HomeMy WebLinkAboutConstruction Plan.4 w- General Notes A. CONCRETE & FOUNDATION DESIGN: 1. ALL CONCRETE GRADE BEAMS AND FOOTINGS SHALL BE 3000 PSI MINIMUM. 2. ALL CONCRETE FILLED SUPPORTED SLABS SHALL BE 2500 PSI MINIMUM, 3 1/2" NOMINAL THICKNESS. 3. FIBERMESH (3/4" PER CUBIC YARD MIN) MEETING APPROPRIATE ACI AND ASTM REQUIREMENTS MAY BE USED IN LIEU OF WELDED WIRE MESH 4. ALL SLABS ON GRADE SHALL BE 4" THICK WITH FIBERMESH. 5. ALL REINFORCING SHALL CONFORM TO ASTM A615, BE GRADE 60 (60 KSI MIN.) DEFORMED BARS, #3 BARS MAY BE GRADE 40 6. ALL OVER POUR CONCRETE FILLED SUPPORTED SLABS SHALL BE 3000 PSI MIN., 2" MINIMUM. THICKNESS. 7. SOIL BEARING PRESSURE SHALL BE A MINIMUM OF 1500 PSF. 8. THE CONCRETE SHALL CONFORM TO ASTM C94 FOR THE FOLLOWING: OPC (PORTLAND CEMENT TYPE 1,- ASTM C 150). AGGREGATES - #6 STONE, ASTM C 33 SIZE NO. 67 LESS THAN 3/4". AIR ENTRAINING +/-1% - ASTM C 260. WATER REDUCING AGENT - ASTM C 494. CLEAN POTABLE WATER. OTHER ADMA'TURES SHALL NOT BE PERMITTED. 9. METAL WELDED WIRE SHALL CONFORM TO ASTM A 185. 10. PREPARE & PLACE CONCRETE ACCORDING TO AMERICAN CONCRETE INSTITUTE MANUAL STANDARD PRACTICE, PART 1, 2, & 3 ALONG WITH HOT WEATHER CONDITIONS RECOMMENDATIONS. 11. IF UTILIZING EXISTING CONCRETE FOR FOUNDATION, CONCRETE SHALL BE A MINIMUM OF 4" IN THICKNESS, VISIBLY FREE OF ANY STRUCTURAL EXCESSIVE CRACKING, SPALLING OR OTHER DETERIORATION. B. MASONRY: I. CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED ON TYPE M OR S MORTAR. 2. ALL MORTAR SHALL BE OF TYPE M OR S. 3.. ALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE MAXIMUM COARSE AGGREGATE SIZE OF 3/8". 4.PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING REINFORCEMENT WHEN GROUT POUR EXCEEDS 5'-0" IN HEIGHT. C. ALUMINUM: 2. HEX BOLTS HAS TO BE ASTM A 325, PLATED WITH STANDARD FLAT WASHERS AND NUTS. 3. ALL CONCRETE SCREWS SHALL BE, SIT PSON, HILTI, RAWL, TAPCON, REDHEAD, DYNABOLT, PORTECT OR APPROVED EQUAL. 4. ALL METAL TIES AND ASSOCIATED ACCESSORIES SHALL BE HOT DIPPED GALVANIZED. 5. ALL LAG BOLTS SHALL HAVE A MINIMUM EMBEDMENT OF 8X BOLT DIAMETER INTO STRUCTURAL FRAMING (G=.42 MIN.). 6. LAG BOLTS AND SCREWS INTO WOOD FRAMING SHALL BE PROVIDED WITH PILOT HOLES HAVING A DIAMETER NOT GREATER THAN 70 PERCENT OF THE THREAD DIAMETER OF THE BOLT OR SCREW. ALL LAG BOLTS AND SCREWS SHALL BE INSERTED IN PILOT HOLES BY TURNING AND UNDER NO CIRCUMSTANCES BY DRIVING WITH A HAMMER. 7. ALL EXPANSION ANCHORS SHALL BE DESIGNED IN ACCORDANCE WITH THE SPECIFIC MANUFACTURER'S REQUIREMENTS AND ALLOWABLE LOADS AND SHALL ONLY BE APPLIED IN CONDITIONS ACCEPTABLE TO MANUFACTURER. FASTENERS SHALL BE A MINIMUM OF SAE GRADE #5 OR BETTER ZINC PLATED. S. ALL FASTENERS CONNECTING ALUMINUM COMPONENTS OR PRESSURE TREATED LUMBER ARE STAINLESS STEEL TYPE 300 18-8, UNLESS MANUFACTURER GALVANIZED BOLTS SPECIFIES FOR USE WITH ACQ PRESSURE TREATED WOOD, OR OTHERWISE NOTED ON PLANS. 