Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
APPROVED 5105 Myrtle Dr PSL Prop Manual J
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 13:49:22 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...nts\Wrightsoft HVAC\5105 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1627Job:Load Short Form 9/27/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Tamez Residence, NisAir Air ConditioningFor: 5105 Myrtle Dr, Fort Pierce, FL 34982 Design Information InfiltrationClgHtg SimplifiedMethod9041Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1S036-230C** AHRI ref Coil CBA27UHE-036-230*++TDR AHRI ref 204289057 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW7.4 Sensible cooling Btuh24220 Heating output Btuh25190 Latent cooling Btuh10380 Temperature rise °F20 Total cooling Btuh34600 Actual air flow cfm1153 Actual air flow cfm1153 Air flow factor cfm/Btuh0.046 Air flow factor cfm/Btuh0.050 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.79 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) WIC 54 1211 397 56 20 Laundry 57 901 966 42 48 AHU 17 0 0 0 0 Master Bed 215 2350 2630 109 131 Master Bath 111 2872 1192 133 59 Living Room 217 2851 4184 132 209 Kitchen Nook 271 1840 4540 85 227 Family Room 184 5140 3850 239 192 Bed 3 149 2399 2049 111 102 Bed 2 164 3489 2075 162 104 Bath 72 1069 748 50 37 Hall 29 0 0 0 0 Foyer 42 729 486 34 24 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 13:49:22 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2 ...nts\Wrightsoft HVAC\5105 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N House 1580 24850 23116 1153 1153 Other equip loads 1459 775 Equip. @ 0.95 RSM 22792 Latent cooling 6309 TOTALS 1580 26310 29102 1153 1153 2021-Dec-16 13:49:22 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...nts\Wrightsoft HVAC\5105 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1627Job:Building Analysis 9/27/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Tamez Residence, NisAir Air ConditioningFor: 5105 Myrtle Dr, Fort Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Other Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 17.144913.1Walls 17.0447417.3Glazing 0.3743.7Doors 6.015661.0Ceilings 21.757083.63.6Floors 10.828391.8Infiltration 21.75700Ducts 00Piping 00Humidification 5.51459Ventilation0Adjustments 100.026310Total Cooling Walls Glazing Other CeilingsInfiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 11.828102.0Walls 24.0574022.1Glazing 0.3753.7Doors 9.723111.5Ceilings 000Floors 3.37930.5Infiltration 26.76367Ducts 3.2775Ventilation 21.05020Internal gains 00Blower 0Adjustments 100.023891Total Latent Cooling Load = 6309 Btuh Overall U-value = 0.115 Btuh/ft²-°F Data entries checked. 2021-Dec-16 13:49:22 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...nts\Wrightsoft HVAC\5105 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1627Job:Component Constructions 9/27/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Tamez Residence, NisAir Air ConditioningFor: 5105 Myrtle Dr, Fort Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 5943.155.10.109189ne 3802.02 7762.0212133.155.10.109385se 7082.0211073.155.10.109351sw 7302.0211423.155.10.109362nw 25942.0240563.155.10.1091287all Partitions Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16" OC Stud 2161.464352.9411.00.101148 Windows Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.18); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (1 ft window ht, 1 ft sep.); 6.8 ft head ht 10617.77813.000.4506ne Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.18); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 4.5 ft overhang (1 ft window ht, 1 ft sep.); 6.8 ft head ht 5317.73913.000.4503ne Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.18); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 4.5 ft overhang (6.7 ft window ht, 1 ft sep.); 6.8 ft head ht 11917.78713.100.4507ne Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.17 ft window ht, 1 ft sep.); 6.8 ft head ht 49622.140318.000.62022ne Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 69122.156118.000.62031ne 2021-Dec-16 13:49:22 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2 ...nts\Wrightsoft HVAC\5105 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 68121.852516.800.58031se Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (2.1 ft window ht, 1 ft sep.); 6.8 ft head ht 12720.110616.800.5806sw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.17 ft window ht, 1 ft sep.); 6.8 ft head ht 97721.875316.800.58045sw 101422.675316.800.58045nw 199122.2150616.800.58090all Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 8 ft overhang (6.7 ft window ht, 1 ft sep.); 6.8 ft head ht 75114.0101018.800.65054sw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (4.17 ft window ht, 1 ft sep.); 6.8 ft head ht 21222.615816.800.5809nw Doors Fbrgls Door 753.73743.697.00.12720ne Ceilings Attic, Shngl Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.0341580 23111.4615660.9930.0 Floors