Loading...
HomeMy WebLinkAboutProject Information• -- wrightsoft® Project Summary Entire House QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOL.COM Project For. LITYNSKYJ RESIDENCE, MEL-RY CONSTRUCTION LOT 1308, NETTLES ISLAND, FL Notes: Design Information Weather: Fort Pierce, FL, US Job: Date: Mar 15, 2016 By: Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range Relative humidity L 50 % Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 15017 Btuh Structure 9681 Btuh Ducts 2530 Btuh Ducts 3772 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 17546 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 12781 Btuh • Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2427 Btuh Ducts 1001 Btuh - Heating Cooling Central vent (0 cfm) 0 Btuh Area (ft2) 1210 1210 Equipment latent load 3428 Btuh Volume (ft3) 10161 10161 Air changes/hour 0.45 0.23 Equipment total load 16209 Btuh Equiv. AVF (cfm) 76 39 Req, total capacity at 0.70 SHR 1.5 ton Heating Equipment Summary Cooling Equipment Summary Make Make Rheem Trade Trade RHEEM; RUUD Model Cond RA1618AJ1 AHRI ref Coil RH1T2417STAN AHRI ref 7940565 Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 100 EFF Efficiency 13.0 EER, 16 SEER 0 kW Sensible cooling 12600 Btuh 0 Btuh Latent cooling 5400 Btuh 0 OF Total cooling 18000 Btuh 600 cfm Actual air flow 600 cfm 0.034 cfm/Btuh Air flow factor 0.045 cfm/Btuh 1.00 in H2O Static pressure 1.00 in H2O Load sensible heat ratio 0.80 P Bold/itaUc values have been manually overridden Calculations approved byACCA to meet all requirements of Manual J `th * wrightsoft` Right -Suite® Universal 2016 15.0.18 RBU08101 ACCA ..cumentslWrightsoft WACILITYNSKYJ RESIDENCE.rup Calc = MJ8 Front Door faces: N 2016-Mar-15 10:25:04 Page 1 *'Wrightsoft° Right-M Worksheet Job: Entire House Date: Mar 15, 2016 QUICK CALCS, INC. By. • 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@,AOL.COM 1 Room name Entire House LIVING ROOM 2 Exposed wall 205.9 ft 41.3 ft 3 Room height 8.6 ft d 8.1 ft heat/cocl 4 5 Room dimensions Room area 1186.5 ft2 1.0 x 286.0 ft 286.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft;°F) (Btuhlft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cod Gross N/P/S Heat Cod 6 W W L-C 13A-4ocs 13A-4ocs 0.143 0.143 n ne 4.00 4.00 2.55 2.55 429 106 429 94 1719 375 1093 238 211 0 211 0 843 0 536 0 2 glazing, cir low-e 0.650 ne 18.20 17.04 12 0 218 204 0 0 0 0 11 13A-4ocs 2 glazing, cir low-e 0.143 0.650 a a 4.00 18.20 2.55 20.97 211 4 187 0 750 73 477 84 0 0 0 0 0 0 0 0 11DO 13A-4ocs 2 glazing, clr low-e 0.390 0.143 0.650 a s s 10.92 4.00 18.20 11.31 2.55 10.68 19 535 6 19 513 6 210 2052 109 218 1305 64 0 0 0 0 0 0 0 0 0 0 0 0 U�J 2 glazinq, clr low-e 0.650 0.143 s sw 18.20 4.00 10.68 2.55 16 211 16 173 291 691 171 439 0 124 0 91 0 363 0 231 V613A-4ocs 2 glazing, cir low-e 2 glazing, cir low-e 13A4ocs 0.650 0.650 0.143 sw sw w 18.20 18.20 4.00 17.42 17.42 2.55 6 33 211 0 0 193 105 598 771 100 572 490 0 33 0 0 0 0 0 598 0 0 572 0 2 glazing, clr low-e 2 glazing, cir low-e 0.650 0.650 w w 18.20 18.20 20.97 20.97 6 12 0 0 109 218 126 252 