PER
COEFFICIENTS.
NEC 250.24(C). 30.
NO TERMINALS SHALL BE ENERGIZED IN THE OPEN POSITION
IN THIS AC MODULE SYSTEM 690.13, 690.15, 690.6.
2. THE ENTIRE ARRAY IS BONDED ACCORDING TO (NEC 690.46 - 250.120
17.
EQUIPMENT GROUNDING CONDUCTOR IS CONNECTED TO A
PARAGRAPH C). THE GROUND IS CARRIED AWAY FROM THE GROUNDING
GROUNDING ELECTRODE SYSTEM PER 250.54(D). 31.
WHERE APPLICABLE: INTERCONNECTION SHALL COMPLY
LUG USING #6 BARE COPPER WIRE OR #8 THWN-2 COPPER WIRE.
WITH 705.12(A) OR 705.12(B)
18.
FUSES FOR PV DISCONNECT HAVE AIC RATINGS OF 200KA AC AND 20KA
3. THIS SYSTEM COMPLIES WITH NEC 2017
DC.
4. BRANCH CIRCUIT CALCULATION FOR WIRE TAG 1 DISPLAYS THE
LARGEST BRANCH CIRCUIT IN SYSTEM. OTHER BRANCH CIRCUITS
SHALL HAVE LOWER DESIGN CURRENT THAN THE ONE SHOWN. IN
ADDITION, VOLTAGE DROP CALCULATIONS FROM PANELS TO THE
COMBINER BOX SHALL BE SHOWN IN A SIMILAR FASHION
5. ALL CONDUCTORS ARE SIZED BASED ON NEC 2017 ARTICLE 310
6. ALL EQUIPMENT INSTALLED IS RATED AT 75°C
7. INVERTER NOC (NOMINAL OPEN CURRENT) OBTAINED FROM
EQUIPMENT DATASHEET
8. CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH ALL
LOCAL AND NATIONAL CODE REQUIREMENTS.
9. EACH MODULE MUST BE GROUNDED ACCORDING TO USER
INSTRUCTIONS
10. ALL EQUIPMENT SHALL BE LISTED PER NEC 690.4(B)
11. PER NEC 690.13, 690.15, PROVIDE A WARNING SIGN AT ALL LOCATIONS
WHERE TERMINALS OF THE DISCONNECTING MEANS MAY BE
ENERGIZED IN THE OPEN POSITION> SIGN SHALL READ *WARNING -
ELECTRIC SHOCK HAZARD - DO NOT TOUCH TERMINALS - OR
EQUIVALENT.
12. PER NEC 705.10, PROVIDE A PERMANENT PLAQUE OR DIRECTORY
SHOWING ALL ELECTRIC POWER SOURCES ON THE PREMISES AT
SERVICE ENTRANCE.
13. INTERCONNECTION METHOD SHALL COMPLY WITH NEC705.12
14. AND OPTION FOR A SINGLE CIRCUIT BRANCH TO BE SPLIT INTO TWO
SUB -CIRCUIT BRANCHES IS ACCEPTABLE.
19. SUPPLY SIDE CONNECTION SHALL BE MADE USING ILSCO INSULATION
PIERCING CONNECTORS (IPC). MAKE, MODEL, AND RATING OF
INTERCONNECTION CAN BE SEEN ON TABLE 1 BELOW.
20. METHOD OF INTERCONNECTION CAN BE SEEN IN FIGURE 1.
21. UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL PHOTOVOLTAIC
SYSTEM COMPONENTS LOCATED AT THE SERVICE ENTRANCE.
22. WORKING CLEARANCES AROUND THE EXISTING AND NEW ELECTRICAL
EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH NEC ARTICLE
110.26.
23. CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT
RESISTANT PER NEC ARTICLE 300.6 (C)(1) AND ARTICLE 310.8 (D).
24. CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR
USE IN WET LOCATIONS PER NEC ARTICLE 310.10 (C).
25. TOTAL AREA OF ALL CONDUCTORS, SPLICES, AND TAPS INSTALLED AT
ANY CROSS SECTION OF THE WIRING DOES NOT EXCEED 75% OF THE
CROSS SECTIONAL AREA OF THE SPACE. NEC 312.8(A)(2).
26. SYSTEM IS CONSIDERED AN AC MODULE SYSTEM. NO DC
CONDUCTORS ARE PRESENT IN CONDUIT, COMBINER, JUNCTION BOX,
DISCONNECT. AND COMPLIES WITH 690.6 - NO DC DISCONNECT AND
ASSOCIATED DC LABELING ARE REQUIRED.
