HomeMy WebLinkAboutProject Informationro ect Summary Job: P wrightsoft® � � Date: MAY 15, 2012 Entire House By: PATRICIA ZIMMERMAN COMFORT CONTROL OF SLC, INC. 1501 SE BILTMORE ST., PORT ST. LUCIE, FL 34983 Phone: 772-878-2799 Fax: 772-785-9144 Web: comfortcontrolofslc.com Proaect Information For: 62' GRAND CARLTON WYNNE BUILDING CORP. FORT PIERCE, FL 34983 alp Notes: Design Information Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range Relative humidity L 50 % Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 17399 Btuh Structure 16133 Btuh Ducts 3009 Btuh Ducts 3659 Btuh Central vent (25 cfm) 773 Btuh Central vent (25 cfm) 414 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 21181 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 19195 Btuh Method Simplified Construction quality Average Fireplaces 0 Heating Cooling Area (ftZ) 1446 1446 Volume (ft') 12558 12558 Air changes/hour 0.45 0.23 Equiv. AVF (cfm) 94 48 Heating Equipment Summary Make Carrier Trade COMFORT 15 PURON SINGLE STAGE Model 25H BC530A AH R I ref no3676266 Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 8.7 HSPF 28400 Btuh @ 47'F 27 OF 947 cfm 0.046 cfm/Btuh 0 in H2O Latent Cooling Equipment Load Sizing Structure 2411 Btuh Ducts 1086 Btuh Central vent (25 cfm) 1049 Btuh Equipment latent load 4547 Btuh Equipment total load 23742 Btuh Req. total capacity at 0.70 SHR ' 2.3 ton Cooling Equipment Summary Make Carrier Trade COMFORT 15 PURON SINGLE STAGE Cond 25HBC530A Coil FX4DN(B,F)031 AHRI ref no3676266 Efficiency 12.5 EER, 15.3 SEER Sensible cooling 19880 Btuh Latent cooling 8520 Btuh Total cooling 28400 Btuh Actual air flow 947 cfm Air flow factor 0.048 cfm/Btuh Static pressure 0 in H2O Load sensible heat ratio 0.82 Calculations approved by ACCA to meet all requirements of Manual * wrightsoft' Right -Suite® Universal 2012 12.0.04 RSU05864 ACM E:\Wrightsoft HVAC\Wynne Corp\62' WYNNE GRAND CARLTON 11 .rrp Calc = MJ8 Front Door faces: N 9 1 ® Load Short Form Job: - wrightsoft Date: MAY 16, 2012 Entire House By: PATRICIA ZIMMERMAN COMFORT CONTROL OF SLC, INC. 1501 SE BILTMORE ST., PORT ST. LUCIE, FL 34983 Phone: 772-878-2799 Fax 772-785-9144 Web: comfortcontrolofslc.com Project• • For: 62' GRAND CARLTON II, WYNNE BUILDING CORP. FORT PIERCE, FL 34983 Design• • Htg Clg Infiltration Outside db (°F) 42 90 Method Simplified Inside db (OF) 70 75 Construction quality Average Design TD (OF) 28 15 Fireplaces 0 Daily range - L Inside humidity (%) 30 50 Moisture difference (gr/lb) 1 61 HEATING EQUIPMENT Make Carrier Trade COMFORT 15 PURON SINGLE STAGE Model 25HBC530A AHRI ref no3676266 Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 8.7 