HomeMy WebLinkAboutAPPROVED, PPB-FERREIRA 2022.01.11 FINAL_PG-3POOL LIGHT U.L.
APPROVED
POOL STEEL
LOW VOTLAGE NICHELESS
LIGHT
1 ½”" PVC CONDUIT
LIGHT NICHE DETAIL
FROM 12V TRANSFORMER
N.T.S.
4" MIN. FROM WATER
LEVEL TO TOP OF LENS
POOL LIGHT U.L.
APPROVED
POOL STEEL
LOW VOTLAGE NICHELESS
LIGHT
1 ½”" PVC CONDUIT
LIGHT NICHE DETAIL
FROM 12V TRANSFORMER
N.T.S.
4" MIN. FROM WATER
LEVEL TO TOP OF LENS
NOTE: BOND WIRE TO BE SECURED
TO STEEL WITH APPROVED CLAMP.
TO BE ENCASED IN DECK SLAB OR CONCRETE BOX
PROVIDING MIN.
3" OF COVER AROUND CLAMP
POOL BOND SCHEMATIC
N.T.S.
POOL BOND SCHEMATIC
N.T.S.
TO POOL EQUIPMENT#8 BARE COPPER WIRE FOR 360°
WITH 4 JUMPERS TO BE 18" TO 24"
FROM WATERS EDGEWATER LINE
3"
N.T.S.
PER FLORIDA BUILDING CODE
ADAPTION OF N.E.C. 2017 SEC 680.26
EQUIPOTENTIAL
BONDING GRID DETAIL
#8 BARE COPPER WIRE FOR 360°
WITH 4 JUMPERS TO BE 18" TO 24"
FROM WATERS EDGEWATER LINE
3"
N.T.S.
PER FLORIDA BUILDING CODE
ADAPTION OF N.E.C. 2017 SEC 680.26
EQUIPOTENTIAL
BONDING GRID DETAIL
NOTE: PROVIDE CONTINOUS
SINGLE #8 COOPER BONDED
IN FOUR POINTS (360 ) AROUND
POOL & SPA AS PER N.E.C.
2017 ART. 680.26 (B) & (C)
o
NOTE: PROVIDE CONTINOUS
SINGLE #8 COOPER BONDED
IN FOUR POINTS (360 ) AROUND
POOL & SPA AS PER N.E.C.
2017 ART. 680.26 (B) & (C)
o
NOTE: BOND WIRE TO BE SECURED
TO STEEL WITH APPROVED CLAMP.
TO BE ENCASED IN DECK SLAB OR CONCRETE BOX
PROVIDING MIN.
3" OF COVER AROUND CLAMP
POOL BOND SCHEMATIC
N.T.S.
TO POOL EQUIPMENT#8 BARE COPPER WIRE FOR 360°
WITH 4 JUMPERS TO BE 18" TO 24"
FROM WATERS EDGEWATER LINE
3"
N.T.S.
PER FLORIDA BUILDING CODE
ADAPTION OF N.E.C. 2017 SEC 680.26
EQUIPOTENTIAL
BONDING GRID DETAIL
NOTE: PROVIDE CONTINOUS
SINGLE #8 COOPER BONDED
IN FOUR POINTS (360 ) AROUND
POOL & SPA AS PER N.E.C.
