HomeMy WebLinkAboutAPPROVED MANJCalculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jun-24 09:43:50
Right-Suite® Universal 2021 21.0.07 RSU27054 Page 1
...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Load Short Form 6/23/2021Date:Entire House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Bove Residence, Groza Builders, IncFor:
123 Eden Creek Ln, Jensen Beach, FL 34957
Design Information
InfiltrationClgHtg
SimplifiedMethod9041Outside db (°F)
AverageConstruction quality7570Inside db (°F)
0Fireplaces1529Design TD (°F)
L-Daily range
5030Inside humidity (%)
572Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make Lennox
Trade Trade LENNOX
Model Cond ML14XC1S036-230C**
AHRI ref Coil CBA27UHE-036-230*++TDR
AHRI ref 204289057
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW8.9 Sensible cooling Btuh24220
Heating output Btuh30349 Latent cooling Btuh10380
Temperature rise °F24 Total cooling Btuh34600
Actual air flow cfm1153 Actual air flow cfm1153
Air flow factor cfm/Btuh0.041 Air flow factor cfm/Btuh0.054
Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.73
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
Flex Room 210 3228 2044 133 110
Foyer 116 960 351 40 19
Bath 61 585 170 24 9
Bed 2 247 3374 1889 139 102
Bed 3 193 1517 873 62 47
WIC 3 36 589 158 24 9
Laundry 47 70 651 3 35
Wtr Clst 23 278 69 11 4
WIC 40 594 161 24 9
M Bath 154 1627 442 67 24
M Hall 20 0 0 0 0
Master Bed 276 4769 3091 196 167
Bed 4 188 2997 1682 123 91
Bath 2 95 1922 556 79 30
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jun-24 09:43:50
Right-Suite® Universal 2021 21.0.07 RSU27054 Page 2
...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
Hall 33 0 0 0 0
Pantry 27 0 0 0 0
KitNook 298 2121 3312 87 179
Great Room 440 2777 5785 114 312
Hall 2 25 0 0 0 0
Lin2 9 0 0 0 0
WIC 2 42 597 163 25 9
Entire House 2577 28002 21395 1153 1153
Other equip loads 2016 1071
Equip. @ 0.95 RSM 21432
Latent cooling 8290
TOTALS 2577 30019 29723 1153 1153
2021-Jun-24 09:43:50
Right-Suite® Universal 2021 21.0.07 RSU27054 Page 1
...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Building Analysis 6/23/2021Date:Entire House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Bove Residence, Groza Builders, IncFor:
123 Eden Creek Ln, Jensen Beach, FL 34957
Design Conditions
Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Heating
Walls
Glazing
Other
Ceilings
Floors
Infiltration
Ducts
Ventilation
% of loadBtuhBtuh/ft²Component
16.148452.6Walls
7.3220210.0Glazing
0.82383.7Doors
8.525451.0Ceilings
23.570562.72.7Floors
13.239642.2Infiltration
23.87153Ducts
00Piping
00Humidification
6.72016Ventilation0Adjustments
100.030019Total
Cooling
Walls
Glazing
Other
Ceilings
Infiltration Ducts
Internal Gains
Ventilation
% of loadBtuhBtuh/ft²Component
13.129501.6Walls
22.0494622.5Glazing
1.12413.7Doors
7.015620.6Ceilings
000Floors
4.710520.6Infiltration
22.95143Ducts
4.81071Ventilation
24.55500Internal gains
00Blower
0Adjustments
100.022466Total
Latent Cooling Load = 8290 Btuh
Overall U-value = 0.080 Btuh/ft²-°F
ERROR: negative wall area in Great Room - check windows.
