HomeMy WebLinkAboutWind Speed & Exposurev. �' CONTRACTOR: The Porch Factory ' 1,C. DESIGN CRITERIA: Applicable Codes, Regulations, and Standards 1. The 5th Edition (2014) Florida Building Code, specifically Chapter 16 Structural Design, Chapter 20 Aluminum, and Chapter 23 Wood. 2. AA ASM 35 and Specifications for Aluminum Structures, Part 1-A of the Aluminum Design Manual prepared by The Aluminum Association, Inc. Washington, D.C., 2010 Edition and the Guide to Aluminum Construction in high wind areas, 2010. 3. ASCE 7-10. Wind Loads 1. Building Occupancy Category, Paragraph 1604.5 and Table 1604.5: Risk Category 1. 2. Basic Wind Speed, Figure 1609C, State of Florida Debris Region & Basic Wind Speed, Paragraph 1609.3.1 and Table 1609.3.1 Equivalent Basic Wind Speed: VULT =150 MPH, Vnsn =116 MPH 3. Exposure Category, Paragraph 1609.4.3: C 4. Screen Roof Enclosure Table 2002.4 Foundation Design Existing concrete. No additional concrete footing or slab is required to resist the loads'imposed by the proposed construction if the existing slab is .1minimum 4" thick with an 8" x 8" thickened slab edge and in sound condition free from structural cracking spalling, or other deterioration. Specifications The following specifications are applicable to this project: 1. Where concrete specifications are required, whether in the screen enclosure scope or not, by one or more regulatory agency, the following specifications are applicable: a. Concrete shall conform to ASTM C94 for the following components: i. Portland Cement Type 1,- ASTM C 150 ii. Aggregates - Large Aggregate 3/4" max - ASTM C 33 iii. Air entraining +/-1%- ASTM C 260 iv.Water reducing agent - ASTM C 494 v. Clean Potable water vi. Other admixtures not permitted b. Metal accessories shall conform to: i. Reinforcing Bars - ASTM A615, grade 60 ii. Welded wire fabric -ASTM Al85 c. Concrete slump at discharge chute not less than 3" or more than 5". Water added after batching is not permitted. d. Prepare and place concrete per American Concrete Institute Manual of Standard Practice, Parts 1, 2, and 3 including hot weather recommendations. e. Moist cure or polyethylene curing permitted. f. Prior to placing concrete, treat the entire subsurface area for termites in compliance with the FBC. g. Concrete shall be placed over a polyethylene vapor barrier. h. All aluminum components embedded within concrete shall be coated with a bituminous paint or epoxy. 2. Aluminum extrusions shall be 6005 T5 Alloy 3. Fasteners are required to be corrosion resistant, minimum SAE Grade 2 or better zinc plated to ASTM B633, or coated stainless steel series "300", or uncoated stainless steel series "400". 