Loading...
HomeMy WebLinkAboutEvaluation ReportEVALUATION REPORT OF METAL SALES MANUFACTURING CORPORATION `26 GA. 5V-CRIMP PANEL' FILE COPY FLORIDA BUILDING CODE 7TH EDITION (2020) FLORIDA PRODUCT APPROVAL FL 14645.4-R4 REVIEWED FOR ROOFING METAL ROOFING CODE COMPLIANCE sr. LuaE couNry eocc �'� ';'/Z4 (vz- Pre mared For: Metal Sale�rporat+ion 545 South 311 Street, Suite 200 Louisville, KY 40202 Telephone: (502) 855-4300 Fax: (502) 855-4290 Prepared By: Bala Sockalingam, Ph.D., P.E. Florida Professional Engineer #62240 1216 N Lansing Ave., Suite C Tulsa, OK 14106 Telephone: (918) 492-5992 FAX: (866) 366-1543 This report consists of Evaluation Report (3 Pages including cover) Installation Details (1 Page) Load Span Table (1 Page) Report No. C2397-4 Date: 10.7.2020 2yoz- O6A7 st%b3e99.E78oB8 �2 a cnG G K A L /!y�`''.�� No 622.4 .rru -3 `• gT+�iE OF oV p1. ,cL 0 V1 gyp' ����;Q `e�fiS / ... Ov y� l 0. 7.2Q?-0 FL 14645.4-R4 C23 97-4 10.7.2020 Page 2 of 3 Manufacturer: Metal Sales Manufacturing Corporation Product Name: 5V-Crimp Panel Description: 24" wide coverage with (5) 1/2" high ribs Materials: Min. 26 ga., 50 ksi steel. Galvanized coated steel (ASTM A653) or Galvalume coated steel (ASTM A792) or painted steel (ASTM A755). Corrosion resistant as per FBC 2020 Section 1507.4.3. Deck Description: Min. 7/16" thick OSB or min. 15/32" thick plywood or min. 1/4" thick wood plank (min SG of 0.42) for new and existing constructions. Designed by others and installed as per FBC 2020. Deck Attachment: 8d x 2.5" long ring shank nails or #8 x 2" long wood screws at 6" o.c. (Minimum) in the plywood field and edges. Designed as per FBC 2020. Underlayment: Minimum underlayment as per FBC 2020 Section 1507.4.5.1. Slope: 1/2:12 or greater in accordance with FBC 2020 Section 1507.4.2. Requires applied lap sealant for roof slopes less than 3:12. Design Uplift Pressure: 30.0 psf at fastener spacing of 36" o.c. (Factor of Safety = 2) 172.5 psf at fastener spacing of 6" o.c. Fastener Pattern: Type: #9-16 or #10-14 hex head wood screws with sealed washer. Fastener shall be of sufficient length to penetrate through the deck a minimum of 3/8" and installed as per Metal Sales current installation procedure. Fasteners are corrosion resistant as per FBC 2020 Section 1507.4.4. At panel ends 6" o.c. across panel width At intermediate 12" o.c. across panel width Test Standards: Roof assembly tested in accordance with UL580-06 `Uplift Resistance of Roof Assemblies' & UL1897-04 `Uplift Tests for Roof Covering Systems'. Test Equivalency: The test procedures in UL 1897-04 comply with test procedures prescribed in UL 1897-12. Code Compliance: The product described herein has demonstrated compliance with FBC 2020 Section 1507.4. Product Limitations: Design wind loads shall be determined for each project in accordance with FBC 2020 Section 1609 or ASCE 7-16 using allowable stress design. The maximum fastener spacing listed herein shall not be FL 14645.4-R4 C2397-4 10.7.2020 Page 3 of 3 exceeded. The design pressure for reduced fastener spacing may be computed using rational analysis prepared by a Florida Professional Engineer or based on Metal Sales load span table. This evaluation report is not applicable in High Velocity Hurricane Zone. Fire classification is not within scope of this Evaluation Report. Refer to FBC 2020 Section 1505 and current approved roofing materials directory or ASTM E108/UL790 report from an accredited laboratory for