HomeMy WebLinkAboutConstruction RevisionFOUNDATION NOTES ALL CONCRETE SHALL HAVE A MIN. COMPRESSIVE STRENGTH OF 2500 PSI ® 28 DAYS FOR FTG'S & SLABS REINFORCING STEEL (REBAR) SHALL BE ASTM. GRADE 60 DEFORMED BILLET STL. CLEAR COVER SHALL BE 3" FOR FOOTINGS & 1-1/2" IN BEAMS. LAPPED STEEL MIN 25". 10" STD. HOOKS W/ 90 DEGREE BENDS. FTGS SHALL BEAR ON UNDISTURBED SOIL A/0 PROPERLY COMPACTED FILL (2000 PSF MIN.). FILL MATERIAL SHALL BE COMPACTED TO 95% DENSITY OF A STANDARD PROCTOR. TO BE VERIFIED BY GENERAL CONTRACTOR/OWNER. ELECTRIC SERVICE GROUND TO BE BONDED TO FTG STEEL CONTRACTOR TO VERIFY ALL HOSE BIBB LOC. & TYPE CONTRACTOR TO ROUGH IN A/H CHASE A/0 DRAIN LINES, & CONDUITS AS NEEDED CONTRACTOR TO VERIFY A/0 PROVIDE FOR SLAB RECESSES, SILLS & CURB REQMTS @ ALL DOORS CONTRACTOR TO DETERMINE ANY SLOPE OF SLAB REQMTS LAP ALL HORIZ FTG REBAR 25" MIN ALL STL MIN. GRADE 60 BOTT OF FTG MIN 12" BELOW FINISH GRADE ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE 2014 ED AND LOCAL CODES AS THEY MAY APPLY N N t 2) #5 BARS CONTINUOUS W/ 25" MIN LAP & #5 VERTICAL BAR @ CORNER (SEE FOUNDATION PLAN) FOOTING CORNER DETAIL MINIMUM 12" SLOPE 1/6 MA OF FOOTING BELOW GRADE 16" A— (2) #5 REBAR- 110A PYi2 6" M I N FI 3" MIN COVER 3" TYP ► 3" TYP MONO EDGE FOOTER FINISHED FLOOR ELEVATION F WEDGE F2 ANCHO p ' NIIIIII16"X16" STEP FOOTER (1)111 REBAR @ BRIG. WALLS 4" CONCRETE SLAB / WIRE F3 BEARING PAD #5 REBAR CONTMOUS 6"x6" WIRE MESH OR FIBER 36• #5 REBAR 8" OC EACH WAY TERMITE NOTES: 1. A PERMANENT SIGN WHICH IDENTIFIES THE TERMITE TREATMENT PROVIDER AND NEED FOR RE -INSPECTION AND TREATMENT CONTRACT RENEWAL SHALL BE PROVIDED. 2. CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST V-0" AWAY FROM BUILDING SIDE WALLS, 3. INITIAL TREATMENT SHALL BE DONE AFTER ALL EXCAVATION AND BACKFILL IS COMPLETE. 4. MINIMUM 6 MIL VAPOR BARRIER MUST BE INSTALLED TO PROTECT AGAINST RAINFALL DILUTION. 5. SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE WITHIN 1'4I OF THE STRUCTURE SIDEWALLS. 6. AN EXTERIOR VERTICAL CHEMICAL BARRIER MUST BE INSTALLED AFTER CONSTRUCTION. 7. A CERTIFICATE OF COMPLIANCE MUST BE ISSUED TO THE BUILDING DEPARTMENT BY A LICENSED PEST CONTROL COMPANY BEFORE FINAL INSPECTION. r- I I-Q" TYPICAL CONCRETE SLAB MAR 0 2 201E ST, Lucie Count 1701�— 00 21 . ST. LUCIE COUNTY BUILDING DIVISION ,4 REVIEWED FOR CD?L/y�}}�N�E REVIEWED BY 1.J._JL/__�_ty. MUST 6E KEPTON JOB OR 10 INSPECTION WILL BE MADE TUB r� BATH 2 WC f------ f 2" VENT C.O. L3 L _] LAV 