HomeMy WebLinkAboutENGINEERINGCOVER PAGE
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-1
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ERICH BARRANTES - MS93856
416 COCONUT AVENUE EAST
PORT ST. LUCIE, FL 34952
3058969234
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
2/10/2022
SYSTEM SIZE (DC ): 11.02 KW
29 MODULES: HANWHA Q.PEAK DUO BLK
ML-G9+ 380
29 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
COVER PAGE
SYSTEAD INFORADATION
MODULE HANWHA Q.PEAK DUO BLK ML-G9+ 380
INVERTER ENPHASE IQ7PLUS-72-2-US
RACKING SUNMODO EZ GRIP
&ECOFASTENCLICKFITSYSTEM 2-RAIL
SYSTEM SIZE (DC)11.02 KW
LOCATION 27.3353320,-80.3307543
HANWHA Q.PEAK DUO BLK ML-G9+ 380
380 WATT MODULE
72.44'' X 40.5'' X 1.26''(SEE DATASHEET)
BUILDING INFORMATION/B.O.M.
# STORIES 1/15
ROOF AREA 2578.59
P.V. AREA 590
ROOFING TYPE CORRUGATED METAL
ROOF PITCH 10
# RAILS 14
# L-FOOT ATTACHMENTS 54
# MODULES 29
# INVERTERS 29
# SKIRTS 0
# ENPHASE COMBINER BOXES 1
EATON 60A FUSIBLE SOLAR AC
DISCONNECT 1
45A FUSES 2
125A LINE TAPS 2
PLAN KEY
PV-1 COVER PAGE
PV-2 SITE PLAN
PV-3 PANEL SPECIFICATION
PV-3.1 PANEL LOAD TESTING RESULTS
PV-3.2 INVERTER SPECIFICATION
PV-3.3 COMBINER BOX SPECIFICATION
PV-3.4 JUNCTION BOX SPECIFICATION
PV-3.5 ATTACHMENT DETAIL
PV-3.6 STRUCTURAL CALCULATION
PV-3.7 SEALANT SPECIFICATION
PV-4 THREE LINE DIAGRAM
PV-4.1 ELECTRICAL NOTES
PV-4.2 EQUIPMENT LABELS
PV-5 STRUCTURAL CERTIFICATION
STRUCTURAL STATEMENT:
THE EXISTING STRUCTURE IS ADEQUATE TO SUPPORT THE NEW LOADS IMPOSED BY THE PHOTOVOLTAIC MODULE
SYSTEM INCLUDING UPLIFT & SHEAR.EXISTING RAFTER SIZES & DIMENSIONS CONFORM TO 7TH EDITION 2020
FLORIDA RESIDENTIAL CODE, 7TH EDITION 2020 FLORIDA BUILDING CODE SECTION 1512 THROUGH 1525 AND
SECTION 1616 THROUGH 1626 FOR HIGH VELOCITY HURRICANE ZONES.
GENERAL NOTES:
THIS PV SYSTEM HAS BEEN DESIGNED TO MEET THE MINIMUM DESIGN STANDARDS FOR BUILDING AND OTHER
STRUCTURES OF THE ASCE 7-16, 7TH EDITION 2020 FLORIDA RESIDENTIAL CODE, 7TH EDITION 2020 FLORIDA
BUILDING CODE, 7TH EDITION 2020 FLORIDA FIRE PREVENTION CODE, NEC 2017 AND ALL LOCAL CODES &
ORDINANCES.
ROOF SHALL HAVE NO MORE THAN TWO LAYERS OF COVERING IN ADDITION TO THE SOLAR EQUIPMENT.
INSTALLATION OF SOLAR EQUIPMENT SHALL BE FLUSH MOUNTED, PARALLEL TO AND NO MORE THAN 6-INCHES
ABOVE THE SURFACE OF THE ROOF FOR SLOPED ROOF AND NO MORE THAN 10-INCHES ABOVE THE SURFACE OF
THE ROOF FOR FLAT ROOF.
ANY PLUMBING VENTS ARE NOT TO BE CUT OR COVERED FOR SOLAR EQUIPMENT INSTALLATION. ANY
RELOCATION OR MODIFICATION OF THE VENT REQUIRES A PLUMBING PERMIT AND INSPECTION.
ALL DESIGN, CALCULATIONS ARE PERFORMED BY DANIEL DUNZIK REGISTERED ARCHITECT. FLORIDA STATE
STATUTE 471.003(3) PROVIDES THAT LICENSED ARCHITECTS ARE EXEMPTED FROM THE PROVISIONS OF
CHAPTER 471 ENGINEERING AND NOT PRECLUDED FROM PERFORMING ENGINEERING SERVICES FOR INTEGRATED
SYSTEMS AND SERVICES THAT ARE INCIDENTAL TO THE DESIGN CONSTRUCTION OR ALTERATION OF BUILDINGS
AND STRUCTURES FOR HUMAN HABITATION.
INVERTER PLACEMENT:
SYSTEM UTILIZES "ENPHASE" MICRO-INVERTERS WITH RAPID SHUTDOWN CONTROL LOCATED ON THE BACK SIDE
OF EACH MODULE.
