HomeMy WebLinkAboutEnergy Efficiency CodeFORM R405-2020
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the
Residential Simulated Performance Alternative shall include:
❑ This checklist
❑ Form R405-2020 report
❑ Input summary checklist that can be used for field verification (usually four pages/may be greater)
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403. 7
❑ Mandatory Requirements (five pages)
Required prior to CO:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page)
❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4
allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to
comply with Section C402.5
❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed
2020 Duct Leakage Test Report - Performance Method (usually one page)
1112/2021 11:44!11 AM EnergyGauge® USA 7.0.00 - FlaRes202O FRO 7th Edition (2020) Compliant Software Page 1 of 1
FORM R405-2020
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: 5507 Hickory Dr PSL Prop
Street: 5507 Hickory Dr
City, State, Zip: Ft. Pierce , FL , 34982
Owner: Allen Residence
Design Location: FL, ST_LUCIE_CO_INTL
Builder Name: PSL Prop
Permit Office:
Permit Number:
Jurisdiction: St. Lucie
County: St. Lucie (Florida Climate Zone 2 )
1.
New construction or existing
New (From Plans)
10. Wall Type�2350.3 sgft.)
Insulation
Area
a. Concrete Block - Ext Insul, Exterior
R=4.1
2032.30 ft2
2.
Single family or multiple family
Detached
b. Frame - Wood, Adjacent
R=11.0
318.00 ft2
3.
Number of units, if multiple family
1
c. N/A
R=
ft2
4.
Number of Bedrooms
3
d. N/A
11. Ceiling Types (2139.0 sqft.)
R=
Insulation
ft2
Area
5.
Is this a worst case?
Yes
a. Under Attic (Vented)
R=30.0
2139.00 ft2
6.
Conditioned floor area above grade (ft2)
2139
b. N/A
R=
112
ft2
Conditioned floor area below grade (ft2)
0
c. N/A
R=
R ft2
7.
Windows(334.3 sqft.) Description
Area
12. Ducts
a. Sup: Attic, Ret: Attic, AH: Attic
6 854
a. U-Factor: Dbl, U=0.65
164.67 ft2
SHGC; SHGC=0.21
b. U-Factor: Ohl, U=0.58
119.04 ft2
13. Cooling systems
kBtu/hr
Efficiency
SHGC: SHGC=0.24
a. Central Unit
42.0
SEER:16.00
c. U-Factor: Dbl, U=0.62
43.11 ft2
SHGC: SHGC=0.22
14, Heating systems
kBtu/hr
Efficiency
Area Weighted Average Overhang Depth:
7.893 ft.
a. Electric Strip Heat
34.7
COP:1.00
Area Weighted Average SHGC:
0.221
8.
Skylights
Area
c. U-Factor:(AVG) N/A
ft2
15, Hot water systems
SHGC(AVG): N/A
a. Electric
Cap: 50 gallons
9.
Floor Types (2139.5 sgft.)
Insulation
Area
EF: 0.960
a. Slab -On -Grade Edge Insulation
R=0.0
2139.50 ft2
b. Conservation features
b. N/A
R=
ft2
None
c. N/A
R=
ft2
16. Credits
Patel
Total
Proposed Modified
Loads: 68.50
PASS
Glass/Floor Area: 0.156
Total Baseline Loads:
69.87
I hereby certify that the plans and specifications covered by
this calculation are in compliance with the Florida Energy
Code. � �,,
PREPARED BY: ` /�4e,;f. e�Fa&m4zg�
DATE: 11 /2/2021
I hereby
certify
that this
building, as
with the
Florida
Energy
Code.
Review of the plans and
specifications covered by this
calculation indicates compliance
with the Florida Energy Code.
Before construction is completed
this building will be inspected for
compliance with Section 553.908
Florida Statutes.
BUILDING OFFICIAL:
DATE:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with R403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 5.00 ACH50 (R402.4.1.2).