23" ' ] ] I ♦I 1 i 2" VENT C.O. ; KITCHEN I J;L ' I I � I 13" 1 SINK I WASH U TI L ; 2" 1 DIN __________J I I I 2° i F LJ ----------- I I � I 3" I LAV 2" I 2" VINT C 0 I ,l I �I . .' I 11 I , 2„ , r-------L TUB `-Z., 3 i----3-------L LAV 2" WC 3" . SHOWER I � I ,• r I 3„ MASTER BATH I I / • I 1 1 I I 4" 4112 WAY C/O I I I I \I W TO SEWER SYSTEM OR APPROVED SEPTIC SYSTEM PLUMBING RISER U,S. NOTE: PLUMBING CONTRACTOR TO VERIFY PLUMBING LAYOUT AND RISER DIAGRAM. PLUMBING CONTRACTOR TO VERIFY PLUMBING WALL LOCATIONS W A T E R- A I R- L A N D 1040 Harbour Drake Dr. chrisbeers@byu.net 941-628-0635 Punta Gorda, Florida 33983 fax 413-687-9013 R TLEN�S , P.E. ID A�b-V64594 Although every effort is made to ensure the accuracy of these plans it is the responsibility of the builder to verify all dimensions, details and specifications shown. Bluestream Design Studio will not be held liable for any errors or omissions on these plans. BLUESTREAM DS DESIGN STUDIO Residental CAD Drafting 3D Renderings Graphic Design services Port Orange, A (386) 256-8978 Port Charlotte, FI (941) 275-9931 www.bluestreamdesignstudio.com 'CAD@bluestreamdesignstudio.com J m Lu U n J M Z J M-I u- Ln I— U o_j a H 3: U-) U) l.— Ce O In 0- III! ��Cail �z/ Y I p rrr YQ m ::3 Im Design and layout or concepts for this design were provided to Bluestream Design Studio by the builder shown. Any similarities to other plans or blueprints is solely the responsibility of the builder. Plans may not be reproduced or copied without the express written consent of the Builder shown. DATE 2/28/18 DESIGN BY: LBB CHECKED BY: TMB JOB NO. MADISONKW3CA REV DESCRIPTION I P105/19/17 2 P2 06/26/17 3 P3 06/30/17 4 P4 07/05/17 5 P5 07/07/17 6 P6 07/17/17 7 P7 09/18/17 8 I W ' Z L Q is J U Y I Lu CM W J ` [)f LL W U �0Of t z 0 W, — �U� a aN0 SHEET Al FOUNDTION SCALE: 1/4" = 1'-0" 20F$ IR Per 17 TYPE DESIGNATION e•UNFILLED FFILLEFFlDFF��---WIIHGROt �'rtM��UDL�IM�CTAWm GRFRAVIAT 8F16-1 B/1 T CASTCRETE PRECAST 0F* NGMINN. WIGiM LWANTT'GFM6FaLDTOPGF AGDEDR LINTEL SCHEDULE IfGRINNL HEIGHT GOMP09IE4ll1IF1 FGR wuFr LGAD T FIE WMI'MTE nT rav w com"os"! U- NIELMIN.ItIpEQp NTGIEAR PL.C!OGM.U. •-'• c+IGOr x � 6HEL0P➢DEDRES°RAT Fora 5'-10"overall lend U-lintel Type 8Fl6-IB/1T: RCTroMGFu-LINT&F VrrY Safe superimposed gravity load =4360 PLY 1WrTWREINFORGNG Safe superimposed uplift load =2080 PLF P 1361)1111 6 6 �J N041N1W107. (SEE HEINFORGNGSCHEODLE) Sat Superimposed lateral load =339 PLY Beam Safe Applied Safe Applied Composite