fire ratings of this product. Supporting Documents: UL580 & 1897 Test Reports PRI Construction Materials Technologies MSMC-017-02-01, Reporting Date 9/20/13 PANEL 5V-CRIMP SEE DETAIL 2 —/,,,�SEE DETAIL 1 FASTENER AT PANEL FLAT REQUIRED FOR PANEL ENDS ONLY. MINIMUM ATTACHMENT: 8d x 2.5" LONG RING SHANK NAIL UNDERLAYMENT SHALL BE INSTALLED OR #8 x 2" LONG WOOD SCREWS AS PER MANUFACTURER'S INSTALLATION SPACED ® 6" O.C. IN THE FIELD GUIDELINES & AT EDGES MIN. 2X- WOOD RAFTER/JOIST/ TRUSS AT MAX. 24' O.C. TYPICAL PANEL INSTALLATION X-SECTION #9-16 OR #10-14 WOODSCREWS WITH SELF SEALING WASHER AT MAXIMUM SPACING OF 36" O.C. UNDERLAYMENT DETAIL 1 #9-16 OR #10-14 WOODSCREWS WITH SELF SEALING WASHER AT MAXIMUM SPACING OF 36" O.C. UNDERLAYMENT DETAIL 2 5V-CRIMP MIN 26 GA. PANEL FASTENER PER UPLIFT LOAD TABLE d 0 0 U N U' uj N Z ~O mN O U � W Lo w Lo �J00 jN N O 00 En I h Ed ILGENERAL NOTES: 1. ARCHITECTURAL ROOF PANEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE a m FLORIDA BUILDING CODE (FBC). CL a m m OSB 7/16" THICK (MIN.) OR 2. ROOF PANELS SHALL BE MIN. 26 GA. (t = 0.019' . EFFECTIVE COVERING " PLYWOOD 15/32 THICK (MIN.) WIDTH OF PANEL = 24". crx oo 3. THE ROOF PANELS SHALL BE INSTALLED OVER SHEATHING & STRUCTURE AS ON THIS DRAWING. > Z m SPECIFIED 4. REQUIRED DESIGN WIND LOADS SHALL BE DETERMINED FOR EACH PROJECT. THIS PANEL SYSTEM MAY NOT BE INSTALLED WHEN THE REQUIRED DESIGN WIND LOADS 0 mz T ARE GREATER THAN THE DESIGN UPLIFT PRESSURES SPECIFIED ON THIS DRAWING.v m 5. ALL FASTENERS MUST BE IN ACCORDANCE WITH THIS DRAWING & THE FLORIDA BUILDING CODE. IF A DIFFERENCE OCCURS BETWEEN THE MINIMUM $ REQUIREMENTS OF THIS DRAWING & THE CODE, THE CODE SHALL CONTROL. 6. RAFTERS/JOISTS/TRUSSES MUST BE DESIGNED TO WITHSTAND WIND LOADS AS 5V-CRIMP REQUIRED ARE THE OF OTHERS. PSEALANT DROOF MIN 26 GA. 7. REQUIRES APPLI DC LAP FOR SLOPE <PO:12BILffY OSB 7/16" THICK (MIN.) OR PLYWOOD 15/32 THICK (MIN.) 1 OF 1 METAL SALES MANUFACTURING CORPORATION 5V-Crimp Uplift Loads (Min. 26 ga.) Description Fastener Spacing along panel length (in) Allowable Uplift Load (psf) Coverage width: 24" Panel Fasteners #9-16 or #10-14 hex head wood screws with sealed washer 6 172.5 9 120.0 4+).0 WN 15 72.0 1.8 60.0 21 51.4 24 _ 45.0 27 40.0 30 36.0 33 32.7 36 30.0 Notes: 1. The bold numbers indicate design loads calculated from test data with safety factor of 2. 2. Panels must be installed as per Evaluation Report FL 14645.4 and Metal Sales current installation procedure. 3. Three or more spans condition. 1216 N Lansing Ave., Suite C Tulsa, Ok 74106 918 492 5992 ��,�yB3E5�PA?OF�S��o. ,�� SGCKAL/I �' `\........ s !V �•. �� �A� @o Q2 , 1`10 62241) . Uj TE OF O•• Q.. 1 G.'i .Za2C� Bala Sockalingam, Ph.D., P.E. FL 62240 FILE COPY REVIEWED FOR CODE COMPLIANCE �� NEMO I etc. . LUCIE COUNTY /I �BOCC Certificate of Authorization 1f32455 7- y8/Z�� 353 Christian Street, Unit #13 Oxford, CT 06478 O� Z� (203) 262-9245 ENGINEER EVALUATE TEST CONSULT REPORTI EVALUATION GAF Evaluation Report 01506.04.08-1123 1Campus Drive FL10626-R23 Parsippany, NJ 07054 Date of Issuance: 04/25/2008 (800) 766-3411 Revision 23:12/14/2021 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the 71h Edition (2020) Florida Building Code sections noted herein. DESCRIPTION: LABELING: Labeling shall be in accordance with the requirements of the Accredited Quality Assurance Agency noted herein and FBC 1507.1.1. . CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance or production facility location(s) changes, or Code provisions that relate to the product(s) change. Acceptance of our Evaluation Reports by the named client constitutes agreement to notify NEMO ETC, LLC of any changes to the product(s), the Quality Assurance or the production facility location(s). NEMO ETC, LLC requires a complete review of its Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Florida Product Approval Number (FL#) preceded by the words "NEMO Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 8. Prepared by: Robert J.M. Nieminen, P.E. `= Florida Registration No. 59166, Florida DC4ANE1983 The facsimile seal appearing was authorized by Robert Nieminen, P.E. on 12/14/2021. This does not serve as an electronically signed document. CERTIFICATION OF INDEPENDENCE: 1. NEMO ETC, LLC does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. NEMO ETC, LLC is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. 5. This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 9)2019 NEMO ETC, LLC ONEMO I etc. ROOFING COMPONENT EVALUATION: Product Category: Roofing Sub -Category: Underlayment Compliance Statement: GAF Roof Underlayments, as produced by GAF, have demonstrated compliance with the following sections of the 7" Edition (2020) Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: Section Property Standard Year 1504.3.1 Wind resistance FM 4474 2011 1507.1.1, 1507.2.4, 1507.2.9.2/R905.1.1, Material standard ASTM D1970 2015 R905.2.8.2 1507.1.1.1(2&3, Exception), 1507.1.1.1(5) / Tear Strength ASTM D4533 2015 R905.1.1.1(2&3, Exception), R905.1.1.1(5) 1507.1.1.1(2&3, Exception), 1507.1.1.1(5) / Tensile strength ASTM D5035 2011 R905.1.1.1(2&3, Exception), R905.1.1.1(5) 1507.1.1.1(5) / R905.1.1.1(5) Liquid water transmission ASTM D4869 2016 1507.1.1 / R905.1.1 Material standard ASTM D6757 2016 1507.3.3, R905.3.3 Material standard FRSA/TR1, Sixth Edition 2018 1507.11.2 Material standard ASTM D6164 2011 TAS 110 Accelerated Weathering ASTM D4798 2011 3. REFERENCES: Entily Examination Reference Date ERD (fST6049) ASTM D1623 & FRSA/TRI (Slippage) G34150.08.11 11/14/11 ERD (TST6049) ASTM D6164 (GA) G40630.01.14-213i-112 01/07/14 ERD (TST6049) ASTM D6164 (GA) G46160.09.14-3A 09/09/14 ERD (TST6049) ASTM D1970 (GA) GAF-SC13285.03.17-3 03/01/17 ERD (TST6049) ASTM D1970 (GA) GAF-SC13285.03.17-4 03/01/17 ERD (TST6049) ASTM D1970 (GA) GAF-SC13285.03.17-1 . 03/08/17 ERD (TST6049) ASTM D1970 (IN) GAF-SC16440.12.17 12/31/17 Intertek (TST1558) ASTM D4869 (Dadra, India) F8549.02-106-18 11/08/16 NEMO (TST6049) Physical Properties (ON) 4q-GAF-I9-SSMBB-03.A 05/13/19 NEMO (TST6049) ASTM D1623 4p-DOW-I9-SSLAP-01.A-112 10/01/19 NEMO (TST6049) ASTM D1970 4j-FTS-20-SSUDL-01.A 12/01/20 NEMO (TST6049) ASTM D1970 4j-GAF-20-SSUDL-01.A 12/22/20 NEMO (TST6049) ASTM D4798, TAS 103 4j-GAF-20-SSUDL-02.A 03/15/21 MEMO (TST6049) ASTM D4798 4j-FTS-2I-SSUDL-02.A 06/09/21 PRI (TST5878) ASTM D226 (OK) GAF-339-02-01 03/13/12 PRI (TST5878) Wind Uplift GAF-434-02-01 09/16/13 PRI (TST5878) Wind Uplift GAF-434-02-03 09/16/13 PRI (TST5878) Wind Uplift GAF-434-02-04 09/16/13 PRI (TST5878) ASTM D4533 (various) GAF-818-02-01 12/05/17 PRI (TST5878) ASTM D1970 (AL) MSA-047-02-01 04/11/18 PRI (TST5878) ASTM D4533 (Dadra, India) GAF-847-02-01 06/04/18 PRI (TST5878) ASTM D4533 (Dadra, India) GAF-914-02-01 04/10/19 PRI (TST5878) ASTM D4533,D5035(VA) 376TOO12 07/15/19 PRI (TST5878) I ASTM D4533 (Parzai, India) 376TOOIS 07/31/19 PRI (TST5878) ASTM