On Grade Depth, Tile Flr Fnsh 00570828.700.989199 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 13:49:22 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...nts\Wrightsoft HVAC\5105 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1627Job:Project Summary 9/27/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Tamez Residence, NisAir Air ConditioningFor:5105 Myrtle Dr, Fort Pierce, FL 34982 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh19151 Structure Btuh16749 Ducts Btuh5700 Ducts Btuh6367Central vent (46 cfm) 1459 Btuh Central vent (46 cfm) Btuh775 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh26310 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh22792 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh2612 Ducts Btuh1928Central vent (46 cfm) Btuh1770 CoolingHeating Outside air15801580Area (ft²) Equipment latent load Btuh6309 1406414064Volume (ft³)Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh29102 Equiv. AVF (cfm) 4789 Req. total capacity at 0.70 SHR ton2.7 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOX Model Cond ML14XC1S036-230C**AHRI ref Coil CBA27UHE-036-230*++TDR AHRI ref 204289057Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW7.4 Sensible cooling Btuh24220Heating output Btuh25190 Latent cooling Btuh10380 Temperature rise °F20 Total cooling Btuh34600Actual air flow cfm1153 Actual air flow cfm1153 Air flow factor cfm/Btuh0.046 Air flow factor cfm/Btuh0.050Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.79 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 13:49:22Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1...nts\Wrightsoft HVAC\5105 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1627Job:Right-J® Worksheet 9/27/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name House WIC 2 Exposed wall 199.0 ft 15.0 ft 3 Room height 8.9 ft 8.0 heat/coolft 4 Room dimensions ft6.0x9.0 5 Room area 1579.5 ft²54.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 278 189 594 380 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 6 0 78 106 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 3 0 39 53 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 7 0 87 119 0 0 0 0 11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 22 0 403 496 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 31 0 561 691 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 20 20 74 75 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 416 385 1213 776 48 48 151 97 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8221.82 31 4 525 681 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 456 351 1107 708 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.1220.12 6 2 106 127 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8121.81 45 5 753 977 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 54 54 1010 751 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 417 362 1142 730 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 9 0 158 212 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 45 0 753 1014 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 148 148 435 216 72 72 212 105 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 1580 1580 1566 2311 54 54 54 79 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 1580 199 5708 0 54 15 430 0 6 c) AED excursion 513 -17 Envelope loss/gain 16312 10936 846 263 12 a) Infiltration 2839 793 87 24 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 4 920 0 0 Appliances/other 4100 0 Subtotal (lines 6 to 13)19151 16749 933 288 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 19151 16749 933 288 15 Duct loads 30%38%5700 6367 30%38%278 109 Total room load 24850 23116 1211 397 Air required (cfm)Air required (cfm)1153 1153 56 20 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 13:49:22Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2...nts\Wrightsoft HVAC\5105 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1627Job:Right-J® Worksheet 9/27/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Laundry AHU 2 Exposed wall 11.5 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.0x9.5 ft3.0x5.5 5 Room area 57.0 ft²16.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.1220.12 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 16 16 50 32 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 76 76 223 111 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 57 57 56 83 17 17 16 24 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 57 12 330 0 17 0 0 0 6 c) AED excursion -42 -1 Envelope loss/gain 660 185 16 23 12 a) Infiltration 29 8 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13)689 693 16 23 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 5 7 -16 -23 14 Subtotal 694 700 0 0 15 Duct loads 30%38%207 266 30%38%0 0 Total room load 901 966 0 0 Air required (cfm)Air required (cfm)42 48 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 13:49:22Right-Suite® Universal 2021 21.0.10 RSU29066 Page 3...nts\Wrightsoft HVAC\5105 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1627Job:Right-J® Worksheet 9/27/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Master Bed Master Bath 2 Exposed wall 16.5 ft 29.5 ft 3 Room height 8.5 heat/coolft 8.0 heat/coolft 4 Room dimensions ft16.5x13.0 ft8.5x13.0 5 Room area 214.5 ft²110.