Project Summary pat wrightsoft° Entire House By: QUICK CALCS, INC. 817 ST.'LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772466-6796. Email: QUICKCALCS@AOL.COM. For: THE GRAND CARLTON WYNNE DEVELOPMENT, FT. PIERCE, FL . Notes: _\ Design Information Weather. Winter Design Conditions Outside db 42 OF Inside db 70 OF Design TD 28 OF Heating Summary Structure 17848 Btuh Ducts 5654 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 . Btuh Piping 0 Btuh Equipment load 23503 Btuh Infiltration Fort Pierce, FL, US Method Simplified Construction quality Average Fireplaces 0 He 14 9 Cool'446 Area ft Volume (ft3) 12511 12511 Air changes/hour 0.45 0.23 Equiv. AVF (cfm) 94 48 Heating Equipment Summary Make Carrier Trade CARRIER AIR CONDITIONING Model 25HBC536A*030 AHRI ref 7914585 Efficiency Heating Input Heating output Temperature rise Actual'air flow Air flow factor Static pressure Space thermostat Capacity balance point = 32 OF Backup: 8.5 HSPF 34600 Btuh @ 47°F OF 1160 cfm 0.049 cfm/Btuh 0.50 in H2O Input = 7 kW, Output = 23009 Btuh, 100 AFUE Summer Design Conditions Outside db 90 OF Inside db 75 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 61 gr/lb Sensible Cooling Equipment Load Sizing Structure 17520 Btuh Ducts 8536 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data Rate/swing multiplier n 0.95 Equipmenf sensible load 24753 Btuh Latent Cooling Equipment,Load Sizing Structure 3203 'Btuh Ducts 2318 Btuh Central vent (0 cfm) 0 Btuh (none). Equipment latent load 5521 Btuh Equipment total load 30274 Btuh Req. total capacity at 0.70 SHR 2.9 ton Cooling Equipment Summary Make Carrier Trade CARRIERAIR CONDITIONING Cond 25HBC536A*030 Coil FX4DN(B,F)037 AHRI ref 7914585 Efficiency 12.0 EER, 15 SEER Sensible cooling 24360 Btuh Latent cooling 10440 Btuh Total cooling 34800 Btuh Actual air flow 1160 cfm Air flow factor 0.045 cfm/Btuh Static pressure 0.50 in H2O Loadsensible heat ratio 0.83 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft" 2017-Apr-11 09:29:38 .�- Right-Sufte® Universal 2017 17.0.14 RSU08101 Page 1 ��` ...uick Calcs\Documents\THE GRAND CARLTON-1446.rup Calc = MJ8 Front Door faces: N -�+ wrightsoft° Right-M Worksheet Job: Entire House Date: sy. QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS AOL.COM 1 Room name Entire House BEDROOM 2 3 Exoosed wall Room height 156.2 ft 8.7 ft d 49.0 ft 8.0 ft heat/cool 4 5 Room dimensions Room area 1445.5 ft2 1.0 x 297.0 ft 297.0 ft2, Ty Construction U-value Or HTM Area 2 Load number (Btuh/ft2-°F) (Stuh/ft2) or perimeter (ft) (Btuh) orperimeter(ft) (Btuuh) . Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 v� 13A flocs' 4A5 tom: '• ' ' 13A-4ocs 0.143 03,70 0.143 n `' . - n:. a 4:00 21 56. 4.00 2,55 19:31 2.55 508 . 38 128 .'