0 0 0 0 0 0 0 0 C 16A-30md 0.032 - 0.90 2.32 864 864 774 2003 156 156 140 362 F 22A-tpl 0.989 - 27.69 0.00 769 124 3432 0 286 41 1142 0 F 22A-tpl 0.989 - 27.69 0.00 84 6 175 0 0 0 0 0 6 c)AED excursion 282 192 Envelope loss/gain 12671 8119 3087 1893 12 a) Infiltration 2345 642 461 126 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 4 920 0 0 Appliances/other 0 0 Subtotal Qlnes 6 to 13) 15017 9681 3547 2019 Less wdemai load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 16017 9681 3547 2019 15 Duct loads 17% 39% 2530 3772 17% 39% 598 787 Total room load 17546 13453 4145 2806 Air required (cfm) 600 600 142 125 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. -P1j_• wrightsoft- 2016-Mar-1510:26:04 I&A Right -Suite® Universal 2015 15.0.18 RSU08101 Page 1 ...cuments\Wrightsoft WAC\LITYNSKYJ RESIDENCE.rup Calc = MA Front Door faces: N -�-�Wrightsoft° Right-M Worksheet Entire House QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOL.COM Job: Date: Mar 15, 2016 By: 1 Room name KTiCHEN DINING ROOM 2 Exposed wall 20.8 ft 11.0 ft 3 Room height 8.1 ft heat/cool 8.1 ft heat/cool 4 5 Room dimensions Room area 1.0 x 117.0 ft 117.0 ft' 9.0 x 7.0 ft 63.0 ft' Ty Construction U-value Or HTM Area number (Btuh/ft;°F) (Stuhlftz) or perimeter (ft) (Btuh) ors perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cod 6 W V1J �-G 13A-4ocs 13A-4ocs 2 glazing, cir low-e 0.143 0.143 0.650 n ne ne 4.00 4.00 18.20 2.55 2.55 17.04 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 13A-4ocs 2 glazing, cir low-e 0.143 0.650 a a 4.00 18.20 2.55 20.97 0 0 0 0 0 0 0 0 32 0 32 0 130 0 82 0 11 DO 13A-4ocs 2 glazing, clr low-e 0.390 0.143 0.650 a s s 10.92 4.00 18.20 11.31 2.65 10.68 0 81 0 0 81 0 0 324 0 0 206 0 0 57 0 0 57 0 0 227 0 0 144 0 2 dazinq, cir low-e 13A-4ocs 0.650 0.143 s sw 18.20 4.00 10.68 2.55 0 88 0 82 0 328 0 208 0 0 0 0 0 0 0 0 2 glazing, dr low-e 2 glazing, cir low-e 0.650 0.650 0.143 sw sw w 18.20 18.20 4.00 17.42 17.42 2.55 6 0 0 0 0 0 105 0 0 100 0 0 0 0 0 0 0 0 0 0 0 0 0 0 VL213A-4ocs 2 glazing, cir low-e 2 glazing, clr low-e 0.650 0.650 w w 18.20 18.20 20.97 20.97 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C F F 16A-30md 22A tpl 22A tpI 0.032 0.989 0.989 - - - 0.96 27.69 27.69 2.32 0.00 0.00 45 117 0 45 21 0 40 575 0 104 0 0 0 63 0 0 11 0 0 305 0 0 0 0 6 c)AED excursion 2 -7 Envelope loss/gain 1372 621 661 220 12 a) Infiltration 232 64 123 34 b) Room ventilation 0 01 01 0 13 Internal gains: Occupants @ 230 4 920 0 0 Appliances/other 0 0 Subtotal pines 6 to 13) 1604 1605 784 253 Less external load 0 0 0 0 Less transfer 0 0 0 0 14 Redistribution Subtotal 0 1604 0 1605 258 1042 90 344 15 Duct loads 17% 39% 270 625 17% 39% 176 134 Total room load 1874 2230 1217 478 Air required (cfm) 64 99 42 21 Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed. wrightsoft- 2016-Mar-1510:25:04 I&K Right -Suite® Universal 2015 16.0.18 RSU08101 Page 2 ...cumentsMightsoft HVAC\LITYNSKYJ RESIDENCE.rup Calc = MA Front Door faces: N * wrightsoft' Right-M Worksheet Job: x Entire House Date: Mar 15, 2016 QUICK CALCS, INC. By. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOL.COM 1 Room name ENTRY BATH 2 Exposed wall 5.0 ft 12.0 ft 3 Room height 8.1 ft heat/cool 8.1 ft heat/cool 4 5 Room dimensions Room area 5.0 x 5.0 ft 25.0 ft2 6.0 x 8.0 ft 48.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ftk°F) (Btuhlft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cod Gross NIP/S Heat Cod 6 W 1l}1 �--G 13A4ocs 13AAocs 2 glazing, cir low-e 0.143 0.143 0.650 n ne ne 4.00 4.00 18.20 2.55 2.55 17.04 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 vl/ I�-GD 11 13A-4ocs 2 glazing, cir low-e 0.143 0.650 a a 4.00 18.20 2.55 20.97 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11DO 13A-4ocs 2 glazing, cir low-e 2 glazinq, cir low-e 13A-4ocs 0.390 0.143 0.650 0.650 0.143 a s s s sw 10.92 4.00 18.20 18.20 4.00 11.31 2.55 10.68 10.68 2.55 0 41 0 0 0 0 41 0 0 0 0 162 0 0 0 0 103 0 0 0 0 65 6 0 0 0 59 6 0 0 0 235 109 0 0 0 150 64 0 0 V�1 I��-G ft-�G 2 glazing, cir low-e 2 glazing, cir low-e 13A-4ocs 0.650 0.650 0.143 sw sw w 18.20 18.20 4.00 17.42 17.42 2.55 0 0 0 0 0 0 0 0 0 0 0 0 0 0 32 0 0 32 0 0 130 0 0 82 V+l 2 glazing, dr low-e 2 glazing, cir low-e 0.650 0.650 w w 18.20 18.20 20.97 20.97 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C 16A-30md 0.032 0.90 2.32 5 5 4 12 48 48 43 ill F 22A-tpl 0.989 27.69 0.00 25 5 138 0 48 12 332 0 F 22A tpl 0.989 27.69 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion -3 -5 Envelope loss/gain 305 ill 850 402 12 a) Infiltration 56 15 134 37 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal Qlnes 6 to 13) 361 126 984 439 Less eAemal load 0 0 0 0 Less transfer 0 0 0 0 14 Redistribution Subtotal -361 0 -126 0 124 1107 88 527 15 Duct loads 17% 39% 0 0 17% 39% 187 205 Total room load Air required (cfm) -T 0 0 0 0 1294 44 733 33 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft' 2016-Mar-15 10:25:04 C�A Right-Sufte�l Universal 2015 15.0.18 RSU08101 Page 3 ...cumentslWrightsofl WACILITYNSKYJ RESIDENCE.rup Cale = MJ8 Front Door faces: N + wrightsoft' Right-J® Worksheet Date: Mar 75, 2o�s Entire House QUICK CALCS, INC. By. • 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Emall: QUICKCALCS@AOL.COM 1 Room name LINEN HALL 2 Exposed wall O ft O ft 3 Room height 8.1 ft heat/cool 8.1 ft heat/cod 4 5 Room dimensions Room area 2.0 x 4.0 ft 8.0 ftZ 1.0 x 36.0 ft 36.0 ft' Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft;°F) (Btuh/ft=) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cod 6 W W L--G 13A4ocs 13A-4ocs 2 glazing, cir low-e 0.143 0.143 0.650 n ne ne 4.00 4.00 18.20 2.55 2.65 17.04 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 13A-4ocs 2 glazing, cir low-e 0.143 0.650 a a 4.00 18.20 2.55 20.97 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 yJ 11DO 13A-4ocs 2 glazing, cir low-e 0.390 0.143 0.650 a s s 10.92 4.00 18.20 11.31 2.55 10.68 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazinq, cir low-e 13A-4ocs 0.650 0.143 s sw 18.20 4.00 10.68 2.55 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, cir low-e 2 glazing, cir low-e 0.650 0.650 0.143 sw sw w 18.20 18.20 4.00 17.42 17.42 