FSEC CERTIFICATION STATEMENT:
PER FL. STATUE 377.705 , I, MINA A. MAKAR PE# 86753, CERTIFICATE OF AUTHORIZATION #33404, AN
ENGINEER LICENSED PURSUANT TO CHAPTER 471,CERTIFY THAT THE PV ELECTRICAL SYSTEM AND ELECTRICAL
COMPONENTS ARE DESIGNED AND APPROVED USING THE STANDARDS CONTAINED IN THE MOST RECENT
VERSION OF THE FLORIDA BUILDING CODE. FBC 2020
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2022.02.11 08:02:58 -05:00
1 / 14
SCALE: 1/8" = 1'-0"
SITE PLAN
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-2
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ERICH BARRANTES - MS93856
416 COCONUT AVENUE EAST
PORT ST. LUCIE, FL 34952
3058969234
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
2/10/2022
SYSTEM SIZE (DC ): 11.02 KW
29 MODULES: HANWHA Q.PEAK DUO BLK
ML-G9+ 380
29 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
NOTE:
1. ROOF COVERING MATERIAL IS COMPOSED OF
2. EXACT ATTACHMENT LOCATION AND QUANTITY OF ATTACHMENTS ARE BASED ON EXISTING RAFTER LOCATIONS OBTAINED FROM FIELD
MEASUREMENTS. . THE LOCATION AND QUANTITY OF ATTACHMENTS MAY VARY BASED ON RAFTER LAYOUT START POINT, SPACING
VARIATIONS AND ROOFING TYPE. VERIFY IN THE FIELD ALL RAFTER LOCATIONS AND ADJUST LAYOUT AS REQUIRED. A TILE ROOF WILL
PRODUCE A STAGERED ATTACHMENT LAYOUT BECAUSE OF EXISTING STAGERED TILE JOINT LOCATIONS
3. EXISTING RESIDENCE EQUIPPED WITH SMOKE/CO DETECTOR IN AND OUTSIDE OF ALL SLEEPING ROOMS HARDWIRED AND
INTERCONNECTED AS PER FEDERAL LAW
CORRUGATED METAL
SITE PLAN
SYMBOL LEGEND
MAIN SERVICE PANEL
UTILITY METER
SKYLIGHT
VENT
CHIMNEY
SUB-PANEL
MSP
SP
M
SOLAR
AC
DISC
UDC
LC
N3R
CB
SOLAR AC DISCONNECT
LOAD CENTER
NEMA 3R BOX W/ ENVOY-S
COMBINER BOX
PIPE VENT
FAN
SATELLITE DISH
MODULE
FIRE SETBACKS
PITCH DIRECTION
UTILITY DISCONNECT
MIN 3'x3' GROUND ACCESS
POINT
WIND PRESSURE ZONE LINES
ROOF PANEL COUNT TILT AZIMUTH SHADING
R1 29 10°271°95%
RAFTER SPACING
24" O.C. (TYP)
CLAMPING MAX SPACING IN ZONE 1 48" O.C
AND IN ZONE 2 AND ZONE 3 24" O.CRIDGERIDGEGUTTER
GUTTERGUTTERGUTTERGUTTERR1
J-BOX
MSPM
SOLAR
AC
DISC
CB
58'-11
2"
58'-11
2"
59'-2"59'-2"
5'-9"
5'-9"
5'-9"
5'-9"
5'-9"5'-9"
5'-9"
5'-9"
5'-9"
5'-9"
5'-9"
5'-9"
5'-9"5'-9"
5'-9"5'-9"
PZ1
PZ1
PZ3
PZ3
PZ3
PZ3
PZ3
PZ3
PZ3
PZ3
PZ1
PZ1
PZ1
PZ1
PZ1
PZ1
PZ1
PZ1
PZ2e
PZ2e
PZ2e
PZ2e
PZ2e
PZ2e
PZ2e
PZ2nPZ2n
PZ2n PZ2n
PZ2r PZ2r
PZ2r PZ2r
PZ2rPZ2r
PZ2rPZ2r
PZ3e
PZ3e
PZ3e
PZ3e
PZ3e PZ3r PZ3r
PZ3rPZ3r FRONT OF RESIDENCECOCONUT AVENUE EASTDigitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2022.02.11 08:02:58 -05:00
2 / 14
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ERICH BARRANTES - MS93856
416 COCONUT AVENUE EAST
PORT ST. LUCIE, FL 34952
3058969234
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
2/10/2022
SYSTEM SIZE (DC ): 11.02 KW
29 MODULES: HANWHA Q.PEAK DUO BLK
ML-G9+ 380
29 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
PANEL SPECIFICATION
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2022.02.11 08:02:58 -05:00
3 / 14
PANEL LOAD TESTING
RESULTS
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.1
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ERICH BARRANTES - MS93856
416 COCONUT AVENUE EAST
PORT ST. LUCIE, FL 34952
3058969234
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
2/10/2022
SYSTEM SIZE (DC ): 11.02 KW
29 MODULES: HANWHA Q.PEAK DUO BLK
ML-G9+ 380
29 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2022.02.11 08:02:58 -05:00
4 / 14
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.2
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ERICH BARRANTES - MS93856
416 COCONUT AVENUE EAST
PORT ST. LUCIE, FL 34952
3058969234
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
2/10/2022
SYSTEM SIZE (DC ): 11.02 KW
29 MODULES: HANWHA Q.PEAK DUO BLK
ML-G9+ 380
29 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
INVERTER SPECIFICATION
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2022.02.11 08:02:58 -05:00
5 / 14
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.3
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ERICH BARRANTES - MS93856
416 COCONUT AVENUE EAST
PORT ST. LUCIE, FL 34952
3058969234
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
2/10/2022
SYSTEM SIZE (DC ): 11.02 KW
29 MODULES: HANWHA Q.PEAK DUO BLK
ML-G9+ 380