9. ALL FASTENERS SHALL COMPLY WITH ASTM A153. I O.ALL CONNECTORS SHALL COMPLY WITH ASTM A653 CLASS G-185. 11. FOR SMS, THE MINIMUM CENTER -TO -CENTER SPACING SHALL BE 3/4" AND MINIMUM CENTER -TO -EDGE SHALL BE 1/2" UNLESS NOTED OTHER WISE. E. REFERENCE STANDARDS: ASTM E 119 ASTME 1300 ASCE 7-10 AA ASM35, AND SPEC. FOR ALUMINUM PART 1-A, & 1-B ASTM C94 ASTM C150 ASTM C33 ASTM C260 ASTM C494 ASTM A615 ASTM A185 FLORIDA BUILDING CODE 5th EDITION (CHAPTERS 16,20 & 23). 2010 ALUMINUM DESIGN MANUAL L ALL STRUCTURAL ALUMINUM SHALL CONFORM TO THE MINIMUM REQUIREMENTS OF 6005-T5 FOR ALLOY WITH A F. ABBREVIATIONS: MINIMUM THICKNESS OF 0.040" FOR SUPPORTING MEMBERS. THE FOLLOWING LIST OF ABBREVIATIONS IS NOT INTENDED 2. WHERE KICK PLATES ARE USED A MINIMUM THICKNESS OF TO REPRESENT ALL THOSE USED ON THESE DRAWINGS, BUT 0.024" SHALL APPLY. 3. STRUCTURAL ALUMINUM DESIGN CONFORMS TO SUPPLEMENT THE MORE COMMON ABBREVIATIONS. TO "PART 1-A - SPECIFICATIONS FOR ALUMINUM 1. TYP --TYPICAL 2. SIM -- SIMILAR STRUCTURES - ALLOWABLE STRESS 3. UON -- UNLESS OTHERWISE NOTED DESIGN' OR "PART 1-13 - SPECIFICATIONS FOR ALUMINUM 4. CONT -- CONTINUOUS STRUCTURES - BUILDING LOAD AND RESISTANCE FACTOR 5. VIF -- VERIFY IN FIELD DESIGN" OF THE ALUMINUM DESIGN MANUAL 2010 PREPARED BY THE ALUMINUM ASSOCIATION, INC.WASHINGTON D.C. THE G. RESPONSIBILITY: FLORIDA BUILDING CODE 5th EDITION ( CHAPTER 16 STRUCTURAL DESIGN &CHAPTER 20 ALUMINUM). 1. ALL SITE WORK SHALL BE PERFORMED BY A LICENSED 4. WHERE ALUMINUM COMES INTO CONTACT WITH STEEL, OR CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDINGCODES, PRESSURE TREATED LUMBER PROVIDE DIELECTRIC LOCAL ORDINANCES, ETC. SEPARATION. 2. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND DETAILS, 5. ALUMINUM MEMBERS SHALL BE STITCHWITH NO LESS NOTIFYING ENGINEER OF ANY DISCREPANCIES BETWEENED THAN #10 SMS 6" FROM THE ENDS AND 12" ON CENTER, IF DRAWINGS, FABRICATED ITEMS, OR ACTUAL FIELD USING #12 SPACING MAYBE 24" ON CENTER, CONDITIONS. 6. VINYL AND ACRYLIC PANELS SHALL BE REMOVABLE. THEY 3. THESE DRAWINGS REPRESENT THE ACCEPTABILITY OF THE SHALL BE IDENTIFIED WITH A DECAL ESSENTIALLY STATING SUNROOM7 ROOM ADDITION ELEMENTS AS PROVIDED BY THE "REMOVABLE PANEL SHALL BE REMOVED WHEN WIND CONTRACTOR. SPEEDS EXCEED 75 MPH" . DECAL SHALL BE PLACED SO IT IS 4, ALL DETAILS ON THESE DRAWINGS ARE ENGINEERED BASED VISIBLE WHEN PANEL IS INSTALLED. ON INFORMATION PROVIDED By THE CONTRACTOR AND 7. 1 "X2"X045" NON-STRUCTURAL MEMBERS SHALL BE MANUFACTURER. ATTACHED TO HOST WITH XONCRETETE EMBEDMENT & 24" 5. ANY DETAILS NOT SHOWN ARE TO BE ENGINEERED BY A C0 O.C. MASONRY SCREW FOR C &EQUIVALENT SIZE LICENSED P.E. IN ACCORDANCE WITH STANDARD WOOD SCREW WHEN IN WOOD & #10X 1/2" EMBEDMENT SMS ENGINEERING PRACTICES. OR TEK SCREWS IN ALUMINUM MP.MRRR c 'rvoTr e T D. FASTENERS: 1. ALL LAG BOLTS SHALL CONFORM TO STAINLESS STEEL TYPE 300 18-8, WITH STANDARD FLAT WASHER UN,LESS MANUFACTURER GALVANIZES BOLTS SPECIFIES FOR USE WITH ACQ PRESSURE TREATED WOOD. H. MISCELLANEOUS: 1. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. I: THE EXISTING STRUCTURE IS ONE OF THESE, A SEPARATE 4TH WALL SUPPORT SYSTEM MUST BE ENGINEERED SO THAT NO ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. 2. IF ENCLOSURE CONTAINS A SWIMMING POOL OR SPA, THE ENCLOSURE SHALL COMPLY WITH RESIDENTIAL SWIMMING BARRIER REQUIREMENTS OF THE FBCR 5th EDITION R 4501.17 IN ITS ENTIRETY, 3. DOOR LOCATIONS MAY BE DETERMINED IN THE FIELD BY CONTRACTOR. 4. IF PAVERS ARE UNDER ALUMINUM MEMBERS THEY SHALL HAVE EPDXY ADHESIVE TO CONCRETE OR IF USING GROUT, ENSURE BONDING AGENT IS USED FIRST. 5. SCREENING MATERIAL, SHALL BE 18X14X0.013 OR EQUIVALENT DENSITY SCREEN MESH ONLY UNLESS NOTED ON DRAWING S-2. 6. PLEASE NOTE: 2x2 QYP) DIAGONAL BRACING SHALL BE 2"X2"X0.055" MATERIAL, UNLESS OTHERWISE NOTED ON S-2. 7. ALL ALUMINUM SCREENED ENCLOSURES SHALL BE DESIGNED SPECIFICALLY FOR THE APPLICATION STATED IN RULE 61G20-1-002: TO REMOVE SCREEN PANELS IN THE EVENT OF FORECAST WINDS THAT EXCEED 75 MPH. LABELS SHALL BE PLACED ON CHAIR RAIL MEMBERS ON ALL SCREEN WALLS IN A LOCATION THAT CAN BE EASILY SEEN AND FOR ALL PANELS ABOVE THE DESIGNED CHAIR RAIL ON ALL SCREEN WALLS SHALL BE CUT AS PRESCRIBED IN THE RULE AND THE CONTRACTOR SHALL COMPLY WITH ALL THE REQUIREMENTS STATED IN RULE 61Q20-1,002 AND SECTION 19 LAWS OF FLORIDA, 553.76, 553.77., ONLY APPLIES IF SHOWN ON PAGE S-2 DRAWING PAGE. DESIGN DATA: I. ULTIMATE DESIGN WIND SPEED Vult, (3 SECOND GUST): NOMINAL DESIGN WIND SPEED Vasd: 2. RISK CATEGORY: 3. WIND EXPOSURE: 4. WIND LOADS: SCREEN ROOF: 8 PSF SCREEN WALLS: 27 PSF SOLID ROOF (SCREEN WALL): N/A rile COPS' CONCEALED FASTENERS OR ATTACHMENTS ARE THE RESPONSIBILITY OF THE CONTRACTOR OF RECORD I-HESE PLANS a►dD A'I L PROPOSED 'NOR, ARE SUBJECT TO ANY CORRECTIONS REQUIRED BY FIELD INSPECTORS THAT I':�Y BE NECEUARY INORDER, M. ;. .'COMPLY MIDI N ILU iVPLICA_.* = CODES. 140 MPH 108 MPH 1 B 5. FACTOR APPLIED TO SCREEN WIND LOADS FOR 18X14XO.013 OR EQUIVALENT DENSITY SCREEN MESH: 0.88 6. FACTOR APPLIED TO SCREEN WIND LOADS FOR ALLOWABLE STRESS DESIGN: 0.6 7. LIVE LOAD: 3001b. VERTICAL DOWNLOAD ON PRIMARY SCREEN ENCLOSURE MEMBERS. 2001b. VERTICAL DOWNLOAD ON SCREEN ENCLOSURE PURLINS. 8. EXISTING 8"X8" LINEAL FOOTING OR 4" MONOLITHIC SLAB SHALL BE ADEQUATE TO RESIST THE UPLOADS FOR THE PROPOSED STRUCTURE. 