2017 ART. 680.26 (B) & (C)
o
E-1E-1 DRAFTED BY: G.S.M.DESIGNER
A Custom Pool Designed Especially For:A Custom Pool Designed Especially For:
1/7/2022
IF SIGNED DIGITALLY ABOVE, PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES
IF THERE IS A DIGITAL SIGNATURE ON THE FRONT/FIRST PAGE OF THIS FILE, THIS SHEET
IS PART OF A DIGITALLY SIGNED FILE AND DOES NOT REQUIRE A SEPARATE DIGITAL
SIGNATURE ON THIS SHEET
WAYNE MARKHAM BENNETT P.E. #57216
MARKHAM SERVICES, INC. (CA 33018)
1820 NE JENSEN BEACH BLVD #685
JENSEN BEACH, FL 34957-7212
(954) 818-3825 / wayne@wmb-pe.com
ELECTRICAL CODE and NOTES:
National Electrical Code (NEC), NFPA 70 - 2017 shall specifically govern, including Article 680
Swimming Pools, Fountains, and Similar Installations
Article 430.32 Continuous-Duty Motors. Each motor used in continues duty application shall
be protected against overload
Article 680.6 Grounding. Electrical equipment shall be grounded in accordance with Parts V, VI
and VII of Article 250 and connected by wiring methods of Chapter 3, except as modified by this
Article. The following equipment shall be grounded: (1) Through-wall lighting assemblies and
underwater luminaires, other than those low-voltage lighting products listed for the application
without a grounding conductor (2) All electrical equipment located within 1.5 m (5 ft) of the inside
wall of the specified body of water (3) All electrical equipment associated with the recirculating
system of the specified body of water (4) Junction boxes (5) Transformer and power supply
enclosures (6) Ground-fault circuit interrupters (7) Panelboards that are not part of the service
equipment and that supply any electrical equipment associated with the body of water
Article 680.9 Overhead Conductor Clearances. Overhead conductors shall meet the
clearance requirements in this section. Where a minimum clearance from the water level is given,
the measurement shall be taken from the maximum water level of the specified body of water. (A)
Power. With respect to service-drop conductors, overhead service conductors, and open
overhead wiring, swimming pool and similar installations shall comply with the minimum
clearances given in Table 680.9(A) and illustrated in Figure 680.9(A). (B) Communications
Systems. Communications, radio, and television coaxial cables within the scope of Articles 800
to 820 shall be permitted at a height of not less than 3.0 m (10 ft) above swimming and wading
pools, diving structures, and observation stands, towers, or platforms. (C) Network-Powered
Broadband Communications Systems. The minimum clearances for overhead network-powered
broadband communications systems conductors from pools or fountains shall comply with the
provisions in Table 680.9(A) for conductors operating at 0 to 750 volts to ground.
Article 680.10 Electric Pool Water Heaters. All electric pool water heaters shall have the
heating elements subdivided into loads not exceeding 48 amperes and protected at not over
60 amperes. The ampacity of the branch-circuit conductors and the rating or setting of
overcurrent protective devices shall not be less than 125 percent of the total nameplate-rated
load.
Article 680.11 Underground Wiring Location. Underground wiring shall be permitted where
installed in rigid metal conduit, intermediate metal conduit, rigid polyvinyl chloride conduit,
reinforced thermosetting resin conduit, or Type MC cable, suitable for the conditions subject to
that location. Underground wiring shall not be permitted under the pool unless this wiring is
necessary to supply pool equipment permitted by this article. Minimum cover depths shall be as
given in Table 300.5.
Article 680.22 Lighting, Receptacles, and Equipment. (A) Receptacles. (1) Required
Receptacle, Location. Where a permanently installed pool is installed, no fewer than one 125-
volt, 15- or 20-ampere receptacle on a general-purpose branch circuit shall be located not less
than 1.83 m (6 ft) from, and not more than 6.0 m (20 ft) from, the inside wall of the pool. This
receptacle shall be located not more than 2.0 m (6 ft 6 in.) above the floor, platform, or grade
level serving the pool. (2) Circulation and Sanitation System, Location. Receptacles that provide
power for water-pump motors or for other loads directly related to the circulation and sanitation
system shall be located at least 1.83 m (6 ft) from the inside walls of the pool. These receptacles
shall have GFCI protection and be of the grounding type. (3) Other Receptacles, Location. Other
receptacles shall be not less than 1.83 m (6 ft) from the inside walls of a pool. (4) GFCI
Protection. All 15- and 20-ampere, single-phase, 125-volt receptacles located within 6.0 m (20 ft)
of the inside walls of a pool shall be protected by a ground-fault circuit interrupter.
