HomeMy WebLinkAbout3412 Trinity Lot 31 blower door and duct blast.pdfInformation
Builder: DR HORTON
Address: 3412 TRINITY
City: FORT PIERCE
Butt Leakage Test Results
System 1
System 2
System 3
Sum of any additional
systems
Total of all systems
Duct Leakage Test Report
Prescriptive or Performance Method
Permit #
nmunity: CREEKSIDE Lot: 31
Unit:
State: FL Zip: 34945
Live Method 0 Performance Method
cfm25 & rescriptive Method cfm25 (total)
To qualify as "substantially leak free" Qn must be less than or equal to 0.04
cfm25 if air handier unit is installed. If air handier unit is not installed, Qn Total
must be less than or equal to 0.03. This testing method meets the
cfm25 requirements in accordance with Section R403.2.2
4_ 4 - 1$28 = 0.02 Qn
Total of all systems Total Conditioned
Square Footage
��j✓'� PASS 11FAIL
Testing Company
Performance Method cfm25 (put or Total)
qualify as "substantially leak free" Qn must not be greater than the
iposed duct leakage Qn specified on Form R405-2014
Leakage Type selected
on Form R405-2014
(Energy Calc)
Qn specified on Form
R405-2014 (Energy Colc)
Company Name: SUN SEAL LLC Phone: 321-412-0035
1 hereby verify that the above duct leakage testing results are iY accordance with the Florida Building Code requirements with the selected
compliance path as stated above, either the Prescriptive MetHod or Performance Method.
Date of Test: 03/01 /2022
Signature of Tester:
r
Printed Name of Tester: DANIEL MURPHY
License/Certification #t 5066440 issuing Authority BPI
Job Information
Builder: DR HORTON
Address: 3412 TR1N
City: FORT PIERCI
Envelope Leakage Test Report
(Blower Door Test)
R405.4.2.1 Compliance
Community:
Permit #
Unit:
State: FL
[Air Leakage Test Results Passing results must be 7ACHj5QJ or less
975 x 60 = 14381.6 = 4.0
CFM(50) Building Volume ACH(50)
Zj PASS FAIL
Lot:
Method for calculating building volume-
0 Retrieved from architectural plans
lode software calculated
Q Field measured and calculated
When ACH(SO) is less than 3, Mechanical Ventilation installation must be verified by building department.
(Certification of Test Results
K4UZ.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes
per hour in Climate Zones 1 and 2, 3 air changes per hour in Climate Zones 3 through 8. Testing shall be conducted with a blower door at a
pressure of 0.2 inches w.g. (50 Pascals). Testing shall be conducted by wither individuals as defined in Section 553.993(5) or (7), F.S. or
individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test
shall be signed by the party conducting the test and provided to the code official. Testing shall be nerfarmPd at anv tr,„Q eft——ml;.,., f
Testing Company
Company Name: SUN SEAL LLC Phone: 321-412-0035
I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected
compliance path as stated above, either the Prescriptive Method or Performance Method.
Date of Test: 03/01 /2022
signature of Tester:'L_
Printed Name of Tester: DANIEL MURPHY
License/Certification # S066440 Issuing Authority