29 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
COMBINER BOX SPECIFICATION
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2022.02.11 08:02:58 -05:00
6 / 14
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.4
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ERICH BARRANTES - MS93856
416 COCONUT AVENUE EAST
PORT ST. LUCIE, FL 34952
3058969234
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
2/10/2022
SYSTEM SIZE (DC ): 11.02 KW
29 MODULES: HANWHA Q.PEAK DUO BLK
ML-G9+ 380
29 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
JUNCTION BOX SPECIFICATION
ROOF JUNCTION BOX SPECIFICATION FOR LOW-SLOPE/TILE/METAL/CONCRETE ROOF
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2022.02.11 08:02:58 -05:00
7 / 14
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.5
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ERICH BARRANTES - MS93856
416 COCONUT AVENUE EAST
PORT ST. LUCIE, FL 34952
3058969234
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
2/10/2022
SYSTEM SIZE (DC ): 11.02 KW
29 MODULES: HANWHA Q.PEAK DUO BLK
ML-G9+ 380
29 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
ATTACHMENT DETAIL
ATTACHMENT DETAIL FOR CORRUGATED METAL ROOF
REVISIONS
REV
A
B
DESCRIPTION
INITIAL RELEASE
ADD B15019-001
BY
LWF
LWF
DATE
10/16/2018
10/24/2018
IN 1/2" PLYWOOD
LOAD DIRECTION
UPLIFT
LATERAL.PERP. TO SLOT
LATERAL.PARALLEL TO SLOT
IN 7/16" OSB
5
4
LOAD DIRECTION
UPLIFT
LATERAL.PERP. TO SLOT
LATERAL.PARALLEL TO SLOT
NOTES
* Factor of Safety as shown
3 * Torque at 3/8" T-Bolt = 15ft.lbs (20 N.m)
* All loads in pounds force
* Values valid only for conditons equal or better than test conditions
* Values valid only when product is used in accordance with SunModo
7
2
installation instruction and other technical documentation
* The kit as shown in the BOM. For alternative configurations, contact
SunModo
4 1/4" Deck Screws in Min 7/16" OSB
8 B
1
B
6
8 B15019-001
7 B15018-001
6 C50001-001
5 B15003-001
4 B20007-002
3 A20062-001
2 B15039-001
1 A50224-001
ITEM
MATERIAL
PART NUMBER
SEE NOTES
Third Angle Projection:
GENERAL SPECIFICATIONS
All Dimensions in inches [millimeters]
Tolerances
X.XXX ±0.01 [0.25mm]
X.XX ±0.02 [0.50mm]
X.X ±0.039 [1.0mm]
Unless otherwise spec'd
DRAWN BY
LWF
THIS DRAWING IS CONFIDENTIAL PROPERTY OF SUNMODO AND ITS CONTENTS MAY
NOT BE DISCLOSED WITHOUT THE PRIOR WRITTEN CONSENT OF SUNMODO CORP.
CHECKED BY
APPROVALS
Break all sharp edges
.010-.020 unless
otherwise specified.
DATE
10/16/2018
B
SCALE:
TITLE
METAL ROOF DECK MOUNT KIT
DRAWING NUMBER
NONE
K50532-001 STRUCTURE
SHEET 1 of 1
SEALING WASHER .26 ID X .50 X .125
HEX CAP SCREW 3/8-16 X 3/4
GASKET, EPDM, WITH ADHESIVE
FLANGE NUT 3/8-16
T-BOLT 3/8-16X1.0", 304 SS
L FOOT
HEX WASHER HEAD LAG BOLT 1/4X3
METAL ROOF DECK MOUNT
DESCRIPTION
SunModo Corp.
14800 NE 65TH STREET, VANCOUVER WA 98682
4
1
2
2
1
1
4
1
QTY
FOS=2
345
140
265
FOS=2
190
125
135
FOS=3
230
95
175
FOS=3
125
85
90
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2022.02.11 08:02:58 -05:00
8 / 14
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.6
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ERICH BARRANTES - MS93856
416 COCONUT AVENUE EAST
PORT ST. LUCIE, FL 34952
3058969234
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
2/10/2022
SYSTEM SIZE (DC ): 11.02 KW
29 MODULES: HANWHA Q.PEAK DUO BLK
ML-G9+ 380
29 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
STRUCTURAL CALCULATION
2-RAIL RACKING PLUS SOLAR SYSTEM DEAD LOAD
COMPONENT WEIGHT/UNIT (LB)#
MODULES 0 29
INVERTERS 4.0 29
RAILS (2-RAIL) @ 1.8LB/LF.1.8 14.0
ATTACHMENT/FLASHING 0.98 54
ARRAY TOTAL AREA (SQFT)590
ARRAY TOTAL WEIGHT (LB)194
TOTAL DEAD LOAD PER SF (LB/SQFT)2.60
10 % OF LEAST HORIZONTAL DIMENSION OR 40% OF THE BUILDING HEIGHT WHICHEVER IS
SMALLER BUT NOT LESS THAN EITHER 4% OF THE LEAST HORIZONTAL DIMENSION OR 3'-0"
WIND PRESSURE ZONE CALCULATION (ASCE FIGURE 30.4-2A, 2B)
HORIZONTAL DIMENSION A 58.1199989318847'X 10% = 5.81199989318848'
HORIZONTAL DIMENSION B 59.2000007629394'X 10% = 5.92000007629394'
BUILDING HEIGHT 15'X 40% = 6'
PRESSURE ZONE WIDTH 5' 9.74 "
CERTIFICATION OF WIND LOAD PRESSURE CALCULATION THIS IS A 2-RAIL DESIGN
DESIGN LOAD CRITERIA. AS PER ASCE 7-16 (2.4.1)
FOR THIS PARTICULAR CASE, THE "DOWNFORCE" CASE 2 AND
UPLIFT HAVE BEEN TAKEN INTO CONSIDERATION.