2021-Jun-24 09:43:50
Right-Suite® Universal 2021 21.0.07 RSU27054 Page 1
...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Component Constructions 6/23/2021Date:Entire House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Bove Residence, Groza Builders, IncFor:
123 Eden Creek Ln, Jensen Beach, FL 34957
Design Conditions
Location: CoolingHeatingIndoor:
7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr
BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft²
Walls
Block R-9 Wall: Blk wall, Stuc Ext, 8" thk, R-9 Foam Fill, 1/2" Gyp Bd 9002.589.00.089350n 5761.65
3821.655972.589.00.089232e
7811.6512222.589.00.089474s
5861.659162.589.00.089356w
23251.6536362.589.00.0891411all
Block R-9 Wall: Frm Wall, Stucco , R-30, 1/2" Gyp Bd Int Fnsh, 2"x4" , 16"
O.C. Stud
511.31802.0430.00.07139e
51.3182.0430.00.0714s
521.31822.0430.00.07140w
1091.311702.0430.00.07183all
Partitions
Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16"
OC Stud
5161.4610392.9411.00.101354
Windows
Impact: Impact; NFRC rated (SHGC=0.22); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang
(0.67 ft window ht, 1 ft sep.); 6.8 ft head ht
137.59159.2800.3202n
Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang
(6 ft window ht, 1 ft sep.); 6.8 ft head ht
81422.03228.7000.30037e
Impact: Impact; NFRC rated (SHGC=0.19); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang
(5.25 ft window ht, 1 ft sep.); 6.8 ft head ht
47820.62088.9900.31023e
Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang
(5.2 ft window ht, 1 ft sep.); 6.8 ft head ht
1459.311368.7000.30016s
102922.04078.7000.30047w
117418.85438.7000.30062all
Impact: Impact; NFRC rated (SHGC=0.20); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 8.7 ft
overhang (8 ft window ht, 1 ft sep.); 6.8 ft head ht
126013.1111411.600.40096w
Doors
2021-Jun-24 09:43:50
Right-Suite® Universal 2021 21.0.07 RSU27054 Page 2
...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
Fbrgls Door 793.73793.697.00.12721n
893.73893.697.00.12724e
723.73713.697.00.12719s
2413.732383.697.00.12765all
Ceilings
Attic, Metal Roof, R-30 Ceil Ins, 5/8" Gyp Bd 0.0342577 15620.6125450.9930.0
Floors
On Grade Depth, Tile Flr Fnsh 00705628.700.989246
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jun-24 09:43:50
Right-Suite® Universal 2021 21.0.07 RSU27054 Page 1
...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Project Summary 6/23/2021Date:Entire House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Bove Residence, Groza Builders, IncFor:123 Eden Creek Ln, Jensen Beach, FL 34957
Notes:
Design Information
St Lucie Co Intl, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75
Design TD °F29 Design TD °F15Daily range L
Relative humidity %50Moisture difference gr/lb57
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh20849 Structure Btuh16252
Ducts Btuh7153 Ducts Btuh5143Central vent (63 cfm) 2016 Btuh Central vent (63 cfm) Btuh1071
Outside air Outside airHumidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh30019 Use manufacturer's data n
Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh21432
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average0Fireplaces Structure Btuh3403
Ducts Btuh2442Central vent (63 cfm) Btuh2445
CoolingHeating Outside air25772577Area (ft²) Equipment latent load Btuh8290
2331923319Volume (ft³)Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh29723
Equiv. AVF (cfm) 62124 Req. total capacity at 0.70 SHR ton2.6
Heating Equipment Summary Cooling Equipment Summary
Make Make LennoxTrade Trade LENNOX
Model Cond ML14XC1S036-230C**AHRI ref Coil CBA27UHE-036-230*++TDR
AHRI ref 204289057Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW8.9 Sensible cooling Btuh24220Heating output Btuh30349 Latent cooling Btuh10380
Temperature rise °F24 Total cooling Btuh34600Actual air flow cfm1153 Actual air flow cfm1153
Air flow factor cfm/Btuh0.041 Air flow factor cfm/Btuh0.054Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.73
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jun-24 09:43:50Right-Suite® Universal 2021 21.0.07 RSU27054 Page 1...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Right-J® Worksheet 6/23/2021Date:Entire House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Entire House Flex Room
2 Exposed wall 246.0 ft 29.5 ft
3 Room height 9.0 ft 10.0 heat/coolft
4 Room dimensions ft17.5x12.0
5 Room area 2577.3 ft²210.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 373 350 900 576 0 0 0 0
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 2 0 15 13 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 21 21 79 79 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 316 232 597 382 96 59 152 97
11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 37 0 322 814 37 0 322 814
GG ImpactImpact 0.3100.310 ee 8.998.99 20.6220.62 23 0 208 478 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 24 24 89 89 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ee 2.042.04 1.311.31 39 39 80 51 24 24 49 31
