HomeMy WebLinkAboutfire departmentSAINT LUCIE COUNTY FIRE DISTRICT
PLAN REVIEW FORM
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
Telephone: 772-621-3322
Fax: 772-621-3604
Web Address: www.slcfd.com
Building Dept. SLC FMO Permit # B-22-59
Project Name A -VENTURES INC. — _ BLDG Permit # 2110-0825
Address 4000 METZGER RD. -- T City FORT PIERCE
Contractor REMNANT CONSTRUCTION
Address 1900 SW FOX POINT TRAIL — --� —_�—� City FORT PIERCE
State IFL — -- Zip 34950 Telephone 772-577-5850
Architect/Engineer DON BERGMAN ARCHITECTURE --—� Telephone 772-466-5832
Occupancy Type S Construction Type Square Feet
Occupant Load 79 -- Number of Stories f 1 — I Access Box REQUIRE Access Key Switch N/A
AFS Permit �_— FA Permit — _ FFP Permit
LL�� L�General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. A Radio coverage Pre -Survey Signal Strength inspection is required before any final inspection is scheduled.
5. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
6. Failed inspections require payment of fee prior to rescheduling of further inspections.
7. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
8. Fire alarm panels shall be located indoors within air conditioned space.
9. Plans and construction are subject to corrections in the field to maintain code compliance.
10. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
11. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE CURRENTLY ADOPTED VERSION OF THE FLORIDA FIRE PREVENTION CODE IS ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
-ANY ALTERATION TO THE FIRE ALARM REQUIRES SEPARATE PERMIT.
-ANY ALTERATION TO THE. FIRE SPRINKLER SYSTEM REQUIRES SEPARATE PERMIT.
Page Fil of 11], Reviewed by BRIAN PUTNAM Date 2022