HSPF 28400 Btuh @ 47°F 27 OF 947 cfm 0.046 cfm/Btuh 0 in H2O COOLING EQUIPMENT Make Carrier Trade COMFORT 15 PURON SINGLE STAGE Cond 25HBC530A Coil FX4DN(B,F)031 AHRI ref no3676266 Efficiency 12.5 EER, 15.3 SEER Sensible cooling 19880 Btuh Latent cooling 8520 Btuh Total cooling 28400 Btuh Actual air flow 947 cfm Air flow factor 0.048 cfm/Btuh Static pressure 0 in H2O Load sensible heat ratio 0.82 ROOM NAME Area (ft2) Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) Clg AVF (cfm) FOYER 60 1144 674 53 32 GRT RM/DINING 483 7087 7281 329 348 LAUNDRY 46 839 1859 39 89 KITCHEN 154 359 2942 17 141 MS BATH 53 907 1146 42 55 MS CLOSET 70 77 149 4 7 MS B D R M 266 4973 2990 231 143 HALL 18 19 37 1 2 BATH 45 514 237 24 11 BDRM 2 196 3577 2100: 166 100 rn_ n44 477 di 1R IVIIA") I t K LA V uu V Calculations approved by ACCA to meet all requirements of * wrightsoft" Right-SuRe® Universal 2012 12.0.04 RSU05864 N ACCK E:\Wrightsoft HVAC\Wynne Corp\62' WYNNE GRAND CARLTON 11 .rrp Calc = MJ8 Front Door faces: N 09:13:19 Page 1 Entire House p 1445 20408 19792 947 947 Other equip loads 773 414 Equip. @ 0.95 RSM 19195 Latent cooling 4547 AA- n4404 7'37A7' OA7 OA7 Calculations approved by ACCA to meet all requirements of Manul J 201-Z-May-15 09:13:19 .+ wrightSOW Right -Suite® Universal 2012 12.0.04 RSU05864 Page 2 ACCK E:\Wrightsoft HVAC\Wynne Corp\62' WYNNE GRAND CARLTON 11 .rrp Calc = MJ8 Front Door faces: N -+- wrightsoft" Right-JO Worksheet Entire House COMFORT CONTROL OF SLC, INC. 1501 SE BILTMORE ST., PORT ST. LUCIE, FL 34983 Phone: 772-878-2799 Fax: 772-785-9144 Web: comfortcontrolofslc.com Job: Date: MAY 15, 2012 By: PATRICIA ZIMMERMAN 1 Room name Entire House FOYER 2 Exposed wall 150.7 ft 6.0 ft 3 Room height 8.7 ft p 8.0 ft heat/cool 4 Room dimensions 6.0 x 10.0 ft 5 Room area 1444.5 ft' 60.0 W Ty Construction U-value Or HTM Area M Load Area (ft) Load number (Btuh/ft''F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 \N12C-Osw 0.091 n 2.55 2.18 315 246 627 537 0 0 0 0 1A-r1omd 1.270 n 35.56 26.39 39 0 1387 1029 0 0 0 0 2A-2ob 0.630 n 17.64 22.24 15 0 265 334 0 0, 0 0 2A-2om 0.840 n 23.52 25.39 15 0 353 381 0 0 0 0 11 WI 12C-Osw 0.091 a 2.55 2.18 490 450 1146 983 0 0 0 0 �--G 2A-2om 0.840 a 23.52 68.19 40 3 931 2699 0 0 0 0 12C-0sw 0.091 s 2.55 2.18 124 83 211 181 48 27 69 59 2A-20m 0:840 s 23.52 25.39 20 20 470 508 . 