Gravity Gravity Uplift Uplift Load Load Load Load OY-8" 8F16-1B-IT 6113 <1000 3060 <500 O4'41 8F16-IB-IT 6113 <1000 3060 <500 4'-6" 8F16-1B-lT 6113 <1000 2707 <500 O4'.6' 8F16-1B-IT 6113 <1000 2707 <500 (� 4'4- 8F16-1B-IT 5365 <1000 2276 <500 OY-6" 8F16-1B-IT 4360 <1000 2080 <500 7 T-10" 81716-13-1T 4360 <1000 2080 <500 O6'-2" 8F16-1B-1T 3480 <1000 1868 <500 OT-4" 8F16-1B-lT 2661 <1000 1624 <500 ]0 7'4" 81716-1B-1T 2661 <1000 1624 <500 11 T-8" 81716-1B-1T 1843 <1000 1136 <500 12 81-01, 8F16-1B-IT 1843 <1000 1136 <500 13 T-4" SF12-1B-IT 1245 <1000 708 <500 14 10'-4" 8F16-lB-lT 1533 <1000 916 <500 IS 10'-8" 8F16-iB-IT 1366 <1000 800 <500 16 12'-8" 81716-1B-1T 1075 <1000 607 <500 0IT-4" 0 8F12-1B-IT 548 <1000 263 <500 PRESTRESSED 18 18-81, 8F16-1B-IT 750 <1000 348 <500 PRESTRESSED 19 O M I N M aB I Ceiling: 1/2" thick stucco on 3/8" hi -rib lath attached to horizontal and vertical wood framing with nails or staples @ 8" o.c. to provide no less than 1-3/4" penetration into horizontal wood framing and 3/4" penetration into vertical wood framing members Per ASTM C1063 and Stucco - ASTM C926 96W1% OPENING PROTECTION OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED. OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1-3/8" THICK, SOLID OR HONEYCOMB CORE STEEL DOORS NOT LESS THAN 1-3/8" THICK, OR 20-MINUTE FlRE-RATED DOORS. Ceiling: 1/2" thick stucco on 3/8" hi -rib lath attached to horizontal and vertical wood framing with nails or staples @ 8" o.c. to provide no less than 1-3/4" penetration into horizontal wood framing and 3/4" penetration into vertical wood framing members Per ASTM C1063 and Stucco - ASTM C926 9'-811 16' 8" 20'-01, 15'-4" 8'-8" Y-2" 4'-1Off -4" 17'-411 '4' 2'-6" 4r_6" 81.41E 18 ■ ■■ ■ --------------------------------------- -- I 1 I 1 I I I I I 1 I I 16 ; LANAI ; 16 8'-0" FLAT CLG AFF I I 81 91-011 6-4" 31-41' ;8 I I I I � I I I I I " O4 11 O well purnp o i pad SH 25 EGRESS I 6068 BP SGD 1 SH 35 EGRESS W. _ (2)SIMPSON O HETA20 Ilz d- I I lice N ( 1 I III it O 00 op 1 01 `\ 1 it 1 if N 13'-0 1/2" - 1 -7 1/2' 16'-7" 3'-0 1/2 EDR OM #2 BAT 2 T-1)" FLAT CLG IL " T-0" FLAT ® G \\ FAMILY ROOM ' MASTETV SUITE VAULT CLG / ■ `` Oi 8'-0" FLM"C CLG N w O 11 M \ - /M � 11 - ■ p�O 8 306'ii1 if1I"II" ■ NfE�r-n-'\I 11 '-0323-71 IfBEDROOM yc�xv' O #3 S'-0"F TCLG 3068 ' 1 F-6 1/2 2-Y 12'-411 4 -3 1 5 -5 LA waG FAUXCO�ELO 3068 -iV. ABOVE r' - ,T' TERT P 1'I1III R&S tf, v ID r--- ------- , ■■ if\I "MASTERBATI L---� Of I 1 DW I 1247,29' If