HomeMy WebLinkAboutProject InformationCalculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-02 11:07:55
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1645Job:Load Short Form 10/18/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Allen Residence, Nisair Air ConditioningFor:
5507 Hickory Dr, Ft. Pierce, FL 34982
Design Information
InfiltrationClgHtg
SimplifiedMethod9041Outside db (°F)
AverageConstruction quality7570Inside db (°F)
0Fireplaces1529Design TD (°F)
L-Daily range
5030Inside humidity (%)
572Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make Lennox
Trade Trade LENNOX
Model Cond ML14XC1S042-230A**
AHRI ref Coil CBA27UHE-042-230*++TDR
AHRI ref 10259441
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW10.2 Sensible cooling Btuh29400
Heating output Btuh34696 Latent cooling Btuh12600
Temperature rise °F23 Total cooling Btuh42000
Actual air flow cfm1400 Actual air flow cfm1400
Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.049
Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.80
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
Utility 78 1727 1593 74 78
Bed 2 138 1579 1654 68 81
WIC 2 48 659 326 28 16
Linen 11 0 0 0 0
Bed 3 204 4911 3227 212 157
Cabana Bath 113 2533 1536 109 75
Hall 71 0 0 0 0
Kitchen 222 1018 3786 44 184
Great Room 299 2323 3894 100 190
Dining Room 168 3359 2221 145 108
Master Bed 279 4949 4322 213 210
Hers 41 829 354 36 17
His 31 39 64 2 3
Master Bath 172 2949 1479 127 72
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-02 11:07:55
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2
...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
Foyer 85 1896 1427 82 69
Nook 108 1915 1872 83 91
WIC 48 606 284 26 14
Wtr Clst 25 1166 720 50 35
House 2139 32461 28758 1400 1400
Other equip loads 1638 870
Equip. @ 0.95 RSM 28265
Latent cooling 7501
TOTALS 2139 34099 35766 1400 1400
2021-Nov-02 11:07:55
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1645Job:Building Analysis 10/18/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Allen Residence, Nisair Air ConditioningFor:
5507 Hickory Dr, Ft. Pierce, FL 34982
Design Conditions
Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Heating
Walls
Glazing
Ceilings
Floors
Infiltration
Ducts
Ventilation
% of loadBtuhBtuh/ft²Component
18.462763.1Walls
17.6598617.9Glazing
000Doors
6.221201.0Ceilings
20.770563.33.3Floors
10.335191.7Infiltration
22.07504Ducts
00Piping
00Humidification
4.81638Ventilation0Adjustments
100.034099Total
Cooling
Walls
Glazing
Ceilings
Infiltration
Ducts
Internal Gains
Ventilation
% of loadBtuhBtuh/ft²Component
13.138811.9Walls
21.3630018.8Glazing
000Doors
10.631301.5Ceilings
000Floors
3.29340.5Infiltration
32.09493Ducts
2.9870Ventilation
16.95020Internal gains
00Blower
0Adjustments
100.029628Total
Latent Cooling Load = 7501 Btuh
Overall U-value = 0.112 Btuh/ft²-°F
Data entries checked.
