EVALUATION REPORT
Ceftmcate of No. 29824
17520 Edinburgh Drive
Tampa, FL 33847
(813) 480-3421
FLORIDA 911ILDINO CODE T" EDITION (2020)
Manufacturer: CONTINENTAL MATERIALS, INC.
Issued October 16, 2020
1614 Old York Road
Abington, PA 19001
(800) 247-6637
Quality Assurance: Intertek Testing Services (QUA1586)
SCOPE
Category: Roofing
Subcategory: Underfayments
Code Edition: Florida Building Code, 7" Edition (2020) Including High -Velocity Hurricane Zones (HVHZ)
Code Sections: 1507.1.1, 1518.4
Properties: Physical properties
REFERENCES
Entity
$gR91L 1�.
Standard
`%C
Intertek Testing Services (TST1585)
102074565COQ-004
AC 188'
2012
Intertek Testing Services (TST1565)
102074565COO-004A
AC 188'
2012
Intertek Testing Services (TST1585)
102074565000-007
ASTM D 228
2009
Intertek Testing Services (TST1585)
10379696000O.003D
AC 188'
2012
Intertek Testing Services (TST1585)
10379696000O-004B
ASTM D 1970
2015a
Intertek Testing Services (CER1497)
CCRR-1045
18C, IRC
2012
PRI Constriction Materials Technologies (TST5878)
CMI-048.02-01A
ASTM D 228
2009
PRI Construction Materials Technologies (TST5878)
CMI.048-02-01B
ASTM D 226
2009
PRI Constriction Malenals Technologies (TST5878)
CMI-048-02-01C
ASTM D 226
2009
PRI Constriction Materials Technologies (TST5878)
CMI-05S02-01
ASTM D 4533
2015
PRI Constnuction Matenals Technologies (TST5878)
CMI-056-02-01
ASTM D 4533
2015
PRI Construction Materials Technologies (TST5878)
CMi-062-02-01
TAS 117(B)
1995
'Determined to be equivalent to ASTM D 226 (2009). Type I and 11
CM115001.5 FL18374-R5 Page 1 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product Changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor Impfy warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
[A CREEK CONTINENTAL MATERIALS, INC.
SocureGrlp Undorlaymonts
TECHNICAL SERVICES, LLC
PRODUCT DESCRIPTION
SecureGrip PROM A mechanically attached, woven polypropylene underlayment (nominal weight = 1.74
Ib/100ft?) used an alternative to ASTM D 226, Type I and Type II with a minimum tear
strength per ASTM D 4533 of 15 pounds, a minimum tensile strength per ASTM D
5035 of 20 poundslinch, and meets liquid water transmission test of Section 8.6 of
ASTM D 4869. The underlayment is available in rolls 48-Inch wide by 250-ft long.
SecureGrIp25TM
A mechanically attached, woven polypropylene underlayment (nominal weight = 2.05
Ib/100ft2) used an alternative to ASTM D 226, Type I and Type II with a minimum tear
strength per ASTM D 4533 of 15 pounds, a minimum tensile strength per ASTM D
transmission test of Section 8.6 of
5035 of 20 pounds/inch, and meets liquid water
ASTM D 4869. The underlayment is available in rolls 48-inch wide by 250-ft long.
SecureGripT" PLUS
A mechanically attached, woven polypropylene underlayment (nominal weight = 2.46
Ib/100ft2) used an alternative to ASTM D 226, Type I and Type II with a minimum tear
strength per ASTM D 4533 of 15 pounds, a minimum tensile strength per ASTM D
liquid water transmission test of Section 8.6 of
5035 of 20 pounds/inch, and meets
ASTM D 4869. The underlayment is available in rolls 48-inch wide by 250-ft long.
SecureGrlpMAX-
A mechanically attached, woven polypropylene underlayment (nominal weight = 3.69
Ib/100ft2) used an alternative to ASTM D 226, Type I and Type II with a minimum tear
strength per ASTM D 4533 of 15 pounds, a minimum tensile strength per ASTM D
5035 of 20 poundsllnch, and meets liquid water transmission test of Section 8.6 of
ASTM D 4869.. The underlayment is available in rolls 48-inch wide by 250-ft long.
SecureGrip'" PS MAX HT
A self -adhered, polymer -modified bitumen underlayment with a synthetic facer
(nominal weight = 18.5 Ib/100ff) used as an alternative to ASTM D 226, Type I and
Type II and ASTM D 1970 with a minimum tear strength per ASTM D 1970 of 20
pounds. The underlayment is available in rolls of 36-inch wide by 72 ft long.
APPLICATION INSTRUCTIONS
FOR SECUREGRIP PROT", SECUREGRIP25Tm, AND SECUREGRip- PLUS
Deck Type:
The roof deck shall be constructed of closely fitted, solid sheathing for new or existing
construction. Sheathing shall be installed in accordance with FBC requirements. New
construction in the HVHZ shall be minimum 19/32-inch plywood. Roof decks shall
have no more than 1/8-inch gap at abutting joints.
Attachment method
Underlayment shall be attached in accordance with the FBC Section 1507.1.1, Table
(non-HVHZ):
1507.1.1.1 and manufacturer's installation instructions.