rwt"'ywsE 1 isIrroc,a \ o G r ■ ■ ■ i i 8'-0" FLA CLG 8'-1" BRG WALL WIC N h S SC -1 lk\ r o ;KITCHEN 1 it N N n a� R-n INMIL,�TIoy 12 W01 V VAULTCLG c HOOD 91-81' 12'-4" 2'-511 6'- /2 1 4'_01 4'_7" t R&s 6'-5 1/2" �� 6r_711 ------ , ■ SIMPSON HTS20 20 MIN. FIRE RATE 1 ST / `� 1 r , 1 ii , , 4 -7 I n 2 -0 r ` N CONNECTED TO SELF CLOSING 6" RISER I ' r ISLAND r \ r �, ^' -4 -5 1 - I e " KN};E(�'E4LL 42" HIGH EACH TRUSS _ _ _ _ _ 12" TREAD - rr - " I, - -1 22 X 54 �' I M F t ' FLAT TOP ` M ` ALONG FRAMED I . 1 ' ATT1�L0CESS I til `` 0 11 I LL ■ BEARING WALLS `` 3'-g`a12' 4'-/ E' - 1/21 1 U.N.O t=-------- �'' r r \ RECESS ¢`� 11 n ¢All TUB REMOVE EXISTING CONCRETE ,�y `( GARAGE w AND DIRT. (3X2)it5 BAR MAT ¢ c _ _ n O 3 vn a j REPLACE CONCRETE ON a N M ' aOGARAGE 8'-0" FLAT CLG AFF O p FLOOR AND VOIDAREA �, WITH 5500 PSI - ■ MAXIMIZER 30' S" 2'-411 14'-3n \\ I 13'-0W2" ■ ------------------ -----------------SIMPSONHTS20 --- z / `\ I II r--- 1 ' I -' - EACH 1 o H a ` of LIVING BOOM ' i TRUSS EACH TRUSS ' ' C DINING ` � ' 8'.011 FLAT CLG _ �' I ALONG FRAMED I � 3 VAULT CLG - � I n BEARING WALLS ■ i GIRDER U.N.O ---- ----- -------------------------------- --- -- 1 ' (2) SIMPSON It n' I HETA 20 301-5" PI POST ' CH NGE `' u If ON if �' ' ' I D4 n.3 I I EV 11 CHANGE' HETA 0 ' (2)3068 ELEV " 8'X8'OHD 16'X8'OHD 17 O n " - V I I t -yy1 n SH36 " 7 'u i 2 -() 7 SH 35 EGRESS O ' 13 SIDE PORCH BEAM (1) CONIC. LINTEL W/ 4 COURSE BLOCK ABOVE SET BTM @ 7 4' AFF 5 I I 1 ' I I ENTRY 1 1 SIDE PORCH B (1) CONC. LINTEL O W/ 4 CO E BLOCK ABOVE TOP @ 10'-911 AFF i i 10'-8" FLAT CLG AFF j "T BTM @ T-4" AFF > 12 WOOD CLG TOP no 10'-9"AFF VINYL RAELING 16"XI6" COL. BLK O FRONT PORCH BEAM (1) 'ONC TEL LINTEL (4) #1 REBAR VERT. W/ 2 COURSE BLOCK ABOVE SET BTM @ 8'-9" AFF TOP @ 10'-9" AFF 8'-01, 2'-0" 16'-011 T-8" '-4' 6' 4" 4' 71-8" -4' 4'.611 5'-011 3 F-4" 18'-011 I T-4" 61'-811 N 0 �o O N WALL LE(;END SYMBOL REPRESENTS CMU WALL - 8" (U.N.O.) BRG. HT. @ 8'-0" AFF INTERIOR SIDE TO PAINTED SMOOTH FINISH EXTERIOR SIDE TO BE STUCCO COATED CMU ®CMU WALL - 8" (U.N.O.) BRG. HT. @ 8'-0" AFF 1/2" GYP. BD. OVER 1x2 P.T. FURRING STRIPS OVER SPRAY APPLIED FOAM INSULATION OVER 8" CMU WALL. EXTERIOR SIDE TO BE STUCCO COATED CMU CMU WALL - 8" (U.N.O.) BRG. HT. @ 10'-8" AFF 1/2" GYP. BD. OVER 1x2 P.T. FURRING STRIPS OVER SPRAY APPLIED FOAM INSULATION OVER 8" CMU WALL. EXTERIOR SIDE TO BE STUCCO COATED CMU ° a CMU KNEEWALL - 8" (U.N.O.) BRG. HT. @ 3'-0" AFF BOTH SIDES TO BE STUCCO COATED CMU