27. SYSTEM COMPLIES WITH 690.12 RAPID SHUTDOWN AND ASSOCIATED
LABELING AS PER 690.56(C). AC VOLTAGE AND SYSTEM OPERATING
CURRENT SHALL BE PROVIDED 690.52.
28. CONDUCTORS IN CONDUIT ARE AC CONDUCTORS BRANCH CIRCUITS
AND NOT PV SOURCE CIRCUITS. 690.6.
INSTRUCTIONS FOR LINE TAPS
FIGURE 1:
1. ADJUST THE CONNECTOR NUT TO SUITABLE
LOCATION
2. PUT THE BRANCH WIRE INTO THE CAP SHEATH FULLY
3. INSERT THE MAIN WIRE, IF THERE ARE TWO LAYS OF
INSULATED LAY IN THE MAIN CABLE, SHOULD STRIP A
CERTAIN LENGTH OF THE FIRST INSULATED LAY
FROM INSERTED END
4. TURN THE NUT BY HAND, AND FIX THE CONNECTOR IN
SUITABLE LOCATION.
5. SCREW THE NUT WITH THE SLEEVE SPANNER.
6. SCREW THE NUT CONTINUALLY UNTIL THE TOP PART
IS CRACKED AND DROPPED DOWN
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
PROFESSIONAL
ENGINEERING
`\xj\IIIIII//////
` A• MA
��
�•'' �. F '• .p
No PE86753
0 STATE OF
II
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Starn
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
SOLAR CONTRACTOR
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
CUSTOMER INFORMATION
TONY PEREIRA - MS93764
409 NORTHEAST OLEANDER AVENUE
PORT ST. LUCIE, FL 34952
7724465444
PV SYSTEM INFORMATION
SYSTEM SIZE (DC): 10.44 KW
29 MODULES: HANWHA Q.PEAK DUO
BLK-G10+ 360
29 INVERTERS: ENPHASE IQ7-60-2-US
PROJECT INFORMATION
INITIAL DATE: 2/10/2022 DESIGNER: SN
REV: DATE: DESIGNER:
REV: DATE: DESIGNER:
ELECTRICAL NOTES
PV-4.1
I
TAG
LABEL
QUANTITY
LOCATION
NOTE
EXAMPLES
momentum
1 AT EVERY SEPARATION BY
SOLAR
0
•
12
AC CONDUITS
ENCLOSURES / WALLS /
PARTITIONS / CEILINGS / FLOORS
AC SOLAR VOLTAGE
OR NO MORE THAN 10'
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
WARNING: PHOTOVOLTAIC PHOTOVOLTAIC
PROFESSIONAL
©
' • •EQUIPPED WITH
1
COMBINER BOX
1 AT ANY COMBINER BOX
RAPID SHUTDOWN
ENGINEERING
AWARNING
\,%GEN SF
i
©ELECTRICAL
SHOCK_
No PE86753TERMINALS _
ON BOTH LINE AND
1
JUNCTION BOX
1 AT ANY JUNCTION BOXR,
y
wi,,-
LOAD ■ - ■
IN THE OPEN POSITION
00
s
=
••.
. •
1131 `
iSTATE OF 4
i F40Rlop-
PHOTOVOLTAIC SYSTEM
AAC DISCONNECT i
ONAI.
RATED AC
OUTPUT CURRENT ASHOCKHAZARD_
ELECTRICAL
e
TERMINALS
ON BOTH LINE AND
Digitally signed by Mina A Makar.
• ■
■ ■
_
--
Reason : This item has been
Op
VOLTAGENOMINAL
AC IN
THE OPEN POSITION
AC DISCONNECT
1 OF EACH AT FUSED AC
-
'"
electronically signed and sealed by
(RSD SWITCH)
DISCONNECT
©
[Mina A. Makar, PE 86753, COA #
010
■ • • '
1
RAPID SHUTDOWN
COMPLETE VOLTAGE AND
33404] On the Date and Time Stamp
SOLAR
TO BE LOCATED
CURRENT VALUES ON
•
shown using a digital signature.