9. SCREEN ROOF TYPE : MANSARD 10. SOLID ROOF TYPE: N/A ALUMINUM STRUCTURAL MEMBERS HOLLOW SECTIONS 2 x 2:---------------------------------------2" x 2" x 0.044„ 2 x 3:---------------------------------------2" x 3" x 0.050„ 2 x 4:---------------------------------------2" x 4" x 0.050„ 2 x 5:---------------------------------------2" x 5" x 0.050„ OPEN BACK SECTIONS 1 x 2:---------------------------------------- V x 2" x 0.040„ 1 x 3:----------------------------------------1" x 3" x 0.045„ SNAP SECTIONS 2 x 2 Snap: ---------------------------------- 2" x 2" x 0,045„ 2 x 3 Snap:---------------------------------2" x 3" x 0.050„ 2 x 4 Snap:--------------------------------- 2" x 4" x 0.045„ SELF MATING fSMB 2 x 4 SMB:------------- •-------- 2" x 4" x 0.044" x 0.100" 2 x 5 SMB:------------- --------- 2" x 5" x 0.050" x 0.118" 2 x 6 SMB:---------------------- 2" x 6" x 0.050" x 0.120" 2 x 7 SMB:------------- --------- 2" x 7" x 0.057" x 0.120„ 2 x 8 SMB:------------- •-------- 2" x 8" x 0.072" x 0.224" 2 x 9 SMB:------------- --------- 2" x 9" x 0.072" x 0.224„ 2 x 10 SMB:------------------- 2" x 10" x 0.092" x 0.374" t 001 - 0(C STi. LiTCZE COUN- TY BITu ING DIVrSYON REW-E-WED FOR CQ91JANCE RE VIEit �Y DATE I� PLANS AND PERMIT MUST BE KEPT ON JOB OR Nu TN'SPECTIONWILL BE MADE. 'i_xus iEBY QRTIFY THAT I HAVE REVIEWED THIS PLAN AND FOUNp IT TO BE IN CowLIAIICE WITH AS�CE7,10,, & FBC 5th EDITION. C" ...... � y,uo-v v��J`C a'o-6 tf Oe } o• wO 70,,(37 c OF o �� 0 STAT ®o 0 I;NCirf* V4Dfa$4C�I@RD: David W. Smith P.E. FLORIDA LICENSE: 53608 Thomas L. Hanson P.E. FLORIDA LICENSE: 38654 Mark :R. Dunn P.E. FLORIDA LICENSE: 73968 Joel Falardeau P.E. FLORIDA LICENSE: 70667 Erik Stuart P.E. FLORIDA LICENSE: 77605 FBC Plans & Engineering Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph# (813)788-5314 Fax# 1-(866)824-7894 E-mail-erb@fbcplans.com Website-Www.fbcplans, co m C.O.A. #29054 DATE: 7-25-2017 DRAWN BY: TLK REVISION: DATE: RO 1 RO 2 RO 3 RO 4 PROM, CT ADDRESS: HAUPT 5404 CITRUS AVE FT. PIERCE, FL 34982 ONTRACTOR: V.H. EXTERIORS 543 NW WAVERLY CIR PORT ST LUCIE, FL 34983 NOTES S-1 THIS DOCUMENT SHALL NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT EXPRESSED WRITTEN PERMISSION OF TRAC DESIGN, I I HEREBY CERTIFY THAT I HAVE REVIEWED THIS PLAN -AND FOUND IT TO BE IN NOTE: DOOR LOCATION MAYBE COMPLIANCE WITH ASCE7-10, & FBC 5th DETERMINED IN THE FIELD Enit[oNG F,, ,,Julie copy . , tiSE a 0 �p o 10667 s o ° OF T E U ® )OA \� / X 1_x2 m M ::E :�i V) Ln X X X X X X CDcv � 2x2(tyP)N N/2(tCN N O F s—s 1 x 2 H 6,_6„� 1 ,_0„ 3,_6„�3,_�„� S-4 -�I` �I`(ty P ) S-4 \A- J2 1x2 ntv4a"pyL-K`UI-K L PU Davidow§flt'� P.E. FLORIDA LICENSE: 53608 Thomas L. Hanson P.E FLORIDA LICENSE: 38654 Mark R. Dunn P.E. Q0 FLORIDA LICENSE: 73968 I x Joel Falardeau