2021-Nov-02 11:07:55
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1645Job:Component Constructions 10/18/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Allen Residence, Nisair Air ConditioningFor:
5507 Hickory Dr, Ft. Pierce, FL 34982
Design Conditions
Location: CoolingHeatingIndoor:
7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr
BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft²
Walls
Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 7283.155.10.109231ne 4662.02
9562.0214953.155.10.109474se
7922.0212393.155.10.109393sw
12032.0218813.155.10.109597nw
34172.0253433.155.10.1091696all
Partitions
Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16"
OC Stud
4641.469342.9411.00.101318
Windows
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.18);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 10 ft overhang (1.25 ft window ht, 1 ft sep.); 6.8 ft head ht
13317.79813.000.4508ne
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (1.33 ft window ht, 1 ft sep.); 6.8 ft head ht
17722.114418.000.6208ne
9122.17418.000.6204ne
26822.121818.000.62012all
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 10 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht
69122.156118.000.62031ne
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 15.9 ft overhang (8 ft window ht, 1 ft sep.); 6.8 ft head ht
76916.090518.800.65048ne
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (3.17 ft window ht, 1 ft sep.); 6.8 ft head ht
13921.111116.800.5807se
16722.612416.800.5807nw
30621.923516.800.58014all
2021-Nov-02 11:07:55
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2
...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (5.17 ft window ht, 1 ft sep.); 6.8 ft head ht
47021.836216.800.58022se
33821.826116.800.58016se
48722.636216.800.58022nw
129522.198516.800.58059all
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 8 ft head ht
34021.826216.800.58016sw
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 4 ft overhang (5.2 ft window ht, 1 ft sep.); 8 ft head ht
21013.526216.800.58016sw
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 12 ft overhang (8 ft window ht, 1 ft sep.); 6.8 ft head ht
100010.4181018.800.65096sw
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 6 ft overhang (5.17 ft window ht, 1 ft sep.); 6.8 ft head ht
35122.626116.800.58016nw
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 4 ft overhang (8 ft window ht, 1 ft sep.); 6.8 ft head ht
33116.039018.900.65021nw
Doors
(none)
Ceilings
Attic, Shngls, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.0342139 31301.4621200.9930.0
Floors
On Grade Depth, Tile Flr Fnsh 00705628.700.989246
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-02 11:07:55
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1645Job:Project Summary 10/18/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Allen Residence, Nisair Air ConditioningFor:5507 Hickory Dr, Ft. Pierce, FL 34982
Notes:
Design Information
St Lucie Co Intl, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75
Design TD °F29 Design TD °F15Daily range L
Relative humidity %50Moisture difference gr/lb57
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh24957 Structure Btuh19265
Ducts Btuh7504 Ducts Btuh9493Central vent (51 cfm) 1638 Btuh Central vent (51 cfm) Btuh870
Outside air Outside airHumidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh34099 Use manufacturer's data n
Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh28265
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average0Fireplaces Structure Btuh2933
Ducts Btuh2582Central vent (51 cfm) Btuh1986
CoolingHeating Outside air21392139Area (ft²) Equipment latent load Btuh7501
2070320703Volume (ft³)Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh35766
Equiv. AVF (cfm) 55110 Req. total capacity at 0.70 SHR ton3.4
Heating Equipment Summary Cooling Equipment Summary
Make Make LennoxTrade Trade LENNOX
Model Cond ML14XC1S042-230A**AHRI ref Coil CBA27UHE-042-230*++TDR
AHRI ref 10259441Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW10.2 Sensible cooling Btuh29400Heating output Btuh34696 Latent cooling Btuh12600
Temperature rise °F23 Total cooling Btuh42000Actual air flow cfm1400 Actual air flow cfm1400
Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.049Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.80
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name House Utility
2 Exposed wall 246.0 ft 18.5 ft
3 Room height 9.7 ft 9.4 heat/coolft
4 Room dimensions ft6.5x12.0
5 Room area 2139.3 ft²78.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 330 231 728 466 0 0 0 0
.GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 8 0 98 133 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 8 0 144 177 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 4 0 74 91 0 0 0 0
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 31 0 561 691 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 48 0 905 769 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 518 474 1495 956 61 55 172 110
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 7 3 111 139 7 1 111 139