2.55 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 VL213A-4ocs 2 glazing, cir low-e 2 glazing, cir low-e 0.650 0.650 w w 18.20 18.20 20.97 20.97 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C F F 16A-30md 22A-tpl 22A-tpl 0.032 0.989 0.989 - - - 0.90 27.69 27.69 2.32 0.00 0.00 8 8 0 8 0 0 7 0 0 19 0 0 34 36 0 34 0 0 30 0 0 79 0 0 61 c)AED excursion 10 -2 Envelope loss/gain 7 18 30 77 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal Qines 6 to 13) 7 18 30 77 Less eAemal load 0 0 0 0 Less transfer 0 0 0 0 14 Redistribution Subtotal -7 0 -18 0 -30 0 -77 0 15 Duct loads 17% 39% 0 0 17% 39% 0 0 Total room load Air required (cfm) 0 0 0 0 0 0 0 0 Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed. ACM - - wrsft ightO' 2016-Mar-15 1 Right -Suite® Universal 2015 15.0.18 RSU08101 PO4 a e ...cumentslWrightsoft HVAC\LITYNSKYJ RESIOENCE.rup Calc = MJ8 Front Door faces: N g -P�wrightsoft' Right-M Worksheet Entire House QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOL.COM Job: Date: Mar 15, 2016 By: 1 Room name BEDROOM CLST 2 Exposed wall 18.2 ft 11.8 ft 3 Room height 8.1 ft heat/cool 8.1 ft heaticool 4 5 Room dimensions Room area 1.0 x 128.5 ft 128.5 ftz 1.0 x 21.0 ft 21.0 fts Ty Construction U-value Or HTM Area (ft2) Load Area (ft') Load number (Btuh/ftk'F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cod Gross N/P/S Heat Cod 6 W Vtl L-C 13A-4ocs 13A-4ocs 2 glazing, cir low-e 0.143 0.143 0.650 n ne ne 4.00 4.00 18.20 2.55 2.55 17.04 0 58 12 0 46 0 0 186 218 0 118 204 0 47 0 0 47 0 0 189 0 0 120 0 V�/ I-G 11 13A-4ocs 2 glazing, cir low-e 0.143 0.650 a a 4.00 18.20 2.55 20.97 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 �p VI! T� 11DO 13A-4ocs 2 glazing, cir low-e 0.390 0.143 0.650 a s s 10.92 4.00 18.20 11.31 2.55 10.68 0 89 0 0 81 0 0 325 0 0 206 0 0 49 0 0 49 0 0 195 0 0 124 0 I{---GG 2 glazing, cir low-e 13A-4ocs 0.650 0.143 s sw 18.20 4.00 10.68 2.55 8 0 8 0 146 0 85 0 0 0 0 0 0 0 0 0 T-Vt/ 2 glazing, cir low-e 2 glazing, cir low-e 13A-4ocs 0.650 0.650 0.143 sw sw w 18.20 18.20 4.00 17.42 17.42 2.55 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I� =4G3 V�/ �L-_-(G 2 glazing, cir low-e 2 glazing, cir low-e 0.650 0.650 w w 18.20 18.20 20.97 20.97 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C F F 16A-30md 22A tpl 22A-tpl 0.032 0.989 0.989 - - 0.90 27.69 27.69 2.32 0.00 0.00 129 129 0 129 18 0 115 503 0 298 0 0 21 21 0 21 12 0 19 325 0 49 0 0 6 c)AED excursion -26 -9 Envelope loss/gain 1493 887 728 284 12 a) Infiltration 203 56 132 36 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal Qines 6 to 13) 1696 942 860 320 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 17 43 0 0 14 Subtotal 1713 985 860 320 15 Duct loads 17% 39% 289 384 17% 39% 145 125 Total room load Air required (cfm) 1 2002 168 1369 61 1 1005 34 445 20 Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed: wrightsoft' 2016-Mar-15 10:26:04 ,ZrARight-Suite® Universal 2015 15.0.18 RSU08101 Page 5 ...cuments\Wrightsoft HVAC\LITYNSKYJ RESIDENCE.rup Cale = MJ8 Front Door faces: N -'wrightsoft0 Right-M Worksheet