Use of 1-inch diameter plastic cap nails where the ultimate design wind speed, V.4
equals or exceeds 170mph is permissible with the following provisions:
1) The attachment density shall be increased by a factor of 3 for SecureGrip PROTM,
SecureGripWm, and SecureGrip TMPLUS
2) The attachment density shall be increased by a factor of 2 for SecureGripMAXTM
Attachment method
Underlayment shall be installed with a minimum 4-inch head lap and minimum 6-inch
(HVHZ):
end lap and be fastened as specified in FBC Section 1518.2.
Allowable roof coverings
Mechanically attached roof systems as prescribed in FBC Table 1507.1.1.1.
(Non-HVHZ):
Allowable roof coverings
Underlayment shall be used with mechanically attached asphalt shingles, metal roof
(HVHZ):
panels and shingles, composite shingles and wood shingles and shakes
CM115001.5 FL16374-R5 Page 2 of 4
This evaluation report Is provided for Stale of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor Imply warranty, Installation, recommended use, or other product attributes that are not
Specifically addressed herein.
-` CREEK CONTINENTAL MATERIALS, INC.
3ocureGrlp Undo►laymortta
TECHNICAL SERVICES, LLC
APPLICA71ON INSTRUCTIONS FOR SECUREGRIP"i PS MAX FIT
Application: All underfayments shell be Installed In accordance with the FBC.
Deck substrates shell be clean, dry, and free from any irregularities and debris. All
fasteners in the deck shall be checked for protrusion and corrected prior to
underlayment application. Pdor to beginning installation, the undertayment shall be
unrolled and allowed to relax for a minimum of 3-5 minutes.
The underlayment shall be installed with the release backer removed and pressed
firmly into place to ensure complete contact with the deck. The underfayment shall be
installed with the roll length parallel to the eave, starting at the eave, and with minimum
3' side laps and minimum Wend laps staggered min. 6-ftfrom preceding course.
In the HVHZ, the underlayment shall be installed over one of more plies of ASTM D 226
Type II or ASTM D 2626 organic felt with minimum 4' head laps and minimum 6' end
laps In accordance with FBC Section 1518.3.
It is permissible to back nail the underlayment 12-inches on -center as needed (nails
shall be installed perpendicular to deck with the nail heads flush to the top surface of
the underlayment).
Min. Application 40'F: Contact the manufacturer when instaffing at temperatures below Me minimum
Temperature: application temperature.
Allowable roof coverings Mechanically attached roof systems as prescribed in FBC Section 1607.1.1.
(Non-HVHZ):
Allowable roof coverings Underiayment shall be used with mechanically attached asphalt shingles, metal roof
(HVHZ): panels and shingles, composite shingles and wool shingles and shakes
LIMITATIONS
1) Fire Classification is not within the scope of this evaluation.
2) Wind uplift resistance is not within the scope of this evaluation.
3) Installation of the evaluated product shall comply with this report, the FBC, and the manufacturer's published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
4) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlayment application.
5) Roof slope limitations shall be in accordance with FBC requirements.
6) All undedayments shall be installed with the roll length parallel to the eave, starting at the eave, and lapped
in success courses installed up the deck in a manner that effectively sheds water from the deck.
7) The underlayment may be used as described in other current FBC product approval documents.
8) Roof coverings shall not be adhered directly to the underlayment Roof coverings shall be mechanically
fastened through the underfayment to the roof deck.
9) The underlayment shall not be installed over existing roof coverings.
10) The underlayment shall be exposed on the roof deck for a maximum 30 days unless otherwise stated.
11) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61 G20-3.
CMI15001.5 FL18374-R5 Page 2 of 4
This evaluation report is provided for State of Florida product approval under Rule 81G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor Imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK CONTINENTAL MATERIALS, INC.
SocureOrip Underlaymanb
TECHNICAL SERVICES, LLC
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code, 7th Edition (2020) including High -Velocity Hurricane Zones (HVHZ) as evidenced in the referenced documents
submitted by the named manufacturer.
S`��,,,RY
No 74021
-O ; Cr
. /STATE OF :lu;
CERTIFICATION OF INDEPENDENCE
2020.10.16
i�-13:44:09
yy+.b MlR�rl
-041001
Zachary R. Priest, P.E.
Florida Registration No. 74021
Organization No. ANE9641
CREEK Technical Services, LLC does not have, norwill It acquire, a financial interest in any company manufacwng or distributing products under this
evaluation.
CREEK Technical Services. LLC Is not owned, operated, or controlled by any company manufacturing or distributing products under this evaluation.
Zachary R. Priest, P.E. does not have, nor wilt acquire, a financial Interest In any company manufacturing or distributing products under this evaluation.
Zachary R. Priest P.E. does not have, nor will acquire, a financial interest in any other entity Involved in the approval process of the product
END OF REPORT
CM115001.5 FL16374-R5 Page 2 of 4
This evaluation report Is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report Is valid.
This evaluation report does not express nor Imply warranty, Installation, recommended use, or other product attributes that are not
specifically addressed herein.