4. All Self Mating Beam Sections are to be stitched with either #14 screws 6" from ends and 24" center to center or # 12 screws 6" from ends and 12" center to center. 5. All Porch Factory Beam Sections are to be stitched with #12 screws, 6" from ends and 12" center to center. 6. Screened enclosures containing swimming pools shall comply with the applicable requirements of FBC R4501.17 Residential Swimming Barrier requirements. 7. Screen material shall be 18/14 screen. unless approved by Suncoast Aluminum Engineering, LLC. 8. Door location shall be determined by contractor in the field.- 9. When installing pavers -over concrete slab or footing which are supporting aluminum members, such as continuous screen tracks or upright, the pavers must be bonded to the concrete with an epoxy, thinset, or 3,000 PSI grout to ensure full positive contact with concrete. 10. All flashing and waterproofing shall be provided by the contractor. 11. Use of these plans acknowledges and accepts a limit of liability not to exceed design and engineering fee. Roof Type Roof Type: MANSARD / HIPPED GABLE WIND SPEED A' "XPOSURE HAVE BEEN DETERMe_ a) USING THE ADVANCED TECHNOLOGY COUNCIL'S WEBSITE AND GOOGLE EARTH. LF1 #--11'-o' --L C ST LUCK COU\TY BLZ DIM DII, TSPIN; R-EVIEWED FOn?=*5d_V DAvIE'�i'ED � I➢ATE PLANS AND PERMIT MUST BE KEPT 3N JOB OR NO INSPECTION WILL BE MADE. 1X2(TYP) X2X2fO 2X2 2X2 2X2 2X2 2X2 2X2 I A-2 - In q(L nT N ao 2X2(TYP) 6 2X2 2X2 2X2 2X2 2X2 n� n� nT In rt I W X lid W W X O N A-2 n I 2X2 2X2 2X2 2X2 2X2 P2X2(TYP) A-3 32'-0' A-3 ------------------------ ' 1X2(TYP) Fv P E!, r% a a. a 6 N 1 'dIL � m tG W N 2X3 2X3 2X3 2X3 2X3 L,_ 0 ii '4 A-3 1 ( ) [QP A-2 6'-5' 6'-5' 6" 5' ��►►Itlli�iii M 'T. - Gj o I O O • 0 N�•.> z n �0 = �C -11'-0'--I ---11'-o' -L G Z ... J Q F '- zn G m N r„ a 8 8 Q W W TT C)W, mm U tip ¢ iV iV Z N W �urW-� THESE I.LANS AND ALL PROPOSED WORK TO ANY CORRECTIONS N AR . Stil3dECT REQUIRED 9Y FIELD INSPECTORS THAT 0 MAY Dfn NECESSARY IN ORDER TO A" APPILiCASl6 C0®E8. Q W CI CAMPY %VITH Z CO LU a r, LU ~ IY N= m Lo N 1 G) Co n M CD I lX2(T W) PONCE�;L►:u FA S T =rJEFS OR AT Tr�CHMENTS DRAWN BY ARE TaE RESPONSIBILITY OF THE TP CONTRACTOR OF RECORD DATE DRAW L 6'—,C 641 09/21/17 File,,rl REVISION SHEET NO. A-1 ALUMINUM MEMBERS DIMENSIC i HOLLOW SECTIONS 2x2: 2"x2"x0.046' 2 x 3: 2" x 3" x 0.050" 2x4: 2"x4"x0.050" 2 x 5: 2" x 5" x 0.050" OPEN BACK SECTIONS 1x2: 1"x2"x0.040" 1x3: 1"x3"x0.045" SNAP SECTIONS 2 x 2 Snap: 2" x 2" x 0.045" 2 x 3 Snap: 2" x 3" x 0.050" 2 x 4 Snap: 2" x 4" x 0.045" SELF MATING (SMB) 2x4SMB: 2" x 4" x 0.044" x 0. 