BRG. PARTITION WALL - 4" (U.N.O.) 1/2" GYP. BD. ON EACH SIDE OF 2x4 WD. STUDS @ 16" O.C. Q=2= BRG. PARTITION WALL - 6" (U.N.O.) 1/2" GYP. BD. ON EACH SIDE OF 2x4 WD. STUDS @ 16" O.C. "f x r ) ex v n. I� SQUARE FOOTAGE LIVING 17950 GARAGE 674 LANAI 240 ENTRY 90 TOT LIVING 15,600 C.F. BUILDING CRITERIA BASIC WIND SPEED, Vult 170 MPH BASIC WIND SPEED, Vasd 132 MPH RISK CATEGORY WIND EXPOSURE C INTERNAL PRESSURE COEFFICIENT +/-0.18 COMPONENT AND CLADDING ASD WIND PRESSURE (PSF) to FULLY ENCLOSED STRUCTURE IMPACT GLASS: X APPROVED SHUTTERS BOTH MAIN WINDFACE RESISTING SYSTEM PER TABLE 1609.6A TRUSS DESIGN SHALL BE IN COMPLIANCE WITH WIND DESIGN METHOD ASCE 7-10 AND THE FBC 2014 5th EDITION TTuL'ifRN',c� '_ W A T E R- A I R- L A N D 1040 Harbour Drake Dr. chdsbeers@byu.net 941-628-0635 Punta Gorda, Florida 33983 fax 413-687-9013 .`�OFESSID 2 •e * HER 0- If llfs94 ........% `% (rr9 DATE Although every effort is made to ensure the accuracy of these plans it is the responsibility of the builder to verify all dimensions, details and specifications shown. Bluestream Design Studio will not be held liable for any errors or omissions on these plans. BLU ESTREAM DS DESIGN STUDIO Residerxal CAD Draftin 3D Ren erin f Graphic Design ervices Port Orange, FI (386) 256-8978 Port Charlotte, FI (941) 275-9931 www.bluestreamdesignstudio.com CAD@bluestreamdesignstudio.com J m LLJ M U to J � M Z J U_ Ln O J CL N V) � O Ln a i •• Design and layout or concepts for this design were provided to Bluestream Design Studio by the builder shown. Any similarities to other plans or blueprints is solely the responsibility of the builder. Plans may not be reproduced or copied without the express written consent of the Builder shown. DATE 2/28/18 DESIGN BY: LBB CHECKED BY: TMB JOB NO. MAMCInaIInAni-A REV I DESCRIPTION W ' � Z g U Y W LL >M Y -flwv U �Q� O C p N 0 G SHEET A2 FLOOR PLAN SCALE: 1/4" = V-O" '� 3OF8 W U 52' 0" 9' 8" 16' 8" 20' 0" 154" y✓j v v v w w w w v CJ1 CJ1 J a 159# UPLt73 J a ^ > J > UP 3 M O217# UeLj 217# UPLIFT �J CD LIFT 285# UPLIFT ><o CV (V D03 # UPLIFT 1637# UPLIFT (2)HETA 20 (DO D02 UPLIFT 857# UPLIFT D01 a ¢ a )1 CJtTUP . V ¢159# IN r`n V� 11P U _ 159# U CJ a CJ3 v # C N �O M N 01CJ5 217# UPLIFT `�° `�° "�' '- CJ5 U UPLIFT ,nIIIIIII 285# UPLIFT _ 4 0 EJ7 EJ7 UPLIFT O 206# UPLIFT O EJ7Q N /:�5t EJ7 UPLIFT 206# UPLIFT M Q O EJ7 VO. EJ7 LIFT 7' 0" 20�Jk(yIPLIFT N 18' 0" EJ7 EJ7 1 O 6 UPLIFT 206# UPLIFT EJ7 =4= X EJ7 UPLIFT 206# UPLIFT EJ7 X EJ7 60 UPLIFT 206# UPLIFT 