E-1 DRAFTED BY: G.S.M.DESIGNER
A Custom Pool Designed Especially For:
1/7/2022
IF SIGNED DIGITALLY ABOVE, PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES
IF THERE IS A DIGITAL SIGNATURE ON THE FRONT/FIRST PAGE OF THIS FILE, THIS SHEET
IS PART OF A DIGITALLY SIGNED FILE AND DOES NOT REQUIRE A SEPARATE DIGITAL
SIGNATURE ON THIS SHEET
WAYNE MARKHAM BENNETT P.E. #57216
MARKHAM SERVICES, INC. (CA 33018)
1820 NE JENSEN BEACH BLVD #685
JENSEN BEACH, FL 34957-7212
(954) 818-3825 / wayne@wmb-pe.com
ELECTRICAL CODE and NOTES:
National Electrical Code (NEC), NFPA 70 - 2017 shall specifically govern, including Article 680
Swimming Pools, Fountains, and Similar Installations
Article 430.32 Continuous-Duty Motors. Each motor used in continues duty application shall
be protected against overload
Article 680.6 Grounding. Electrical equipment shall be grounded in accordance with Parts V, VI
and VII of Article 250 and connected by wiring methods of Chapter 3, except as modified by this
Article. The following equipment shall be grounded: (1) Through-wall lighting assemblies and
underwater luminaires, other than those low-voltage lighting products listed for the application
without a grounding conductor (2) All electrical equipment located within 1.5 m (5 ft) of the inside
wall of the specified body of water (3) All electrical equipment associated with the recirculating
system of the specified body of water (4) Junction boxes (5) Transformer and power supply
enclosures (6) Ground-fault circuit interrupters (7) Panelboards that are not part of the service
equipment and that supply any electrical equipment associated with the body of water
Article 680.9 Overhead Conductor Clearances. Overhead conductors shall meet the
clearance requirements in this section. Where a minimum clearance from the water level is given,
the measurement shall be taken from the maximum water level of the specified body of water. (A)
Power. With respect to service-drop conductors, overhead service conductors, and open
overhead wiring, swimming pool and similar installations shall comply with the minimum
clearances given in Table 680.9(A) and illustrated in Figure 680.9(A). (B) Communications
Systems. Communications, radio, and television coaxial cables within the scope of Articles 800
to 820 shall be permitted at a height of not less than 3.0 m (10 ft) above swimming and wading
pools, diving structures, and observation stands, towers, or platforms. (C) Network-Powered
Broadband Communications Systems. The minimum clearances for overhead network-powered
broadband communications systems conductors from pools or fountains shall comply with the
provisions in Table 680.9(A) for conductors operating at 0 to 750 volts to ground.
Article 680.10 Electric Pool Water Heaters. All electric pool water heaters shall have the
heating elements subdivided into loads not exceeding 48 amperes and protected at not over
60 amperes. The ampacity of the branch-circuit conductors and the rating or setting of
overcurrent protective devices shall not be less than 125 percent of the total nameplate-rated
load.
Article 680.11 Underground Wiring Location. Underground wiring shall be permitted where
installed in rigid metal conduit, intermediate metal conduit, rigid polyvinyl chloride conduit,
reinforced thermosetting resin conduit, or Type MC cable, suitable for the conditions subject to
that location. Underground wiring shall not be permitted under the pool unless this wiring is
necessary to supply pool equipment permitted by this article. Minimum cover depths shall be as
given in Table 300.5.
Article 680.22 Lighting, Receptacles, and Equipment. (A) Receptacles. (1) Required
Receptacle, Location. Where a permanently installed pool is installed, no fewer than one 125-
volt, 15- or 20-ampere receptacle on a general-purpose branch circuit shall be located not less
than 1.83 m (6 ft) from, and not more than 6.0 m (20 ft) from, the inside wall of the pool. This
receptacle shall be located not more than 2.0 m (6 ft 6 in.) above the floor, platform, or grade
level serving the pool. (2) Circulation and Sanitation System, Location. Receptacles that provide
power for water-pump motors or for other loads directly related to the circulation and sanitation
system shall be located at least 1.83 m (6 ft) from the inside walls of the pool. These receptacles
shall have GFCI protection and be of the grounding type. (3) Other Receptacles, Location. Other
receptacles shall be not less than 1.83 m (6 ft) from the inside walls of a pool. (4) GFCI
Protection. All 15- and 20-ampere, single-phase, 125-volt receptacles located within 6.0 m (20 ft)
of the inside walls of a pool shall be protected by a ground-fault circuit interrupter.
