Loading...
HomeMy WebLinkAboutProject InformationCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-02 11:07:55 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1645Job:Load Short Form 10/18/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Allen Residence, Nisair Air ConditioningFor: 5507 Hickory Dr, Ft. Pierce, FL 34982 Design Information InfiltrationClgHtg SimplifiedMethod9041Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1S042-230A** AHRI ref Coil CBA27UHE-042-230*++TDR AHRI ref 10259441 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW10.2 Sensible cooling Btuh29400 Heating output Btuh34696 Latent cooling Btuh12600 Temperature rise °F23 Total cooling Btuh42000 Actual air flow cfm1400 Actual air flow cfm1400 Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.049 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.80 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Utility 78 1727 1593 74 78 Bed 2 138 1579 1654 68 81 WIC 2 48 659 326 28 16 Linen 11 0 0 0 0 Bed 3 204 4911 3227 212 157 Cabana Bath 113 2533 1536 109 75 Hall 71 0 0 0 0 Kitchen 222 1018 3786 44 184 Great Room 299 2323 3894 100 190 Dining Room 168 3359 2221 145 108 Master Bed 279 4949 4322 213 210 Hers 41 829 354 36 17 His 31 39 64 2 3 Master Bath 172 2949 1479 127 72 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-02 11:07:55 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2 ...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N Foyer 85 1896 1427 82 69 Nook 108 1915 1872 83 91 WIC 48 606 284 26 14 Wtr Clst 25 1166 720 50 35 House 2139 32461 28758 1400 1400 Other equip loads 1638 870 Equip. @ 0.95 RSM 28265 Latent cooling 7501 TOTALS 2139 34099 35766 1400 1400 2021-Nov-02 11:07:55 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1645Job:Building Analysis 10/18/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Allen Residence, Nisair Air ConditioningFor: 5507 Hickory Dr, Ft. Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 18.462763.1Walls 17.6598617.9Glazing 000Doors 6.221201.0Ceilings 20.770563.33.3Floors 10.335191.7Infiltration 22.07504Ducts 00Piping 00Humidification 4.81638Ventilation0Adjustments 100.034099Total Cooling Walls Glazing Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 13.138811.9Walls 21.3630018.8Glazing 000Doors 10.631301.5Ceilings 000Floors 3.29340.5Infiltration 32.09493Ducts 2.9870Ventilation 16.95020Internal gains 00Blower 0Adjustments 100.029628Total Latent Cooling Load = 7501 Btuh Overall U-value = 0.112 Btuh/ft²-°F Data entries checked. 2021-Nov-02 11:07:55 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1645Job:Component Constructions 10/18/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Allen Residence, Nisair Air ConditioningFor: 5507 Hickory Dr, Ft. Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 7283.155.10.109231ne 4662.02 9562.0214953.155.10.109474se 7922.0212393.155.10.109393sw 12032.0218813.155.10.109597nw 34172.0253433.155.10.1091696all Partitions Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16" OC Stud 4641.469342.9411.00.101318 Windows Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.18); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 10 ft overhang (1.25 ft window ht, 1 ft sep.); 6.8 ft head ht 13317.79813.000.4508ne Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (1.33 ft window ht, 1 ft sep.); 6.8 ft head ht 17722.114418.000.6208ne 9122.17418.000.6204ne 26822.121818.000.62012all Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 10 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 69122.156118.000.62031ne Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 15.9 ft overhang (8 ft window ht, 1 ft sep.); 6.8 ft head ht 76916.090518.800.65048ne Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (3.17 ft window ht, 1 ft sep.); 6.8 ft head ht 13921.111116.800.5807se 16722.612416.800.5807nw 30621.923516.800.58014all 2021-Nov-02 11:07:55 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2 ...