60 LO 2 N p EJ7 EJ7 5# UPLIFT 206# UPLIFT U U i0 EJ71 EJ7 141= 1# UPLIFT 206# UPLIFT CJ2 CJ2 EJ71 CJ1 J EJ7 ZD ri 206# UPLIFT w CJ2 Jg _ n J 1# UPL a a a a a a J a 159# 11 LI N 1 at EJ7 u M 181 �P.ZM N N U E] U 217j UP EJ7 B09 # UPLIFT 206# UPLIFT 4' 0" 72# UPLIFT B08 EJ7 206# UPLIFT 272# UPLIFT 1379# UPLIFT 2 607 EJ7 284# UPLIFT 1365# UPLIFT 13' 024q!P'UPLIFT 306 EJ7 92# UPLIFT 1157# UPLIFT 206# UPLIFT _ N V N o BOS EJ7 # UPLIFT O 670# UPLIFT in o B04 N EJ7 �' 1 O 0# UPLIFT 1348# UPLIFT 2 HTSIN BO II\ EJ7 6# UPLIFT 1089# UPLIFT 206# UPLIFT B02 CJS 2225# U LIFr 285# UPLIFT V07 f� CJ3 2ll UP UPLIFT O J J J1 J Ja LQ ff ih CJ1D P # CJ1 159# U LIFT Ix D E02 I tiv _` xk M In N 7_1LfJ lA to IA In m C) 0 W Lu LU Lu Lu W W uj Lu Lu uj � U U w Lu w w w w w w w w w w w w U U U E01 _ jFr; PL - O 9 # o Ln p Ln J1 i7 J1 (2)HETA 20 1 PL 1 1 .�.) J J J J 5 5 -Mi 5 My� U :k w # w' Lu u 4 4tI U `2 N H ti H ti ti � 31' 4" 1 1 1 8' 12' 4" 61' 8" Typical End Detail N.T.S. 12 5�� I4-1/16" PRE-ENGINEERED WOOD TRUSSES 2X4 PROPOSED ROOF PLAN 5/12 ROOF PITCH,12"OVERHANG,PLUMB CUT FASCIA SHINGLE ROOF NOTE: GC TO VERIFY ROOF PITCH, OVERHANG AND ROOF FINISH CONNECTOR SCHEDULE NAILSTSIZE PER CONNEECTIOON (lOd NAILS ARE 1-1/2" LONG FOR SINGLE MEMBER TRUSS) CONNECTOR CONNECTOR UPLIFT FORCE LATERAL LOAD PARALLEL TO LATERAL LOAD PARALLEL TO BEAM F1 BEAM F2 O TYPICAL TRUSS TO MASONRY WALL (1) SIMPSON HETA20 1810 340 725 (12) 10d X 1-1/2" NAILS EA. STRAP (2)SIM (2) SIMPSON 2500 1225 1520 (16) 10d X 1-1/2" NAILS EA. STRAP ADD 2X4 SCAB 12" LONG TO 1PLY TRUSS 8-16d NAILS O TYPICAL TRUSS TO WOOD FRAME BRG SIMPSON HTS20 1450 -------- ---------- (24) 10d X 1-1/2" NAILS EA. STRAP WALL (2) SIMPSON HTS20 2900 --------- ---------- (48) 10d X 1-1/2" O TYPICAL TRUSS TO WOOD FRAME WALL SIMPSON MGT 3965 ---------- ---------- (22) 10d NAILS EA. STRAP O TYPICAL TRUSS TO MASONRY WALL SIMPSON VGT 4940 TO GIRDER: 32-SDSn"x3 TO WALL: 2-5/8 2 PLY (MIN.) ' TRUSS BRACING ST ONE TRUSS B- OVERLAP SPACE MINIMUM (2) 16d PER JOINT L-MINIMUM 2X4 SYP OR SPACED AT 15-0' MAX. SPF TRUSS BRACING TRUSS BRACING OVERLAP DETAIL N.T.S. I tch Legend G.C. TO PROVIDE BLOCIONG TO COMPLY WITH APA RECOMMENDATIONS F'OR SPAN RATING OF 7/18' OSB NOTE: BIRDSEYE VIEW OR ROOF TRUSS LAYOUT IS FOR PERMIT PURPOSES ONLY. I fie root truss layout or oiraseye view or the TOOT aepictea on tnese plans are schematic designs only. If found that the final truss manufacturer's layout drawings differ in configuration or bearing points from