HomeMy WebLinkAboutGeotechnical ReportSince 1988 Florida's Leading Engineering Source • Geotechnical • Construction Materials Testing • Threshold and Special Inspections •Plan Review & Code Compliance November 17, 2016 Phoenix Realty Homes, Inc. Attention: Alan Tarpell 1760 N. Jog Road, Suite 140 West Palm Beach, Florida 33411 OR IGIN A L RE: Soil Exploration Addendum #2 - Helical Piers for Pool Proposed One -Story Residence 121 Queen Gunevier Court, Fort Pierce, Florida GFA Project # 16-1614.01 (Reference GFA Geotechnical Report # 16-1614.00 dated 7/26/2016) (Reference GFA Report # 16-1614.01 Report of Test Pits and Auger Borings dated 11/16/2016) Dear Mr. Tarpell: GFA International was requested to provide helical pile recommendations for pool support at the above referenced project. The subsurface exploration activities from reports referenced above were performed in accordance with Chapter 18 of the Florida Building Code (latest addition) and applicable ASTM standards. The boring logs and site plans are attached to this report for reference. Helical pile recommendations are provided below based on the borings. Pile Foundation (Helical Piers) Helical piers consist of galvanized steel shafts with helical flight augers on the bottom shaft. The shafts are bolted together as the shafts are drilled into the subsurface. The torque applied to the piers during drilling is correlated to the compression capacity of the helical pier. The shafts are cut to the appropriate cut-off elevation, and typically pile caps, grade beams, or footings are cast on the top of the helical piers. Helical piers for these type of structures generally require a 4 to 12 ton capacity. We recommend the piers be spaced at least 3 diameters (largest helical diameter) apart center -to -center. To obtain required axial capacity, the piers would likely have to be installed and seated into the medium dense to very dense sand encountered from about 18%z to 35 feet below existing grade. The length of the piers could extend beyond 35 feet before achieving the required torque and corresponding capacity. Each pier must be installed with a minimum of twice their design capacity. The capacity of several piers must be verified by shear pins or other calibration techniques as required by the Florida Building Code. 2010 ed as noted below. 521 NW Enterprise Drive - Port St. Lucie, Florida 34986 • (772) 924.3575 • (772) 924-3580 (fax) • www.teamgfa.com OFFICES THROUGHOUT FLORIDA Soil Exploration Addendum(,-' ';!Helical Piers for Pool 1121 Queen Gunevier Court, V __,,,Pierce, FL GFA Project# 16-1401.01 November 17, 2016 In accordance with Section 1810.3.3.1.9 of the Florida Building Code, 2010 ed, the allowable axial design load, Pa, of helical piles shall be determined as follows: Pa = 0.5 P„ (Equation 18-4) where P„ is the least value of: 1. Sum of the areas of the helical bearing plates times the ultimate bearing capacity of the soil or rock comprising the bearing stratum. 2. Ultimate capacity determined from well -documented correlations with installation torque. 3. Ultimate capacity determined from load tests. 4. Ultimate axial capacity of pile shaft. 5. Ultimate axial capacity of pile shaft couplings. 6. Sum of the ultimate axial capacity of helical bearing plates affixed to pile. Helical pier design and installation is proprietary in nature. The locations and required capacity of the piers must be designed by the structural engineer or other qualified professional. Helical pile support recommendations are based on the existing structures (including existing footings and slabs if applicable) having structural integrity which will be determined by others. GFA recommends that a representative of GFA monitor the helical pier installation in accordance with the Florida Building Code. Installation of piers should be performed after all utilities have been identified and located to avoid installation problems and for safety reasons. These services were not within our scope of services. Fill and backfill should be "clean" sand with less than 5% fines (percent of dry weight passing a U.S. No. 200 sieve). The fill (including backfill around pile caps and grade beams) should be placed in 12- inch thick compacted lifts with each lift compacted to at least 95% of the modified Proctor maximum dry density (A�TV`111697h, J' The compaction should be checked with field density tests. %d ;; o ego �� OO,��o Sincerel)$�,��i: • -9 `moo GFA In �o�al, Inco n �p FBPE �_ 3 Donald V1��,�f(er.,.P.E.....