0 0 0 0 D 11J0 0.600 s 16.80 17.40 21 21 353 365 21 21 353 365 W 12C-Osw 0.091 sw 2.55 2.18 34 34 86 74 0 0 0 0 W 12C-Osw 0.091 w 2.55 2.18 282 276 702 602 0 0 0 0 L-G 2A-2om 0.840 w 23.52 66.18 6 1 141 397 0 0 0 0 W 13A-5ocs 0.125 w 3.50 2.22 64 64 224 142 0 0 0 0 P 12B-Obw 0.097 2.72 0.85 204 204 554 174 80 80 217 68 C 16B-30ad 0.032 0.90 1.68 1389 1389 1244 2333 60 60 54 101 C 16C-19al 0.049 1.37 2.08 56 56 77 117 0 0 0 0 F 22A-tph 1.358 38.02 0.00 1445 151 5729 0 60 6 228 0 6 c) AED excursion 423 -35 Envelope loss/gain 14501 11279 921 558 12 a) Infiltration 2898 794 108 29 b) Room ventilation 0 0 0 0 13 Intemal gains: Occupants @ 230 2 460 0 0 Appliances/other 3600 0 Subtotal (lines 6 to 13) 17399 16133 1027 588 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 17399 16133 1027 588 15 Duct loads 17% 23% 3009 3659 11% 15%1 117 87 Total room load 20408 19792 1144 674 Air required (cfm) 947 947 53 32 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. �I . wri htsoft" 2012-May-15 09:13:19 ^I ' 9 Right -Suite® Universal 2012 12.0.04 RSU05864 Page 1 'C01'` E:1Wrightsoft HVAC\Wynne Corp162' WYNNE GRAND CARLTON II .rrp Calc = MJ8 Front Door faces: N �.+ wrightsoft' Right-JO Worksheet Entire House COMFORT CONTROL OF SLC, INC. 1501 SE BILTMORE ST., PORT ST. LUCIE, FL 34983 Phone: 772-878-2799 Fax 772-785-9144 Web: comfortcontrolofstc.com Job: Date: MAY 15, 2012 By: PATRICIA ZIMMERMAN 1 Room name GIRT RM/DINING LAUNDRY 2 Exposed wall 45.0 ft 6.5 ft 3 Room height 9.8 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 482.5 ft 7.0 x 6.5 ft 5 Room area 482.5 ft' 45.5 ft' Ty Construction U-value Or HTM Area (M Load Area (ft� Load number (Btuh/ff- °F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 12C-0sw 0.091 n 2.55 2.18 196 157 400 343 0 0 0 0 1A-rlomd 1.270 n 35.56 26.39 39 0 1387 1029 0 0 0 0 2A-2ob 0.630 n 17.64 22.24 0 0 0 0 0 0 0 0 2A-2om 0.840 n 23.52 25.39 0 0 0 0 0 0 0 0 11 12C-Osw 0.091 a 2.55 2.18 245 205 523 449 0 0 0 0 IW 2A-2om 0.840 a 23.52 68.19 40 3 931 2699 0 0 0 0 12C-0sw 0.091 s 2.55 2.18 0 0 0 0 0 0 0 0 2A-20m 0.940 s 23.52 25.39 0 0 0 0 0 0 0 0 D 11J0 0.600 s 16.80 17.40 0 0 0 0 0 0 0 0 12C-Osw 0.091 sw 2.55 2.18 0 0 0 0 0 0 0 0 W 12C-Osw 0.091 w 2.55 2.18 0 0 0 0 52 52 132 114 1W 2A-2om 0.840 w 23.52 66.18 0 0 0 0 0 0 0 0 W 13A-5ocs 0.125 w 3.50 2.22 0 0 0 0 0 0 0 0 P 1213-0bw 0.097 2.72 0.85 0 0 0 0 56 56 152 48 C 16B-30ad 0.032 0.90 1.68 483 483 432 811 46 46 41 76 C 16C-19al 0.049 1.37 2.08 0 0 0 0 0 0 0 0 F 22A-tph 1.358 38.02 0.00 483 45 1711 0 46 7 247 0 6 c) AED excursion 288 -83 Envelope loss/gain 5385 5519 573 155 12 a) Infiltration 977 268 115 32 b) Room ventilation 0 0 0 0 13 Intemal gains: Occupants @ 230 2 460 0 0 Appliances/other 0 1200 Subtotal (lines 6 to 13) 6362 6346 688 1387 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 6362 6346 688 1387 15 Duct loads 11% 15% 725 935 22% 34% 151 472 Total room load 7087 7281 839 1859 Air required (cfm) 3291 in 1 1391 89 Calculations