P (PSF) = 1xD + 1x PNET (DOWNFORCE)
P (PSF) = 0.6xD + 0.6x PNET (UPLIFT)
(P = TOTAL DESIGN LOAD)
(PNET = WIND LOAD)
(D = DEAD LOAD)
PNET HAVE BEEN CALCULATED FOLLOWING THE ALLOWABLE STRESS DESIGN METHOD.
THE MAXIMUM ABSOLUTE VALUE OF THE 2 CASES IS THE UPLIFT LOAD.
THIS 2-RAIL DESIGN IS WELL UNDER THE CAPACITY OF THE INDIVIDUAL ATTACHMENT
CAPACITIES FOR THE DESIGN. THE PHOTOVOLTAIC MODULES USED IN CONJUNCTION WITH
2-RAIL ATTACHMENT SYSTEM ADDED HAVE A DESIGN CAPACITY OF -4,000 PA., 84 PSF. THIS
DESIGN IS WITHIN THE LOADING CAPACITIES OF THE PHOTOVOLTAIC MODULE 2-RAIL DESIGN
TESTING CAPACITIES THAT HAVE BEEN PERFORMED BY INDEPENDENT TESTING BY THE PANEL
MANUFACTURERS ENGINEERS. SEE ATTACHED MANUFACTURERS TEST DATA.
WIND LOAD CALCULATIONS (ASCE 7-16 EQ. 29.4-7)
VELOCITY PRESSURE Qh = 0.00256 Kz*Kzt*Kd*Ke*V^2(LB/SQFT) (EQ. 26.10-1)
EXPOSURE B
V (WIND SPEED)175
MEAN HEIGHT 15.00
EFFECTIVE WIND AREA (AREA OF ONE PANEL)20.37
Kz (VELOCITY PRESSURE EXPOSURE)0.57
Kzt (TOPOGRAPHIC FACTOR)1
Kd (WIND DIRECTIONALITY)0.85
Ke (GROUND ELEVATION FACTOR)1
LF (LOAD FACTOR BASED ON ASD DESIGN)0.6
Qh (VELOCITY PRESSURE)22.98
ra (SOLAR PANEL PRESSURE EQUALIZATION FACTOR)0.68
TOTAL PRESSURE AND ATTACHMENT SPACING FOR GABLE ROOF WITH 7 to 20 DEGREE TILT
GCp p- (LB/SQFT)p+
(LB/SQFT)
pnet- (LB/SQFT)pnet+
(LB/SQFT)
ATTACHMENT SPACING (INCH)UPLIFT PRESSURE FOR EACH
ATTACHMENT (LB)
ZONE UPLIFT DOWNWARD ARRAY INTERIOR ARRAY EDGE ARRAY INTERIOR ARRAY EDGE ARRAY INTERIOR ARRAY EDGE ARRAY INTERIOR ARRAY EDGE
1 -1.98 0.30 -30.82 -46.23 4.66 -16.93 -26.18 7.26 48.00 24.00 -204.41 -158.01
2e -1.98 0.30 -30.82 -46.23 4.66 -16.93 -26.18 7.26 24.00 24.00 -102.20 -158.01
2n -2.56 0.30 -39.76 -59.63 4.66 -22.29 -34.22 7.26 24.00 24.00 -134.58 -206.57
2r -2.56 0.30 -39.76 -59.63 4.66 -22.29 -34.22 7.26 24.00 24.00 -134.58 -206.57
3e -2.56 0.30 -39.76 -59.63 4.66 -22.29 -34.22 7.26 24.00 24.00 -134.58 -206.57
3r -3.04 0.30 -47.31 -70.96 4.66 -26.82 -41.02 7.26 24.00 16.00 -161.93 -165.07
WIND PRESSURE PNET IS CALCULATED BY ASCE 7-16 EQ. 29.4.7, WHERE Qh IS CALCULATED BY
EQ. 29.4-7 (PARAMETERS SHOWN IN THE TABLE).
GCp ARE CHOSEN FROM FIGURE 30.3-A-I FOR SPECIFIC ROOF TYPE AND ROOF TILT WITH
EFFECTIVE WIND AREA EQUALS TO 10 SQFT (INTERPOLATION MAY REQUIRED).