100" 2 x 5 SMB: 2" x 5" x 0.050" x 0.100" 2 x 6 SMB: 2" x 6" x 0.050" x 0.120" 2x7SMB: 2"xT'x0.057'x0.120" 2 x 8 SMB: 2" x 8" x 0.072" x 0.124" 2x9SMB: 2"x9"x0.072"x0.IX' 2 x 10 SMB: 2" x 10" x 0.092" x 0.398" MINIMUM FASTENER EDGE DISTANCE: 1/2" NIINDAUM FASTENER SPACING: 3/4" CONCRETE SCREW ANCHOR SIMPSON TITEN HD OR EQUIVALENT SHEET METAL SCREWS (SMS): ITW / BUILDEX OR EQUIVALENT PFB: PORCH FACTORY BEAM MEMBER SIZE EDGE "C" 2X4SMB i2" 2X5SMB V 2X6-2X10SMB 1y" MEMBER SIZE EDGE "C" 3.75 PFB Y" 5.75 PFB 1 X. 6.75 PFB 1 Y" EAVE RAIL (SEE A-1 FOR SIZE) INTERNALLY SCREW THRU BEAM W/ (3) #10 x 1 1 W SMS V x FASTEN TO EAVE RAIL W/ #10 x 1 12" SMS 6" FROM UPRIGHT & 24' O.C. (1) 1/2" DIA. x 212" THRU BOLT W/ NYLOCK JAM NUT - IN LIEU OF NYLOCK JAM NUT, JAM NUT W/THREADLOCKER MAY BE USED INSTALLATION REQUIREMENTS: BOLT IS TO BE INSTALLED AS TO NOT DAMAGE BASE MATERIAL DO NO OVER TIGHTEN. BEAM NOTCHED OVER UPRIGHT (SEE A-1 FOR SIZE) 1.. I MIN. i I UPRIGHT (SEE A-1 FOR SIZE) I ' PATENT PENDING UPRIGHT TO BEAM CONNECTION A-2 SCALE: NTS 1 /8" x 2" x 7EXTRUDED ANGLE 5052 H-32 ALLOY EA SIDE ,A . 11W MIN CONC 2114• MIN CONC a ANCHOR EMBEDIVID .ANCHOR EMBEDMENT 2' �e. s • s MW c SLAB / FOOTING ej' . '.4 : ®a•: SEE PLAN SIDE VIEW (1) 3/8" DIA. CONCRETE SCREWANCHORS-II11!11 (21/4" CONC. EMBED) "x 7' O:B. BASE PLATE-TYP 5d MIN EDGE DISTANCE FROM EXTERIOR OF COLUMN TO OUTSIDE EDGE OF SLAB (1)12" DIA. THRU BOLT w/ NYLOCK JAM NUT - IN LIEU OF NYLOCK JAM NUT, JAM NUTw/THREADLOCKER MAY BE USED TIGHTEN TO CONTACT -DO NOT OVERTIGHTEN d ae �•' ° �• . < V x 2" BASE PLATE ANCHORED TO e. s . • CONC W/ 1M' CONCRETE SCREW ANCHOR (MIN. 1 1/4" EMBED) SLAB / FOOTING "' R W MAX EACH SIDE OF POSTAND SEE PLAN sa . , nt ;, 24" O.C. MAX FRONT VIEW B UPRIGHT TO CONCRETE DETAIL A-2 SCALE: NTS 2•' x PURLINS ATTACHED TO BEAM w/MIN (4) #10 x 1 12" SMS PLACE WASHER UNDER SCREW IN GUSSET CORNER 3116" 5052-H32 1 1/4" NOTE: SEE CALL -OUT BELOW FOR# OF SCREWS. SCREWS SHOWN FOR ILLUSTRATIVE PURPOSES ONLY. DO NOT COUNT SCREWS ON DRAWING. #14 SMS @ 1 1/4" O.C. r(16 TOTAL) NOTES: 1. GUSSET DIMENSIONS ARE MINIMUM (2) REQ'D -(1) EA SIDE OFBEAM-MAYBE _ INTERNAL OR EXTERNAL 2. AS BEAM SIZE CHANGES, ADD OR SUBTRACT SCREWS TO MAINTAIN 1 1/4" C/C SPACING. 