Entire House QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOL.COM Job: Date: Mar 15, 2016 By: 1 Room name AM STAIRS 2 Exposed wall 0 ft 25.0 ft 3 Room height 8.1 ft heat/cool 14.1 ft heat/cool 4 5 Room dimensions Room area 5.0 x 4.0 It 20.0 ft2 1.0 x 92.0 ft 92.0 ft' Ty Construction U-value Or HTM Area (ft') Load Area (ft2) Load number (Btuh/ftk-*F) (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/PIS Heat Cod Gross N/P/S Heat Cod 6 W �-C 13A4ocs 13A4ocs 2 glazing, cir low-e 0.143 0.143 0.650 n ne ne 4.00 4.00 18.20 2.55 2.55 17.04 0 0 0 0 0 0 0 0 0 0 0 0 130 0 0 130 0 0 519 0 0 330 0 0 V}1 ��Gp 11 13A-4ocs 2 glazing, clr low-e 0.143 0.650 a a 4.00 18.20 2.55 20.97 0 0 0 0 0 0 0 0 105 4 101 0 406 73 258 84 V�! 11D0 13A4ocs 2 glazing, clr low-e 2 glazinq, dr low-e 13A4ocs 0.390 0.143 0.650 0.650 0.143 a s s s sw 10.92 4.00 18.20 18.20 4.00 11.31 2-55 10.68 10.68 2.55 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I�_GG 2 glazing, clr low-e 2 glazing, cir low-e 13A4ocs 0.650 0.650 0.143 sw sw w 18.20 18.20 4.00 17.42 17.42 2.55 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, dr low-e 2 glazing, cir low-e 0.650 0.650 w w 18.20 18.20 20.97 20.97 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C 16A-30md 0.032 - 0.90 2.32 0 0 0 0 92 92 82 213 F 22A tvi 0.989 - 27.69 0.00 20 0 0 0 0 0 0 0 F 22A-tpl 0.989 - 27.69 0.00 0 0 0 0 68 4 ill 0 6 c) AED excursion 0 7 Envelope loss/gain 0 0 1191 892 12 a) Inflitration 0 0 324 89 b) Room ventilation 0 0 1 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 0 0 1514 980 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 14 Redistribution Subtotal 0 0 0 0 15 1529 38 1019 15 Duct loads 17% 39% 0 0 17% 39% 258 397 Total room load Air required (cfm) 0 0 0 0 1 1787 611 1416 63 Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed. -r 1F wrightsoft. Un iversal 2016-Mar-1510:25:04 C�A g-Suersl niversal 2015 15.0.18 RSU08101 Page 6 ...cuments\Wrightsoft WACILITYNSKYJ RESIDENCE.rup Calc = MJ8 Front Door faces: N _' 'wrightsoft' Right-J® Worksheet Job: Entire House Date: Mar 15, 2016 QUICK CALCS, INC. By: • 317 ST, LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOL.COM 1 Room name STORAGE LINEN CLST 2 3 Exposed wall Room height 4.0 ft 8.1 ft heat/cool 0 ft 8.1 ft heat/cod 4 5 Room dimensions Room area 4.0 x 4.0 ft 16.0 ft' 4.0 x 2.0 ft 8.0 ft2 Ty Construction number U-value (Btuh/ft;°F) Or HTM (Btuhlft') Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat cod Gross N/PIS Heat Cod 6 W yJ L--C 13A4ocs 13A-4ocs 2 glazing, cir low-e 0.143 0.143 0.650 n ne ne 4.00 4.00 18.20 2.55 2.55 17.04 32 0 0 32 0 0 130 0 0 82 0 0 0 0 0 0 0 0 0 0 0 0 0 0 �1 11 13A-4ocs 2 glazing, cir low-e 0.143 0.650 a a 4.00 18.20 2.55 20.97 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 �p 11D0 13AAocs 2 glazing, cir low-e 2 glazinq, dr low-e 13A-4ocs 0.390 0.143 0.650 0.650 0.143 a s s s sw 10.92 4.00 18.20 18.20 4.00 11.31 2.55 10.68 10.68 2.55 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 V�/ IF--(C' vil 2 glazing, cir low-e 2 glazing, cir low-e 13A4ocs 0.650 0.650 0.143 sw sw w 18,20 