ARRAY EDGE FACTOR rE = 1.5 FOR ARRAY EDGES UPLIFT PRESSURE IF ARRAY EDGE IS MORE
THAN 10 FEET (0.5h) TO ROOF EDGES AND MORE THAN 4 FEET TO ADJACENT ARRAY OR NEXT
ADJACENT PANEL. rE = 1.0 FOR ARRAY INTERIOR UPLIFT PRESSURE AND ALL DOWNWARD
PRESSURE AS DEFINED IN ASCE 7-16 29.4.4.
NO PANEL ARE LOCATED IN ARRAY EDGE AREA AS DEFINED BY ASCE 7-16 29.4.4. FOR
THIS PROJECT.
ALLOWABLE LOAD / ATTACHMENT 5/16” LAG SCREW W/ 3.00” EMBEDMENT INTO RAFTER
BELOW ACCORDING TO THE NATIONAL DESIGN SPECIFICIFICATION FOR WOOD
CONSTRUCTION 2015 EDITION. = W' = W X CD X CT. - PER TABLE 11.3.1 NDS
5/16” DIA. 4" LONG LAG W/ 3.00” EMBEDMENT INTO 2X ROOF RAFTER
W' = 266LB/IN (NDS11.3.1 TABLE 12.2A) FOR DF. LARCH, S.Y.P., AND S.P.F. SPECIES
CD = 1.6 (TABLE 2.3.2 2015 NDS), CT = 1.0 (TABLE 10.3.4 2015 NDS)
W' = 266LB/IN X 3.00” X 1.6 X 1.0 = 1,276.8LBS = ULTIMATE
MAX ALLOWABLE UPLIFT PRESSURE WITH 60% OF ULTIMATE CAPACITY
1,276.8LBS X 0.6 = 766.08LBS
-THREAD MUST BE EMBEDDED IN THE SIDE GRAIN OF A TRUSSES OR OTHER
STRUCTURAL MEMBER INTEGRAL WITH THE BUILDING STRUCTURE.
-LAG BOLTS MUST BE LOCATED IN THE MIDDLE THIRD OF THE STRUCTURAL MEMBER.
-THESE VALUES ARE NOT VALID FOR WET SURFACE.
-INSTALL LAG BOLTS WITH HEAD AND WASHER FLUSH TO SURFACE (NO GAP). TORQUE
AS PER MANUFACTURERS SPECIFICATIONS. DO NOT OVER-TORQUE.
-WITHDRAWAL DESIGN VALUES FOR LAG SCREW CONNECTIONS SHALL BE MULTIPLIED
BY APPLICABLE ADJUSTMENT FACTORS IF NECESSARY. SEE TABLE 10.3.1 IN THE
AMERICAN WOOD COUNCIL NDS FOR WOOD CONSTRUCTION.
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2022.02.11 08:02:58 -05:00
9 / 14
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.7
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ERICH BARRANTES - MS93856
416 COCONUT AVENUE EAST
PORT ST. LUCIE, FL 34952
3058969234
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
2/10/2022
SYSTEM SIZE (DC ): 11.02 KW
29 MODULES: HANWHA Q.PEAK DUO BLK
ML-G9+ 380
29 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
SEALANT SPECIFICATION
SEALANT SPECIFICATION FOR CORRUGATED METAL ROOFS
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2022.02.11 08:02:58 -05:00
10 / 14
ENPHASE 80A
AC COMBINER
BOX
10A/15A BREAKER
(MANUFACTURER
SUPPLIED FOR
ENVOY)
20A BREAKER (A)
20A BREAKER (B)
20A BREAKER (C)
2A
2B
2C
3
GND
NEU
TERMINATION CAP
INSTALLED ON
END OF CABLE
=...==
INVERTERS
INSTALLED ON
RAIL SYSTEM
=...==
=...==
1A TO 1C
ROOF
JUNCTION
BOX
BRANCH CIRCUIT A
10 MICRO-INVERTERS
BRANCH CIRCUIT B
10 MICRO-INVERTERS
BRANCH CIRCUIT C
9 MICRO-INVERTERS
29 HANWHA Q.PEAK DUO BLK ML-G9+ 380 380W MODULES PAIRED WITH
29 ENPHASE IQ7PLUS-72-2-US MICRO-INVERTERS
GND BUS
NEU BUS
POWER
GROUND
EXISTING SQUARE D 200A
MAIN SERVICE PANEL 240 V
MAIN BREAKER: 150A
150A
UTILITY
METER
GRID
GND BUS
NEU BUS
POWER
GROUND
EXISTING SQUARE D 200A
MAIN SERVICE PANEL 240 V
MAIN BREAKER: 150A
150A
UTILITY
METER
GRID
GND
NEU
4
EATON 60A FUSIBLE
SOLAR AC DISCONNECT
45A
45A FUSES
SOLAR CIRCUIT
DISCONNECTING MEANS
GND BUS
NEU BUS
POWER
GROUND
EXISTING SQUARE D 200A
MAIN SERVICE PANEL 240 V
MAIN BREAKER: 150A
150A
UTILITY
METER
GRID
PV SYSTEM CURRENT 43.8625 A
SOLAR
AC
DISCONNECT
EMPHASE
COMBINER
BOX
EXISTING
METER
MSP LOCATED INSIDE
OF STRUCTURE
MSP
METER
RISER
#2/0 AWG SERVICE
CONDUCTOR FROM
OVERHEAD FOR
200AMP SERVICE
HOT LINE TAPS
MINUMUM BEND
RADIUS 4"
ENCLOSURE DIMENSIONS
LENGTH: 21.31"
WIDTH:10.3"
DEPTH:9.06"
#2/0 AWG SERVICE
CONDUCTOR FROM
UTILITY METER FOR
200AMP SERVICE
Wire Tag Conduit Wire Qty Wire
Gauge Wire Type Temp.