P.E. FLORIDA LICENSE: 70667 N Erik Stuart P.E. X Q0 FLORIDA LICENSE: 77605 FBC Plans & Engineering Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph#(813)788-5314 Fax# 1-(E166)824-7894 E-mail-erb@fbcplans.com W ebsite- Www. fbcplans,co m C.O,A.429054 DATE: 7-25-2017 DRAWN BY: TLK REVISION: DATE: RO 1 RO 2 RO 3 RO 4 PROJECT ADDRESS: HAUPT 5404 CITRUS AVE FT. PIERCE, FL 34982 :ONTRACTOR: V.H. EXTERIORS 543 NW WAVERLY CI PORT ST LUCIE, FL 34983 FLOOR PLAN S-2 THIS DOCUMENT SHALL NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT EXPRESSED WRITTEN PERMISSION OF TRAC DESIGN, LLC 3/16" ALUMINUM GUSSET 2" x_PURLINS (SEE A-1 PLATE FOR SIZE)ATTACHED TO B #14 SMS BEAM w/MIN (4) #10 x 1 Y2" SMS • • • o 1" X 5" OR 7" X6" WIDTH EXTRUDED GUTTER \ e BRACKET(THICKNESS OF LEG @ LAG • o SCREW SHALL BE 0.125" MIN. LONG LEG SHALL • • •\ o \ BE 0.072" MIN) @ EACH BEAM W/ (4) S Sy • • \ #10X3/4" SMS V SPA. INTO GUTTER LIP _��( \ 2" x 2" x 0.045" PB W/ (4)#10X \ • • • • • • 1-1/2' INTO SCREW BOSS & (2) f #12X2-1/2" SMS EA SIDE INTO • ti GUTTER TN eSE�S�'B�� \ � 53 BEAM O OR _r PURLIN O BEAM "B" "N" "S1" "S2" "S3" "W' 2X4 12 4 3/4" 1-1" 16" 3.75" 2X5 12 4 3/4" 1 16" 4.75" 2X6 16 5 1" 1 Z" 19" 5.75" 2X7 20 6 1" 1 1-j" 22" 6.75" 2X8 24 7 1" 11 s' 23" 7.75" 2X9 24 7 1" 18 23" 8.75" 2X10 28 8 1" 1 24" 9.75" NOTES: 1. "N" NUMBER OF SCREWS IN ANY DIRECTION. 2. TOTAL NUMBER OF SCREWSPER JOINT EQUALS 4 TIMES "B". 3. PLATE WIDTH SHALL BE DETERMINED FROM ANGLE OF BEAM AND MIN. SPACE REQUIRED. 4. GUSSET PLATES MAY BE INTERNAL OR EXTERNAL. S. INTERNAL SCREWS FOR PURLIN CONNECTION MAY BE INCLUDED IN TOTAL NUMBER OF SCREWS. 6. GABLE SPLICE WILL HAVE THE SAME PATTERN. B BEAM SPLICE GUSSET DETAIL TYPICAL S' 3 SCALE: NTS EDGE MEMBER 1OX4" SMS INTO SCREW ES FOR EDGE MEMBERS 1.0625" 6063-T6 FLAT PLATE V/ (12)#10X3/4" SMS MIN. 1/2" EDGE DISTANCE) EDGE MEMBER OR PURLIN E X4 SMB BEAMONLY REQUIRES 4"UTTERBRACKETW/ (2)3/8" 4 3147 LAG SNEWS @ 1 SPACING,1/2" EDGE DISTANCE @ EA. GUTTER BRACKET & (1) BRACKET BETWEEN EA. BEAM & (1)1/4" LAG @ 12" O.C. MAX ATTACHING GUTTER TO FASCIA- MIN EMBEDMENT SHALL BE 2" (1) 3/80 X 2" MIN. EMBEDMENT @ BRACKET & 24" O.C. (2) 2" x 2" x Vs" XALUMINUM O THE HOST STRUCTURE SHALL ANGLE W/ (2) #14 x 3/4" SMS EA ANGLE INTO BEAM FASCIA AND ROOF TRUSS ON EA SIDE SYSTEM. CONTRACTOR SHALL VERIFY THIS AND IF OPTIONAL: 2"12"10.062" (4) #14 x 3/4" SMS SMALLER- CONTRACTOR RECEIVING INTO GUTTER SHALL BRING STRUCTURE UP CHANNEL W/ (2) #14X 3/4" EA SIDE TO A 2"X4" FASCIA AND EA SIDE TO COVER EXPOSED ENSURE LESS THAN A T-O" BEAM _. OVERHANG. A GUTTER BRACKET & BEAM ATTACHMENT DETAIL S _ 3 N.T.S. BEAM SCREWS 2" X 4" SMB 6 2" X 5 "SMB 6 2" X 6 "SMB B 2" X 7" SMB 8 2" X 8" SMB 10 2" X 9" SMB 10 2" X 10" SMB 12 FOR SLOPED