POWER TO THIS SERVICE
AT AC
DISCONNECT LABEL
Printed copies of this document are
DISCONNECT
-
ALSPHOTOVOLTAIC
• ■ ' • •
OUTSIDE THE
not considered signed and sealed
INSTALLED
SOLAR GENERATION ,., ;
BY MOMENTUM SOLAR
•
HOUSE
614
and the signature must be verified
AC SYSTEM■ •
07080
®�
0
on any electronic copies
SOLAR CONTRACTOR
•
=
CAMERON CHRISTENSEN
REVENUEI METER
- _
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
�
MOMENTUM SOLAR
A
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
0
DUAL POWER SUPPLY
1
UTILITY METER.=
CUSTOMER INFORMATION
SECONDARY •
1 AT UTILITY METER ANC
PHOTOVOLTAIC SYSTEM
DIRECTORY PLACARD
TONY PEREIRA - MS93764
@
409 NORTHEAST OLEANDER AVENUE
PORT ST. LUCIE, FL 34952
EMERGENCY RESPONDER©
SOLARTHIS • -- ■
�
7724465444
PV SYSTEM INFORMATION
RAPIDWITH SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH TO THE" OFF"
POSITION TO SHUT DOWN .a E.E
ENTIRE PV SYSTEM
DUAL POWER SUPPLY
1
INTERCONNECTION
POINT
__ _ -
I I
SYSTEM SIZE (DC): 10.44 KW
29 MODULES: HANWHA Q.PEAK DUO
■ _SECONDARY
SOURCE
BLK-G10+ 360
■_PHOTOVOLTAIC
29 INVERTERS: ENPHASE IQ7-60-2-US
1 OF EACH AT BUILDING
I
.
INTERCONNECTION POINT AND
POWER SOURCEOUTPUT CONNECTION.-210
1
BACKFEED PANEL
ONE DIRECTORY PLACARD
_�
. 135182e
v >'' ''
PROJECT INFORMATION
INITIAL
DATE: 2/10/2022
DESIGNER: SN
•
O
■
NOMINAL OPERATING AC VOLTAGE: 240V
NOMINAL
POOPERAWER
MAXIMUM ,.
e�uu��am
��■�
REV:
DATE:
DESIGNER:
REV:
DATE:
DESIGNER:
EQUIPMENT LABELS
_
MAXIMUM OVERCURRENTDEVICE FOR
1
AC CURRENT PV
MODULES
P V — 4 2
AC MODULE PROTECTION: 1
0
© BACKFEED
■
Daniel W. Dunzik Architect LEED-AP
370 Burnt Hill Rd. Skillman NJ. 08558
908-872-3664
StudioGdesign@comcast.net February 9, 2022
Re: Proposed Photovoltaic Solar Panel Installation
Tony Pereira
409 NORTHEAST OLEANDER AVENUE
PORT ST. LUCIE, FL 34952
Dear Plan Reviewer:
Certification: I have reviewed the engineering testing reports for the racking and attachments to be used on this project
and I certify that the products are capable of supporting the code required loads and are suitable for this installation
when installed in strict compliance with the manufacturers printed instructions.
Regarding the solar panel array installation on the above referenced project please note that an inspection was
performed by a representative of the Architect/Engineer of Record, and analysis of the existing structure was
conducted. There is adequate structural capacity for the installation of the array with the following recommendations:
1. The array will be installed on the existing roof. The roof ftaming is constructed of 2"x4" wood trusses @24" o.c.
spanning 14' with a top chord length of 14' 9" with intermediate supports at 1/2 points, making the effective longest
span equals 8' with 1/2" plywood sheathing. The new array (See Site map by contractor) will add 2.63 Lb. / Sf. overall
to the roof. The existing structure is sufficient to support the new loads associated with the additional weight & wind
resistance. No additional structural support is required for the roof structure.
2. The attachment system shall be secured to the roof and shall be in strict compliance with manufacturers printed
instructions. The attachment system shall be UL 1703 approved tested. Provide 6 mil. vapor barrier between dissimilar
metals. Provide water tight gasket and sealant at all penetrations. Attachments shall follow panel rows as specified by
the system manufacturer's installation manual. The panel angle shall match the roof slope. Reference summary table
below:
Roof Type:
Corrugated Metal
Fastener Max Spacing (in.)
Attachment System:
"ROOFTECH"® "RT MINI 11" & "Ecol aster" Click Fit® Attachment Systems
Please See Manufacture Specification and PV-
min. 5/16" x 4" long stainless -steel lags with a min.
Fastener Info:
3.6
embedment of 3" into the rafters
3. Solar Modules shall be UL-1703 rated. Refer to manufacturers specifications sheets.
4. Positive drainage of the system shall be so as not to void the existing roof warranty.
5. All aspects of the installation shall comply with the Florida Administrative Code, 2020 Florida Building Code -
Residential Seventh Edition, ASCE-7-16, 2020 Florida Building Code - Energy Conservation, Seventh Edition, 2017
National Electric Code, All Local Governing County and Municipal Ordinances adopted by reference or enacted by
law. All components used meet the criteria of the Florida Solar Energy Center.