11/2/2021 11:44 AM EnergyGaugeN> USA 7.0.00 - FlaRes2020 FBC 7fh Edition (2020) Compliant Software Page 1 of 7
PROJECT
Title: 5507 Hickory Dr PSL Prop Bedrooms: 3 Address Type: Street Address
Building Type: User Conditioned Area: 2139 Lot#
Owner Name: Allen Residence Total Stories: 1 Block/Subdivision:
# of Units: 1 Worst Case: Yes PlatBook:
Builder Name: PSL Prop Rotate Angle: 90 Street: 5507 Hickory Dr
Permit Office: Cross Ventilation: No County: St. Lucie
Jurisdiction: St. Lucie Whole House Fan: No City, State, Zip: Ft. Pierce ,
Family Type: Detached FL, 34982
New/Existing: New (From Plans)
Comment:
CLIMATE
Design Temp Int Design Temp Heating Design Daily Temp
Design Location TMY Site 97.5 % 2.5 % Winter Summer Degree Days Moisture Range
FL, ST_LUCIE_CO_INTL FL_ VERO_BEACH_MUNI 39 90 70 75 299 58 Medium
BLOCKS
Number Name Area Volume
1 Entire House 2139 20699.8
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated
1 Utility 78 733.2 No 0 1 Yes Yes Yes
2 Bed 2 138 1297.2 No 0 1 1 Yes Yes Yes
3 WIC 2 48 451.2 No 0 1 Yes Yes Yes
4 Linen 11 103.4 No 0 1 Yes Yes Yes
5 Bed 3 204 1917.6 No 0 1 1 Yes Yes Yes
6 Cabana Bath 113 1062.2 No 0 1 Yes Yes Yes
7 Hall 71 6674 No 0 1 Yes Yes Yes
8 Kitchen 222 2220 Yes 2 1 Yes Yes Yes
9 Great Room 299 2990 No 2 1 Yes Yes Yes
10 Dining Room 168 1680 No 0 1 Yes Yes Yes
11 Master Bed 279 2790 No 0 i 1 Yes Yes Yes
12 Hers 41 385.4 No 0 1 Yes Yes Yes
13 His 31 291.4 No 0 1 Yes Yes Yes
14 Master Bath 172 1616.8 No 0 1 Yes Yes Yes
15 Foyer 85 850 No 0 1 Yes Yes Yes
16 Nook 106 1060 No 0 1 Yes Yes Yes
17 WIC 48 384 No 0 1 Yes Yes Yes
18 Wtr Clst 25 200 No 0 1 Yes Yes Yes
11/2/2021 11:44 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7lh Edition (2020) Compliant Software Page 2 of 7
ORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
FLOORS
# Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet
1 Slab -On -Grade Edge Insulatio Utility 18.5 ft 0 78 ft' ____ 1 0 0
2 Slab -On -Grade Edge Insulatio Bed 2 11.5 it 0 138 ft' ____ 1 0 0
3 Slab -On -Grade Edge Insulatio WIC 2 6 ft 0 48 ft' ____ 1 0 0
4SIab-On-Grade Edge Insulatio Linen 1 If 0 10.5 ft' ____ 1 0 0
5 Slab -On -Grade Edge Insulatio Bed 3 41 it 0 204 ft' ____ 1 0 0
6Slab-On-Grade Edge Insulatio Cabana Bath 20 it 0 113 ft° __-- 1 0 0
7Slab-On-Grade Edge Insulatio Hall 1 ft 0 70.5 ft' ____ 1 0 0
8 Slab -On -Grade Edge Insulatio Kitchen 9.5 ft 0 222.3 ft' ____ 1 0 0
9 Slab -On -Grade Edge Insulatio Great Room 9.5 ft 0 298.8 ft' ____ 1 0 0
10SIab-On-Grade Edge Insulatio Dining Room 27 ft 0 168 ft' ____ 1 0 0
11Slab-On-Grade Edge Insulatio Master Bed 32 ft 0 279.3 ft° ____ 1 0 0
12SIab-On-Grade Edge Insulatio Hers 8 ft 0 41.3 ft' ____ 1 0 0
13SIab-On-Grade Edge Insulatio His 1 It 0 30.5 W ____ 1 0 0
14SIab-On-Grade Edge Insulatio Master Bath 26.5 ft 0 171.8 f? ____ 1 0 0