Rating
Wire
Ampacity (A)
Temp.
Derate
Conduit
Fill Derate
Derated
Ampacity (A)
Inverter
Qty NOC (A)NEC
Correction
Design
Current (A)
Ground
Size
Ground Wire
Type
1A TO 1C OPEN AIR 3 12 AWG Trunk Cable 90°C 30 0.96 1 28.80 10 1.21 1.25 15.13 06 AWG BARE CU
2A
3/4" PVC 6
10 AWG THWN-2 75°C 35 0.96 0.8 26.88 10 1.21 1.25 15.13
08 AWG THWN-22B10 AWG THWN-2 75°C 35 0.96 0.8 26.88 10 1.21 1.25 15.13
2C 10 AWG THWN-2 75°C 35 0.96 0.8 26.88 9 1.21 1.25 13.61
3 3/4" PVC 3 + G 08 AWG THWN-2 75°C 50 0.96 1 48.00 29 1.21 1.25 43.86 08 AWG THWN-2
4 3/4" PVC 3 + G 06 AWG THWN-2 75°C 65 0.96 1 62.40 29 1.21 1.25 43.86 THWN-2
THREE LINE DIAGRAM
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-4
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ERICH BARRANTES - MS93856
416 COCONUT AVENUE EAST
PORT ST. LUCIE, FL 34952
3058969234
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
2/10/2022
SYSTEM SIZE (DC ): 11.02 KW
29 MODULES: HANWHA Q.PEAK DUO BLK
ML-G9+ 380
29 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
ELECTRICAL SERVICE ELEVATION INTERCONNECTION DETAIL
NOTE: LETTER "G" IN WIRE QTY TAB STANDS FOR GROUNDING CONDUCTOR.
FSEC CERTIFICATION STATEMENT:
PER FL. STATUE 377.705 , I, MINA A. MAKAR PE# 86753,
CERTIFICATE OF AUTHORIZATION #33404, AN ENGINEER
LICENSED PURSUANT TO CHAPTER 471,CERTIFY THAT THE PV
ELECTRICAL SYSTEM AND ELECTRICAL COMPONENTS ARE
DESIGNED AND APPROVED USING THE STANDARDS
CONTAINED IN THE MOST RECENT VERSION OF THE FLORIDA
BUILDING CODE. FBC 2020
SOLAR INSTALLER NOTES:
150AMP METER/RISER/FEEDER REPLACEMENT REQUIRED
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2022.02.11 08:02:58 -05:00
11 / 14
ELECTRICAL NOTES
SUB PANEL
BREAKER SIZE
# OF MODULES PV BREAKER
PER BRANCH
UP TO 16 20A
PV ADODULE RATINGS
MODULE MAKE HANWHA
MODEL Q.PEAK DUO BLK
ML-G9+ 380
MAX POWER 380W
OPEN CIRCUIT VOLTAGE 45.04V
MPP VOLTAGE 37.85V
SHORT CIRCUIT CURRENT 10.5A
MPP CURRENT 10.04A
NUMBER OF MODULES 29
UL1703 COMPLIANT YES
INVERTER RATINGS
INVERTER MAKE ENPHASE
MODEL IQ7PLUS-72-2-
US
MAX OUTPUT POWER 290W
OPEN DC VOLTAGE 60V
NOMINAL AC VOLTAGE 240V
MAX AC CURRENT 1.21A
CEC INVERTER EFFICIENCY 97%
NUMBER OF INVERTERS 29
UL1703 COMPLIANT YES
VOLTAGE DROP CALCULATIONS
FORMULA USED PER NEC 2014 HANDBOOK 215.2(A)(4) WHERE APPLICABLE
WIRE RUN Vmp Imp R L (FT)Vo % Vo WIRE SIZE
BRANCH TO J-BOX 240.00
J-BOX TO LOAD
CENTER 240.00
LOAD CENTER TO AC
DISCONNECT 240.00
AC DISCONNECT TO
INTERCONNECTION 240.00
#NUM!1.98 #NUM!#NUM!#NUM!12 AWG
0 1.24 50.00 0.000 0.00%10 AWG
0 1.24 3.00 0.000 0.00%10 AWG
0 1.24 10.00 0.000 0.00%10 AWG
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-4.1
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ERICH BARRANTES - MS93856
416 COCONUT AVENUE EAST
PORT ST. LUCIE, FL 34952
3058969234
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
2/10/2022
SYSTEM SIZE (DC ): 11.02 KW
29 MODULES: HANWHA Q.PEAK DUO BLK
ML-G9+ 380
29 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
MAKE MODEL VOLTAGE
RATING
CONDUCTOR
RANGE MAIN
CONDUCTOR
RANGE TAP
ILSCO IPC 4020 600 V 4/0-4 AWG 6-14 AWG
ILSCO IPC 4006 600 V 4/0-2 AWG 2/0-6 AWG
INSTRUCTIONS FOR LINE TAPS
FIGURE 1:
1.ADJUST THE CONNECTOR NUT TO SUITABLE
LOCATION
2.PUT THE BRANCH WIRE INTO THE CAP SHEATH FULLY
3.INSERT THE MAIN WIRE, IF THERE ARE TWO LAYS OF
INSULATED LAY IN THE MAIN CABLE, SHOULD STRIP A
CERTAIN LENGTH OF THE FIRST INSULATED LAY
FROM INSERTED END
4.TURN THE NUT BY HAND, AND FIX THE CONNECTOR IN
SUITABLE LOCATION.