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 509 474 1222 781 16 16 41 26
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 16 13 136 145 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 19 19 71 72 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ss 2.042.04 1.311.31 4 4 8 5 4 4 8 5
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 499 356 916 586 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 47 0 407 1029 0 0 0 0
GG ImpactImpact 0.4000.400 ww 11.6011.60 13.1213.12 96 75 1114 1260 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ww 2.042.04 1.311.31 40 40 82 52 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 354 354 1039 516 155 155 455 226
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 2577 2577 2545 1562 210 210 207 127
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 2577 246 7056 0 210 30 846 0
6 c) AED excursion 1208 137
Envelope loss/gain 16886 9699 2081 1464
12 a) Infiltration 3964 1052 312 83
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 5 1150 0 0
Appliances/other 4350 0
Subtotal (lines 6 to 13)20849 16252 2393 1547
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 10 6
14 Subtotal 20849 16252 2403 1552
15 Duct loads 34%32%7153 5143 34%32%824 491
Total room load 28002 21395 3228 2044
Air required (cfm)Air required (cfm)1153 1153 133 110
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jun-24 09:43:50Right-Suite® Universal 2021 21.0.07 RSU27054 Page 2...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Right-J® Worksheet 6/23/2021Date:Entire House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Foyer Bath
2 Exposed wall 7.5 ft 5.5 ft
3 Room height 10.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft15.5x7.5 ft11.0x5.5
5 Room area 116.3 ft²60.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 60 36 93 59 44 44 113 73
11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 20.6220.62 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 24 24 89 89 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ee 2.042.04 1.311.31 15 15 31 20 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ss 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.4000.400 ww 11.6011.60 13.1213.12 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ww 2.042.04 1.311.31 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 116 116 115 70 61 61 60 37
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 116 8 215 0 61 6 158 0
6 c) AED excursion -20 -10
Envelope loss/gain 542 219 331 100
12 a) Infiltration 167 44 98 26
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)709 263 429 126
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 5 3 7 4
14 Subtotal 714 266 436 129
15 Duct loads 34%32%245 84 34%32%149 41
Total room load 960 351 585 170
Air required (cfm)Air required (cfm)40 19 24 9
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jun-24 09:43:50Right-Suite® Universal 2021 21.0.07 RSU27054 Page 3...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Right-J® Worksheet 6/23/2021Date:Entire House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bed 2 Bed 3
2 Exposed wall 31.5 ft 12.5 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft17.0x14.5 ft193.3x1.0
5 Room area 246.5 ft²193.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 116 93 239 153 0 0 0 0
11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 20.6220.62 23 0 208 478 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ee 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 136 136 350 224 100 84 217 139
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 16 13 136 145
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ss 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.4000.400 ww 11.6011.60 13.1213.12 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ww 2.042.04 1.311.31 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 247 247 243 149 193 193 191 117
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 247 32 903 0 193 13 359 0
6 c) AED excursion 28 -50
Envelope loss/gain 1945 1032 903 352
12 a) Infiltration 561 149 223 59
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 250 250
Subtotal (lines 6 to 13)2506 1431 1125 661
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 5 3 4 2
14 Subtotal 2512 1435 1129 663
15 Duct loads 34%32%862 454 34%32%387 210
Total room load 3374 1889 1517 873
Air required (cfm)Air required (cfm)139 102 62 47
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jun-24 09:43:50Right-Suite® Universal 2021 21.0.07 RSU27054 Page 4...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Right-J® Worksheet 6/23/2021Date:Entire House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name WIC 3 Laundry
2 Exposed wall 6.0 ft 0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft6.0x6.0 ft8.5x5.5