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.17 ft window ht, 1 ft sep.); 6.8 ft head ht 47021.836216.800.58022se 33821.826116.800.58016se 48722.636216.800.58022nw 129522.198516.800.58059all Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 8 ft head ht 34021.826216.800.58016sw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 4 ft overhang (5.2 ft window ht, 1 ft sep.); 8 ft head ht 21013.526216.800.58016sw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 12 ft overhang (8 ft window ht, 1 ft sep.); 6.8 ft head ht 100010.4181018.800.65096sw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 6 ft overhang (5.17 ft window ht, 1 ft sep.); 6.8 ft head ht 35122.626116.800.58016nw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 4 ft overhang (8 ft window ht, 1 ft sep.); 6.8 ft head ht 33116.039018.900.65021nw Doors (none) Ceilings Attic, Shngls, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.0342139 31301.4621200.9930.0 Floors On Grade Depth, Tile Flr Fnsh 00705628.700.989246 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-02 11:07:55 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1645Job:Project Summary 10/18/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Allen Residence, Nisair Air ConditioningFor:5507 Hickory Dr, Ft. Pierce, FL 34982 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh24957 Structure Btuh19265 Ducts Btuh7504 Ducts Btuh9493Central vent (51 cfm) 1638 Btuh Central vent (51 cfm) Btuh870 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh34099 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh28265 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh2933 Ducts Btuh2582Central vent (51 cfm) Btuh1986 CoolingHeating Outside air21392139Area (ft²) Equipment latent load Btuh7501 2070320703Volume (ft³)Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh35766 Equiv. AVF (cfm) 55110 Req. total capacity at 0.70 SHR ton3.4 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOX Model Cond ML14XC1S042-230A**AHRI ref Coil CBA27UHE-042-230*++TDR AHRI ref 10259441Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW10.2 Sensible cooling Btuh29400Heating output Btuh34696 Latent cooling Btuh12600 Temperature rise °F23 Total cooling Btuh42000Actual air flow cfm1400 Actual air flow cfm1400 Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.049Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.80 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name House Utility 2 Exposed wall 246.0 ft 18.5 ft 3 Room height 9.7 ft 9.4 heat/coolft 4 Room dimensions ft6.5x12.0 5 Room area 2139.3 ft²78.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 330 231 728 466 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 8 0 98 133 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 8 0 144 177 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 4 0 74 91 0 0 0 0 11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 31 0 561 691 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 48 0 905 769 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 518 474 1495 956 61 55 172 110 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 7 3 111 139 7 1 111 139 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 22 5 362 470 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 16 4 261 338 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 520 393 1239 792 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 16 4 262 340 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 16 31 262 210 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 96 192 1810 1000 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 662 597 1881 1203 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 7 0 124 167 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 22 0 362 487 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 261 351 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 21 0 390 331 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 318 318 934 464 113 113 331 165 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 2139 2139 2120 3130 78 78 77 114 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 2139 246 7056 0 78 19 531 0 6 c) AED excursion 605 10 Envelope loss/gain 21438 13311 1222 538 12 a) Infiltration 3519 934 106 28 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 4 920 0 0 Appliances/other 4100 500 Subtotal (lines 6 to 13)24957 19265 1328 1066 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 24957 19265 1328 1066 15 Duct loads 30%49%7504 9493 30%50%399 528 Total room load 32461 28758 1727 1593 Air required (cfm)Air required (cfm)1400 1400 74 78 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 2 WIC 2 2 Exposed wall 11.5 ft 6.0 ft 3 Room height 9.4 heat/coolft 9.4 heat/coolft 4 Room dimensions ft11.5x12.0 ft6.0x8.0 5 Room area 138.0 ft²48.