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 22 5 362 470 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 16 4 261 338 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 520 393 1239 792 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 16 4 262 340 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 16 31 262 210 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 96 192 1810 1000 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 662 597 1881 1203 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 7 0 124 167 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 22 0 362 487 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 261 351 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 21 0 390 331 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 318 318 934 464 113 113 331 165
CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 2139 2139 2120 3130 78 78 77 114
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 2139 246 7056 0 78 19 531 0
6 c) AED excursion 605 10
Envelope loss/gain 21438 13311 1222 538
12 a) Infiltration 3519 934 106 28
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 4 920 0 0
Appliances/other 4100 500
Subtotal (lines 6 to 13)24957 19265 1328 1066
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 24957 19265 1328 1066
15 Duct loads 30%49%7504 9493 30%50%399 528
Total room load 32461 28758 1727 1593
Air required (cfm)Air required (cfm)1400 1400 74 78
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bed 2 WIC 2
2 Exposed wall 11.5 ft 6.0 ft
3 Room height 9.4 heat/coolft 9.4 heat/coolft
4 Room dimensions ft11.5x12.0 ft6.0x8.0
5 Room area 138.0 ft²48.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 108 93 292 187 56 56 178 114
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 16 2 261 338 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 138 138 137 202 48 48 48 70
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 138 12 330 0 48 6 172 0
6 c) AED excursion 69 -9
Envelope loss/gain 1019 796 397 175
12 a) Infiltration 187 50 98 26
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 250 0
Subtotal (lines 6 to 13)1206 1095 495 201
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 8 11 12 17
14 Subtotal 1214 1107 507 218
15 Duct loads 30%50%365 548 30%50%152 108
Total room load 1579 1654 659 326
Air required (cfm)Air required (cfm)68 81 28 16
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 3...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Linen Bed 3
2 Exposed wall 0 ft 41.0 ft
3 Room height 9.4 heat/coolft 9.4 heat/coolft
4 Room dimensions ft10.5x1.0 ft17.0x12.0
5 Room area 10.5 ft²204.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 160 138 436 279
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 22 3 362 470
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 113 97 306 196
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 16 2 262 340
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 113 113 355 227
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 11 11 10 15 204 204 202 298
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 11 0 0 0 204 41 1176 0
6 c) AED excursion -1 -91
Envelope loss/gain 10 15 3100 1720
12 a) Infiltration 0 0 668 177
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 250
Subtotal (lines 6 to 13)10 15 3768 2147
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -10 -15 8 11
14 Subtotal 0 0 3776 2158
15 Duct loads 30%50%0 0 30%50%1135 1068
Total room load 0 0 4911 3227
Air required (cfm)Air required (cfm)0 0 212 157
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 4...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Cabana Bath Hall
2 Exposed wall 20.0 ft 0 ft
3 Room height 9.4 heat/coolft 9.4 heat/coolft
4 Room dimensions ft113.0x1.0 ft70.5x1.0
5 Room area 113.0 ft²70.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 113 113 355 227 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 75 55 172 110 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 21 0 390 331 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 113 113 112 165 71 71 70 103
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 113 20 574 0 71 0 0 0
6 c) AED excursion 79 -4
Envelope loss/gain 1602 913 70 99
12 a) Infiltration 326 87 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)1928 1000 70 99
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 19 28 -70 -99
14 Subtotal 1948 1027 0 0
15 Duct loads 30%50%586 508 30%50%0 0
Total room load 2533 1536 0 0
Air required (cfm)Air required (cfm)109 75 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 5...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Kitchen Great Room
2 Exposed wall 9.5 ft 9.5 ft
3 Room height 10.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft222.3x1.0 ft298.8x1.0
5 Room area 222.3 ft²298.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 95 47 148 95
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 0 0 0 0 48 48 905 500
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 95 95 279 139 0 0 0 0
CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 222 222 220 325 299 299 296 437
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 222 10 272 0 299 10 272 0
6 c) AED excursion -106 169
Envelope loss/gain 772 357 1621 1201
12 a) Infiltration 0 0 165 44
