Loading...
HomeMy WebLinkAboutGas Riser Diagram GAS ISOMETRIC RISER DIAGRAM Javier Toro 7691 Wexford Way Port St Lucie, FL 34986 Gas Codes Based on 402.4 Series FBC Codes Gas Piping Codes based on NFPA 54/58 Codes. Type of Gas: 500g LP Tank Pipe Sizing for trench: 17’ ¾ PE @ 10psi Appliances: 22kw Gen @ 330,000BTU Excel Electric LLC 8241 Business Park Dr Port St Lucie, FL 34952 Phone: 772-529-1091 Email: ExcelOffice77@gmail.com Qualifier: Ronnie Kellar LP Gas State License # 45010 Tank will comply with all setbacks of 10 feet from sources of ignition, property line elements and the residence 500g LP Tank Anchored/Anode 1st Stage Reg 22Kw Gen ¾ Shut off ¾ Riser 2nd Stage Reg Up to 17’ of ¾ PE @ 10psi