18.20 4.00 17.42 17.42 2.55 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W 2 glazing, cir low-e 2 glazing, cir low-e 0.650 0.650 w w 18.20 18.20 20.97 20.97 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C F F 16A30md 22A-tpl 22A-tpl 0.032 0.989 0.989 - - - 0.90 27.69 27.69 Z32 0.00 0.00 0 16 0 0 4 0 0 111 0 0 0 0 8 0 0 8 0 0 7 d 0 19 0 0 6 c) AED excurslon -3 0 Envelope loss/gain 240 80 7 18 12 a) Infiltration 45 12 0 0 b) Room ventilation 0 0 01 0 13 Internal gains: Occupants @ 230 0 0 0 0 Applianceslother 0 0 Subtotal Qines 6 to 13) 285 92 7 18 Less external load 0 0 0 0 14 Less transfer Redistribution Subtotal 0 0 285 0 0 92 0 -7 01 0 -18 0 15 Duct loads 17% 39% 48 36 17% 39% 01 0 Total room load Alr required (cfm) 333 11 - 128 6 0 0 0 0 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrightsoft- 2016-Mar-1510:25:04 CA Rlght-Suite® Universal 2015 15.0.18 RSU08101 Page 7 ...cumentslWrightsoft HVACILITYNSKYJ RESIDENCE.rup Cale = MJ8 Front Door faces: N I- +-wrightsoft° Right-M Worksheet , .lob: Entire House Date: Mar 15, 2016 QUICK CALCS, INC. By. - 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOL.COM 1 Room name W/D MASTER BEDROOM 2 3 Exposed wall Room height 0 ft 8.1 ft heat/cool 27.0 ft 8.1 ft heat/cool 4 5 Room dimensions Room area 5.0 x 4.0 ft 20.0 ft2 1.0 x 186.5 ft 186.5 ft2 Ty Construction number U-value (Btuh/ftMF) Or HTM (Btuhlft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cod Gross N/P/S Heat Cod 6 W VIJ �•--G 13AAocs 13A-4ocs 2 glazing, cir low-e 0.143 0.143 0.650 n ne ne 4.00 4.00 18.20 2.55 2.55 17.04 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 V)J �L--:G 11 13A flocs 2 glazing, cir low-e 0.143 0.650 a a 4.00 18.20 2.55 20.97 0 0 0 0 0 0 0 0 73 0 54 0 215 0 137 0 11D0 13A-4ocs 2 glazing, cir low-e 2 glazinq, cir low-e 13A-4ocs 0.390 0.143 0.650 0.650 0.143 a s s s sw 10.92 4.00 18.20 18.20 4.00 11.31 2.55 10.68 10.68 2.55 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 19 113 0 8 0 19 105 0 8 0 210 422 0 146 0 218 268 0 85 0 p V�/ I�-�-G �1 2glazing, cir low-e 2 glazing, cir low-e 13A-4ocs 0.650 0.650 0.143 sw sw w 18.20 18.20 4.00 17.42 17.42 2.55 0 0 0 0 0 0 0 0 0 0 0 0 0 0 32 0 0 32 0 0 130 0 0 82 I---G 2 glazing, cir low-e 2 glazing, cir low-e 0.650 0.650 w w 18.20 18.20 20.97 20.97 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C F F 16A-30md 22A-tol 22A-tpI 0.032 0.989 0.989 - - 0.90 27.69 27.69 2.32 0.00 0.00 20 0 0 20 0 0 18 0 0 46 0 0 187 0 16 187 0 2 167 0 64 433 0 0 6 c)AED excursion .1 -25 Envelope loss/gain 18 45 1354 1199 12 a) Infiltration 0 0 301 83 b) Room ventilation 0 0 0 0 13 internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal Qlnes 6 to 13) 18 45 1655 1281 Less external load 0 0 0 0 Less transfer 0 0 0 0 14 Redistribution Subtotal -18 0 45 0 48 1703 51 1332 15 Duct loads 17% 39% 0 0 17% 39% 287 519 Total room load Air required (cfm) 0 0 0 0 1990 68 1851 83 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrightsoft- 2016-Mar-1510:25:04 CAA Right -Suite® Universal 2015 15.0.18 RSU08101 Page 8 ...cumentslWrightsoft HVACILITYNSKYJ RESIDENCE.rup Calc = MJ8 Front Door faces: N +'wrightsoft' Right-M Worksheet Entire House QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOL.COM Job: Date: Mar 15, 2016 By: 1 Room name M WIC A/C CHASE 2 Exposed wall 10.0 ft 2.0 ft 3 Room height 8.1 ft heat/cool 8.1 ft heat/coci 4 5 Room dimensions Room area 1.0 x 20.5 ft 20.5 ft2 2.0 x 4.0 ft 8.0 ft' Ty Construction U-value Or HTM Area (ft.) Load Area (ft') Load number (Btuh/ft1-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cod Gross NIP/S Heat Cool 6 W . V►/ 13A-4ocs 13A-4ocs 2 glazing, cir low-e 0.143 0.143 0.650 n ne ne 4.00 4.00 18.20 2.55 2.55 17.04 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -G 11 13A-4ocs 2 glazing, clr low-e 0.143 0.650 a a 4.00 18.20 2.55 20.97 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 DO 13A-4ocs 2 glazing, cir low-e 2 glazina, clr low-e 13A-4ocs 0.390 0.143 0.650 0.650 0.143 a s s s sw 10.92 4.00 18.20 18.20 4.00 11.31 2.55 10.68 10.68 2.55 0 41 0 0 0 0 41 0 0 0 0 162 0 0 0 0 103 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 V+/ {�-CG' 2 glazing, clr low-e 2 glazing, clr low-e 13A-4ocs 0.650 0.650 0.143 sw sw w 18.20 18.20 4.00 17.42 17.42 2.55 0 0 41 0 0 29 0 0 114 0 0 73 0 0 16 0 0 16 0 0 65 0 0 41 2 glazing, clr low-e 2 glazing, cir low-e 0.650 0.650 w w 18.20 18.20 20.97 20.97 0 12 0 0 0 218 0 252 0 0 0 0 0 0 0 0 C F F 16A-30md 22A-tiol 22A-tpl 0.032 0.989 0.989 - - - 0.90 27.69 27.69 Z32 0.00 0.00 21 0 0 21 0 0 18 0 0 48 0 0 8 0 0 8 0 0 7 0 0 19 0 0 6 c)AED excursion 119 -2 Envelope loss/gain 513 593 72 58 12 a) Infiltration 112 31 22 6 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal Qines 6 to 13) 625 624 94 64 Less wdemal load 0 0 0 0 14 Less transfer Redistribution Subtotal 0 0 625 0 0 624 0 .94 0 0 -64 0 15 Ductloads 17% 39% 105 243 17% 39% 0 0 Total room load Air required (cfm) 730 251 867 39 0 0 0 0 Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed. wrightsoft- 2016-Mar-15 10:25:04 le . Right -Suite® Universal 2015 15.0.18 RSU08101 Page 9 ... cuments\Wrightsoft HVAC\LITYNSKYJ RESIDENCE.rup Calc = MJ8 Front Door faces: N -**wrightsoft° Right-M Worksheet Entire House QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOL.COM Job: Date: Mar 15, 2016 By: 1 Room name M BATH 2 Exposed wall 18.0 ft 3 Room height 8.1 ft heat/cool 4 5 Room dimensions Room area 1.0 x 83.0 ft 83.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area Load number (Btutdft2-*F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cod Gross N/P/S Heat Cod 6 W ' W L-G 13AAocs 13A-4ocs 2 glazing, cir low-e 0.143 0.143 0.650 n ne ne 4.00 4.00 18.20 2.55 2.55 17.04 57 0 0 57 0 0 227 0 0 144 0 0 11 13A-4ocs 2 glazing, cir low-e 0.143 0.650 a a 4.00 18.20 2.55 20.97 0 0 0 0 0 0 0 0 11D0 13A-4ocs 2 glazing, cir low-e 0.390 0.143 0.650 a s s 10.92 4.00 18.20 11.31 2.55 10.68 0 0 0 0 0 0 0 0 0 0 0 0 1�/ li-- (G` Tifs13A-4ocs 2 glazinq, cir low-e 0.650 0.143 s sw 18.20 4.00 10.68 2.55 0 0 0 0 0 0 0 0 2 glazing, cir low-e 0.650 sw 18.20 17.42 0 0 0 0 2 glazing, cir low-e 0.650 0.143 sw w 18.20 4.00 17.42 2.55 0 89 0 83 0 333 0 212 T:i13A-4ocs 