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 2 460 2 460
Appliances/other 1700 900
Subtotal (lines 6 to 13)772 2517 1786 2605
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 11 15 0 0
14 Subtotal 783 2533 1786 2605
15 Duct loads 30%50%235 1254 30%50%537 1289
Total room load 1018 3786 2323 3894
Air required (cfm)Air required (cfm)44 184 100 190
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 6...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Dining Room Master Bed
2 Exposed wall 27.0 ft 32.0 ft
3 Room height 10.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft14.0x12.0 ft279.3x1.0
5 Room area 168.0 ft²279.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 120 81 256 164 0 0 0 0
.GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 8 0 98 133 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 31 0 561 691 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 140 92 290 185
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 0 0 0 0 48 48 905 500
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 40 40 126 81 180 158 499 319
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 22 0 362 487
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 110 110 323 160 0 0 0 0
CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 168 168 167 246 279 279 277 409
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 168 27 774 0 279 32 918 0
6 c) AED excursion -63 343
Envelope loss/gain 2305 1412 3251 2243
12 a) Infiltration 277 74 555 147
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 500
Subtotal (lines 6 to 13)2582 1485 3805 2891
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 2582 1485 3805 2891
15 Duct loads 30%50%776 735 30%50%1144 1431
Total room load 3359 2221 4949 4322
Air required (cfm)Air required (cfm)145 108 213 210
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 7...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Hers His
2 Exposed wall 8.0 ft 0 ft
3 Room height 9.4 heat/coolft 9.4 heat/coolft
4 Room dimensions ft7.5x5.5 ft30.5x1.0
5 Room area 41.3 ft²30.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 5 5 15 9 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 71 71 222 142 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 41 41 41 60 31 31 30 45
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 41 8 229 0 31 0 0 0
6 c) AED excursion -10 -2
Envelope loss/gain 507 202 30 43
12 a) Infiltration 130 35 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)638 237 30 43
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 638 237 30 43
15 Duct loads 30%50%192 117 30%50%9 21
Total room load 829 354 39 64
Air required (cfm)Air required (cfm)36 17 2 3
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 8...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Master Bath Foyer
2 Exposed wall 26.5 ft 8.0 ft
3 Room height 9.4 heat/coolft 10.0 heat/coolft
4 Room dimensions ft171.8x1.0 ft85.0x1.0
5 Room area 171.8 ft²85.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 94 86 271 173 80 32 101 64
.GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 4 0 72 89 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 4 0 74 91 0 0 0 0
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 0 0 0 0 48 0 905 769
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 85 85 267 171 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 71 71 222 142 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 172 172 170 251 85 85 84 124
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 172 27 760 0 85 8 229 0
6 c) AED excursion -42 -40
Envelope loss/gain 1835 875 1319 918
12 a) Infiltration 432 115 139 37
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)2267 989 1458 955
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 2267 989 1458 955
15 Duct loads 30%50%682 490 30%50%438 473
Total room load 2949 1479 1896 1427
Air required (cfm)Air required (cfm)127 72 82 69
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 9...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Nook WIC
2 Exposed wall 12.0 ft 6.0 ft
3 Room height 10.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft107.5x1.0 ft6.0x8.0
5 Room area 107.5 ft²48.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 48 48 151 97
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 55 39 124 79 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 16 16 262 210 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 10.4110.41 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 65 50 156 100 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 261 351 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 16.0316.03 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 108 108 107 157 48 48 48 70
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 108 12 344 0 48 6 172 0
6 c) AED excursion 284 -8
Envelope loss/gain 1254 1182 371 159
12 a) Infiltration 208 55 83 22
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)1462 1237 454 181
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 11 15 12 17
14 Subtotal 1473 1252 466 198
15 Duct loads 30%50%443 620 30%43%140 86
Total room load 1915 1872 606 284
Air required (cfm)Air required (cfm)83 91 26 14