this plan, it is the responsibility of the general contractor to have said truss manufacturer's drawings reviewed and approved by the structural engineer of record, before the construction of the roof system. The drafting company and the engineer of record will not be held liable for any discrepancies between this schematic roof truss layout / birdseye view and the final manufacturer's layout. Z L LI ROOF SHEETING ATTACHMENT DETAIL 1. MINIMUM NAIL SIZE = 8d RING SHANK (MIN. 2" LONG) 2. MINIMUM SCREW SIZE = #8 X 2" 3. MINIMUM SHEATHING THICKNESS 15132" CDX PLYWOOD 4. USE NAILS OR SCREWS BASED ON PRESSURE FOR ROOF STATED IN PERMIT INFO BOX ON THESE PLANS FOR ZONE 3 3 20'-0' MAX 20'-0' MAX � �� CONTINUOUS 80 CNOtA SEE DETAIL � ` BRACING 2X4 MI 1. SEE DETAIL S O B aq ill I I OWN NEW NOTE: 1) SEE TRUSS MANUFACTURER'S TRUSS ENGINEERING CUT SHEETS FOR ADDITIONAL PERMANENT BRACING THAT MAY BE REQUIRED 2) 'T' BRACING MAY BE USED IN PLACE OF PERMANENT BRACING W Z L L] LLJ J m Q 0 L TOP h BOTTOM CHORD GABLE END BRACING O 4'-V O.C. MAX FOR FIRST (4) ROWS OF TRUSSES TO PERMANENT TRUSS BRACING REQUIRED N.T.S. 17 MI R VETLMfl W A T E R- A I R- L A N D 1040 Harbour Drake Dr. chdsbeers@byu.net 941-628-0635 Punta Gorda, Florida 33983 fax 41B-RR7-At11� QNER O m'2.v`lz: z 3HRIS '(HER D. BEER - .� FLORIta ;IC L*0,, ;54 94 DATE Although every effort is made to ensure the accuracy of these plans it is the responsibility of the builder to verify all dimensions, details and specifications shown. Bluestream Design Studio will not be held liable for any errors or omissions on these plans. BLUESTREAM %05 DESIGN STUDIO Residential CAD Draftin 3D Ren erin s Graphic Design Services Port Orange, FI (386)256-8978 Port Charlotte, FI (941) 275-9931 www. bl uestreamdesig nstud io. com CAD@bl uestream desig nstud io. com J M U LMI) J d' M � Z J LL LLJ H U 0 J a � in Ln O in M V z= W I W Cr Design and layout or concepts for this design were provided to Bluestream Design Studio by the builder shown. Any similarities to other plans or blueprints is solely the responsibility of the builder. Plans may not be reproduced or copied without the express written consent of the Builder shown. DATE 2/28/18 DESIGN BY: LBB CHECKED BY: TMB JOB NO. MADISONKW3CA REV DESCRIPTION 1 P1 05/19/17 2 P2 06/26/17 3 P3 06/30/17 4 P4 07/05/17 5 P5 07/07/17 6 P6 07/17/17 7 P7 7 09/18/1 6 L.L W ' Z L Q M J U Y I W C� Lu J 0 LL Y �LuCW) �OOf Z Lu 0-1QOf 0 0 Lj SHEET A6 ROOF PLAN SCALE: 1/4" = 1'-0" 6OF8 IR Pet