rements wrightsoft' Right -Suite® Universal 2012 12.0.04 RSU05864 .4E5CK EAWrightsoft HVAC1Wynne Corp162' WYNNE GRAND CARLTON 11 .rrp Calc = MJ8 Front Door faces: N 5 09:13:19 Page 2 A. wrightsoft' Right-J® Worksheet Job: Date: MAY 1s, 2012 Entire House • By: PATRICIA ZIMMERMAN COMFORT CONTROL OF SLC, INC. 1501 SE BILTMORE ST., PORT ST. LUCIE, FL 34983 Phone: 772-878-2799 Fax: 772-785-9144 Web: comfortcontrolofslc.com 1 Room name KITCHEN NIS BATH 2 Exposed wall 0 ft 7.5 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 154.0 ft 7.0 x 7.5 ft 5 Room area 154.0 ft' 52.5 ft' Ty Construction U-value Or HTM Area (ft� Load Area (ft� Load number (Btuh/ft? °F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 12C-0sw 0.091 n 2.55 2.18 0 0 0 0 0 0 0 0 1A-r1omd 1.270 n 35.56 26.39 0 0 0 0 0 0. 0 0 N 2A-2ob 0.630 n 17.64 22.24 0 0 0 0 0 0, 0 0 2A-2om 0.840 n 23.52 25.39 0 0 0 0 0 0 0 0 11 W 12C-0sw 0.091 a 2.55 2.18 0 0 0 0 0 0 0 0 G, 2A-2om 0.840 a 23.52 68.19 0 0 0 0 0 0 0 0 12C-0sw 0.091 s 2.55 2.18 0 0 0 0 0 0 0 0 2A-20m 0.840 s 23.52 25.39 0 0 0 0 0 0 0 0 D 11J0 0.600 s 16.80 17.40 0 0 0 0 0 0 0 0 12C-0sw 0.091 sw 2.55 2.18 0 0 0 0 0 0 0 0 W W 12C-0sw 0.091 w 2.55 2.18 0 0 0 0, 60 54 138 118 L-G 2A-2om 0.840 w 23.52 66.18 0 0 0 0 6 1 141 397 W 13A-5ocs 0.125 w 3.50 2.22 0 0 0 0 0 0 0 0 P 12B-0bw 0.097 2.72' 0.85 68 68 185. 58 0 0 0 0 C 168-30ad 0.032 0.90 1.68 154 154 138 259 53 53 47 88 C 16C-19al 0.049 1.37 2.08 0 0 0 D 0 0 0 0 F 22A4ph 1.358 38.02 0.00 154 0 0 0 53 8 285 0 6 c) AED excursion -153 215 Envelope loss/gain 323 164 611 818 12 a) Infiltration 0 0 133 36 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 2400 1 0 Subtotal (lines 6 to 13) 323 2564 744 855 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 323 2564 744 855 15 Duct loads 11% 11% jWgA Wqe78 % % 164 291 Total room load 94 907 1146 Air required (cfm) 14 42 55 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. _ 4 wrightsoft' Ri ht-Suite® Universal 2012 12.0.04 RSU05864 2012-May-15 09:1e 3 g Page 3 'CC,k E:\Wrightsoft HVAC\Wynne Corp\62' WYNNE GRAND CARLTON 11 .rrp Calc = MJ8 Front Door faces: N 9- wrightsoft° Right-J® Worksheet Entire House COMFORT CONTROL OF SLC, INC. 1501 SE BILTMORE ST., PORT ST. LUCIE, FL 34983 Phone: 772-878-2799 Fax: 772-785-9144 Web: comfortcontrolofslc.com Job: Date: MAY 15, 2012 By: PATRICIA ZIMMERMAN 1 Room name MS CLOSET MS BDRM 2 Exposed wall 0 ft 42.0 It 3 Room height 8.0 It heat/cool 8.5 ft heat/cool 4 Room dimensions 7.0 x 10.0 ft 14.0 x 19.0 ft 5 Room area 70.0 ftz 266.0 ft' Ty Construction U-value Or HTM Area (ftl Load Area (W) Load number (Btuh/W °F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Vh12C-Osw 0.091 n 2.55 2.18 0 0 0 0 119 89 227 194 1A-rlomd 1.270 n 35.56 26.39 0 0 0 0 0 0 0 0 2A-2ob 0.630 n 17.64 22.24 0 0 0 0 15 0 265 334 2A-2om 0.840 n 23.52 25.39 0 Q 0 0 15 0 353. 