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-02 11:07:55Right-Suite® Universal 2021 21.0.08 RSU29066 Page 10...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1645Job:Right-J® Worksheet 10/18/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Wtr Clst
2 Exposed wall 10.5 ft
3 Room height 8.0 heat/coolft
4 Room dimensions ft25.0x1.0
5 Room area 25.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area Load
number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 W Blk Wall, Stucco Ext 0.109 ne 3.15 2.02 36 32 101 64
.G Impact, Clear Low-e 0.450 ne 13.05 17.69 0 0 0 0
.G Impact, Clear Low-e 0.620 ne 17.98 22.15 4 0 72 89
.G Impact, Clear Low-e 0.620 ne 17.98 22.15 0 0 0 0
11 G Impact, Clear Low-e 0.620 ne 17.98 22.15 0 0 0 0
G Impact, Clear Low-e 0.650 ne 18.85 16.03 0 0 0 0
W Blk Wall, Stucco Ext 0.109 se 3.15 2.02 0 0 0 0
G Impact, Clear Low-e 0.580 se 16.82 21.08 0 0 0 0
G Impact, Clear Low-e 0.580 se 16.82 21.81 0 0 0 0
G Impact, Clear Low-e 0.580 se 16.82 21.81 0 0 0 0
W Blk Wall, Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0
G Impact, Clear Low-e 0.580 sw 16.82 21.82 0 0 0 0
G Impact, Clear Low-e 0.580 sw 16.82 13.48 0 0 0 0
G Impact, Clear Low-e 0.650 sw 18.85 10.41 0 0 0 0
W Blk Wall, Stucco Ext 0.109 nw 3.15 2.02 48 41 128 82
G Impact, Clear Low-e 0.580 nw 16.82 22.64 7 0 124 167
G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0
G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0
G Impact, Clear Low-e 0.650 nw 18.85 16.03 0 0 0 0
P Frm Wall, 1/2" Gyp B 0.101 -2.94 1.46 0 0 0 0
C Attic, Shngls, R-30 0.034 -0.99 1.46 25 25 25 37
F On Grade Depth, Tile 0.989 -28.68 0.00 25 11 301 0
6 c) AED excursion 25
Envelope loss/gain 751 463
12 a) Infiltration 146 39
b) Room ventilation 0 0
13 Internal gains: Occupants @ 230 0 0
Appliances/other 0
Subtotal (lines 6 to 13)897 502
Less external load 0 0
Less transfer 0 0
Redistribution 0 0
14 Subtotal 897 502
15 Duct loads 30%43%270 218
Total room load 1166 720
Air required (cfm)50 35
2021-Nov-02 11:07:56
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1645Job:Duct System Summary 10/18/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Allen Residence, Nisair Air ConditioningFor:
5507 Hickory Dr, Ft. Pierce, FL 34982
CoolingHeating
External static pressure in H2O0.70in H2O0.70
Pressure losses in H2O0in H2O0
Available static pressure in H2O0.70in H2O0.70
Supply / return available pressure 0.501 / 0.199 in H2O in H2O0.501 / 0.199
Lowest friction rate in/100ft0.281in/100ft0.281
Actual air flow cfm1400cfm1400
Total effective length (TEL) ft249
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st3110.021.1VlFx0x06.00.38297821654cBed 2
st4130.047.9VlFx0x08.00.2811882544911hBed 3
st4125.045.3VlFx0x06.00.294901312533hCabana Bath
75.02.0VlFx0x06.00.6501301743359hDining Room
st1105.031.1VlFx0x06.00.36883981896hFoyer
st2100.023.2VlFx0x06.00.406114601947cGreat Room
st2100.024.3VlFx0x06.00.403114601947cGreat Room-A
st1105.031.7VlFx0x04.00.3662143829hHers
st1105.031.0VlFx0x04.00.3684264cHis
st2100.022.0VlFx0x06.00.410111261893cKitchen
st2100.020.7VlFx0x06.00.415111261893cKitchen-A
st1105.035.5VlFx0x07.00.356861532949hMaster Bath
st1105.041.9VlFx0x06.00.3411261282475hMaster Bed
st1105.033.0VlFx0x06.00.3631261282475hMaster Bed-A
st4130.044.1VlFx0x06.00.288109991872cNook
st3110.022.2VlFx0x05.00.37993891593cUtility
st4125.045.5VlFx0x04.00.2941731606hWIC
st4125.048.2VlFx0x04.00.2891934659hWIC 2
st1110.042.5VlFx0x05.00.32842601166hWtr Clst
Bold/italic values have been manually overridden
2021-Nov-02 11:07:56
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2
...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st4 Peak AVF 550 423 0.281 700 12.0 0x0 VinlFlx st2
st1 Peak AVF 612 489 0.328 780 12.0 0x0 VinlFlx
st2 Peak AVF 723 872 0.281 816 14.0 0x0 VinlFlx
st3 Peak AVF 171 190 0.379 710 7.0 0x0 VinlFlx
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb1 0x 9770 1082 70.8 0.281 612 18.0 x0 0 VlFx
rb3 0x 1130 113 0 0 0 0 x0 0 VlFx
rb6 0x 3010 277 0 0 0 0 x0 0 VlFx
rb4 0x 2880 208 0 0 0 0 x0 0 VlFx
2021-Nov-02 11:07:56
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ts\Wrightsoft HVAC\5507 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1645Job:Manual S Compliance Report 10/18/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Allen Residence, Nisair Air ConditioningFor:
5507 Hickory Dr, Ft. Pierce, FL 34982
Cooling Equipment
Design Conditions
°F76.9Entering coil DB:Btuh29628Sensible gain:°F90.4Outdoor design DB:
°F63.9Entering coil WB:Btuh7501Latent gain:°F77.4Outdoor design WB:
Btuh37129Total gain:°F75.0Indoor design DB:
cfm1400Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ACEquipment type:
ML14XC1S042-230A**+CBA27UHE-042-230*++TDRModel:LennoxManufacturer:
cfm1400Actual airflow:
% of load99Btuh29400Sensible capacity:
% of load168Btuh12600Latent capacity:
%70SHR:% of load113Btuh42000Total capacity:
Heating Equipment
Design Conditions
°F68.4Entering coil DB:Btuh34099Heat loss:°F41.0Outdoor design DB:
°F70.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Elec stripEquipment type:
Model:Manufacturer:
cfm1400Actual airflow:
°F50Temp. rise:% of load102kW10.2Output capacity:
Meets all requirements of ACCA Manual S.