3. GUSSET LENGTHS REMAIN CONSTANT, WIDTHS CHANGE TO MATCH BEAM SIZE. NTS DETAIL - 21/7' x 1/8" x (GIRT OR PURLIN WIDTH + 1l2" x BEAM DEPTH OR UPRIGHT DEPTH -1/2) ALUM BACKING PLATE 6063-T6 ALUMNINUM CHAIR RAIL MEMBER Al x 1 1/2" SMS INTO /BEAM ' C PURLIN OR GIRT TO BEAM OR POST DETAIL A-2 SCALE: NTS 2"x7' V x 7' x 0.044" OPEN BACK FASTEN TO EAVE RAIL W/ #10 x 1 12" SMS SPACED 3" FROM UPRIGHT & @ 24" O.C. x PURLIN 2"x7'x118"x3"LONGALUM ANGLE EACH SIDE UP UPRIGHT W/ (2) #12 x 3/4" SMS INTO PURLIN (2) #12 x 3/4" SMS INTO 7' x 7' (2) #12 x 314" SMS INTO UPRIGHT (2) #12 x 314" SMS INTO 1" x 7' F SLOPED PURLIN-CONNECTION DETAIL A-2 SCALE: NTS ui OLu j �a-- d mo WLL m LL z ac 0m am LILIw �� HD Z aW Z Lu W rn W z G z V W U O U z LLJ N tJi H LL 2 I! z u J tW- J N i Q (D00 Zoo a _ F- znom $ I W � " 04 64 O 7� 2 Q N N � z (L7 z mug i o 61J m W Q r 1 U N N LLI W Z W co 8-(� mmw W O w a Lo O m rn o (ID OJOLL d �M40 DRAWN BY TP DATE DRAWN 09/21 /17 REVISION SHEET NO: A-2 y 6" WIDE x 0.125"'T' BRACKET 3/16" S.S. CABLE \\\��� T p�� ���� %1/ @ EACH BEAM ATTACHED TO NOTE: (2) 3/8" DIA x 4" LAG SCREWS FOR x 6" x 1 GALV. Wl (2) 3EEL CLIP W/ (2) 3/8 DIA STEEL �� ! ` �/ , •' • • • • • • �� �� FASCIA W/ 3/8" x 3" LAGS (3 SPANS GREATER THAN 30'-0' x 2 3/4" EMBEDMENT ` .• 2 i PER BRACKET) AND (1) 36' x 3" CONCRETE SCREW • LAG @ 24" O.C. AT GUTTER (1) 3/8" DIA. x 4" LAG ANCHOR Q: 11 SCREW INTO EXISTING l p J 1" x 7' x 0.044" OPEN BACK OVERHANG FRAMING _— �- W EE. Q �C W/. (2) #10 x 21l2" SMS THRU OR RAFTER TAIL DBL COMPRESSION ; ! BEAM INTO SCREW BOSSES SLEEVES <• . — (1) #10 x 1 1/7' SMS 9' FROM BEAM AND 24" O.C. a 'a ' rA V ` •� a % O . •'Pq \� PRCSd f PEAL \ SLAB / FOOTING MATING SEE PLAN i ELEMENT • • 3/16" S.S. CABLE Q • • CONTRACTOR TO VERIFY 1 1/4" x 5 5/8" x 1/9' O Ld • 2" x 4" FASCIA - IF LESS ALUM FLAT BAR U ui a ` THAN 2" x 4" FASCIA 7 x 4" r 6063-T6 ALUMINUM Lu CL 1/8"x7'x7'x7'ALUM • •• SUB FASCIA SHALL BE a w $+ ANGLE W/ (4) #14 x 3/4" 5" SUPER PLACED OVER, LENGTHEN LL (7 SMS EACH FLANGE GUTTER LAG SCREWS TO FULLY SLAB/FOOTER `� i id EACH SIDE OF BEAM PENETRATE SUB FASCIA a m MID DEPTH CC w O cm co 1 IF OTHER FASCIA, ADD 7' x e Lu H D 4" PT FASCIA w/ 10 LAG s • ' " ° m BOLTS -1 112" INTO TRUSS °a "". z Z Q w 2118" x 1 1/8" x .062" (MIN.) TAILS -COUNTERSINK FLUSH. WHEN INSTALLING a ° w z >LLJ u C) u_ ALUM RECEIVING CHANNEL 1/2" LAG SCREWS, x z I— _ W/ MIN. (2) #12 x 3/4"SMS PRE -DRILL w/ 3/8"DRILLTO Lu LL ~ LL PREVENT SPLITTING. (1) 3/8" DIA. x 3" EMBED SLAB / FOOTING CONCRETE SCREW ANCHOR SEE PLAN Z_ ... 