Loading...
HomeMy WebLinkAboutOuanalao Resort Temp Service One Line 14150 NW 3RD Ave • Miami, FL 331 6 8 • Tel 954·255·0371 • Fax 954-255-0374 www.ceielectric.net 200 amp 120/240 volt 1PH Meter Main #2 AL Grounding Electrode Conductor (2) 5/8” x 10’ Copper Ground Rods 8’ Apart 200-amp 240-volt single phase Fused Disconnect Nema 3R with 125- amp Fuses 2.5” Underground conduit to FPL Handhole with (3) 250MCM AL (1) 2” Conduit with (3) 2/0 AL & (1) #4 AL Grd Job Address: 7650-7700 S. Ocean Dr. St. Lucie County, FL 34957 Owner: Ouanalao Resort FPL Account: Unknown SCOPE OF WORK: Install New Temporary 200 Amp Underground Electrical Service to FPL Handhole. Install New Meter & Disconnect on New H-Frame. New Wiring from Main Disconnect to existing 125-amp Main Breaker Panel mounted to the exterior of the Prefab Sales Trailer. Temp Service to be removed after construction is complete. Existing Prefab Sales Trailer with (1) 125-amp Main Breaker Single Phase exterior mounted Electrical Panel. Existing 125-amp Main Breaker Electrical Panel attached to Sales Trailer Jose I Barreto EC13007709 New (3) 250 MCM AL To FPL Handhole (3) 250 MCM AL (1) 4 THHN AL 2.5” Conduit