15SIab-On-Grade Edge Insulatio Foyer 8 ft 0 85 ft' ____ 1 0 0
16Slab-On-Grade Edge Insulatio Nook 12 ft 0 107.5 ft' ____ 1 0 0
17SIab-On-Grade Edge Insulatio WIC 6 ft 0 48 ft' ____ 1 0 0
18SIab-0n-Grade Edge Insulatio Wtr Clst 10.5 ft 0 25 ft' ____ 1 0 0
ROOF
Roof Gable Roof Red Solar SA Emitt Emitt Deck Pitch
# Type Materials Area Area Color Barr Absor, Tested Tested Insul. (deg)
1 Hip Composition shingles 2392 fl' 0 ft' Medium N 0.3 No 0.9 No 0 26.57
/ ATTIC
V # Type Ventilation Vent Ratio (1 in) Area RBS IRCC
1 Full attic Vented 150 2139 ft' N N
11/2/2021 11:44 AM EnergyGaugeO USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 7
ORM R405-2020 INPUT SUMMAKY (:HI:L;KLIJ I Ktt'UK I
CEILING
# Ceiling Type Space R-Value Ins Type Area Framing Free Truss Type
1 Under Attic (Vented) Utility 30 Blown 78 W 0.1 Wood
2 Under Attic (Vented) Bed 2 30 Blown 138 ft2 0.1 Wood
_ 3 Under Attic (Vented) WIC 2 30 Blown 48 ft2 0.1 Wood
4 Under Attic (Vented) Linen 30 Blown 11 ft2 0.1 Wood
5 Under Attic (Vented) Bed 3 30 Blown 204 ft2 0.1 Wood
6 Under Attic (Vented) Cabana Bath 30 Blown 113 ft2 0.1 Wood
7 Under Attic (Vented) Hall 30 Blown 71 ft2 0.1 Wood
8 Under Attic (Vented) Kitchen 30 Blown 222 ft2 0.1 Wood
9 Under Attic (Vented) Great Room 30 Blown 299 ft2 0.1 Wood
10 Under Attic (Vented) Dining Room 30 Blown 168 ft2 0.1 Wood
11 Under Attic (Vented) Master Bed 30 Blown 279 T 0.1 Wood
12 Under Attic (Vented) Hers 30 Blown 41 ft' 0.1 Wood
13 Under Attic (Vented) His 30 Blown 31 ft2 0.1 Wood
_ 14 Under Attic (Vented) Master Bath 30 Blown 172 ft2 0.1 Wood
15 Under Attic (Vented) Foyer 30 Blown 85 ft2 0.1 Wood
16 Under Attic (Vented) Nook 30 Blown 106 ft' 0.1 Woad
17 Under Attic (Vented) WIC 30 Blown 48T OA Wood
18 Under Attic (Vented) Wlr Gist 30 Blown 25 W 0.1 Wood
WALLS
` / Adj1acent Space Cavity Width Height Sheathing Framing Solar Below
V 9 ll t TWR I T�f P R-\/ I Ft In Ft in AMR R-Sinlue Frantinn Ah o l` A ^/
_ 1 SE=>SW Exterior Concrete Block - Ext Insul Utility 4.1 6 6 9 5 61.2 ft' 0 0 0.3 0
_ 2 NE=>SE Garage Frame - Wood Utility 11 12 0 9 5 113.0 ft2 0 0.25 0.8 0
3 SE=>SW Exterior Concrete Block - Ext Insul Bed 2 4.1 11 6 9 5 108.3 ft2 0 0 0.3 0
_ 4 SE=>SW Exterior Concrete Block - Ext Insul WIC 2 4.1 6 0 9 5 66.5 ft' 0 0 0.3 0
5 SE=>SW Exterior Concrete Block - Ext Insul Bed 3 4.1 17 0 9 5 160.1 ft2 0 0 0.3 0
6 SW=>NW Exterior Concrete Block - Ext Insul Bed 3 4.1 12 0 9 5 113.0 ft2 0 0 0.3 0
7 NW=>NE Exterior Concrete Block - Ext Insul Bed 3 4.1 12 0 9 5 113.0 ft2 0 0 0.3 0
8 SW=>NW Exterior Concrete Block - Ext InsiGhbana Bath 4.1 12 0 9 5 113.0 ft2 0 0 0.3 0
9 NW=>NE Exterior Concrete Block - Ext InsObbana Bath 4.1 8 0 9 5 75.3 W 0 0 0.3 0
10 SE=>SW Garage Frame - Wood Kitchen 11 2 6 10 0 25.0 ft2 0 0.25 0.8 0