.. -465 : 0 83 1862 : 815 333 .: 1184 ; 730 212 72 : 0 0 72 ; 0 0 ' 288 `-0 0 183 0 0 11 I-- G l-D 1A-clom 11DO 1.270 0.390 a a 35.56 10.92 87.29 11.31 24 21 2 21 848 229 2082 238 0 0 0 0 0 0 0 0 IN .. Vdl 13A-4bc"s 13AAocs 0.143 0.143 se s 4.00 4.00 2.55 2.55 34, 360 34 353 136 1414 86 899 0 216 0 216 -0 865 0 550 IA-clom 1.270 s 35.56 34.77 7 7 247 241 0 0 0 0 13A-04,ocs 1Ac1onn 12C-0sw 16A=30md' - -- 0143 1.270 6-770 0.091 0:032 w w , w: ;, 4.06 35.56, 21.56 2.55, : 0 90' 2.55 55.21 19.31 1.28 2 32 310 32 ` : 41: 192. .:.. : 1446 237 2 41 192 1445 949 1140 880 489 -, 1295 603 1770 ;+:. 788 246 ::. 3354 104 • 32 _ p 0 ` -. `.297 72 .. 2 '- 0 0 .` `• 291 288 1140 : 0; 0 ; ;: 266 183 1770 0 0 :-. 689. P C F.. 22A-tpl 0.989 - 27.69 0.00 1446 156 4325 0 297 49 1357 0 6 c)AED exursion 918 627 Envelope loss/gain 14961 13349 4204 4003 12 a) Infiltration 2887 791 848 232 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 6 1380 3 .690 Appliances/other 2000 0 Subtotal (lines 6 to 13) 17848 17520 5053 4925 Less eMemal load 0 0 0 0 Less.transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 17848 17520 5053 4925 15 Duct loads 32"/0 49% 5654 8536 32% 49% 1601 2400 Total room load 23503 26056 6653 7325 Air required (cfm) 1 11601 1160 328 326 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -- wcightsoft� 2017-Apr-11 09:29:38 -A Right:Suite® Universal 2011 17.0.14 RSU08101 Page 1 uick Calcs\Documents\THE GRAND CARLTON-1446.rup . Calc = MJ8 Front Door faces: N AL wrightsoft- Right-.1®Worksheet Job: Entire House Date: ay QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772A66-6796 Email: QUICKCALCS@,AOL.COM 1 Room name WIC WCHEN 2 Bqposed wall O ft O ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 6.0 x 9.0 ft 1.0 x 172.0 ft 5 Room area 54.0 ft2 172.0 ftz Ty Construction U-value Or HTM Area (ft') Load . Area (ft.) Load number (Btuh/ft"F). (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross WP/S Heat Cool Gross WP/S Heat Cool 6 13A-4ocs ,-- 0143 n :; 4 00 2:55 0 J p .` p 0, p; 0 0 U 0770. •ri' 21.56 1981 0 0 • 0 ;0 0`': 0. 0 .. 0 ::4A52om;: 13A-4ocs 0.143 a 4.00 2.55 0 .0 0 0 0 0 0 0 1Aclom 1.270 a 35.56 87.29 0 0 0 0 0 0 0 0 11 11D0 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0 W ,: 13A-4ods. 0143. se 4.00 2:55 0 0. 0 0 0. 0 0 0 V►/ t-G 13A-4ocs 0.143 s 4.00 2.55 0 0 0 0 0 0 0 0 1A-clam 1.270 s 35.56 34.77 0 0 0 0 0 0 0 0 13A46cs 0.143 •. w 4.00. 2.55 0 0 0 0 0 0 A 0 1Ac1om 1.270 - w 35.56 55.21 0 0 0 0 0 ;0 0 0 4A5 tom .0.770 w 21 56. 19.31 0: 0 0 .0 0'. . U : 0 0 P 12C-Osw 0.091 - 2.55 1.28 0 0 0 0 64 64 163 82 C 16A-30md . '0:032 - :. : 0 90' -2 3-2 . .54 ;.: 54 .. 48 ; `125 ,. .172 :. - , 172 : 154 ':. '. ;399 F 72A-tpl 0.989 - 27.69 0.00 54 0 0 0 172. 0 0 0 6 c)AED excursion -9 -170 Envelope loss/gain 48 117 317 311 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 01 2000 Subtotal (lines 6 to 13) 48 117 317 2311 Less wdemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 48 117 317 2311 15 Duct loads 32% 49% 15 57 32% 49% 100 1126 Total room load 64 174 418 3437 Air required (cfm) 3 8 21 153 Calculations approved byACCA to meet all requirements'of Manual J 8th Ed. AOUP, wrightsoft' Right -Suite® Universal 2017 17.0.14 RSU08101 2017-Apr-11 0 Page 2 ...uick Calcs%DocumentslTHE GRAND CARLTON-1446.mp Calc = MJ8 Front Door faces: N - wrightsoft Righ-WO Worksheet Job: Entire House . Date: QUICK CALLS, INC. By: 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@gOL.COM 1 Room name BATH BEDROOM 2 2 3 E)qposed wall Room height 5.0 ft 8.0 ft heat/cool 34.2 ft 8.0 ft heat/cool 4 5 Room dimensions Room area 9.0 x 5.0 ft 45.0 ftz 1.0 x 203.5 ft 203.5 ftz Ty Construction number LI-value (Btuh/ftl-°F) Or HTM (Btuh/ft2) Area t2) or perimeter (ft) Load (Btuh) Art-) orsperimeter . (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross NIP/S Heat Cool 6 y/ 13A4ocs_'.,.. 13A4ocs 0 770 0.143 . n = a , .2156 4.00 2,55•., 19.31 2.55. '40- U 0 40 0 0 160 . 0 0 .'. 102 . ". 0 0 128> ' : 0 80 12t1:` :" p 56 513 225 326 143 11 1Aclom 11D0 .13A4ocs 13A-4ocs 1Aclom 13A.4aos 1Ac1om 1.270 0.390 0:143 0.143 1.270 .0.143 1;270 a a se s s w. w : 35.56 10.92 .4:00 4.00 35.56 4.00 3556; 87.29 11.31 2.55 2.55 34.77 2.55 55.21' 0 0 0 0 0 0 •0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 .. 0 24 0 34 32 0 0 0:. 2 0 .34 32 0 0, 0 848 0 136 128 0 0 . 0 2082 0 86 81 0 0 :. 0. W AA&26m -. 12C-0sw. 16A 30md - -. 22A tpl 0.770 0.091. : 0.032 0.989 . W' - - - - - 2156 2.55 0:90 27.69 19.31 1.28. 232 0.00 0 0 . . 45 45 0 0 ; '. 45 5 :: 0 0 -40 138 b 0 ,. .104 0 _ - 0 0 ' 204 204 ."- 0 0 : - 204 34 . `0 0 : 182 946 .. 0 0 ' 472 p P G F 6 c)AED excursion -16 -85 Envelope loss/gain 339 190 2978 3106 12 a) Infiltration . 87 24 593 162 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 1 230 Appliances/other 0 0 Subtotal Qines 6 to 13) 425 214 3571 3498 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 425 214 3571 3498 15 Duct loads 320. 49% 135 104 32% 49% 1131 17M Total room load 560 318 4702 5203 Air required (cfm) 28 14 12321 232 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. A wright9oft' Right -Suite® Universal2017 17.0.14 RSU08101 2017-Apr-11 0 Page 3 ...nick Caics\Documents\THE GRAND CARLTON-1446.rup Calc = MJ8 Front Door faces: N - wrightsoft' Right-JO Worksheet Job: Entire House' Date: QUICK CALCS, INC. By: 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS ,AOL.COM 1 Room name LAUNDRY GREAT/DINING 2 Exposed wall 6.0 ft 47.0 ft 3 Room height 8.0 ft heat/cool 9.8 ft heat/cool 4 5 Room dimensions Room area 7.0 x 6.0 ft 42.0 ftz 1.0 x 526.0 fit 526.0 ftz Ty Construction U-value Or HTM Area (ft-) Load Area (ftz) Load number (Btuh/ftz-°F) (Btuhlft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A• flocs 13A-4ocs 0.143 0.143 n :' " e 4 00 4.00 2 55 1931.. 2.55 0 0 0 0 0 0 0 0 0 0 . 0 0 .. 255 . 38 0 217 - ' 0 .0 869 -815 0 552 .. ` 730 0 11 IA-c1om 11DO 1.270 0.390 a a 35.56 10.92 87.29 11.31 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W--'13A-Aocs 0:143 se AM 2.55 0 0 0 0 0 0, 0 0 Vdl 13AAocs 0.143 s 4.00 2.55 48 48 192 122 0 0 0 0 1Aclom 1.270 s 35.56 34.77 0 0 0 0 0 0 0 0 _G 13AA6cs • 1A:c1om - '.4A5 tom _: 0.143 1:270 0;7/0 w w , , w : 4.00 35.56 21i56 2.55 55.21 19:31 0 0 0 0 - 0 0 : 0 .