2 glazing, dr low-e 2 glazing, cir low-e 0.650 0.650 w w 18.20 18.20 20.97 20,97 6 0 0 0 109 0 126 0 C 16A-30md 0.032 0.90 2.32 83 83 74 193 F 22A-tpl 0.989 27.69 0.00 0 0 0 0 F 22A-tpl 0.989 27.69 0.00 0 0 0 0 6 c)AED excursion 46 Envelope loss/gain 743 721 12 a) Infiltration 201 55 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13) 944 776 Less wdemal load 0 0 Less transfer 0 0 14 Redistribution Subtotal 57 1001 38 814 15 Duct loads 17% 39% 169 317 Total room load Air required (cfm) 1169 40 1131 50 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrigfitsoft` Right -Suite® Universal 2015 15.0.18 RSU08101 2016-Mar-15 10:Page 10ge 10 ...currents\Wrightsoft HVACILITYNSKYJ RESIDENCE.rup Calc = MJ8 Front Door faces: N - wrightsoft° Duct System Summary Entire House QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@,AOL.COM -YL,roject intormation For: LITYNSKYJ RESIDENCE, MEL-RY CONSTRUCTION LOT 1308, NETTLES ISLAND, FL External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 600 cfm Job: Date: Mar 15, 2016 By: Cooling 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 600 cfm 170 ft Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mad Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH h 1294 44 33 1.000 4.0 Ox0 VIFx 20.7 115.0 st2 BEDROOM h 2002 68 61 1.000 4.0 OxO VIFx 18.5 115.0 st2 CLST h 1005 34 20 1.000 4.0 Ox0 VIFx 30.0 115.0 st2 DINING ROOM h 1217 42 21 1.000 4.0 OxO VIFx 7.8 115.0 st3 KITCHEN c 2230 64 99 1.000 5.0 Ox0 VIFx 11.0 115.0 st3 LIVING ROOM h 4145 142 125 1.000 6.0 Ox0 VIFx 6.2 115.0 st3 M BATH c 1131 40 50 1.000 4.0 Ox0 VIFx 25.2 135.0 st4 M WIC c 867 25 39 1.000 4.0 Ox0 VIFx 34.1 135.0 st4 MASTER BEDROOM c 1851 68 83 1.000 5.0 Ox0 VIFx 27.7 135.0 st4 STAIRS c 1416 61 63 1.000 4.0 Ox0 VIFx 34.6 135.0 st4 STORAGE h 333 11 6 1.000 4.0 Ox 0 VIFx 1 4.1 95.0 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st1 Peak AVF 194 235 1.000 879 7.0 0 x 0 VinlFlx st4 Peak AVF 194 235 1.000 879 7.0 0 x 0 VinlFlx st1 st2 Peak AVF 147 114 1.000 749 6.0 0 x 0 VinlFlx st3 Peak AVF 247 246 1.000 709 8.0 0 x 0 VinlFlx Bold/italic values have been manuaW overridden .` Wil htsoft` 2016-Mar-1510:25:11 4-- 9 Right -Suite® Universal 2015 15.0.18 RSU08101 Page 1 ..cuments\Wrightsoft HVAC\LITYNSKYJ RESIDENCE.rup Calc = MJ8 Front Door faces: N ` Return Branch Detail Table Name Grill Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mad Trunk rbl Ox 0 600 600 0 0 0 0 Ox 0 VIFx C htsoft= 2016-Mar-1510:25:11 wrl 9 Right -Suite® Universal 2015 15.0.18 RSU08101 Page 2 ...cuments\Wrightsoft WACILITYNSKYJ RESIDENCE.rup Cale = MJ8 Front Door faces: N This document was created with Win2PDF available at http://www.win2pdf.com. The unregistered version of Win2PDF is for evaluation or non-commercial use only. This page will not be added after purchasing Win2PDF. • . s :yv M LA� } z I _ ?ND FLOOPLPLLMING RISER N TS. If it —I °r I 'I I BAiYri2 ff� � I I ss'ea 1ST FLOOR PLIAv®ING RISER N.T.S. 2ND FLOOR HVAC PLAN 1/4' - 1'-O' PR vm eAi.tav®AWMn wAuu � IST FLOOR HVAC PLAN 1/4' - 1'-0' Fl.rovae =•• ••..._, act �nrttr H au trcr esaara