_ 11 NE=>SE Garage Frame - Wood Kitchen 11 7 0 10 0 70.0 W 0 0.25 0.8 0
12 SW=>NW Exterior Concrete Block - Ext InsGreat Room 4.1 9 6 10 0 95.0 ft2 0 0 0.3 0
_ 13 NE=>SE Exterior Concrete Block - Ext InsDining Room 4.1 12 0 10 0 120.0 ft2 0 0 0.3 0
_ 14 NW=>NE Exterior Concrete Block - Ext InsDining Room 4.1 4 0 10 0 40.0 T 0 0 0.3 0
_ 15 SE=>SW Garage Frame - Wood Dining Room 11 11 0 10 0 110.0 ft2 0 0.25 0.8 0
16 SW=>NW Exterior Concrete Block - Ext InsMaster Bed 4.1 14 0 10 0 140.0 ft2 0 0 0.3 0
_ 17 NW=>NE Exterior Concrete Block - Ext InstMaster Bed 4.1 18 0 10 0 180.0 ft2 0 0 0.3 0
18 SW=>NW Exterior Concrete Black -Exl Insul Hers 4.1 0 6 9 5 4.7 ft2 0 0 0.3 0
19 NW=>NE Exterior Concrete Block- Ext Insul Hers 4.1 7 6 9 5 70.6 ft2 0 0 0.3 0
20 NE=>SE Exterior Concrete Block - Ext InsWlaster Bath 4.1 10 0 9 5 94.2 ft2 0 0 0.3 0
21 SE=>SW Exterior Concrete Block - Ext InsMaster Bath 4.1 9 0 9 5 84.8 ft' 0 0 0.3 0
22 NW=>NE Exterior Concrete Block - Ext InsMaster Bath 4A 7 6 9 5 70.6 ft2 0 0 0.3 0
11/2/2021 11:44 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 7
ITiT/TR
Adjacent Space Cavity Width Height Sheathing Framing Solar Below
V# O 1 Tn Wall Ty p R-Val a Ft In Ft In 0 na R-VnIuA Frnnfion Ahcn Grade
23 NE=>SE Exterior Concrete Block - Ext Insul Foyer 4.1 8 0 10 0 80.0 ft' 0 0 0.3 0
24 SW=>NW Exterior Concrete Block - Ext Insul Nook 4.1 5 6 10 0 55.0 ft' 0 0 0.3 0
25 NW=>NE Exterior Concrete Block -Exl Insul Nook 4.1 6 6 10 0 65.0 ft' 0 0 0.3 0
26 SE=>SW Exterior Concrete Block- Ext Insul WIC 4.1 6 0 8 0 48.0 ft' 0 0 0.3 0
27 NE=>SE Exterior Concrete Block - Ext Insul Wtr Clst 4.1 4 6 8 0 36.0 ft' 0 0 0.3 0
28 NW=>NE Exterior Concrete Block - Ext Insul Wtr Clst 4.1 6 0 8 0 48.0 ft' 0 0 0.3 0
WINDOWS
Orientation shown is the entered orientation (=>) changed to Worst Case.
/ Wall Overhang
V # Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Inl Shade Screening
1 SE=>SW 1 Metal Low-E Double Yes 0.58 0.24 Y 6.6 ft' 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
2 SE=>SW 3 Metal Low-E Double Yes 0.58 0.24 Y 15.5 ft' 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
3 SE=>SW 5 Metal Low-E Double Yes 0.58 0.24 Y 21.5 ft' 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
4 SW=>NW 6 Metal Low-E Double Yes 0,58 0.24 Y 15.5 ft' 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
5 NW=>NE 9 Metal Low-E Double Yes 0.65 0.21 Y 20.7 ft2 4 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
6 SW=>NW12 Metal Low-E Double Yes 0.65 0.21 Y 48.0 W 12 it 0 in 1 ft 0In Drapes/blinds Exterior 5
7 NE=>SE 13 Metal Low-E Double Yes 0.45 0.18 Y 7.5 W 10 it 0 in 1 it 0 in Drapes/blinds Exterior 5
8 NE=>SE 13 Metal Low-E Double Yes 0.62 0.22 Y 31.0 ft' 10 ft 0 in 1 It 0 in Drapes/blinds Exterior 5
9 SW=>NW16 Metal Low-E Double Yes 0.65 0.21 Y 48.0 ft' 12 It 0 in 1 ft 0 in Drapes/blinds Exterior 5