FERREIRA, STEPHEN
4625 S INDIAN RIVER DR
FORT PIERCE, FL 34982
MONIKA POLAK
FERREIRA, STEPHEN
4625 S INDIAN RIVER DR
FORT PIERCE, FL 34982
MONIKA POLAKELECTRICAL RISER DIAGRAM
N.T.S.
¾” PVC CONDUIT W/ 2 #6 HOT,
1 #10 GRND. 1 #10 NEUTRAL
EXISTING PANEL 2P
60A BREAKER
FEEDING POOL
48" MIN.
(2) 12V 24W L.E.D. NICHELESS LIGHTS (POOL)
1" NON-CORROSIVE
CONDUIT
2 #12,
1 # 12
GRND.
(1) JUNCTION BOX
BELOW WATEREXISTING
METER
F.P.L.
POOL
DECK
LEVEL
8" MIN.4" - 6"ELECTRICAL CONTRACTOR SHALL VERIFY THAT THE EXISTING SERVICE AND PANEL HAS
ENOUGH CAPACITY TO ACCOMMODATE THE ADDED POOL EQUIPMENT LOAD PER NEC 220.82"
SALT CHLORINATOR 2 #12 , 1 #12 GRND. ½” PVC
POOL PUMP 3 #12, 1 #12 GRND. GFCI PROTECTED ½” PVC
GFCI 6' TO 20'
FROM WATER
GFCI 6' TO 20'
FROM WATER
1. IN POOL AREA GROUND ALL BOXES, RAILS, LIGHT, MOTOR ECT WITH
#8 BARE COPPER WIRE
2. ALL ELECTRICLA TO COMPLY WITH 2017 NATIONAL ELECTRICAL
CODE. ELECTRICAL CONTRACTOR TO VERIFY ADEQUATE CAPACITY
AT POINT OF CONNECTION
3. #12 THHN CU ½” MIN. CONDUIT FOR POOL LIGHT(S).
4. ALL POOL PUMPS TO BE GFCI PROTECTED PER NEC 680.22(B).
5. LOAD CALCULATIONS FOR EXISTING SERVICE AND PANEL – BY OTHERS
6. PROVIDE G.F.C.I. OUTLET 6' MIN - 20' MAX FROM WATER’S EDGE.
POOL
PANEL PUMP (1) – 2 P-20A GFCI
LIGHT – CHLORINATOR (1) – 1P-15A
NOTE:
BASED ON INFORMATION PROVIDED TO THIS OFFICE, THE EXISTING SERVICE
IS ADEQUATE FOR THE PROPOSED ADDITIONAL POOL EQUIPMENT LOAD
TRANSFORMER 120-12V 300 W/ TRANSF
ELECTRICAL RISER DIAGRAM
N.T.S.
¾” PVC CONDUIT W/ 2 #6 HOT,
1 #10 GRND. 1 #10 NEUTRAL
EXISTING PANEL 2P
60A BREAKER
FEEDING POOL
48" MIN.
(2) 12V 24W L.E.D. NICHELESS LIGHTS (POOL)
1" NON-CORROSIVE
CONDUIT
2 #12,
1 # 12
GRND.
(1) JUNCTION BOX
BELOW WATEREXISTING
METER
F.P.L.