0 G GUTTER BRACE & MATING ELEMENT ATTACHMENT DETAIL H-1 CABLE CONNECTIONS AT FOUNDATION _j c A-3 SCALE: NTS A_3 SCALE: NTS a z_ o o E- Z�am s (11 � I-umgg H a LL, LLI z '?' O 7�^^ GUSSET PLATE SELF MATING z V PER ESERIES BEAM J z 0 In W u� W 4" PURLIN MAX (9) #14 x 3/4 SMS 1/8" PLATE ON 45• ANGLE l WOOD: CONTRACTOR TO INSTALL 6063-T6 ALUMINUM i #10 x 3" WOOD SCREWS, 6" (2) #14 x 2" SMS THRU BRACE (n FROM GIRT & @ 17' O.C. INTO BEAM THRU GUSSET i i W CONC: PLATE — LU 114" DIA. x 3" CONCRETE • • • • / LU SCREW ANCHOR, 6" 24" O.C. DETAIL #2 • / - z Q U FROM GIRT & @ — — — — — / (n a W (4) #10 x 1 1/2" INTO • W O SCREW BOSS IZ L0 LLJ EYE BOLT FOR CABLE TENSION =O mH� Mcco-1U-lJi Hx2" 11/2 CONTRACTOR SHALL RUN DRAWN BY X W HOLLOW k4' 1/4" THRU BOLT TO ATTACH W/ NYLON WASHER $PERIMETER 3 FRAMING TP DATE DRAWN SECTION GIRT STAINLESS STEEL NUT 09/21/17 Li REVISION 1 117 x 5" x 1/8" 5052-H32 PLATE 4) #12 EA MEMBER f'� _ ® DETAIL#1 �.• ,. a - SHEET NO: C-� 1X2 TO HOST STRUCTURE DETAIL H_3 ROOF BRACING CONNECTION DETAIL H-2 CABLE CONNECTION AT CORNER A-3 S°ALE: NITS A-3 SCALE: NTS /� -3 SCALE: NTS LA-3_ I i o 2y l tw- N�•• z° 5 ��•�. 'co // I I PROFES�IONALSEAL ❑ IS C` fY Ov Ld U ,. ai d W d z CD�m LL (� Z g z OLL �Wm QWm z Lu LL W z Z W (A z z W W z WL cW� cQc C z O u Q z W tALL HLL a G z • .� V o J W J J z FWZ o pom Q W 1" x.2" O.B. FASTENED TO CORNER Q W cm m POST W/ #12 x 1 1/2" SMS AT TFROM ( ( I TOP & BOTTOM RAILS. TYPICALLY @ z C7 3 �G p 1/8" x 2" x 2" EXTRUDED (4) #14 X 3/4"SMS /INTO 3 I 24" O.C. 1 z m q� oc e e DJ ANGLE 5052 H32 ALLOY / i 1/8" x 2" x 2" EXTRUDED ANGLE 5052 I r i In W N e e I CORNER POST ! H-32 ALLOY EA CORNER W/ (2) #14 x 2" SMS INTO POST & (1) 3/8" DIA. I I CONCRETE SCREW ANCHOR INTO 6" CONCRETE ,(2)#10X11/T'SMSCONC ° LN-H THRUSCREWBOSSESBEDMENTSLAB N / FOOTING a' ..21/ CONC SEE PLANANCHOR EMBEDMENT < a . •. ° SLAB / FOOTING v N W < • SEE PLAN ai • . ,' Q 0 SIDE VIEW W Z SIDE VIEW W Q cn a U �2"--} CORNER POST W/ 1"x2" @ I W ~ Ix LU (4) #14 x 3/4"SMS BACKSIDE LL,Q W �O a to (1) 3/8" DIA CONCRETE 1 INTO POST 0 = m N v 0 SCREW ANCHORS 2" x 7' DJ 3/8" x LENGTH AS REQUIRED O CD (21/4" CONC. EMBED) ; FOR 21/4" EMBED CONCRETE _ cO Q Q J d M J Q "LL LL SCREWANCHOR INTO I j CONCRETE DRAWN BY — - _ 1"x 2" BnsE PLATE 1 -• ANCHORED TO CONC W/ 1/4" .., •• : °` TP CONCRETE SCREW ANCHOR DATE DRAWN (MIN.11/4"EMBED) ® +� 1"x 7' BASE PLATE ' 6" MAX EACH SIDE OF POST a v • , ` MAX"/21 24D.C.o.c. M /17 e a ANCHORED TO CONC W/ 1/4" �• e ' AND {I - CONCRETE SCREW ANCHOR e d , a o. °f o REVISION 1 Q (MIN. 1 1/4" EMBED) l ° ° •1• : , s • c. W MAX EACH SIDE OF POST' • .., • ; �. , ° v AND 24" O.C. MAX 6" FRONT VIEW FRONT VIEW SHEEP NO: DJ-1 DOOR JAMB TO CONCRETE DETAIL CP-1 CORNER POST TO CONCRETE DETAIL A4 SCALE: NTS /i-4 SCALE: NTS A-4