10 NW=>NE17 Metal Low-E Double Yes 0.58 0.24 Y 21.5 ft' 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
11 NE=>SE 20 Metal Low-E Double Yes 0.62 0.22 Y 4.0 ft' 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
12 NE=>SE 20 Metal Low-E Double Yes 0.62 0.22 Y 4.1 ft' 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
13 NE=>SE 23 Metal Low-E Double Yes 0.65 0.21 Y 48.0 ft' 15 ft 11 in 1 It 0 in Drapes/blinds Exterior 5
14 SW=>NW24 Metal Low-E Double Yes 0,58 0.24 Y 15.5 ft' 4 ft 0 in 1 It 0 in Drapes/blinds Exterior 5
15 NW=>NE25 Metal Low-E Double Yes 0.58 0.24 Y 15.5 ft' 6 ft 0 in 1 It 0 in Drapes/blinds Exterior 5
16 NE=>SE 27 Metal Low-E Double Yes 0.62 0.22 Y 4.0 fl' 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
17 NW=>NE28 Metal Low-E Double Yes 0.58 0.24 Y 7.4 ft' 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
GARAGE
# Floor Area Ceiling Area Exposed Wall Perimeter Avg Wall Height Exposed Wall Insulation
1 382.8 ft' 382.8 ft° 64 ft 8 ft 1
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .000307 1725 94.64 177.67 .0974 5
11/2/2021 11:44 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 7
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
HEATING SYSTEM
# System Type
Subtype
Speed Efficiency
Capacity
Block
Ducts
1 Electric Strip Heat/
None
COP:1
34.7 kBtu/hr
1
sys#1
COOLING SYSTEM
# System Type
Subtype
Subtype Efficiency
Capacity
Air Flow
SHR
Block
Ducts
1 Central Unit/
Split
Singl SEER: 16
42 kBtu/hr
1260 cfm
0.85
1
sys#1
HOT WATER SYSTEM
# System Type
SubType
Location
EF Cap
Use
SetPnt
Conservation
1 Electric
None
Garage
0.96 50 gal 62.3 gal
120 deg
None
SOLAR HOT WATER SYSTEM
FSEC
Collector
Storage
Cart # Company Name
System Model # Collector Model
# Area
Volume
FEF
None None
ft2
DUCTS
/ ---- Supply ----
---- Return ----
Air
CFM 25
CFM25
HVAC #
V # Location R-Value
Area
Location
Area Leakage Type
Handler
TOT
OUT QN
RLF
Heat Cool
1 Attic
6 854 ft2
Attic
854 ft2 Default Leakage
Attic
(Default)
(Default)
1 1
TEMPERATURES
Programablee
CEeij]ling Fans:Coo
Jan Feb
Heating [X] Jan [X] Feb
Hive
[X] Mar
fr j ]
May `Xi Jun EX] Jul
f j
[X] Aug
[X]
[ ]Sep
cl
Oct
[(Xj] Nov
Nov
Dec
[�Xj�
Mar
Apr
Jun 1 Jul
I 1 Aug
[ 1 Sep
[X]
[ ]DDec
ec
Venting [[ 11 Jan [[ 11 Feb
[IX1I
I ) t 1
Thermostat Schedule: HERS 2006 Reference
Hours
Schedule Type
1
2 3
4 5 6
7
8
9
10
11
12
Cooling (WD) AM
78
78 78
78 78 78
78
78
78
80
78
80
78
80
78
80
78
PM
80
80 78
78 78 78
78
Cooling (WEH) AM
78
78 78
78 78 78
78
78
78
78
78
78
78
78
78
78
PM
78
78 78
78 78 78
78
78
Heating (WD) AM
66
66 66
66 66 68
68
68
68
68
68
68
68
68
68
66
68
66
PM
68
68 68
68 68 68
Heating (WEH) AM
66
66 66
66 66 68
68
68
68
68
68
68
68
68
66
68
66
PM
68
68 68
68 68 68
68
MASS
Mass Type
Area
Thickness
Furniture Fraction
Space
Default(8 Ibs/sq.ft.