BEAMS, MAINTAIN ALL SCREW SPACING FROM EDGE OF BEAM 2" x 2" EAVE RAIL SECTION (UNLESS OTHERWISE SHOWN ON S-2) - ATTACHED TO BEAM w/ (3)1OX 2" SMS INTO SCREW BOSS & W/ .125" ANGLE & EAVE MEMBER & UPRIGHT W/ (2) #14X3/4" EA. LEG 1" X 2" OPEN BACK EAVE RAILATTACHED TO UPRIGHT w/(2) #10 x 1 Y2" SMS INTO SCREW BOSS #10 X 1 Y2" SMS 12" C/C #14X 3/4" SCREWS SPACING MAY VARY (SEE TABLE ABOVE) O SELF -MATING BEAM` SHALL BE NOTCHED ® itI FOR UPRIGHT ® ®il� ® 0 i i (MIN) UPRIGHT E ROOF BRACING CONNECTION DETAIL I I S'3 SCALE: N.T.S. `�1 UPRIGHT TO BEAMCONNECTION - ALL WIND ZONES \ S'3 SCALE: NTS 1 f H61inBY-C$RTIFYTHAT I HAVE REVIEWED THIS PLAN�ALND 00 DITTO BE IN CON�PLiAN( W(ITWASOt7.1.0, & FBC 5th • TDITIONX°o°ua°oo°� U 'fie Cray - o s��cErvs� °®g�7 '-o O ° +� e° Np, 70667 PURLIN UPRIGHT WEB LAPPED OVER PURLIN ®"0.a STATE OF «° [tj W/ (4) #10X3/4" SMS EACH SIDE `AO�. /�������' ®//�� o o . -teo'q=� 2" x 2" xO.045" EAVE RAIL MEMBER O\y ENIGIRr� PA ( ft,130pRD: (UNLESS OTHERWISE NOTED ON S-2) ATTACHED TO PURLIN W/ (2) 00, David W. Smith P.E. #10 X 4" SMS THRU SCREW BOSS FLORIDA LICENSE: 53608 Thomas L. Hanson P.E 1"12"10.045" OPEN BACK ATTACHED TO PURLIN W 2 NOTCH POST ASNEEUED FLORIDA LICENSE: 38654 41OX1-1/2" SMS INTO SCREW Mark R. Dunn P.E. Boss 1"72"10.045" OPEN BACK FLORIDA LICENSE: 73968 ATTACHED TO2"X2"X0,045" UPRIGHT Joel Falardeau P.E. EAVE RAIL MEMBER 410311-1/2"SMS FLORIDA LICENSE: 70667 @12"O.0 Erik Stuart P.E. FLORIDA LICENSE: 77605 C SLOPED OR FLAT PURLIN UPRIGHT LAP DETAIL S' 3 SCALE: NTS FBC Plans & Engineering Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph#(813)788-5314 Fax# 1-(866)824-7894 E-mail-erb@fbcplans.com Website-WWw.fbcplans.com C.O.A.429054 DATE: 7-25-2017 DRAWN BY: TLK HINGE LOCATION REVISION; DATE: RO 1 2" x 2" EXTRUSION—,2" x 2" EXTRUSION RO 2 HINGE LOCATION DOOR RO 3 RO 4 PROJECT ADDRESS: HAUPT 5404 CITRUS AVE HINGE LOCATION FT. PIERCE, FL 34982 NOTES: CONTRACTOR: 1. HINGES SHALL BE ATTACHED TO STRUCTURE W/ (4) #10 x 5/8" SMS MINIMUM. 2. DOOR SHALL BE ATTACHED TO ENCLOSURE w/(2) HINGES MINIMUM. V.H. EXTERIORS 3. HINGES SHALL BE ATTACHED TO DOOR WITH (3)#10 x 5/8" SMS. FASTEN A 543 NVV WAVERLY C I R 1" x 2" x 0.044" TO UPRIGHT W/#12 x 1" SMS @ 12" O.C. AND WITHIN 3" FROM END OF THE UPRIGHT. PORT -`T LUCIE, FL 34983 F TYPICAL SCREEN DOOR CONNECTION DETAIL S' 3 SCALE: NTS DETAILS S-3 THIS DOCUMENT SHALL NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT EXPRESSED WRITTEN PERMISSION OF TRAC DESIGN, LLC OCOPYRIGHT -rile u0j)v OPTIONAL Z-BRACKET 7 0.250" 2" GUTTER BRACKET REQUIRED AT PURLIN ATTACHMENT POINTS w/ (2) #12 X 3/4" SMS INTO GUTTER LIP F -X0.250" D GUTTER CKET (1) 3/8" LAG SCREWS @ EA, GUTTER BRACKET & (1) @ 12" O.C. MAX- MIN EMBEDMENT SHALL BE 2" 2" x 2" x %" X ALUMINUM ANGLE w/ (4) #12 x 3/4" SMS INTO PURLIN ON EA THE HOST STRUCTURE SHALL SIDE HAVE AT LEAST A 2"X4" & (4) 12X1-1/2" INTO FASCIA AND ROOF TRUSS GUTTER SYSTEM. CONTRACTOR SHALL VERIFY THIS AND IF SUPER GUTTERJ SMALLER- CONTRACTOR SHALL BRING STRUCTURE UP TO A 2"X4" FASCIA AND ENSURE LESS THAN A 2'-0" A 1 OVERHANG. GUTTER BRACKET & PURLIN ATTACHMENT DETAIL S-4 N.T.S. OPTION #1 (4)410 x 1 !