6. Please refer to the attached structural calculations.
If you have any questions relating to this matter, please contact me at your earliest convenience. Thank you.
Daniel W. Dunzik, RA. LEED-AP
FL. Lic. No. AR98795
Daniel W. Dunzik
370 Burnt Hill Rd. Skillman NJ. 08558
StudioGdesign@comcast.net
Gravity Load Calculation Criteria
Structural Design Loads per ASCE 7-16
Dead Loads = 10 psf + 2.6 psf (new solar panels) = 12.6 psf
Roof Live Load = 20 psf
Ground Snow Load/Live Load = 0 psf
Roof Slope = 18 degrees
Basic Wind Speed = 160 mph
Roof Mean Height = 15 R
Exposure = B
Wind Load Calculation Criteria
Wind Loads per ASCE 7-16, Equation 29.4-7
Using an effective wind area of 10 SF, external pressure coefficient from Figure 30.3-A-I
Array Interior: Array Edge:
Zone 1 = -50.8 psf Zone 1 = -76.2 psf
Zone 2e = -50.8 psf Zone 2e = -76.2 psf
Zone 2n = -76.2 psf Zone 2n = -114.3 psf
Zone 2r = -76.2 psf Zone 2r = -114.3 psf
Zone 3e = -76.2 psf Zone 3e = -114.3 psf
Zone 3r = -91.44 psf Zone 3r =-137.16 psf
Per section 2.4.1, ASD combo = 0.613 + 0.6W:
Array Interior:
Zone 1 = 0.6 x 2.6 psf+ 0.6 x (-50.8 psf) = -28.92 psf
Zone 2e = 0.6 x 2.6 psf + 0.6 x (-50.8 psf) = -28.92 psf
Zone 2n = 0.6 x 2.6 psf + 0.6 x (-76.2 psf) = -44.16 psf
Zone 2r = 0.6 x 2.6 psf + 0.6 x (-76.2 psf) = -44.16 psf
Zone 3e = 0.6 x 2.6 psf+ 0.6 x (-76.2 psf) = -44.16 psf
Zone 3r = 0.6 x 2.6 psf + 0.6 x (-91.44 psf) = -53.3 psf
Array Edge:
Zone 1 = 0.6 x 2.6 psf+ 0.6 x (-76.2 psf) = -44.16 psf
Zone 2e = 0.6 x 2.6 psf + 0.6 x (-76.2 psi) = -44.16 psf
Zone 2n = 0.6 x 2.6 psf + 0.6 x (-114.3 psf) = -67.02 psf
Zone 2r = 0.6 x 2.6 psf+ 0.6 x (-114.3 psf) = -67.02 psf
Zone 3e = 0.6 x 2.6 psf+ 0.6 x (-114.3 psf) = -67.02 psf
Zone 3r = 0.6 x 2.6 psf+ 0.6 x (-137.16 psf) = -80.74 psf
Check Attachment to Wood Truss
Use 5/16 dia. Lag screw w/ 3" embedment into 2 in. wide roof rafter
Please refer to design PV-3.6 and manufacturer specification for maximum allowable span.
Architect LEED-AP
908-872-3664
February 9, 2022
isino�z_l-e,
SOLAR
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, N3
(732)902-6224
MOMENTUMSOLAR.COM
PROFESSIONAL
ENGINEERING
````11111111111/''
A.
No PE86753
.Q 4i Z
0 STATE OF
ci
is10NA1.1E ��♦
/111111
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Starn
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
SOLAR CONTRACTOR
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
CUSTOMER INFORMATION
TONY PEREIRA - MS93764
409 NORTHEAST OLEANDER AVENUE
PORT ST. LUCIE, FL 34952
7724465444
PV SYSTEM INFORMATION
SYSTEM SIZE (DC): 10.44 KW
29 MODULES: HANWHA Q.PEAK DUO
BLK-G10+ 360
29 INVERTERS: ENPHASE IQ7-60-2-US
I PROJECT INFORMATION I
I INITIAL I DATE: 2/10/2022 I DESIGNER: SN I
IREV: IDATE: IDESIGNER:
IREV: IDATE: IDESIGNER: I
UCTURAL CERTIFICATIO
PV- 5