0 ft2
0 ft
0.3
Utility
Default(8 Ibs/sq.ft.
ft2
ft
0.3
Bed 2
Default(8 lbs/sq.ft.
ft2
ft
0.3
WIC 2
Default(B Ibs/sq.ft.
ft2
ft
0.3
Linen
Default(8 Ibs/sq.ft.
ft2
ft
0.3
Bed 3
Default(8 lbs/sq.ft.
ft2
ft
0.3
Cabana Bath
Default(8 lbs/sq.ft.
ft2
it
0.3
Hall
Default(8 lbs/sa.ft.
ft2
ft
0.3
Kitchen
11/2/2021 11:44 AM EnergyGauge®USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 6 of 7
FORM R405-2020
INPUT SUMMARY
CHECKLIST
REPORT
MASS
Mass Type
Area
Thickness
Furniture Fraction
Space
Default(8 Ibs/sq.ft.
ft2
ft
0.3
Great Room
Defaull(B Ibs/sq.ft.
ft2
ft
0.3
Dining Room
Default(8 Ibs/sq.ft.
W
ft
0.3
Master Bed
Default(8 lbs/sq.fl.
ft2
ft
0.3
Hers
Defaull(B lbs/sq.ft.
ft2
ft
0.3
His
Default(8 Ibs/sq.ft.
ft2
ft
0.3
Master Bath
Default(8 lbs/sq.ft.
ft2
ft
0.3
Foyer
Default(8 lbs/sq.ft.
ft2
ft
0.3
Nook
Default(8 lbs/sq.ft.
ft2
ft
0.3
WIC
rinfni IltIA Ihq/an ft
ft2
ft
0.3
wlr Clsl
11/2/2021 11:44 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7lh Edition (2020) Compliant Software Page 7 of 7
FORM R405-2020
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY (4 RD
ESTIMATED ENERGY PERFORMANCE INDEX* = 98
The lower the EnergyPerformance Index, the more efficient the home.
5507 Hickory Dr, Ft. Pierce, FL, 34982
1.
New construction or existing
New (From Plans)
10. Wall Type and Insulation
Insulation
Area
a. Concrete Block - Insul, Exterior
R=11.
2318.00 ft2
2.
Single family or multiple family
Detached
Adjacent
b. Frame -Wood, Adjacent
R=11.0
318.00 ft2
3.
Number of units, if multiple family
1
c. N/A
R=
ft2
d. N/A
R=
ft2
4.
Number of Bedrooms
3
11. Ceiling Type and insulation level
Insulation
Area
5.
Is this a worst case?
Yes
a. Under Attic (Vented)
R=30.0
2139.00 ft2
6.
Conditioned floor area ft)
2139
b. N/A
R=
ft2
c. N/A
R=
ft2
7.
Windows** Description
Area
12. Ducts, location & insulation level
R ft2
a. U-Factor: Dbl, U=0.65
164.67 ft2
a. Sup: Attic, Rat: Attic, AH: Attic
6 854
SHGC: SHGC=0.21
b. U-Factor: Dbl, U=0.58
119.04 ft2
SHGC: SHGC=0.24
13. Cooling systems
kBtu/hr
Efficiency
c. U-Factor: Dbl, U=0.62
43.11 ft2
a. Central Unit
42.0
SEER:16.00
SHGC: SHGC=0.22
d. U-Factor: other (see details)
7.50 ft2
14. Heating systems
kBtu/hr
Efficiency
SHGC: other (see details)
a. Electric Strip Heat
34.7
COP:1.00
Area Weighted Average Overhang Depth:
7.893 ft.
Area Weighted Average SHGC:
0.221
8. Skylights Description
Area
15. Hot water systems
Cap: 50 gallons
a. U-Factor(AVG): N/A
ft2
a. Electric
EF: 0.96
SHGC(AVG): N/A
b. Conservation features
9. Floor Types
Insulation
Area
None
a. Slab -On -Grade Edge Insulation
R=0.0
2139.50 ft2
Credits (Performance method)
Pstat
b. N/A
R=
ft2
c. N/A
R=
ft2
I certify that this home has complied with the Florida Energy Efficiency Code for Building
Construction through the above energy saving features which will be installed (or exceeded)
in this home before final inspection. Oth se, a new Display Card will be completed
based on installed Code compliant f re
Builder Signature: Date: (� I
Address of New Home: ToIr City/FL Zip: cr{ Zi1e(!E� Fl
34q$ 7
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code,
Energy Conservation, contact the Florida Building Commission's support staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
11/2/2021 11:44 AM EnergyGauge® USA 7.0.00-FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 7th Edition (2020)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
I ADDRESS: 5507 Hickory or Permit Number: I
Ft. Pierce , FL , 34982
MANDATORY REQUIREMENTS =See individual code sections for full details.
V SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory).The building official shall require that an energy performance level (EPL) display
card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law (Section
El
553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold
residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a
dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and
specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
SECTION R402 BUILDING THERMAL ENVELOPE
❑ R402A Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.
The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed In accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraff and flue dampers shall be closed, but not sealed beyond intended
infllralion control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
R402.4.2 Fireplaces. New wood -burning
fireplaces shall have
light -fitting Flue dampers
or doors, and outdoor combustion air. Where using
❑
tight -fitting doors on factory -built fireplaces
listed and labeled in
accordance with UL 127,
the doors shall be tested and listed for the
fireplace. Where using light -fitting doors on
masonry fireplaces,
the doors she be listed
and labeled in accordance with UL 907.
R402.4.3 Fenestration air leakage.
Windows, skylights and sliding glass doors shall have
an air infiltration rate of no more than 0.3 cfm
❑
per square fool (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square
foot (2.6
L/s/m2), when tested according to NFRC 400 or
AAMA/ WDIVI 101/I.S.2/A440
by an accredited, independent laboratory and
listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
11/2/2021 11:44 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
❑R402.4A Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open
combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a
room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table
R402.1.2, where the walls, Floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully
gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1.
Direct vent appliances
with both Intake and exhaust
pipes installed continuous to the outside.
2.
Fireplaces and stoves
complying with Section R402.4.2
and Section R1006 of the Florida Building Code, Residential.
❑R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between
conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than
2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be
sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
R403.1 Controls.
❑ R403.1A Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially as free" in
accordance with Section R403.3.3.
❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturers designation for an air leakage of no more than 2 percent of
the design airflow rate when tested in accordance with ASHRAE 193.
❑ 11403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system,
including the manufacturers air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise
sealed during the lest.
2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0A inch w.g. (25 Pa) across the entire
system, including the manufacturers air handler enclosure. Registers shall be taped or otherwise sealed during the test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section
R405 compliance where credit is taken for leakage, and a duct air leakage on to the outside of less than 0.080 (where Qn =
duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the
compliance report for the proposed design.
A written report of the results of the lest shall be signed by the party conducting the test and provided to the code official.
❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
❑R403A Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying Fluids above 105OF (41 °C) or
below 55OF (130C) shall be insulated to a minimum of R-3.
❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused
by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the
material. Adhesive tape shall not be permitted.
El installed,
Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are
installed, they shall be in accordance with Section R403.5.1.1. Heal trace temperature maintenance systems shall be in accordance with
Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be
❑ a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating
hot water system pumps shall start the pump based on the identification of a demand for hot water wn the occupancy. The controls shall
automatically turn off the pump when the water In the circulation loop is at the desired temperature and when there is no demand for hot water.
❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall
automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times
when heated water is used in the occupancy.
11/2/2021 11:44 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS = (Continued)
❑ R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heal traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3 % Inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
❑ R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature selling
range shall be from 100OF to 140OF (38°C to 60"C).
❑ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of
combustion types of service water -heating systems to be turned off.
❑ R403.5.6.2 Water heating equipment. Water -healing equipment installed in residential units shall meet the minimum efficiencies of Table
C404.2 In Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water healers shall meet the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in Installed solar
water -heating systems should meet the following criteria:
1. Be installed with a lilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system Is not operating.
❑ R403.6A Whole house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical ventilation
system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical
ventilation, the air handler shall be powered by an electronically commutated motor.
❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-191 space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment.
R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on
❑
the equipment loads calculated in accordance with ACCA Manual J or other approved healing and cooling calculation methodologies,
based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor
units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in
Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect
equipment sizing. System sizing calculations shall not Include loads created by local intermittent mechanical ventilation such as
standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating
equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed.
TABLE R403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFMNJATT)
AIRFLOW RATE MAXIMUM
(CFM)
HRV or ERV
Any
1.2 cfm/wall
Any
Range hoods
Any
2.8 cfm/wall
Any
In -line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1 1.4 cfm/watt
<90
Bathroom, utility room
90
2.8 cfm/watt Any
For SI: 1
cfm
= 28.3 L/min.
a.
When tested in
accordance with HVI Standard 916
11/2/2021 11:44
AM
EnergyGauge® USA
7.0.00
- FlaRes2020 FBC
7lh Edition (2020) Compliant Software
Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than
Elthe calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section
R403.7, or the closest available size provided by the manufacturers product lines. The corresponding latent capacity of the equipment shall
not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the Indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions: -
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by aFlorida-registered engineer, in attached single- and multiple -family units, the capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
R403.7.1.2.2 Electric resistance furnaces.
