HomeMy WebLinkAboutEvaluation ReportDIVISION: 08 00 00—OPENINGS SECTION: 08 95 43—VENTS/FOUNDATION FLOOD VENTS i REPORT HOLDER: SMARTVENT PRODUCTS, INC. 430 ANDBRO DRIVE, UNIT 1 PITMAN, NEW JERSEY 08671 EVALUATION SUBJECT: r SMART VENT® AUTOMATIC FOUNDATION FLOOD VENTS: MODELS #1540-520; #1540-521; #1540-510; #1540-511; #1540-570; #1540-574; #1540-524; #1540-514 ICC ICC ICC C� PMG LISTED Look for the trusted marks of Conformity! "2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPQ Award in Excellence" ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, exprms or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved. % a*& MR.— A Subsidiaryof �s�`cO ICC-ES Evaluation Report ESR-2074 Reissued February 2015 Revised May 2016 This report is subject to renewal February 2097. wwwJcc-es.ora 1 (800) 423-6687 1 (562) 699-0543 A Subsidiary of the International Code Council® DIVISION: 08 00 00—OPENINGS Section: 08 9643—Vents/Foundation Flood Vents REPORT HOLDER: SMARTVENT PRODUCTS, INC 430 ANDBRO DRIVE, UNIT 1 PITMAN, NEW JERSEY 08071 (877) 441-8368 www.smartvent.com info martvent.com EVALUATION SUBJECT: SMART VENT® AUTOMATIC FOUNDATION FLOOD VENTS: MODELS #1540-520; #1540-521; #1540-510; #1540-511; #1540.570; #1540-574; #1540-524; #1640-514 1.0 EVALUATION SCOPE Compliance with the following codes: ■ 2015, 2012, 2009 and 2006 International Building Code® (IBC) ■ 2015, 2012, 2009 and 2006 International Residential Code® (IRC) ■ 2013 Abu Dhabi Intemational Building Code (ADIBC)t tThe ADIBC is based on the 2009 IBC. 2009 IBC code sections referenced in this report are the same sections in the ADIBC. Properties evaluated: ■ Physical operation ■ Water flow 2.0 USES The Smart Vent® units are engineered mechanically operated flood vents (FVs) employed. to equalize hydrostatic pressure on walls of enclosures subject to rising or falling flood waters. Certain models also allow natural ventilation. 3.0 DESCRIPTION 3.1 General: When subjected to rising water, the Smart Vent® FVs internal floats are activated, then pivot open to allow flow in either direction to equalize water level and hydrostatic pressure from one side of the foundation to the other. The FV pivoting door is normally held. in the closed position by a buoyant release device. When subjected to rising water, the buoyant release device causes the unit to unlatch, allowing the door to rotate out of the way and allow flow. The water level stabilizes, equalizing the lateral forces. Each unit is fabricated from stainless steel. Smart Vent® Automatic Foundation Flood Vents are available in various models and sizes as described in Table 1. The Smar1VENT® Stacking Model #1540-511 and FloodVENT® Stacking Model #1540-521 . units each contain two vertically arranged openings per unit. 3.2 Engineered Opening: The FVs comply with the design principle noted in Section 2.7.2.2 and Section 2.7.3 of ASCE/SEI 24-14 [Section 2.6.2.2 of ASCE/SEI 24-05 (2012, 2009, 2006 IBC and IRC)] for a maximum rate of rise and fall of 5.0 feet per hour (0.423 mm/s). In order to comply with the engineered opening requirement of ASCE/SEI 24, Smart Vent FVs must be installed in accordance with Section 4.0. 3.3 Ventilation: The SmartVENT® Model #1540-510 and SmartVENr Overhead Door Model #1540-514 both have screen covers with 1/4-inch-by-1/4-inch (6.35 by 6.35 mm) openings, yielding 51 square inches (32 903 mm2) of net free area to supply natural ventilation. The SmartVENr Stacking Model #1540-511 consists of two Model #1540-510 units in one assembly., and provides 102 square inches (65 806 mm2) of net free area to supply natural ventilation. Other FVs recognized in this report do not offer natural ventilation. 4.0 DESIGN AND INSTALLATION SmartVENr and FloodVENT® are designed to be installed into walls. or overhead doors of existing or new construction from the exterior side. Installation of the vents must be in accordance with the manufacturer's instructions, the applicable code and this report. Installation Gips allow mounting in masonry and concrete walls of any thickness. In order to comply with the engineered opening design principle noted in Section 2.7.2.2 and 2.7.3 of ASCE/SEI 24-14 [Section 2.6.2.2 of ASCE/SEI 24-05 (2012, 2009, 2006 IBC and IRC)], the Smart Vent® FVs must be installed as follows: ■ With a minimum of two openings on different sides of each enclosed area. ■ With a minimum of one 'FV for every 200 square feet (18.6 m) of enclosed area, except that the SmartVENT® Stacking Model #1540-511 and FloodVENT® Stacking Model #1540-521 must be installed with a minimum of