/2" INTO SCREW BO OPTION #2 2"72" OR 2"X3" _j I I 0.062" ALUMINUM INTERNAL OR MEMBER I W 4RNAL #10 X3/4"1 NTO INTONG BEAM B AM)OR UPRIGHT. (2) #14X 3/4" EA. LEG INTO GIRT OR PURLIN - (0.062" ANGLE CLIPS w/ (2) #14x3/4" SMS A LEG) iUPRIGHT OR BEAM -SNAP OR SELF MATING OR HOLLOW H PURLIN OR GIRT TO BEAM OR POST DETAIL s_4- SCALE:NTS (4) #10 X 3/4" SMS FASTENING SECONDARY ANGLE TO COLUMN (TYPE EACH SIDE) (B) - CONCRETE SCREW ANCHOR INTO SECONDARY ANGLE(TYP EACH SIDE) (SEE TABLE) i fiil(EBY QRTIFY THAT I HAVE REVIEWED THIS PLAN AND FOUND IT TO BE IN COMPLIAN(;E WITI3tASCE7.10, & FBC 5th EDIT[ON� :•e �EOF o� ANCHOR SPA �LL ®,,,r A _ ® .oao.°' _ (MIN) CM)(SEE TABLE) (1) - CONCRETE SCREW (SEE G1 TABLE) ANCHOR INTO PRIMARY ANGLE AND @ 1/4" O CONCRETE 3" (MIN) SCREW ANCHOR @ 24" O.C. BETWEEN COLUMNS Column Size 1/4"& 3/8" 0 Concrete Screw Anchor B Min. Spa 2x3-1 4 2x4-1/4' 2x - /4' 2x6-3/8' 2x7-3 8' 2x8-3/8' 2 2x9-3 8" 2 4 2x10-3 8' 2 SECONDARY ANGLE MIN 0.125" THICK (NOT REQUIRED FOR 2X3 MEMBER) PRIMARY 2" X 2" X 0.125" ANGLE (2) #10 X 3/4" SMS FASTENING COLUMN TO PRIMARY ANGLE 0 O (TYP EACH SIDE) O 1" X 2" BASE MEMBER (TYP EACH SIDE) NOTES: (TYP EACH SIDE) 1. NUMBER OF ANCHORS "B" IS EACH SIDE INTO THE SECONDARY ANGLE AND DOES NOT INCLUDE THE ANCHOR INTO THE 1X2. 2. MINIMUM EMBEDMENT OF ANCHORS INTO CONCRETE FOOTING SHALL BE 2-3/4" ATAT ALL UPRIGHT LOCATIONS. ALL SCREW LENGTHSAT UPRIGHT CONNECTIONS SHALL BE OF SUFFICIENT LENGTH FOR REQUIRED EMBEDMENT INTO CONCRETE FOOTING WHEN A PAVER DECK IS PRESENT. 3. CONCRETE SCREW ANCHOR DESIGNS ARE BASED ON THOSE LISTEI ON S-1, D. FASTENERS, OTHER BRAND & TYPE SHALL BE APPROVED BY ENGINEER. 4.2X3W/1X2 CORNER POST SHALL REQUIRE SAME BASE CONNECTIONS AS 2X4 SHOWN IN TABLE. 5. IF FORAN IN -FILL, TOP OF COLUMN CONNECTION SIMILAR IF CONCRETE LINTEL. IF' WOOD LINTEL SUBSTITUTE 1/4" 0 X 3" LAG SCREW FOR 3/8"0 LDT FOR BOTH PRIMARY & SECONDARY ANGLES. 6.2X2X.045 DOORJAMB MEMBER SHALL CONNECT SIMILAR TO 2X3 MEMBER. G 2" x 3" OR LARGER UPRIGHT TO CONCRETE W WO PAVER DETAILS S_4 SCALE:NTS NOTE: WHEN USING OPTION #2 5' CONNECTION CABLE MUST BE OPTION #1- A-36 STEEL WITHIN 6" OF CORNER OR CLIP MAY BY PLACED ON PRIMARY MEMBER. ALUMINUM 45, TOP OR SIDE OF DECK W/ 1" X 2" X 1/8" ANGLETE @ 45° DOUBLE COMPRESSION 3/8"X 3" SLEEVE LE W/ 1" SLEEVES [(2) TOP OF ANCHOR (4) #12 X 3/4"SMS BREAK @ 90° W/ K#143/4 CONCRETE (TYPTOP AND SIDE)LOCK LT 4" NOMINAL SLAB N ® ® NUT & MINIMUM d HER EA SIDE 4, d 1/8" DIA. STAINLESS STEEL CABLE . a 3/8" 0 x 3" MASONRY 25 0 PSI OPTION #1 CONCRETE W/ 3/8" WELDED STAINLESS ANCHOR (MIN 3-3/4" EMBEDMENT) (4" SLAB ONLY) WELDED WIRE STEEL EYE BOLT (8)#14X3/4SM OPTION #3 OR FIBERMESH Side View 0.125" STAINLESS 2500 PSI 1" 0 (MIN) WASHER i a STEEL CABLE CONCRETE W/ BENEATH NUT TOP OF WELDED WIRE CONCRET R FIBER -MESH ® ® e — • G a , ® ® 6 e 4" NOMINAL SLAB O d TO V1eW • p 3/8"0ADJUSTABLEEYE MINIMUM a I11 BOLT FOR CABLE TENSION a o • 1-1/2" X5-1/2" ALUMINUM OPTION #Z o 1/8" 0 STAINLESS STRAP W/ (2) 3/8 "0 X 3" OPTION #2 STEEL CABLE MASONRYANCHOR (MIN 3-3/4" EMBEDMENT) (USE WITH FOOTING) PERIMETER FRAMING TT 2"X2"X 1/8" EXTRUDED ANGLE 11 CABLE TO FOUNDATION CONNECTION DETAIL Side View ON 45° ANGLE S-4 SCALE:NTS OPTION #1 12 CABLE CONNECTION AT CORNER SCALE:NTS David VIA`: Smith P.E. FLORIDA LICENSE: 53608 Thomas L. Hanson P.E FLORIDA LICENSE: 38654 Mark R. Dunn P.E. FLORIDA LICENSE: 73968 Joel Falardeau P.E. FLORIDA LICENSE: 70667 Erik Stuart P.E. FLORIDA LICENSE: 77605 FBC Plans & Engineering Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhijls, FL 33542 Ph#(813)788-5314 Fax# 1-(a66)824-7894 E-mail-erb@fbcplans.com Website-Www. fbcplans. co m C.O.A. #29054 DATE: 7-25-2017 DRAWN BY: TLK REVISION: DATE: RO 1 RO 2 RO 3 RO 4 PROJECT ADDRESS: HAUPT 5404 CITRUS AVE FT. PIERCE, FL 34982 ONTI;ACTOR: V.H. EXTERIORS 543 NW WAVERLY CIR PORT '�T LUCIE, FL 34983 DETAILS S-4 THIS DOCUMENT SHALL NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT EXPRESSED WRITTEN PERMISSION OF TRAC DESIGN, co co I I 0 I Z `J f— W I UJ Lo LL_ r cYn co OLnr-CV Z ®� I i J r � Z O I = 0... ui Z Q 0 � > Wh Qa-J M U) LLI z DI al 3 w 0 of I I copy I I x I 5400 CITRUS AVENUE y F.F.E. 15.61 FEET NIV A 1t1. `tl • mil'. 4' WOOD FENCE x�ti ", X X X 4 WOOD X ENCE X X x X X x X X X X- I REEVE STREET (NOT IN USE) SET 5/8" IRON ROD & CAP. STAMPED "LB 7805" S89048'17"E 311.48' C 145'(P) 111.48'(C) 50'(P) 50'(P) 0" PROPOSED IRRIGATION WELL .. 37.W 100, a LOT 1 v 9 to 7 3' 1.3' w W 6s" .`� R POSED CONC. 'P,9 x° Q • q ® 3' PATIO o/ ; Q G O M PROPOSED CONC. PORCH 3'o s?�' 36" `s z ® 17.5' Y ,> it cd ®� Z M 30"; �z.W W PROPOSED 1 STORY C.B.S. RESIDENCE 14s' ZI 12" PROPOSED F.F.E. 14.80 FEET W a i z MAI�LBO PROPOSED 20 CONC. DRIVE i o, 24" M to/ / LOT 8 M r Q 172.61 ° }r 3 gi 54.0 LOT 2 ---LOT —,, 0 a SIGN tojr afi0.20' a" PROPOSED 15'X60' 0 0 0 L SEPTIC DRAINFIELD AREA ca 3f " Q SET 5/8" IRON ROD do CAP Zs" J.A. SMITH SUBDIVISION (n I STAMPED "LB 7805" 145'(P) " PLAT BOOK 4. PAGE 104 SET 5/8 IRON ROD & CAP S89"48'170E 111.47'(C) STAMPED "LB 7805" `- EAST RIGHT OF WAY LINE " (SEE SURVEYOR'S NOTE NO. 12) Sn 11 �� Ult /4, 27.00'(P)--1 � _t,