Electric resistance
furnaces shall be
sized within 4 kW of the
design
requirements
LJ calculated according to the procedure selected
in Section R403.7.1.
R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or healing within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections C403
and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403.
❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50OF (100% and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40OF (4.80C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall
be in accordance with Sections R403.10.1 through R403.10.5.
R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of
such switch shall not change the setting of the healer thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
11/2/2021 11:44 AM EnergyGauge®USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 5
�-1 R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
L1 the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heal pump or solar energy source, covers or other vapor -retardant means shall not be required.
❑ R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
efficiency of 82 percent for healers manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with
AHRI 1160, Table 2, Standard Rating Conditions -Low AirTemperature, A test report from an independent laboratory is required to
verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements:
1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house
is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day.
2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air.
3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2.
4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential.
R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13,
conform to the following requirements:
1. If a ducted dehumidifier Is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft
damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct.
2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system,
a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct.
3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the
central cooling evaporator coil.
4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an
efficacy of at least 45 lumen -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt.
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
11/2/2021 11:44 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 5
2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: 5507 Hickory Dr PSL Prop Builder Name: PSL Prop
Street: 5507 Hickory Dr Permit Office:
City, State, Zip: Ft. Pierce , FL , 34982 Permit Number:
U
Owner: Allen Residence Jurisdiction: St. Lucie
w
x
Design Location: FL, ST_LUCIE_CO_INTL
O
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
requirements
Breaks or joints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with the
The insulation in any dropped ceiling/soffit
Ceiling/attic
insulation and any gaps in the air barrier shall be sealed.
shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
Walls
The junction of the top plate and the top of exterior walls shall be
shall be Insulated by completely filling the cavity with
sealed.
a material having a thermal resistance of R-3 per
Knee walls shall be sealed.
inch minimum.
Exterior thermal envelope insulation for framed walls
shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/door jambs and framing, and
skylights and framing shall be sealed.
and doors
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
(including
insulation.
maintain permanent contact with the underside of
above -garage
subfloor decking, or floor framing cavity insulation
and cantilevered
shall be permitted to be in contact with the top side
floors)
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace wall
.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
cavities shall be filled by Insulation that on
Narrow cavities
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac
Is.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the finished surface.
thermal envelope shall be air tight and IC rated.
Batt insulation shall be cut neatly to fit around wiring
Plumbing and wiring
and plumbing in exterior walls, or Insulation that on
installation readily conforms to available space shall
extend hind DIDIna and wirin .
Shower/tub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the showers and tubs.
be Insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub -floor, wall covering or
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sealed in a manner that is recommended by the manufacturer.
sprinklers
Caulking or other adhesive sealants shall not be used to fill voids
between fire sprinkler cgver aisles and walls or c " s.
2. In addition,
inspection
of log
walls
email
be In accomance
wnn
nie piuwsivns vi iw-+oo.
11/2/2021 11:44
AM
EnergyGauge®USA 7.0.00 - FlaRes2020 FBC 7th Edition
(2020)
Compliant
Software
Page 1
of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction: St. Lucie
Permit #:
Job Information
Builder: PSL Prop Community: Lot: NA
Address: 5507 Hickory Dr
City: Ft. Pierce State: FL Zip: 34982
Air Leakage Test Results Passing results must meet either the Performance, Prescriptive, or ERI Method
PRESCRIPTIVE METHOD -The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air
changes per hour at a pressure of 0.2 inch w.g. (50 Pascals) in Climate Zones 1 and 2.
F
Q PERFORMANCE or ERI METHOD -The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding
the selected ACH(50) value, as shown on Form R405-2020 (Performance) or R406-2020 (ERI), section labeled as infiltration, sub -section ACH50.
ACH(50) specified on Form R405-2020-Energy Calc (Performance) or R406-2020 (ERI): 5.000
x 60 = 20700 — Method for calculating building volume:
CFM(50) Building Volume ACH(50) O Retrieved from architectural plans
PASS • Code software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals).
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or Individuals licensed as set forth in Section
489.105(3)(f), (g), or (I) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to Precede official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and Flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
11/2/2021 11:44:26 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1