D4533 (Umerkui Kilvani, India) 976TOO18 07/31/19 PRI (TST5878) ASTM D1970 (AR) 376T0032 10/22/19 PRI (TST5878) ASTM D4533 (Gujarat, India) 376TOO58 02/18/20 NEMO ETC, LLC Evaluation Report 01506.04.08-R23 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION FL10626-R23 GAF Roof Underlayments Revision 23:12/14/20ZI Page 2 of 9 M 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12 ONEMOJetc. Entity Examination Reference natp PRI (TST5878) ASTM D226(S-CA) 376T0054 02/18/20 PRI (TST5878) ASTM D5035 (various) 376TO103 09/11/20 PRI (TST5878) ASTM D4533, D5035 (Rajasthan, India) 376T0111 12/22/20 PRI (TST5878) ASTM D4533, D5035 (Gujarat, India) 376TO113 12/22/20 PRI (TST5878) ASTM D5035 (Gujarat, India) 376TO146 03/11/21 PRI (TST5878) ASTM D4533, D5035 (Rajasthan, India) 376TO161 05/07/21 PRI (TST5878) ASTM D226,Type 11 376TO192 09/16/21 NEMO Traceability FBC Cross -Listing 04/22/20 NEMO Traceability FBC Cross -Listing 04/08/21 UL, LLC (QUA9625) Quality Control Service Confirmation (AL) 05/04/20 UL, LLC (QUA9625) Quality Control Service Confirmation (various) 06/10/21 UL, LLC (QUA9625) I Quality Control I Florida BCIS I Cu­­ PRODucT I • Product Material Standard Plant(s) GAF Extended Dry -In Membrane ASTM D1970 Langley, BC Canada Liberty" SBS Self -Adhering Base/Ply Mt. Vernon, IN Sheet ASTM D1970 Savannah, GA StormGuard® Film -Surfaced Leak Barrier ASTM D1970 (Table 1) 1 Mt. Vernon, IN Savannah, GA WeatherWatchO Mineral -Surfaced Leak Arkadelphia, AR Barrier ASTM D1970 Savannah, GA Tuscaloosa, AL Deck -Armor'"' Premium Breathable Roof 1507.1.1.1(2&3, Exception) / Deck Protection R905.1.1.1(2&3, Exception) Dadra, India Dadra, India 1507.1.1.1(2&3, Exception), Gujarat, India FeltBuster° Synthetic Roofing Felt 1507.1.1.1(5) / R905.1.1.1(2&3, (CPP) Rajasthan, India Exception), R905.1.1.1(5) (MIP) Rajasthan, India Richmond, VA Spartanburg, SC Shingle -Mite') Roof Deck Protection ASTM D226, Type II (Table 1) Pryor, OK Shafter, CA StormSafeT"" Anchor Sheet 1507.1.1.1(2&3, Exception) / North Bay, ON R905.1.1.1(2&3, Exception) Dadra, India Tiger Paw'" Premium Roof Deck 1507.1.1.1(2&3, Exception) / Gujarat, India Protection R905.1.1.1(2&3, Exception) Parzai, India Umerkui Kilvani, India VersaShieldm Fire -Resistant Roof Deck Protection ASTM D226, Type II Conover, NC Ruberoid" Map Granule ASTM D6164 Savannah, GA FRSA/TRI 09-18 Ruberoid° Mop Granule FR ASTM D6164 Savannah, GA FRSA/TR109-18 StormGuard ° Film -Surfaced Leak Barrier has been found through comparative testing to have a lesser coefficient of friction than ASTM D226 roofing felt when tested at standard laboratory conditions. Agreement between purchaser and seller, as set forth in Section 4.3, Note 1 of ASTM D1970-15, should be established as to slip resistance. NEMO ETC, LLC Evaluation Report 01506.04.08-R23 Certificate ofAuthorization #32455 7T" EDITION (2020) FBC NON-HVHZ EVALUATION FL10626-R23 GAF Roof Underlayments Revision 23: 12/14/2022 Page 3 of 8 NEnno etc. 5.1 This is a building code evaluatiop. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in FBC High Velocity Hurricane Zone jurisdictions (i.e., Broward and Miami - Dade Counties). 5.3 This Evaluation Report pertains to above -deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. 5.4 This Evaluation Report does not include evaluation of fire classification. Refer to FBC 1505 for requirements and limitations regarding roof assembly fire classification. Refer to FBC 2603 for requirements and limitations concerning the use of foam plastic insulation. 