381 11 W 12C-0sw 0.091 a 2.55 2.18 0 0 0 0 77 77 195 167 I� 2A-2om 0.840 a 23.52 68.19 0 0 0 0 0 0 0 0 12C-0sw M91 s 2.55 2.18 0 0 0, 0 0 0. 0 0 2A-2om 0.840 s 23.52. 25.39 0 0 0 0 0 0 0 0 D 11J0 0.600 s 16.80 17.40 0 0 0 0 0 0 0 0 W 12C-Osw 0.091 sw 2.65 2.18 0 0 0 0 0 0 0 0 12C-Osw 0.091 w 2.55 2.18 0 0 0 0 162 162' 412 353 IW c--G 2A-2om 0.840 w 23.62 66.18 0 0` 0 0 0 0 0 0 W 13A-5ocs 0.125 w 3.50 2.22 0 0 0 0 0 0 0 0 P 12B-Obw 0.097 2.72 0.85, 0 0 0 0 0 0 0 0 C 1613-30ad 0.032 0.90 1.68 70 70 63 118 266 266 238 447 C 16C-19al 0.049 1.37 2.08 0 0 0 0 0 0 0 0 F 22A-tph 1.358 38.02 0.00 70 0 0 0 266 42 1597 0 6 c) AED excursion -7 139 Envelope loss/gain 63 111 3286 2014 12 a) Infiltration 0 0 791 217 b) Room ventilation 0 0 0 0 13 Intemal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 63 ill 1 4077 2231 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 63 ill 4077 2231 15 Duct loads 22% 34% 14 38 22% 34% 896 760 Total room load 77 1491 4973 2990 Air required (cfm) 4 7 231 143 Calculations all reauirements of wr'ightsoft' Right -Suite® Universal 2012 12.0.04 RSU05864 �` E:\Wrightsoft HVAC\Wynne Corp\62' WYNNE GRAND CARLTON 11 .rrp Calc = MJ8 Front Door faces: N 19 .4 wrightsofr Right-J® Worksheet Enure House COMFORT CONTROL OF SLC, INC. 1501 SE BILTMORE ST., PORT ST. LUCIE, FL 34983 Phone: 772-878-2799 Fax: 772-785-9144 Web: comfortcontrolofslc.com Job: Date: MAY 15, 2012 By: PATRICIA ZIMMERMAN 1 Room name HALL BATH 2 Exposed wall 0 ft 5.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 3.5 x 5.0 ft 9.0 x 5.0 ft 5 Room area 17.5 ft' 45.0 ft2 Ty Construction U-value Or HTM Area M Load Area (ft� Load number (Btuh/ft' °F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 1A-rlom n 0 0 0 0 0 0 0 0 1A-rlomd 1.091 1.270 n 5.55 35.56 6.39 26.39 0 0 0 0 0 0 0 0 2A-2ob 0.630 n 17.64 22.24 0 0 0 0 0 0 0 0 2A-2om 0.840 n 23.52 25.39 0 0 0 0 0 0 0 0 11 12C-Osw 0.091 a 2.55 2.18 0 0 0 0 40 40 102 87 2A-2om 0.840 a 23.52 68.19 0 0 0 0 0 0 0 0 0.091 s 2.55 2.18 0 0 0 0 0 0 0 0 tj12C-0sw 2A-20m 0.840 s 23.52 25.39 0 0 0 0 0 0 0 0 11J0 0.600 s 16.80 17.40 0 0 0 0 0 0 j0 0 0 W 12C-Osw 0.091 sw 2.55 2.18 0 0 0 0 0 0 0 WI 12C-0sw 0.091 w 2.55, 2.18 0 0 0 0 0 0 0 0 L-G 2A-2om 0.840 w 23.52 66.18 0 0 0 0 0 0 0 0 W 13A-5ocs 0.125 w 3.50 2.22 0 0 0 0 0 0 0 0 P 12B-Obw 0.097 2.72 0.85 0 0 0 0 0 0 0 0 C 16B-30ad 0.032 0.90 1.68 18 18 16 29 45 45 40 76 C 16C-19al 0.049 1.37 2.08 0 0 0 0 0 0 0 0 F 22A-tph 1.358 38.02 0.00 18 0 0 0 45 5 190 