HomeMy WebLinkAbout3419 Trinity Lot 86 blower door and duct blast.pdfDuct Leakage Test Report
Prescriptive or Performance Method
Permit #
Job Information
Builder: DR HORTON
Community: CREEKSIDE Lot: 86
Address: 3419 TRINITY CIRCLE
Unit:
City: FORT PIERCE
State: FL Zip: 34945
Duct Leakage Test Results
Presciptive Method 0 Performance Method
System 1
System 2
System 3
Sum of any additional
systems
cfm25 &Prescriptive Method cfm25 (total)
To qualify as "substantially leak free" Qn must be less than or equal to 0,04
cfm25 if air handler unit is installed, If air handler unit is not installed, Qn Total
must be less than or equal to 0.03. This testing method meets the
cfm25 reauirements in accordance with Section R403.2.2
(Total of all systems
I cfm25
54
1916 = 0.02 Qn
Total of all systems
Total Conditioned
j
Square Footage
F�/
PASS
El
FAIL
Performance Method cfm25 (Out or Total)
qualify as "substantially leak free" Qn must not be greater than the
)posed duct leakage Qn specified on Form R405-2014
Leakage Type selected Qn specified on Form
on Form R405-2014 R405-2014 (Energy. Cold
(Energy Calcl
Testing Company
Company Name: SUN SEAL LLC Phone: 321-412-0035
1 hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected
compliance path as stated above, either the Prescriptive Method or Performance Method.
Date of Test: 03101 /2022
Signature of Tester:
Printed Name of Tester: DANIEL MURPHY
License/Certification # 5066440 Issuing Authority BPI
Envelope Leakage Test Report
(Blower Door Test)
R405.4.2.1 Compliance
Permit #
Job Information
Builder: DR HORTON Community
CREEKSIDE Lot: 86
Address: 3419 TRINITY CIRCLE
unit:
City: FORT PIERCE
State: FL Zip: 34945
Air Leakage Test Results Possing results must be 7ACH(50) or less
1520 x 60 _ 16477.6 . 5.5
Method for calculating building volume:
CFM(50) Building Volume ACH(50)
0 Retrieved from architectural plans
(RrCode software calculated
vPASS El
FAI L
Field measured and calculated
When ACH(50) is less than 3, Mechanical Ventilation installation must be verified by building department.
Certification of Test Results
R402.4.i.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes
per hour in Climate Zones 1 and 2, 3 air changes per hour in Climate Zones 3 through 8. Testing shall be conducted with a blower door at a
pressure of 0.2 inches w.g. (50 Pascals). Testing shall be conducted by wither individuals as defined in Section 553.993(5) or (7), F.S. or
individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test
shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of
an peneiravons OF ine Kwiming inermat envelope,
Testing Company
Company Name: SUN SEAL LLC Phone: 321-412-0035
I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected
compliance path as stated above, either the Prescriptive Method or Performance Method.
Date of Test: 03/01 /2022
Signature of Tester.
Printed Name of Tester: DANIEL MURPHY
License/Certification # 5066440 Issuing Authority BPI