5.5 GAF Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering. 5.6 Allowable Roof Covers: TABLE 1: ROOF COVER OPTIONS FBC Section: 1507.2 1507.3 1,507 an 507.5 1507.7 1507.8 and 1507.9 Asphalt Clay and Concrete Tile Metal Slate or Wood Mechanical Adhesive- Underlament Y Shingles Slate -Type Attach Set Panes Shingles Shingles Shingles Shakes Yes Yes GAF Extended Dry -In Membrane Yes No No Ye Yes Yes (joint strips, (joint strips, 1507.1.1.3 / 1507.1.1.3 / R905.1.1.3) R905.1.1.3) Liberty- SBS Self -Adhering � �, Yes Yes Base/Ply Sheet Yes No No x`fy No No o G ps, (joint strips, •Ny' 1507.1.1.3 / 1507.1.1.3 / - R905.1.1.3) R905.1.1.3) $tOfrl'IGUafd�UffaCedLeak Barriers „ J Yes No No Yes Yes Yes (joirYstrips, 1507.1.1.3 / (joi [strips, 1507.1.1.3 / R905.1.1.3) R905.1.1.3) WeatherWatch" Mineral -Surfaced Yes Yes Leak Barrier Yes No No No No No (joint strips, (joint strips, 1507.1.1.3 / 1507.1.1.3 / R905.1.1.3) R905.1.1.3) Deck -Armor" Premium Breathable Roof Deck Protection Yes No No Yes Yes Yes No No FeltBuster° Synthetic Roofing Felt Yes No No No No No No No Shingle -Mate° Roof Deck Protection Yes No No No No No No No Tiger Paw'" Premium Roof Deck Protection Yes No No Yes Yes Yes No No VersaShield" Fire -Resistant Roof Deck Protection Yes No No No No No No No Yes Yes Ruberoid° Mop Granule No (Cap Sheet in (Cap Sheet in No No No No No 2-ply system) 2-ply system) See 5.6.1 Yes Yes Ruberoid° Mop Granule FR No (Cap Sheet in (Cap Sheet in No No No No No 2-ply system) 2-ply system) See 5.6.1 MEMO ETC, LLC Evaluation Report 01506.04.08-1123 Certificate of Authorization#32455 7THEDITION (2020) FBC NON-HVHZ EVALUATION FL10626-R23 GAF Roof Underlayments Revision 23: 12/14/2021 Page 4 of 8 NNEMOjetc. 5.6.1 Adhesive -set is limited to use of following underlayment / tile -adhesive combinations. TABLE IA: ALLOWABLE UNDERLAYMENT/ TILE -ADHESIVE COMBINAT(ONS2 Underlayment Adhesive Florida Product Approval Ruberoid° Mop Granule; Ruberoid° Mop Granule FR Dupont "Tile Bond" Roof Tile Adhesive" FL22525 5.7 Allowable Substrates: TABLE 2: SUBSTRATE OPTIONS FOR ADHERED UNDERLAYMENTS Underlayment Application Primer Substrates GAF Extended Dry -In Membrane self -adhering None plywood Liberty'" SBS Self -Adhering Base/Ply Sheet self -adhering (optional) ASTM D41 plywood StormGuard° Film -Surfaced Leak Barrier Weather Watch° Mineral -Surfaced Leak Barrier Liberty"" SBS Self -Adhering Base/Ply Sheet self -adhering None ASTM D226 felt, Type II StormGuard° Film -Surfaced Leak Barrier Weather Watch° Mineral -Surfaced Leak Barrier Liberty'" SBS Self -Adhering Base/Ply Sheet kmetaF.(flashing mefal, vahey meta, Stogy rnG a d m-5-5ur d'Leak Barrier y 'self -adhering ASTM p4 r" Weather Watch° Mineral -Surfaced Leak Barrier Ruberoid° Mop Granule hot asphalt ASTM D41 structural concrete Ruberoido Mop Granule FR Ruberoid° Mop Granule hot asphalt None GAFGLAS° #80 Ultima— Base Sheet or Ruberoid° 20 Smooth FRuberoid® Ruberoid Mop Granule FR 5.8 Attachment Limitations: 5.8.1 For use under mechanically attached NON -TILE prepared roof coverings, attachment shall be in accordance with the manufacturer's installation instructions, but —for mechanically attached underlayments or base sheets - not less than FBC 1507.1.1 or R905.1.1. 