0 6 c) AED excursion -2 -11 Envelope loss/gain 16 28 332 152 24II 12 a) Infiltration 0 0 89 0 b) Room ventilation 0 0 0 13 Intemal gains: Occupants @ 230 0 0 0 0 Appliances/other 1 0 1 0 Subtotal (lines 6 to 13) 16 28 421 177 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 16 28 421 177 15 Duct loads 22% 34% 31 91 22% 34% 93 60 Total room load �M 514 237 Air required (cfm) 11 2 t!7 A rill 24 11 Calculations approved by ACCA to meet all requirement 4oPanuVJ Wild. wrightsoft' Right -Suite® Universal 2012 12.0.04 RSU05864 -4E5GK E:1Wrightsoft HVAC\Wynne Corp162' WYNNE GRAND CARLTON 11 .rrp Calc = MJ8 Front Door faces: N 2012-May-15 09:13:19 Page 5 -+- wrightsoft" Right-J® Worksheet Job: r Entire House Date: MAY 15, 2012 By: PATRICIA ZIMMERMAN COMFORT CONTROL OF SLC, INC. 1501 SE BILTMORE ST., PORT ST. LUCIE, FL 34983 Phone: 772-878-2799 Fax: 772-785-9144 Web: comfortcontrolofslc.com 1 Room name BDRM 2 MASTER LAV 2 Exposed wall 30.7 ft 8.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 195.5 ft 7.0 x 8.0 ft 5 Room area 195.5 ft' 56.0 ft' Ty Construction U-value Or HTM Area (ft) Load Area (ft� Load number (Btuh/W °F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 12C-Osw 0.091 n 2.55 2.18 0 0 0 0 0 0 0 0 1A-rlomd 1.270 n 35.56 26.39 0 0 0 0 0 0 0 0 N 2A-2ob 0.630 n 17.64 22.24 0 0 0 0 0 0 0 0 2A-2om 0.840 n 23.52 25.39 0 0 0 0 0 0 0 0 11 W 12C-Osw 0.091 a 2.55 2.18 128 128 326 280 0 0 0 0 G 2A-2om 0.840 a 23.52 68.19 0 0 0 0 0 0 0 0 0.091 s 2.55 2.18 76 56 143 122 0 0 0 0 ti12C-Osw 2A-2om 0.840 s 23.52 25.39 20 20 470 508 0 0 0 0 11J0 0.600 s 16.80 17.40 0 0 0 0 0 0 0 0 W 12C-Osw 0.091 sw 2.55 2.18 34 34 86 74 0 0 0 0 WI 12C-Osw 0.091 w 2.55 2.18 8 8 20 17 0 0 0 0 I -- L--G 2A-2om 0.840 w 23.52 66.18 0 0 0 0 0 0 0 0 W 13A-5ocs 0.125 w 3.50 2.22 0 0 0 0 64 64 224 142 P 1213-0bw 0.097 2.72 0.85 0 0 0 0 0 0 0 0 C 1613-30ad 0.032 0.90 1.68 196 196 175 328 0 0 0 0 C 16C-19al 0.049 1.37 2.08 0 0 0 0 56 56 77 117 F 22A-tph 1.358 38.02 0.00 196 31 1166 0 56 8 304 0 6 c) AED excursion 88 -17 Envelope loss/gain 2387 1417 605 242 12 a) Infiltration b) Room ventilation 545 0 149 0 142 0 39 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 01 10 Subtotal (lines 6 to 13) 2932 1567 747 281 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2932 1567 747 281 15 Duct loads 22% 34% 645 533 22% • 34% 164 96 Total room load 3577 In 9 31 Air required (cfm) 166 1 IN Al 18 Calculations approved by ACCA to meet all requirements of 1Aalth h u r T htsOft" 2012-May-1509:13:19 Wri 9 Right -Suite® Universal 2012 12.0.04 RSU05864 Page 6 �� E:\Wrightsoft HVAC\Wynne Corp\62' WYNNE GRAND CARLTON 11 .rrp Calc = MJ8 Front Door faces: N