•' 'a`�� C i an Collie, E.I. Senior Geol.'e�,�f Yg6g1n ftO P j t Manager Florida Reg istr��i�nitlw4t975 Attachments: Attachments from GFA Geotechnical Report # 16-1614300 dated 7/26/2016 (7 pages) Attachments from GFA Report # 16-1614.00 Report of Test Pits and Auger Borings dated 11/16/2016 (4 pages) Copies: Client (2) .A 151 It �-e2016 Googlo. t 1 -4j 1994 Imagery Date: 1/23/2016 lat 27.515805O2 40 , 60 c� lik -80.3218860 elev 3 ft eye alt 654 ft /yRNA1ti�C'P� Test Location Plan 121 Queen Gunevier Court Fort Pierce, FL GFA Project No. 16-1614.00 Vie• o" 10 Oe ase � o N\r _ells a5 a�ed'anl �•� sos`vs�c SQ�eQ a�`O ass ah A13-3 �'•� off°. 40 \ i AB-2 z, SPTA z *v- o ``\t __ o V\ o O1 O \ Q 0 0 n M in I - z • � tF � i N58' 36' 10' N 130.00' Le-gend + Approximate Standard Penetration Test (SPT) Boring & Auger Boring (AB) Locations GFA INTERNATIONAL 521 N.W. ENTERPRISE DRIVE, PORT ST. LuCiE, FLORIDA 34986 PHONE: (772) 924-3575 - FAX: (772) 924-3580 STANDARD PENETRATION TEST BORING (ASTM D-1586) Client: Phoenix Realty Homes, Inc. Project No.:16-1614.00 Lab No.: Project: 121 Queen Gunevier Ct. Page: 1 of 2 Fort Pierce, FL Date: 7/12/2016 Elevation: Existing Grade Drill Rig: Simco-24 Water Level: 6 feet after 0 hours Drilling Fluid commenced at depth of 10 feet Field Party: JS/ES TEST LOCATION: SPT - 1 N27.5155400 W80.3225490 Laboratory Tests Depth Blows/ N Sample Layer: USCS Description Passing Moisture Organic (feet) 6 in. Value No. From/to No. 200 Content Content 2 0 - 6h SP Light brown fine sand 6� 10 1 •9.......... --- 3 --2 - 9 --- - ---- 9 18 2 _7. ---- 5 8 ------ ......7 9 3 ---- 6 _13 ... 5 6'Y2 - 8 SP-SC Gray fine sand, little silt and clay 8 _ _ _----- 10 18 4 8 •• 8-9 SM,ML Gray silt and sand WOH _ 1 WOH=Weight of Hammer 3 4 5 9-10 SP Gray fine sand, trace shell --- 10.... - --- 11 ------- ------ 12 .............. 13 ------- ------ 14 WOH ------- 13Y2 - 15 SM,ML Gray fine sand and silt and shell WOH WOH=Weight of Hammer ----15 - 3- .3. 6 16 ---- --- 17 ---- --- 18 .............. 18%2 - 20 SP Gary fine sand and shell 19 ..47 _- ______ 38 33 71 7 1 J GFA INTERNATIONAL 521 N.W. ENTERPRISE DRIVE, PORT ST. LuciE, FLORIDA 34986 PHONE: (772) 924-3575 - FAX: (772) 924-3580 STANDARD PENETRATION TEST BORING (ASTM D-1586) Client: Phoenix Realty Homes, Inc. Project No.:16-1614.00 Lab No.: Project: 121 Queen Gunevier Ct. Page: 2 of 2 Fort Pierce, FL Date: 7/12/2016 Elevation: Existing Grade Drill Rig: Simco-24 Water Level: 6 feet after 0 hours Drilling Fluid commenced at depth of 10 feet Field Party: JS/ES TEST LOCATION: SPT - 1 N27.5155400 W80.3225490 Laboratory Tests Depth (feet) Blows/ 6 in. N Value Sample No. Layer: From/to USCS Description Passing No. 200 Moisture Content Organic Content 20 ------- ---- 21 ---- --- 22 ---- --- 23 .............. 24 -9 _ 10 ----- 23'/2 - 25 SP Gray fine sand, trace shell ---- 25 -_ 15 .......25..... 8 26 .............. 27 ---- --- 28 .............. 29 --12......... 18 28'/2 - 30 SP Dark gray fine sand ---- 30 _26 44 9 31 ---- --- 32 .............. 33 •... •-- 34 -14 ......... 33'/2 - 35 SP Dark gray fine sand and shell 20 35 ..26 -_ _ 46_ _ 10 37 ---- --- 38 ---- --- 39 9 .......... 