5.8.2 For use under tile roof systems, attachment shall be in accordance with the manufacturer's installation instructions, but —for mechanically attached base sheets - not less than: • FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition, Appendix A, Table 1 (for Two -Ply Asphalt Applied Hot Mop Underlayment) or • Section 5.8.3 herein (for other underlayment systems). 5.8.3 Wind Resistance for Underlayment Systems in Tile Roof Applications: The following wind uplift limitations apply to underlayment systems that are not prescriptive in the FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition. The Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). 5.8.3.1 Direct -to -Deck: The maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition, Appendix A, Table 1A or the critical (highest) design pressure determined in accordance with FBC 1609 or FBC Residential Chapter 3. -'Refer to Tile Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance. NEMO ETC, LLC Evaluation Report 01506.04.08-R23 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION FL10626-R23 GAF Roof Underlayments Revision 23: 12/14/2021 Page 5 of 8 NNEMOletc. #1 Maximum Design Pressure = -442 5 psf. Deck: Min. 2,500 psi structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction Base Sheet: GAFGLAS #75 Base Sheet, Tri-Ply #75 Base Sheet, GAFGLAS #80 Ultima Base Sheet, GAFGLAS Ply 4, Tri-Ply Ply 4 or GAFGLAS Flex Ply 6 applied in full mopping of ASTM D312, Type IV hot asphalt at 20 to 25 Ibs/square. Cap Sheet: Ruberoid° Mop Granule or Ruberoid® Mop Granule FR applied in full mopping of ASTM D312, Type IV hot asphalt at 20 to 25 Ibs/square. 5.8.3.2 Mechanically -Attached Base Sheet: The maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition, Appendix A, Table 1A or the critical (highest) design pressure determined in accordance with FBC 1609 or FBC Residential Chapter 3. Alternatively, the maximum design pressure for the selected assembly shall meet or exceed at least the Zone 1 design pressure determined in accordance with FBC 1609 or FBC Residential Chapter 3. Elevated pressure zones shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (February 2020) for enhancements. #2 Maximum Design Pressure= -45 psf. Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: GAFGLAS° #80 Ultima' Base Sheet or Ruberoid® 20 Smooth mechanically attached with 12 ga., min. 1.25-inch long ring shank nails through 32 ga., 1-5/8-inch diameter tin caps spaced 9-inch o.c. at the min. 4-inch wide side laps and 9-inch o.c. at two (2), equally spaced, staggered center rows in the field of the sheet. Cap Sheet: Ruberoid® Mop Granule or Ruberoid® Mop Granule FR applied in full mopping of ASTM D312, Type IV hot asphalt at 20 to 25 Ibs/square. #3 Maximum Design Pressure = -75 psf. Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: GAFGLASI #80 UltimaT" Base Sheet or Ruberoid' 20 Smooth mechanically attached with 12 ga., min. 1.25-inch long ring shank nails through 32 ga., 1-5/8-inch diameter tin caps spaced 8-inch o.c. at the min. 4-inch wide side laps and 8-inch o.c. at three (3), equally spaced, staggered center rows in the field of the sheet. Cap Sheet: Ruberoid® Mop Granule or Ruberoid® Mop Granule FR applied in full mopping of ASTM D312, Type IV hot asphalt at 20 to 25 Ibs/square. #4 Maximum Design Pressure = -97 5 psf. Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: GAFGLAS° #80 Ultima'" Base Sheet or Ruberoid° 20 Smooth mechanically attached with 11 ga., min. 1.25-inch long ring shank nails through 32 ga., 1-5/8-inch diameter tin caps spaced 4-inch o.c. at the min. 2-inch wide side laps and 4-inch o.c. at four (4), equally spaced center rows in the field of the sheet. Cap Sheet: Ruberoid® Mop Granule or Ruberoid° Mop Granule FR applied in full mopping of ASTM D312, Type IV hot asphalt at 20 to 25 Ibs/square. NEMO ETC, LLC Evaluation Report 01506.04.08-R23 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION FL30626-1123 GAF Roof Underlayments Revision 23: 12/14/2021 Page 6 of 8 NNEMOletc. 5.9 Exposure Limitations: TABLE 3: EXPOSURE LIMITATIONS Underlayment Prepared Roof Cover Maximum Exposure Installation Type (days) Deck -Armor'" Premium Breathable Roof Deck Protection, FeltBuster° Synthetic Roofing Felt, Shingle-Mate0l Roof Deck Protection, StormSafeT"" Anchor Sheet, Tiger Paw'" Premium Roof Deck Protection, VersaShield® Fire -Resistant Roof Deck Mechanically attached 30 Protection, Liberty— SBS Self -Adhering Base/Ply Sheet, StormGuardo Film -Surfaced Leak Barrier and WeatherWatchO Mineral -Surfaced Leak Barrier GAF Extended Dry -In Membrane Mechanically attached 180 �, Ruberoid Mop Granule and Ruberoid Mop Granule FR Adhesive -set tile roof system 180 Mechanically attached UNLIMITED 5.10 Tile Slippage Limitations: When loading roof tiles on the underlayment in direct -deck tile roof assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. TABLE 4: TILE SLIPPAGE LIMITATIONS FOR DIRECT -DECK TILE INSTALLATIONS Underlayment Tile Profile Staging Method Maximum Staging Slope Ruberoid® Mop Granule Flat Max. 10-tile stack 4:12 Flat Max. 6-tile stack (4 over 2) 5:12 Lugged Max. 10-tile stack 5:12 Ruberoid' Mop Granule FR Flat or Lugged Max. 6-tile stack (4 over 2) 5:12 Lugged Max. 10-tile stack 4:12 6. INSTALLATION* 6.1 GAF Roof Underlayments shall be installed in accordance with GAF published installation instructions subject to the Limitations set forth in Section 5 herein and the specifics noted below. 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application and prime the substrate (if applicable). 6.3- -Deck-Armor'" Premium Breathable Roof Deck Protection -or Tiger Paw*" Premium Roof Deck Protection: 6.3.1 Shall be installed in compliance with requirements for a synthetic underlayment in FBC 1507.1.1.1(2, Exception) or 1507.1.1.1(3, Exception) or FBC Residential R905.1.1.1(2, Exception) or R905.1.1.1(3, Exception) for the type of prepared roof covering to be installed, and the manufacturer's installation instructions. FBC requirements take precedence over the manufacturer's installation instructions. 6.4 FeltBuster° Synthetic Roofing Felt: 6.4.1 Shall be installed in compliance with requirements for a synthetic underlayment in FBC 1507.1.1.1(2, Exception), 1507.1.1.1(3, Exception) or 1507.1.1.1(5) or FBC Residential R905.1.1.1(2, Exception), R905.1.1.1(3, Exception) or R905.1.1.1(5) for the type of prepared roof covering to be installed, and the manufacturer's installation instructions. FBC requirements take precedence over the manufacturer's installation instructions. 6.5 StormSafe— Anchor Sheet: 6.5.1 StormSafeTm Anchor Sheet is limited to use as a mechanically attached base layer in 2-ply underlayment systems. 6.5.2 Shall be installed in compliance with requirements for a synthetic underlayment in FBC 1507.1.1.1(2, Exception) or 1507.1.1.1(3, Exception) or FBC Residential R905.1.1.1(2, Exception) or R905.1.1.1(3, Exception) for the type of prepared roof covering to be installed, and the manufacturer's installation instructions. FBC requirements take precedence over the manufacturer's installation instructions. NEMO ETC, LLC Evaluation Report 01506.04.08-R23 Certificate of Authorization#32455 7THEDITION (2020) FBC NON-HVHZ EVALUATION FL10626-R23 GAF Roof Underlayments Revision 23: 12/14/2021 Page 7 of 8 ONEMOletc. 