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 140 109 344 220 68 68 214 137 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8221.82 31 4 525 681 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 104 98 308 197 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.1220.12 0 0 0 0 6 2 106 127 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 64 64 202 129 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 215 215 213 314 111 111 110 162 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 215 17 473 0 111 30 846 0 6 c) AED excursion 116 -8 Envelope loss/gain 1554 1331 1785 744 12 a) Infiltration 254 71 428 120 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13)1808 1902 2213 863 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 3 4 0 0 14 Subtotal 1811 1906 2213 863 15 Duct loads 30%38%539 724 30%38%659 328 Total room load 2350 2630 2872 1192 Air required (cfm)Air required (cfm)109 131 133 59 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 13:49:22Right-Suite® Universal 2021 21.0.10 RSU29066 Page 4...nts\Wrightsoft HVAC\5105 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1627Job:Right-J® Worksheet 9/27/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Living Room Kitchen Nook 2 Exposed wall 14.5 ft 11.0 ft 3 Room height 10.0 heat/coolft 9.5 heat/coolft 4 Room dimensions ft14.0x15.5 ft270.5x1.0 5 Room area 217.0 ft²270.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 145 91 288 184 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.1220.12 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 54 54 1010 751 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 105 82 259 165 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 22 0 377 507 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 217 217 215 317 271 271 268 396 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 217 15 416 0 271 11 315 0 6 c) AED excursion 338 -5 Envelope loss/gain 1929 1591 1219 1063 12 a) Infiltration 263 73 189 53 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 2 460 Appliances/other 900 1700 Subtotal (lines 6 to 13)2192 3024 1408 3276 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 5 7 10 14 14 Subtotal 2197 3031 1418 3290 15 Duct loads 30%38%654 1152 30%38%422 1251 Total room load 2851 4184 1840 4540 Air required (cfm)Air required (cfm)132 209 85 227 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 13:49:22Right-Suite® Universal 2021 21.0.10 RSU29066 Page 5...nts\Wrightsoft HVAC\5105 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1627Job:Right-J® Worksheet 9/27/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Family Room Bed 3 2 Exposed wall 39.0 ft 15.0 ft 3 Room height 9.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft8.0x23.0 ft11.0x13.5 5 Room area 184.0 ft²148.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 110 73 229 147 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 6 0 78 106 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 31 0 561 691 DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 72 72 227 145 40 40 126 81 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 207 162 511 327 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.1220.12 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8121.81 45 5 753 977 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 72 50 156 100 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 22 0 377 507 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 184 184 182 269 149 149 147 217 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 184 39 1119 0 149 15 430 0 6 c) AED excursion 287 -89 Envelope loss/gain 3325 2612 1572 1152 12 a) Infiltration 636 178 272 76 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 250 Subtotal (lines 6 to 13)3961 2789 1844 1478 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 5 6 14 Subtotal 3961 2789 1848 1485 15 Duct loads 30%38%1179 1060 30%38%550 564 Total room load 5140 3850 2399 2049 Air required (cfm)Air required (cfm)239 192 111 102 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 13:49:22Right-Suite® Universal 2021 21.0.10 RSU29066 Page 6...nts\Wrightsoft HVAC\5105 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1627Job:Right-J® Worksheet 9/27/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 2 Bath 2 Exposed wall 32.0 ft 9.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft163.8x1.0 ft9.0x8.0 5 Room area 163.8 ft²72.