5 Room area 36.0 ft²46.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 20.6220.62 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ee 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 48 48 124 79 0 0 0 0
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ss 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.4000.400 ww 11.6011.60 13.1213.12 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ww 2.042.04 1.311.31 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 36 36 36 22 47 47 46 28
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 36 6 172 0 47 0 0 0
6 c) AED excursion -9 -37
Envelope loss/gain 331 92 46 -9
12 a) Infiltration 107 28 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 500
Subtotal (lines 6 to 13)438 120 46 491
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 6 3
14 Subtotal 438 120 52 494
15 Duct loads 34%32%150 38 34%32%18 156
Total room load 589 158 70 651
Air required (cfm)Air required (cfm)24 9 3 35
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jun-24 09:43:50Right-Suite® Universal 2021 21.0.07 RSU27054 Page 5...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Right-J® Worksheet 6/23/2021Date:Entire House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Wtr Clst WIC
2 Exposed wall 3.5 ft 6.0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft6.5x3.5 ft40.0x1.0
5 Room area 22.8 ft²40.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 48 48 124 79
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 20.6220.62 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ee 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ss 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.4000.400 ww 11.6011.60 13.1213.12 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ww 2.042.04 1.311.31 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 28 28 82 41 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 23 23 22 14 40 40 39 24
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 23 4 100 0 40 6 172 0
6 c) AED excursion -4 -9
Envelope loss/gain 205 51 335 94
12 a) Infiltration 0 0 107 28
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)205 51 442 122
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 2 1 0 0
14 Subtotal 207 52 442 122
15 Duct loads 34%32%71 16 34%32%152 39
Total room load 278 69 594 161
Air required (cfm)Air required (cfm)11 4 24 9
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jun-24 09:43:50Right-Suite® Universal 2021 21.0.07 RSU27054 Page 6...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Right-J® Worksheet 6/23/2021Date:Entire House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name M Bath M Hall
2 Exposed wall 18.0 ft 0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft153.8x1.0 ft4.5x4.5
5 Room area 153.8 ft²20.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 52 50 130 83 0 0 0 0
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 2 0 15 13 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 20.6220.62 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ee 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ss 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.4000.400 ww 11.6011.60 13.1213.12 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ww 2.042.04 1.311.31 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 92 92 270 134 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 154 154 152 93 20 20 20 12
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 154 18 516 0 20 0 0 0
6 c) AED excursion -25 -1
Envelope loss/gain 1083 298 20 11
12 a) Infiltration 116 31 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)1199 329 20 11
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 12 7 -20 -11
14 Subtotal 1211 335 0 0
15 Duct loads 34%32%415 106 34%32%0 0
Total room load 1627 442 0 0
Air required (cfm)Air required (cfm)67 24 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jun-24 09:43:50Right-Suite® Universal 2021 21.0.07 RSU27054 Page 7...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Right-J® Worksheet 6/23/2021Date:Entire House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Master Bed Bed 4
2 Exposed wall 44.0 ft 29.0 ft
3 Room height 8.5 heat/coolft 8.0 heat/coolft
4 Room dimensions ft275.9x1.0 ft187.5x1.0
5 Room area 275.9 ft²187.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 145 145 372 238 0 0 0 0
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 20.6220.62 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ee 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 85 66 169 108 124 124 319 204
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 19 19 71 72 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ss 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 145 113 292 187 108 92 238 152
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 31 0 271 686 16 0 136 343