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 108 93 292 187 56 56 178 114 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 16 2 261 338 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 138 138 137 202 48 48 48 70 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 138 12 330 0 48 6 172 0 6 c) AED excursion 69 -9 Envelope loss/gain 1019 796 397 175 12 a) Infiltration 187 50 98 26 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 0 Subtotal (lines 6 to 13)1206 1095 495 201 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 8 11 12 17 14 Subtotal 1214 1107 507 218 15 Duct loads 30%50%365 548 30%50%152 108 Total room load 1579 1654 659 326 Air required (cfm)Air required (cfm)68 81 28 16 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 3...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Linen Bed 3 2 Exposed wall 0 ft 41.0 ft 3 Room height 9.4 heat/coolft 9.4 heat/coolft 4 Room dimensions ft10.5x1.0 ft17.0x12.0 5 Room area 10.5 ft²204.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 160 138 436 279 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 22 3 362 470 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 113 97 306 196 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 16 2 262 340 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 113 113 355 227 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 11 11 10 15 204 204 202 298 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 11 0 0 0 204 41 1176 0 6 c) AED excursion -1 -91 Envelope loss/gain 10 15 3100 1720 12 a) Infiltration 0 0 668 177 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 250 Subtotal (lines 6 to 13)10 15 3768 2147 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -10 -15 8 11 14 Subtotal 0 0 3776 2158 15 Duct loads 30%50%0 0 30%50%1135 1068 Total room load 0 0 4911 3227 Air required (cfm)Air required (cfm)0 0 212 157 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 4...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Cabana Bath Hall 2 Exposed wall 20.0 ft 0 ft 3 Room height 9.4 heat/coolft 9.4 heat/coolft 4 Room dimensions ft113.0x1.0 ft70.5x1.0 5 Room area 113.0 ft²70.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 113 113 355 227 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 75 55 172 110 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 21 0 390 331 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 113 113 112 165 71 71 70 103 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 113 20 574 0 71 0 0 0 6 c) AED excursion 79 -4 Envelope loss/gain 1602 913 70 99 12 a) Infiltration 326 87 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1928 1000 70 99 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 19 28 -70 -99 14 Subtotal 1948 1027 0 0 15 Duct loads 30%50%586 508 30%50%0 0 Total room load 2533 1536 0 0 Air required (cfm)Air required (cfm)109 75 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 5...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Kitchen Great Room 2 Exposed wall 9.5 ft 9.5 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft222.3x1.0 ft298.8x1.0 5 Room area 222.3 ft²298.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 95 47 148 95 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 0 0 0 0 48 48 905 500 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 95 95 279 139 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 222 222 220 325 299 299 296 437 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 222 10 272 0 299 10 272 0 6 c) AED excursion -106 169 Envelope loss/gain 772 357 1621 1201 12 a) Infiltration 0 0 165 44 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 2 460 Appliances/other 1700 900 Subtotal (lines 6 to 13)772 2517 1786 2605 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 11 15 0 0 14 Subtotal 783 2533 1786 2605 15 Duct loads 30%50%235 1254 30%50%537 1289 Total room load 1018 3786 2323 3894 Air required (cfm)Air required (cfm)44 184 100 190 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 6...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Dining Room Master Bed 2 Exposed wall 27.0 ft 32.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft14.0x12.0 ft279.3x1.0 5 Room area 168.0 ft²279.