5.SCREW THE NUT WITH THE SLEEVE SPANNER.
6.SCREW THE NUT CONTINUALLY UNTIL THE TOP PART
IS CRACKED AND DROPPED DOWN
THIS SOLAR PHOTOVOLTAIC SYSTEM COMPLIES WITH THE 2020
FLORIDA BUILDING CODE AND THE 2017 NATIONAL ELECTRICAL CODE
1.ALL CALCULATIONS FOR VOC, VMAX, IMP AND ISC HAVE BEEN
CALCULATED USING THE MANUFACTURED STRING CALCULATOR BASED
ON ASHRAE 2% HIGH AND EXTREME MINIMUM TEMPERATURE
COEFFICIENTS.
2.THE ENTIRE ARRAY IS BONDED ACCORDING TO (NEC 690.46 - 250.120
PARAGRAPH C). THE GROUND IS CARRIED AWAY FROM THE GROUNDING
LUG USING #6 BARE COPPER WIRE OR #8 THWN-2 COPPER WIRE.
3.THIS SYSTEM COMPLIES WITH NEC 2017
4.BRANCH CIRCUIT CALCULATION FOR WIRE TAG 1 DISPLAYS THE
LARGEST BRANCH CIRCUIT IN SYSTEM. OTHER BRANCH CIRCUITS
SHALL HAVE LOWER DESIGN CURRENT THAN THE ONE SHOWN. IN
ADDITION, VOLTAGE DROP CALCULATIONS FROM PANELS TO THE
COMBINER BOX SHALL BE SHOWN IN A SIMILAR FASHION
5.ALL CONDUCTORS ARE SIZED BASED ON NEC 2017 ARTICLE 310
6.ALL EQUIPMENT INSTALLED IS RATED AT 75°C
7.INVERTER NOC (NOMINAL OPEN CURRENT) OBTAINED FROM
EQUIPMENT DATASHEET
8.CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH ALL
LOCAL AND NATIONAL CODE REQUIREMENTS.
9.EACH MODULE MUST BE GROUNDED ACCORDING TO USER
INSTRUCTIONS
10.ALL EQUIPMENT SHALL BE LISTED PER NEC 690.4(B)
11.PER NEC 690.13, 690.15, PROVIDE A WARNING SIGN AT ALL LOCATIONS
WHERE TERMINALS OF THE DISCONNECTING MEANS MAY BE
ENERGIZED IN THE OPEN POSITION> SIGN SHALL READ *WARNING -
ELECTRIC SHOCK HAZARD - DO NOT TOUCH TERMINALS - OR
EQUIVALENT.
12.PER NEC 705.10, PROVIDE A PERMANENT PLAQUE OR DIRECTORY
SHOWING ALL ELECTRIC POWER SOURCES ON THE PREMISES AT
SERVICE ENTRANCE.
13.INTERCONNECTION METHOD SHALL COMPLY WITH NEC705.12
14.AND OPTION FOR A SINGLE CIRCUIT BRANCH TO BE SPLIT INTO TWO
SUB-CIRCUIT BRANCHES IS ACCEPTABLE.
ELECTRICAL NOTES:
15.ALL CONDUCTORS MUST BE COPPER.
16.NEUTRAL AND EQUIPMENT GROUNDING CONDUCTOR BONDED AS PER
NEC 250.24(C).
17.EQUIPMENT GROUNDING CONDUCTOR IS CONNECTED TO A
GROUNDING ELECTRODE SYSTEM PER 250.54(D).
18.FUSES FOR PV DISCONNECT HAVE AIC RATINGS OF 200KA AC AND 20KA
DC.
19.SUPPLY SIDE CONNECTION SHALL BE MADE USING ILSCO INSULATION
PIERCING CONNECTORS (IPC). MAKE, MODEL, AND RATING OF
INTERCONNECTION CAN BE SEEN ON TABLE 1 BELOW.
20.METHOD OF INTERCONNECTION CAN BE SEEN IN FIGURE 1.
21.UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL PHOTOVOLTAIC
SYSTEM COMPONENTS LOCATED AT THE SERVICE ENTRANCE.
22.WORKING CLEARANCES AROUND THE EXISTING AND NEW ELECTRICAL
EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH NEC ARTICLE
110.26.
23.CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT
RESISTANT PER NEC ARTICLE 300.6 (C)(1) AND ARTICLE 310.8 (D).
24.CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR
USE IN WET LOCATIONS PER NEC ARTICLE 310.10 (C).
25.TOTAL AREA OF ALL CONDUCTORS, SPLICES, AND TAPS INSTALLED AT
ANY CROSS SECTION OF THE WIRING DOES NOT EXCEED 75% OF THE
CROSS SECTIONAL AREA OF THE SPACE. NEC 312.8(A)(2).