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 120 98 308 197 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 22 0 403 496 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 48 48 151 97 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.1220.12 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 88 88 277 177 72 63 197 126 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 9 0 158 212 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 164 164 162 240 72 72 71 105 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 164 32 918 0 72 9 258 0 6 c) AED excursion -90 50 Envelope loss/gain 2219 1116 685 494 12 a) Infiltration 464 130 130 36 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 0 Subtotal (lines 6 to 13)2683 1495 815 530 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 6 8 9 12 14 Subtotal 2688 1504 824 542 15 Duct loads 30%38%800 572 30%38%245 206 Total room load 3489 2075 1069 748 Air required (cfm)Air required (cfm)162 104 50 37 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-16 13:49:22Right-Suite® Universal 2021 21.0.10 RSU29066 Page 7...nts\Wrightsoft HVAC\5105 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1627Job:Right-J® Worksheet 9/27/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Hall Foyer 2 Exposed wall 0 ft 6.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.5x4.5 ft7.0x6.0 5 Room area 29.3 ft²42.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 48 18 57 37 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 3 0 39 53 .GG Impact, Clear Low-e 0.450Impact, Clear Low-e 0.450 nene 13.0513.05 17.6917.69 0 0 0 0 7 0 87 119 11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 20 20 74 75 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.1220.12 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 29 29 29 43 42 42 42 61 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 29 0 0 0 42 6 172 0 6 c) AED excursion -2 -21 Envelope loss/gain 29 40 472 324 12 a) Infiltration 0 0 87 24 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)29 40 559 348 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -29 -40 3 4 14 Subtotal 0 0 562 352 15 Duct loads 30%38%0 0 30%38%167 134 Total room load 0 0 729 486 Air required (cfm)Air required (cfm)0 0 34 24 2021-Dec-16 13:49:23 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...nts\Wrightsoft HVAC\5105 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1627Job:Duct System Summary 9/27/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Tamez Residence, NisAir Air ConditioningFor: 5105 Myrtle Dr, Fort Pierce, FL 34982 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.446 / 0.254 in H2O in H2O0.446 / 0.254 Lowest friction rate in/100ft0.286in/100ft0.286 Actual air flow cfm1153cfm1153 Total effective length (TEL) ft245 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st4120.035.9VlFx0x05.00.28645601069hBath st4115.034.1VlFx0x07.00.2991241943489hBed 2 st4115.032.8VlFx0x06.00.3021231342399hBed 3 st5115.040.9VlFx0x07.00.2861151432570hFamily Room st5115.039.8VlFx0x07.00.2881151432570hFamily Room-A st395.07.6VlFx0x04.00.4352941729hFoyer st5115.036.3VlFx0x07.00.295136512270cKitchen Nook st5115.036.0VlFx0x07.00.295136512270cKitchen Nook-A st390.06.5VlFx0x04.00.4625850966cLaundry st2105.016.3VlFx0x08.00.3682501594184cLiving Room st2105.023.9VlFx0x07.00.346711602872hMaster Bath st2105.019.1VlFx0x05.00.35979651315cMaster Bed st2105.017.3VlFx0x05.00.36579651315cMaster Bed-A st2105.025.3VlFx0x05.00.34224671211hWIC Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 387 292 0.286 877 9.0 0x0 VinlFlx st1 st5 Peak AVF 389 502 0.286 640 12.0 0x0 VinlFlx st1 st1 Peak AVF 776 794 0.286 743 14.0 0x0 VinlFlx st2 Peak AVF 517 503 0.342 658 12.0 0x0 VinlFlx st3 Peak AVF 91 87 0.435 666 5.0 0x0 VinlFlx Bold/italic values have been manually overridden 2021-Dec-16 13:49:23 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2 ...nts\Wrightsoft HVAC\5105 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb3 0x 1940 124 88.7 0.286 557 8.0 x0 0 VlFx rt1 rb2 0x 1340 123 85.1 0.299 500 7.0 x0 0 VlFx rt1 rb1 0x 8580 956 79.3 0.320 541 18.0 x0 0 VlFx rt1 rb4 0x 1980 181 0 0 0 0 x0 0 VlFx Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 1186 1203 0.286 861 16.0 0x0 VinlFlx 2021-Dec-16 13:49:23 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...nts\Wrightsoft HVAC\5105 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1627Job:Manual S Compliance Report 9/27/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Tamez Residence, NisAir Air ConditioningFor: 5105 Myrtle Dr, Fort Pierce, FL 34982 Cooling Equipment Design Conditions °F76.6Entering coil DB:Btuh23891Sensible gain:°F90.4Outdoor design DB: °F63.8Entering coil WB:Btuh6309Latent gain:°F77.4Outdoor design WB: Btuh30201Total gain:°F75.0Indoor design DB: cfm1153Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: ML14XC1S036-230C**+CBA27UHE-036-230*++TDRModel:LennoxManufacturer: cfm1153Actual airflow: % of load101Btuh24220Sensible capacity: % of load165Btuh10380Latent capacity: %70SHR:% of load115Btuh34600Total capacity: Heating Equipment Design Conditions °F68.4Entering coil DB:Btuh26310Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm1153Actual airflow: °F50Temp. rise:% of load96kW7.4Output capacity: Meets all requirements of ACCA Manual S.