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 120 81 256 164 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 8 0 98 133 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 31 0 561 691 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 140 92 290 185 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 0 0 0 0 48 48 905 500 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 40 40 126 81 180 158 499 319 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 22 0 362 487 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 110 110 323 160 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 168 168 167 246 279 279 277 409 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 168 27 774 0 279 32 918 0 6 c) AED excursion -63 343 Envelope loss/gain 2305 1412 3251 2243 12 a) Infiltration 277 74 555 147 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)2582 1485 3805 2891 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2582 1485 3805 2891 15 Duct loads 30%50%776 735 30%50%1144 1431 Total room load 3359 2221 4949 4322 Air required (cfm)Air required (cfm)145 108 213 210 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 7...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Hers His 2 Exposed wall 8.0 ft 0 ft 3 Room height 9.4 heat/coolft 9.4 heat/coolft 4 Room dimensions ft7.5x5.5 ft30.5x1.0 5 Room area 41.3 ft²30.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 5 5 15 9 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 71 71 222 142 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 41 41 41 60 31 31 30 45 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 41 8 229 0 31 0 0 0 6 c) AED excursion -10 -2 Envelope loss/gain 507 202 30 43 12 a) Infiltration 130 35 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)638 237 30 43 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 638 237 30 43 15 Duct loads 30%50%192 117 30%50%9 21 Total room load 829 354 39 64 Air required (cfm)Air required (cfm)36 17 2 3 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 8...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Master Bath Foyer 2 Exposed wall 26.5 ft 8.0 ft 3 Room height 9.4 heat/coolft 10.0 heat/coolft 4 Room dimensions ft171.8x1.0 ft85.0x1.0 5 Room area 171.8 ft²85.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 94 86 271 173 80 32 101 64 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 4 0 72 89 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 4 0 74 91 0 0 0 0 11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 0 0 0 0 48 0 905 769 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 85 85 267 171 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 71 71 222 142 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 172 172 170 251 85 85 84 124 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 172 27 760 0 85 8 229 0 6 c) AED excursion -42 -40 Envelope loss/gain 1835 875 1319 918 12 a) Infiltration 432 115 139 37 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2267 989 1458 955 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2267 989 1458 955 15 Duct loads 30%50%682 490 30%50%438 473 Total room load 2949 1479 1896 1427 Air required (cfm)Air required (cfm)127 72 82 69 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 9...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Nook WIC 2 Exposed wall 12.0 ft 6.0 ft 3 Room height 10.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft107.5x1.0 ft6.0x8.0 5 Room area 107.5 ft²48.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 48 48 151 97 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 55 39 124 79 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 16 16 262 210 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 65 50 156 100 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 261 351 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 108 108 107 157 48 48 48 70 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 108 12 344 0 48 6 172 0 6 c) AED excursion 284 -8 Envelope loss/gain 1254 1182 371 159 12 a) Infiltration 208 55 83 22 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1462 1237 454 181 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 11 15 12 17 14 Subtotal 1473 1252 466 198 15 Duct loads 30%50%443 620 30%43%140 86 Total room load 1915 1872 606 284 Air required (cfm)Air required (cfm)83 91 26 14 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 10...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Wtr Clst 2 Exposed wall 10.5 ft 3 Room height 8.0 heat/coolft 4 Room dimensions ft25.0x1.0 5 Room area 25.