26.SYSTEM IS CONSIDERED AN AC MODULE SYSTEM. NO DC
CONDUCTORS ARE PRESENT IN CONDUIT, COMBINER, JUNCTION BOX,
DISCONNECT. AND COMPLIES WITH 690.6 - NO DC DISCONNECT AND
ASSOCIATED DC LABELING ARE REQUIRED.
27.SYSTEM COMPLIES WITH 690.12 RAPID SHUTDOWN AND ASSOCIATED
LABELING AS PER 690.56(C). AC VOLTAGE AND SYSTEM OPERATING
CURRENT SHALL BE PROVIDED 690.52.
28.CONDUCTORS IN CONDUIT ARE AC CONDUCTORS BRANCH CIRCUITS
AND NOT PV SOURCE CIRCUITS. 690.6.
29.ALL GROUNDING SHALL COMPLY WITH 690.47(A) IN THAT THE
AC MODULES WILL COMPLY WITH 250.64.
30.NO TERMINALS SHALL BE ENERGIZED IN THE OPEN POSITION
IN THIS AC MODULE SYSTEM 690.13, 690.15, 690.6.
31. WHERE APPLICABLE: INTERCONNECTION SHALL COMPLY
WITH 705.12(A) OR 705.12(B)
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2022.02.11 08:02:58 -05:00
12 / 14
ELECTRICAL SHOCK HAZARD
TERMINALS ON BOTH LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING
QUANTITY LOCATION
A
LABELTAG
B
C
D
E
F
1
1
JUNCTION BOX
INTERCONNECTION
POINT
1 UTILITY METER
1 COMBINER BOX
1
1 AT ANY COMBINER BOX
1 AT ANY JUNCTION BOX
1 OF EACH AT FUSED AC
DISCONNECT
COMPLETE VOLTAGE AND
CURRENT VALUES ON
DISCONNECT LABEL
1 OF EACH AT BUILDING
INTERCONNECTION POINT AND
ONE DIRECTORY PLACARD
1 AT UTILITY METER AND ONE
DIRECTORY PLACARD
NOTE EXAMPLES
A B
D
REVENUE METER
C
POWER TO THIS SERVICE IS
ALSO SUPPLIED FROM ON-SITE
SOLAR GENERATION
AC SYSTEM DISCONNECT
WARNING
WARNING: PHOTOVOLTAIC
POWER SOURCE
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH
RAPID SHUTDOWN
RAPID SHUTDOWN SWITCH FOR
SOLAR PV SYSTEM
1
AC SOLAR VOLTAGE
G
12 AC CONDUITS
1 AT EVERY SEPARATION BY
ENCLOSURES / WALLS /
PARTITIONS / CEILINGS / FLOORS
OR NO MORE THAN 10'
F G BACKFEED
DUAL POWER SUPPLY
SECONDARY SOURCE IS
PHOTOVOLTAIC SYSTEM
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON BOTH LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING
NOMINAL OPERATING AC VOLTAGE : 240V
NOMINAL OPERATING AC FREQUENCY : 60HZ
MAXIMUM AC POWER : VA
MAXIMUM AC CURRENT : 40A
MAXIMUM OVERCURRENT DEVICE RATING FOR
AC MODULE PROTECTION : 20A
AC CURRENT PV
MODULES
1
BACKFEED PANEL
H
CAUTION
CAUTION
POWER SOURCE OUTPUT CONNECTION.
DO NOT RELOCATE THIS OVERCURRENT
DEVICE
WARNING
PHOTOVOLTAIC SYSTEM
INSTALLED BY MOMENTUM SOLAR
3096 B HAMILTON BLVD
S. PLAINFIELD, NJ 07080
PHONE NUMBER:732-902-6224
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
ENTIRE PV SYSTEM
SOLAR ELECTRIC
PV PANELS
SECTIONS OF THE PV SYSTEM THAT
ARE SHUT DOWN WHEN THE RAPID
SHUTDOWN SWITCH IS OPERATED
SECTIONS OF THE PV SYSTEM THAT
ARE NOT SHUT DOWN WHEN THE RAPID
SHUTDOWN SWITCH IS OPERATED
EMERGENCY RESPONDER
THIS SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
RATED AC
OUTPUT CURRENT
NOMINAL OPERATING
AC VOLTAGE
A
240 V
PHOTOVOLTAIC SYSTEM
AC DISCONNECT
AC DISCONNECT
(RSD SWITCH)
RAPID SHUTDOWN
TO BE LOCATED
AT AC
DISCONNECT
OUTSIDE THE
HOUSE
DUAL POWER SUPPLY
SECONDARY SOURCE IS
PHOTOVOLTAIC SYSTEM
EQUIPMENT LABELS
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-4.2
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ERICH BARRANTES - MS93856
416 COCONUT AVENUE EAST
PORT ST. LUCIE, FL 34952
3058969234
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
2/10/2022
SYSTEM SIZE (DC ): 11.02 KW
29 MODULES: HANWHA Q.PEAK DUO BLK
ML-G9+ 380
29 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2022.02.11 08:02:58 -05:00
13 / 14
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-5
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ERICH BARRANTES - MS93856
416 COCONUT AVENUE EAST
PORT ST. LUCIE, FL 34952
3058969234
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
2/10/2022
SYSTEM SIZE (DC ): 11.02 KW
29 MODULES: HANWHA Q.PEAK DUO BLK
ML-G9+ 380
29 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
STRUCTURAL CERTIFICATION
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.