one FV for every 400 square feet (37.2 m) of enclosed area. lCC-liS Liva/uauon Reports arc not to he construed as representing aesthetics or any other attributes not specifically addressed nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by !CC Evaluation Service, U.C. express or implied, as to airy finding or other matter in this report, or as to any product covered by the report. , mrnmmc �� Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 3 ESR-2074 I Most Widely Accepted and 'i , - _illd Page 2 of 3 ■ Below the base flood elevation. ■ With the bottom of the FV located a maximum of 12 inches (305.4 mm) above the higher of the final grade or floor and finished exterior grade immediately under each opening. 5.0 CONDITIONS OF USE The Smart Vent® FVs described in this report comply with, or are suitable alternatives to what is specified in, those codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 The Smart Vent® FVs must be installed in accordance with this report, the applicable code and the manufacturer's installation instrucfions. In the event of a conflict, the instructions in this report govern. 5.2 The Smart Vent® FVs must not be used in the place of "breakaway walls" in coastal high hazard areas, but are permitted for use in conjunction with breakaway walls in other areas. 6.0 EVIDENCE SUBMITTED Data in accordance with the ICC-ES Acceptance Criteria for Mechanically Operated Flood Vents (AC364), dated August 2015. 7.0 IDENTIFICATION The Smart VENT models recognized in this report must be identified by a label bearing the manufacturer's name (Smartvent Products, Inc.), the model number, and the evaluation report number (ESR-2074). TABLE 1—MODEL SIZES MODEL NAME MODEL NUMBER MODEL SIZE (in.) COVERAGE (sq. fL) FloodVEN 1540-520 15 /4' X 73/4" 200 SmartVENT 1540-510 153/4" X 73/4" 200 FloodVENT Overhead Door 1540-524 153/4" X 73/4" 200 SmartVENT Overhead Door 1540-514 153/4" X 73/4" 200 Wood Wall FloodVENr 1540-570 14" X 83/4" 200 Wood Wall FloodVENr Overhead Door 1540-574 14" X 83/4" 200 SmarlVENT Stacker 1540-511 16" X 16" 400 FloodVent® Stacker 1540-521 16" X 16" 400 or ar 1 in = 25.4 mm; i square foot = m x L C it • L I Y 1 L t r 1 i _ IMES Evaluation Report ESR-2074 FBC Supplement Reissued February 2015 Revised March 2016 This report is subject to renewal February 2017. www.icc-6s.org 1 (800) 423-6587 1 (562) 699-0543 A Subsidiary of the Intemational Code Council® DIVISION: 08 00 00—OPENINGS Section: 08 95 43—Vents/Foundation Flood Vents REPORT HOLDER: SMARTVENT PRODUCTS, INC. 430 ANDBRO DRIVE, UNIT 1 PITMAN, NEW JERSEY 08071 (877)441-8368 www.smartvent.com info martvent.com EVALUATION SUBJECT: SMART VENT® AUTOMATIC FOUNDATION FLOOD VENTS: MODELS #1540520; #1540-521; #1540.510; #1640511; #1540570; #1540-574; #1540524; #1540414 1.0 REPORT PURPOSE AND SCOPE Purpose: The purpose of this evaluation report supplement is to indicate that Smart Vent® Automatic Foundation Flood Vents, recognized in ICC-ES master report ESR-2074, have also been evaluated for compliance with the codes noted below. Applicable code editions: ■ 2014 Florida Building Code —Building (FBC) ■ 2014 Florida Building Code —Residential (FRC) 2.0 CONCLUSIONS The Smart Vent® Automatic Foundation Flood Vents, described in Sections 2.0 through 7.0 of the master evaluation report ESR-2074, comply with the FBC and the FRC, provided the design and installation are in accordance with the Intemational Building Code® provisions noted in the master report. Use of the Smart Vent® Automatic Foundation Flood Vents has also been found to be in compliance with the High -Velocity Hurricane Zone provisions of the FBC and the FRC. For products falling under Florida Rule 9N-3, verification that the report holder's quality assurance program is audited by a quality assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the responsibility of an approved validation entity (or the code official when the report holder does not possess an approval by the Commission). This supplement expires concurrently with the master report, reissued February 2015 and revised May 2016 ICC'-h-;S 1,-valuation Reports are not to he consented as representing aesthetics or any other attributes not spectfcally addressed, nor are they to be construed as an endorsement of dte .subjeci dlf the report or a recommendation for its use. Mere is no warranty by 1C'C Evaluation Service, LLC. express or implied, as in any, finding or other matter in this report, or as to ant product covered by the report Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved. d Page 1 of 1