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blk Wall, Stucco Ext 0.109 ne 3.15 2.02 36 32 101 64 .G Impact, Clear Low-e 0.450 ne 13.05 17.69 0 0 0 0 .G Impact, Clear Low-e 0.620 ne 17.98 22.15 4 0 72 89 .G Impact, Clear Low-e 0.620 ne 17.98 22.15 0 0 0 0 11 G Impact, Clear Low-e 0.620 ne 17.98 22.15 0 0 0 0 G Impact, Clear Low-e 0.650 ne 18.85 16.03 0 0 0 0 W Blk Wall, Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 G Impact, Clear Low-e 0.580 se 16.82 21.08 0 0 0 0 G Impact, Clear Low-e 0.580 se 16.82 21.81 0 0 0 0 G Impact, Clear Low-e 0.580 se 16.82 21.81 0 0 0 0 W Blk Wall, Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 G Impact, Clear Low-e 0.580 sw 16.82 21.82 0 0 0 0 G Impact, Clear Low-e 0.580 sw 16.82 13.48 0 0 0 0 G Impact, Clear Low-e 0.650 sw 18.85 10.41 0 0 0 0 W Blk Wall, Stucco Ext 0.109 nw 3.15 2.02 48 41 128 82 G Impact, Clear Low-e 0.580 nw 16.82 22.64 7 0 124 167 G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 G Impact, Clear Low-e 0.650 nw 18.85 16.03 0 0 0 0 P Frm Wall, 1/2" Gyp B 0.101 -2.94 1.46 0 0 0 0 C Attic, Shngls, R-30 0.034 -0.99 1.46 25 25 25 37 F On Grade Depth, Tile 0.989 -28.68 0.00 25 11 301 0 6 c) AED excursion 25 Envelope loss/gain 751 463 12 a) Infiltration 146 39 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)897 502 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 897 502 15 Duct loads 30%43%270 218 Total room load 1166 720 Air required (cfm)50 35 2021-Nov-02 11:07:56 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1645Job:Duct System Summary 10/18/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Allen Residence, Nisair Air ConditioningFor: 5507 Hickory Dr, Ft. Pierce, FL 34982 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.501 / 0.199 in H2O in H2O0.501 / 0.199 Lowest friction rate in/100ft0.281in/100ft0.281 Actual air flow cfm1400cfm1400 Total effective length (TEL) ft249 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st3110.021.1VlFx0x06.00.38297821654cBed 2 st4130.047.9VlFx0x08.00.2811882544911hBed 3 st4125.045.3VlFx0x06.00.294901312533hCabana Bath 75.02.0VlFx0x06.00.6501301743359hDining Room st1105.031.1VlFx0x06.00.36883981896hFoyer st2100.023.2VlFx0x06.00.406114601947cGreat Room st2100.024.3VlFx0x06.00.403114601947cGreat Room-A st1105.031.7VlFx0x04.00.3662143829hHers st1105.031.0VlFx0x04.00.3684264cHis st2100.022.0VlFx0x06.00.410111261893cKitchen st2100.020.7VlFx0x06.00.415111261893cKitchen-A st1105.035.5VlFx0x07.00.356861532949hMaster Bath st1105.041.9VlFx0x06.00.3411261282475hMaster Bed st1105.033.0VlFx0x06.00.3631261282475hMaster Bed-A st4130.044.1VlFx0x06.00.288109991872cNook st3110.022.2VlFx0x05.00.37993891593cUtility st4125.045.5VlFx0x04.00.2941731606hWIC st4125.048.2VlFx0x04.00.2891934659hWIC 2 st1110.042.5VlFx0x05.00.32842601166hWtr Clst Bold/italic values have been manually overridden 2021-Nov-02 11:07:56 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2 ...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 550 423 0.281 700 12.0 0x0 VinlFlx st2 st1 Peak AVF 612 489 0.328 780 12.0 0x0 VinlFlx st2 Peak AVF 723 872 0.281 816 14.0 0x0 VinlFlx st3 Peak AVF 171 190 0.379 710 7.0 0x0 VinlFlx Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 9770 1082 70.8 0.281 612 18.0 x0 0 VlFx rb3 0x 1130 113 0 0 0 0 x0 0 VlFx rb6 0x 3010 277 0 0 0 0 x0 0 VlFx rb4 0x 2880 208 0 0 0 0 x0 0 VlFx 2021-Nov-02 11:07:56 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1645Job:Manual S Compliance Report 10/18/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Allen Residence, Nisair Air ConditioningFor: 5507 Hickory Dr, Ft. Pierce, FL 34982 Cooling Equipment Design Conditions °F76.9Entering coil DB:Btuh29628Sensible gain:°F90.4Outdoor design DB: °F63.9Entering coil WB:Btuh7501Latent gain:°F77.4Outdoor design WB: Btuh37129Total gain:°F75.0Indoor design DB: cfm1400Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: ML14XC1S042-230A**+CBA27UHE-042-230*++TDRModel:LennoxManufacturer: cfm1400Actual airflow: % of load99Btuh29400Sensible capacity: % of load168Btuh12600Latent capacity: %70SHR:% of load113Btuh42000Total capacity: Heating Equipment Design Conditions °F68.4Entering coil DB:Btuh34099Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm1400Actual airflow: °F50Temp. rise:% of load102kW10.2Output capacity: Meets all requirements of ACCA Manual S.