GG ImpactImpact 0.4000.400 ww 11.6011.60 13.1213.12 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ww 2.042.04 1.311.31 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 276 276 272 167 188 188 185 114
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 276 44 1262 0 188 29 832 0
6 c) AED excursion 164 74
Envelope loss/gain 2710 1623 1710 888
12 a) Infiltration 833 221 517 137
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 500 250
Subtotal (lines 6 to 13)3544 2344 2227 1275
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 7 4 5 3
14 Subtotal 3551 2348 2232 1278
15 Duct loads 34%32%1218 743 34%32%766 404
Total room load 4769 3091 2997 1682
Air required (cfm)Air required (cfm)196 167 123 91
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jun-24 09:43:50Right-Suite® Universal 2021 21.0.07 RSU27054 Page 8...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Right-J® Worksheet 6/23/2021Date:Entire House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bath 2 Hall
2 Exposed wall 19.5 ft 0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft10.0x9.5 ft33.0x1.0
5 Room area 95.0 ft²33.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 80 59 151 97 0 0 0 0
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 21 21 79 79 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 20.6220.62 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ee 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ss 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 76 76 196 125 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.4000.400 ww 11.6011.60 13.1213.12 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ww 2.042.04 1.311.31 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 95 95 94 58 33 33 33 20
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 95 20 559 0 33 0 0 0
6 c) AED excursion -32 -1
Envelope loss/gain 1079 327 33 19
12 a) Infiltration 348 92 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)1426 419 33 19
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 5 3 -33 -19
14 Subtotal 1431 422 0 0
15 Duct loads 34%32%491 134 34%32%0 0
Total room load 1922 556 0 0
Air required (cfm)Air required (cfm)79 30 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jun-24 09:43:50Right-Suite® Universal 2021 21.0.07 RSU27054 Page 9...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Right-J® Worksheet 6/23/2021Date:Entire House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Pantry KitNook
2 Exposed wall 0 ft 18.0 ft
3 Room height 10.5 heat/coolft 10.5 heat/coolft
4 Room dimensions ft3.0x9.0 ft297.6x1.0
5 Room area 27.0 ft²297.6 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 20.6220.62 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ee 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ss 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 89 89 230 147
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.4000.400 ww 11.6011.60 13.1213.12 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ww 2.042.04 1.311.31 0 0 0 0 21 21 43 27
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 79 79 231 115
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 27 27 27 16 298 298 294 180
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 27 0 0 0 298 18 516 0
6 c) AED excursion -1 -190
Envelope loss/gain 27 15 1314 280
12 a) Infiltration 0 0 246 65
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 2 460
Appliances/other 0 1700
Subtotal (lines 6 to 13)27 15 1560 2505
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -27 -15 19 11
14 Subtotal 0 0 1579 2516
15 Duct loads 34%32%0 0 34%32%542 796
Total room load 0 0 2121 3312
Air required (cfm)Air required (cfm)0 0 87 179
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jun-24 09:43:50Right-Suite® Universal 2021 21.0.07 RSU27054 Page 10...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Right-J® Worksheet 6/23/2021Date:Entire House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Great Room Hall 2
2 Exposed wall 9.5 ft 0 ft
3 Room height 10.5 heat/coolft 8.0 heat/coolft
4 Room dimensions ft439.5x1.0 ft4.5x5.5
5 Room area 439.5 ft²24.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 20.6220.62 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ee 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ss 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 81 -15 -39 -25 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.4000.400 ww 11.6011.60 13.1213.12 96 75 1114 1260 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ww 2.042.04 1.311.31 19 19 39 25 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 440 440 434 266 25 25 24 15
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 440 10 272 0 25 0 0 0
6 c) AED excursion 1204 -1
Envelope loss/gain 1820 2730 24 14
12 a) Infiltration 222 59 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 3 690 0 0
Appliances/other 900 0
Subtotal (lines 6 to 13)2042 4379 24 14