2 38'/2 - 40 CH Gray silt and clay, some sand 1 3 11 Boring terminated at 40 feet 010- Since 1988 Florida's Leading Engineering Source AUGER BORING LOGS WITH HAND CONE PENETROMETER (HCP) TESTS Client: Phoenix Realty Homes, Inc. Project: 121 Queen Gunevier Ct. Fort Pierce, FL Elevation: Existing Grade Project No: Lab No: Test Date: Technician: 16-1614.00 7/12/2016 JS/ES TEST LOCATION: AB — 1 N27.5155080 W80.3223600 HCP Depth (feet) Description (color, texture, consistency, remarks) Depth Reading 0-2 Gray fine sand SP 1 70 2-5 Dark gray fine sand, some silt and clay SC 2 45 5-8 Dark gray fine sand, trace shell SP 3 80+ 8-10 Gray silt and sand SM,ML 4 1 80+ 5 60 6 25 7 20 8 15 9 10 10 15 Water table at 5 feet below ground surface TEST LOCATION: AB — 2 N27.5154970 W80.3222600 HCP Depth (feet) Description (color, texture, consistency, remarks) Depth Reading 0-2 Light brown fine sand SP 1 45 2-4 Gray fine sand, trace shell SP 2 55 4-9 Gray fine sand, some silt and clay SC 3 70 9-10 Gray fine sand, some shell SP 4 1 80+ 5 60 6 50 7 35 8 15 9 20 10 10 Water table at 5.5 feet below ground surface Florida's Leading Engineering Source AUGER BORING LOGS WITH HAND CONE PENETROMETER (HCP) TESTS Client: Phoenix Realty Homes, Inc. Project: 121 Queen Gunevier Ct. Fort Pierce, FL Elevation: Existing Grade Project No: Lab No: Test Date: Technician: 16-1614.00 7/12/2016 JS/ES TEST LOCATION: AB — 3 N27.515571 ° W80.3223600 HCP Depth (feet) Description (color, texture, consistency, remarks) Depth Reading 0 - 2'/2 Light brown fine sand SP 1 55 2'/2 - 6 Gray fine sand, trace shell SP 2 65 6 - 10 Gray fine sand, some silt and clay and shell SC 3 80+ 4 80+ 5 50 6 35 7 40 8 20 9 15 10 25 Water table at 5.5 feet below ground surface \ � .J NOTES RELATED TO RECORDS OF TEST BORING AND GENERALIZED SUBSURFACE PROFILE 1. Groundwater level was encountered and recorded (if shown) following the completion of the soil test boring on the date indicated. Fluctuations in groundwater levels are common; consult report text for a discussion. 2. The boring location was identified in the field by offsetting from existing reference marks and using a cloth tape and survey wheel. 3. The borehole was backfilled to site grade following boring completion, and patched with asphalt cold patch mix when pavement was encountered. 4. The Record of Test Boring represents our interpretation of field conditions based on engineering examination of the soil samples. 5. The Record of Test Boring is subject to the limitations, conclusions and recommendations presented in the Report text. 6. "Field Test Data" shown on the Record of Test Boring indicated as 11/6 refers to the Standard Penetration Test (SPT) and means 11 hammer blows drove the sampler 6 inches. SPT uses a 140-pound hammer falling 30 inches. 7. The N-value from the SPT is the sum of the hammer blows required to drive the sampler the second and third 6- inch increments. 8. The soil/rock strata interfaces shown on the Records of Test Boring are- approximate and may vary from those shown. The soil/rock conditions shown on the Records of Test Boring refer to conditions at the specific location tested; soil/rock conditions may vary between test locations. 9. Relative density for sands/gravels and consistency for silts/clays are described as follows: SPT CPT SANDS/GRAVELS SPT CPT SILTS/CLAYS BLOWS/FOOT KG/CM RELATIVE DENSITY BLOWS/FOOT KG/CMJ CONSISTENCY 0-4 0-16 Very loose 0-1 0-3 Very soft 5-10 17-40 Loose 2-4 4-6 Soft 11-30 41-120 Medium Dense 5-8 7-12 Firm 31-50 1 121-200 1 Dense 9-15 13-25 Stiff 50+ over 200 Very Dense 16-30 25-50 Very stiff >30 >50 Hard 10. Grain size descriptions are as follows: NAME SIZE LIMITS Boulder 12 Inches or more Cobbles 3 to 12 Inches Coarse Gravel % to 3 Inches Fine Gravel No. 4 sieve to % inch Coarse Sand No. 10 to No. 4 sieve Medium Sand No. 40 to No. 10 sieve Fine Sand No. 200 to No. 40 sieve Fines Smaller than No. 200 sieve 11. Definitions related to adjectives used in soil/rock descriptions: PROPORTION ADJECTIVE APPROXIMATE ROOT DIAMETER ADJECTIVE <5% Trace Less than 1/32" Fine roots 5%to 12% Little 1/32" to'/4" Small roots 12% to 30% Some '/4" to 1" Medium roots 30% to 50% And Greater than 1" Large roots Organic Soils: Soils containing vegetable tissue in various stages of decomposition that has a fibrous to amorphous texture, usually a dark brown to black color, and an organic odor. Organic Content <25%: Slightly to Highly Organic; 25% to 75%: Muck; >75%: Peat GF