6.5.3 One the same day, install Liberty'"" SBS Self -Adhering Base/Ply; StormGuard° Film -Surfaced Leak Barrier or WeatherWatch° Mineral -Surfaced Leak Barrier over the StormSafell Anchor Sheet. 6.6 : Shingle -Mate® Roof Deck Protection: 6.6.1 Shall be installed in compliance with requirements for an approved mechanically attached underlayment (ASTM D226, Type II) in FBC Table 1507.1.1.1 or FBC Residential Table R905.1.1.1 for the type of prepared roof covering to be installed, and the manufacturer's installation instructions. FBC requirements take precedence over the manufacturer's installation instructions. 6.7 VersaShield° Fire -Resistant Roof Deck Protection: 6.7.1 Shall be installed in compliance with requirements for an approved mechanically attached underlayment (ASTM D6757) in FBC Table 1507.1.1.1 or FBC Residential Table R905.1.1.1 for the type of prepared roof covering to be installed, and the manufacturer's installation instructions. FBC requirements take precedence over the manufacturer's installation instructions. 6:8 GAF Extended Dry -In Membrane, Liberty'" SBS Self -Adhering Base/Ply Sheet, StormGuard° Film -Surfaced Leak Barrier or WeatherWatch®:Mineral-Surfaced Leak Barrier: o.o..i 311du ue mswiiea in compliance wren requirements for an approved self -adhering underlayment (ASTM D1970) in FBC 1507.1.1.1 or 1507.1.1.3 or FBC Residential R905.1.1.1 or R905.1.1.3 for the type of prepared roof covering to be installed, and the manufacturer's installation instructions. 6.8.2 Back -nailing is required. Back -nailing shall consist of Approved cap nails spaced 18-inch o.c., encapsulated within min. 4-inch side laps. 6.8.3 When installed over a mechanically attached, FBC Approved ASTM D226 Type II felt, the felt shall be fastened in accordance with FBC 1507.1.1 or R905.1.1. 6.8.4 GAF Extended Dry -In Membrane, Liberty'"" SBS Self -Adhering Base/Ply Sheet, StormGuard® Film -Surfaced Leak Barrier or WeatherWatch® Mineral -Surfaced Leak Barrier may be installed as a secondary water barrier using minimum 4-inch wide rolls to seal plywood deck joints prior to installation of the primary underlayment system. 6.9 Ruberoid° Mop Granule;•Ruberoid® Mop Granule FIR: 6.9.1 Shall be installed in compliance with requirements as an alternate to the "Hot Asphalt Applied Cap Sheet" in the "Two Ply System" in the FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition, and the manufacturer's installation instructions. 6.9.2 Refer to Section 5.8 herein for attachment limitations. 6.9.3 Refer to Table 4 for tile staging limitations. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction to properly evaluate the installation of this product. -8. MANUFACTURING PLANTS: Contact the named CIA entity for manufacturing facilities covered by F.A.C. Rule 61G20-3 QA requirements. Refer to Section 4 herein for products and production locations having met codified material standards. QUALITY UL, LLC.—QUA9625; (613) 371-2765; Jacob.StewartCcDul.com - END OF EVALUATION REPORT - NEMO ETC, LLC Evaluation Report 01506.04.08-R23 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION FL10626-1123 GAF Roof Underlayments Revision 23: 12/14/2021 Page 8 of 8