POOL
DECK
LEVEL
8" MIN.4" - 6"ELECTRICAL CONTRACTOR SHALL VERIFY THAT THE EXISTING SERVICE AND PANEL HAS
ENOUGH CAPACITY TO ACCOMMODATE THE ADDED POOL EQUIPMENT LOAD PER NEC 220.82"
SALT CHLORINATOR 2 #12 , 1 #12 GRND. ½” PVC
POOL PUMP 3 #12, 1 #12 GRND. GFCI PROTECTED ½” PVC
GFCI 6' TO 20'
FROM WATER
1. IN POOL AREA GROUND ALL BOXES, RAILS, LIGHT, MOTOR ECT WITH
#8 BARE COPPER WIRE
2. ALL ELECTRICLA TO COMPLY WITH 2017 NATIONAL ELECTRICAL
CODE. ELECTRICAL CONTRACTOR TO VERIFY ADEQUATE CAPACITY
AT POINT OF CONNECTION
3. #12 THHN CU ½” MIN. CONDUIT FOR POOL LIGHT(S).
4. ALL POOL PUMPS TO BE GFCI PROTECTED PER NEC 680.22(B).
5. LOAD CALCULATIONS FOR EXISTING SERVICE AND PANEL – BY OTHERS
6. PROVIDE G.F.C.I. OUTLET 6' MIN - 20' MAX FROM WATER’S EDGE.
POOL
PANEL PUMP (1) – 2 P-20A GFCI
LIGHT – CHLORINATOR (1) – 1P-15A
NOTE:
BASED ON INFORMATION PROVIDED TO THIS OFFICE, THE EXISTING SERVICE
IS ADEQUATE FOR THE PROPOSED ADDITIONAL POOL EQUIPMENT LOAD
TRANSFORMER 120-12V 300 W/ TRANSF
ELECTRICAL RISER DIAGRAM
N.T.S.
¾” PVC CONDUIT W/ 2 #6 HOT,
1 #10 GRND. 1 #10 NEUTRAL
EXISTING PANEL 2P
60A BREAKER
FEEDING POOL
48" MIN.
(2) 12V 24W L.E.D. NICHELESS LIGHTS (POOL)
1" NON-CORROSIVE
CONDUIT
2 #12,
1 # 12
GRND.
(1) JUNCTION BOX
BELOW WATEREXISTING
METER
F.P.L.
POOL
DECK
LEVEL
8" MIN.4" - 6"ELECTRICAL CONTRACTOR SHALL VERIFY THAT THE EXISTING SERVICE AND PANEL HAS
ENOUGH CAPACITY TO ACCOMMODATE THE ADDED POOL EQUIPMENT LOAD PER NEC 220.82"
SALT CHLORINATOR 2 #12 , 1 #12 GRND. ½” PVC
POOL PUMP 3 #12, 1 #12 GRND. GFCI PROTECTED ½” PVC
GFCI 6' TO 20'
FROM WATER
1. IN POOL AREA GROUND ALL BOXES, RAILS, LIGHT, MOTOR ECT WITH
#8 BARE COPPER WIRE
2. ALL ELECTRICLA TO COMPLY WITH 2017 NATIONAL ELECTRICAL
CODE. ELECTRICAL CONTRACTOR TO VERIFY ADEQUATE CAPACITY
AT POINT OF CONNECTION
3. #12 THHN CU ½” MIN. CONDUIT FOR POOL LIGHT(S).
4. ALL POOL PUMPS TO BE GFCI PROTECTED PER NEC 680.22(B).
5. LOAD CALCULATIONS FOR EXISTING SERVICE AND PANEL – BY OTHERS
6. PROVIDE G.F.C.I. OUTLET 6' MIN - 20' MAX FROM WATER’S EDGE.
POOL
PANEL PUMP (1) – 2 P-20A GFCI
LIGHT – CHLORINATOR (1) – 1P-15A
NOTE:
BASED ON INFORMATION PROVIDED TO THIS OFFICE, THE EXISTING SERVICE
IS ADEQUATE FOR THE PROPOSED ADDITIONAL POOL EQUIPMENT LOAD
TRANSFORMER 120-12V 300 W/ TRANSF
(1) 20W L.E.D. BUBBLER