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 26 15 -24 -14
14 Subtotal 2067 4394 0 0
15 Duct loads 34%32%709 1391 34%32%0 0
Total room load 2777 5785 0 0
Air required (cfm)Air required (cfm)114 312 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jun-24 09:43:50Right-Suite® Universal 2021 21.0.07 RSU27054 Page 11...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Right-J® Worksheet 6/23/2021Date:Entire House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Lin2 WIC 2
2 Exposed wall 0 ft 6.0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft3.0x3.0 ft6.0x7.0
5 Room area 9.0 ft²42.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 48 48 124 79
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 20.6220.62 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ee 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ss 2.042.04 1.311.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.4000.400 ww 11.6011.60 13.1213.12 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0710.071 ww 2.042.04 1.311.31 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 9 9 9 5 42 42 41 25
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 9 0 0 0 42 6 172 0
6 c) AED excursion 0 -9
Envelope loss/gain 9 5 337 95
12 a) Infiltration 0 0 107 28
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)9 5 444 124
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -9 -5 0 0
14 Subtotal 0 0 444 124
15 Duct loads 34%32%0 0 34%32%152 39
Total room load 0 0 597 163
Air required (cfm)Air required (cfm)0 0 25 9
2021-Jun-24 09:43:51
Right-Suite® Universal 2021 21.0.07 RSU27054 Page 1
...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Duct System Summary 6/23/2021Date:Entire House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Bove Residence, Groza Builders, IncFor:
123 Eden Creek Ln, Jensen Beach, FL 34957
CoolingHeating
External static pressure in H2O0.70in H2O0.70
Pressure losses in H2O0in H2O0
Available static pressure in H2O0.70in H2O0.70
Supply / return available pressure 0.523 / 0.177 in H2O in H2O0.523 / 0.177
Lowest friction rate in/100ft0.256in/100ft0.256
Actual air flow cfm1153cfm1153
Total effective length (TEL) ft273
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st6140.054.3VlFx0x04.00.2691129585hBath
st5140.059.1VlFx0x06.00.26336951922hBath 2
st6140.061.2VlFx0x07.00.2601221673374hBed 2
st5140.062.1VlFx0x05.00.25956751517hBed 3
st5140.061.2VlFx0x07.00.2601091482997hBed 4
st2100.031.3VlFx0x07.00.3981321603228hFlex Room
st6140.051.7VlFx0x04.00.2732347960hFoyer
st2100.030.9VlFx0x07.00.399187692892cGreat Room
st2100.034.7VlFx0x07.00.388187692892cGreat Room-A
st2100.025.0VlFx0x06.00.418107521656cKitNook
st2100.031.6VlFx0x06.00.397107521656cKitNook-A
st5140.057.3VlFx0x04.00.265423651cLaundry
st195.011.0VlFx0x05.00.49329801627hM Bath
st3120.034.2VlFx0x06.00.3391001182385hMaster Bed
st3120.033.8VlFx0x06.00.3401001182385hMaster Bed-A
st195.014.8VlFx0x04.00.4761029594hWIC
st1100.019.2VlFx0x04.00.4391129597hWIC 2
st5140.063.9VlFx0x04.00.2561029589hWIC 3
st195.012.5VlFx0x04.00.486414278hWtr Clst
2021-Jun-24 09:43:51
Right-Suite® Universal 2021 21.0.07 RSU27054 Page 2
...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st5 Peak AVF 351 254 0.256 794 9.0 0x0 VinlFlx st4
st6 Peak AVF 243 156 0.260 696 8.0 0x0 VinlFlx st4
st4 Peak AVF 594 409 0.256 756 12.0 0x0 VinlFlx st2
st3 Peak AVF 236 200 0.339 675 8.0 0x0 VinlFlx st1
st1 Peak AVF 389 254 0.339 880 9.0 0x0 VinlFlx
st2 Peak AVF 995 1130 0.256 809 16.0 0x0 VinlFlx
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb9 0x 6680 823 69.1 0.256 589 16.0 x0 0 VlFx
rb5 0x 2650 210 0 0 0 0 x0 0 VlFx
rb4 0x 1770 119 0 0 0 0 x0 0 VlFx
rb3 0x 1070 110 0 0 0 0 x0 0 VlFx
rb2 0x 1670 122 0 0 0 0 x0 0 VlFx
2021-Jun-24 09:43:51
Right-Suite® Universal 2021 21.0.07 RSU27054 Page 1
...nts\Wrightsoft HVAC\123 Eden Creek Lane GBI.rup Calc = MJ8 Front Door faces: N
1537Job:Manual S Compliance Report 6/23/2021Date:Entire House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Bove Residence, Groza Builders, IncFor:
123 Eden Creek Ln, Jensen Beach, FL 34957
Cooling Equipment
Design Conditions
°F76.4Entering coil DB:Btuh22466Sensible gain:°F90.4Outdoor design DB:
°F64.0Entering coil WB:Btuh8290Latent gain:°F77.4Outdoor design WB:
Btuh30756Total gain:°F75.0Indoor design DB:
cfm1153Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ACEquipment type:
ML14XC1S036-230C**+CBA27UHE-036-230*++TDRModel:LennoxManufacturer:
cfm1153Actual airflow:
% of load108Btuh24220Sensible capacity:
% of load125Btuh10380Latent capacity:
%70SHR:% of load112Btuh34600Total capacity:
Heating Equipment
Design Conditions
°F67.8Entering coil DB:Btuh30019Heat loss:°F41.0Outdoor design DB:
°F70.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Elec stripEquipment type:
Model:Manufacturer:
cfm1153Actual airflow:
°F50Temp. rise:% of load101kW8.9Output capacity:
Meets all requirements of ACCA Manual S.