` U 0 . - 0 ' 0 206 0: .. • 41 165 ..0. : - 41' 661 0 . SBO. 420 0 • 'T88; P 12C-Osw 0.091- . = 2.55 .1:28 . 56 56 143 72 0- 0 0 . . 0 30md.. _ !0 032 - ;0.90 2.32 : " 42 ' ;° ` 42 ' . .. 38 -97 , .526 , - .. ' 526 ; 47.1: `: - >1220 F 22A-tpl 0.989 27.69 0.00 42 6 166 0 526. 47 1302 0 6 c)AED excursion -22 668 Envelope loss/gain 539 270 4997 4379 12 a) Infiltration 104 26 997 273 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 2 460 Appliances/other 0 0 Subtotal (lines 6 to 13) 643 298 5994 5112 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal' 643 298 6994 5112 15 Duct loads 1 32% 49%1 204 145 32% 49% 1899 2490 Total room load 846 443 7892 7602 Air required (cfm) 42 20 390 338 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. A A 'Fk wrightsoft- RightSuite® Universal 2017 17.0.14 RSU08101 2017-Apr-11 0 Page 4 uick Calcs\Documents\THE GRAND CARLTON-1446.rup Caic = MJ8 Front Door faces: N + wrightsoft' Right-JO Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS AOL.COM 1 Room name FOYER M. BATH 2 Exposed wall 7.0 ft 8.0 ft 3 Room height 8.0 ft heaticool 8.0 ft heat/cool 4 Room dimensions 1.0 x 50.0 ft 7.0 x 8.0 ft 5 Roorri area 50.0 ft2 56.0 ft2. Ty Construction LI-value Or HTM Area (ft-) Load Area Lo number (Btuh/ft;°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross WP/S Heat Cool 6 V�/ 13A-Aocs..,. :0.143 n=: �4:00', 255 8. 8 32 20 0 0° ;.:0 0. ::4A5 2om.. 0.770 . n . 21.'W 19:31; '0 p > : p ,. . p : O r, U r 0 ,. 0 V�/�G 13A.4ocs 0.143 a 4.00 2.55 48 27 108 69 0 0 0 0 IA-clom 1.270 a 35.56 87.29 0 0 0 0 0 0 0 0 11 r-D 11D0 0.390 a 10.92 11.31 21 21 229 238 0 0 0 0 W - ..13A-4ocs OAQ se 4.00 2.55 0 0 0- 0 0 0. 0 0 13A-4ocs 0.143 s 4.00 2.55 0 0 0 0 64 57 228 145 �G 1A-clom 1.270 s 35.56 34.77 0 0 0 0 7 7 247 241 13A1tocs 0.143 w 4:00 2.55 0 0 0 0 0 '0 . .0 0. X.clom. ,_ 1.270 w. ` 35.56 55 21 0- 0 0 0- 0 0 0 0 4A5-2om _ 0:770 , w:' 21.56.. 19 31` 0 . 0 0 0 0 ' 0 ;0 .. 0, P- 12C-Osw ' 0.091 - 2.55 1.28 72 72 183 92 0 0 . 0 0 C ; „16A40 d - 0 032 , _ - 0 90: • 2 32 . r50 ' . : 50 . 45 : 116 .- - 56 F" 56 : 5.0 ... ; - ,130 F . 22A tpl 0.686 - 27.69 0.00 50 7 194 0 56 8 , 222 0 6 c)AED excursion -39 -38 Envelope loss/gain 792 496 747 478 12 a) Infiltration 121 33 138 38 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 913 529 885 516 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 913 529 885 516 15 Duct loads 132% 49% 289 258 32% 49% 280 251 Total room load I 1202 787 1166 768 Air required (cfm) 1 1 59 351 58 34 Calculations approved byACCA to meet all requirements of Manual .J 8th Ed. wrightsoft' . Right -Suite® Universal 2017 17.0.14 RSU08101 2017-Apr-11 0 Page 5 ...uick CalcslDocuments\THE GRAND CARLTON-1446.rup Calc = MJS Front Door faces: N wrightsoft° Duct.System Summary pat Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone:.772-466-6799: Fax 772-466-6796 Email: QUICKCALCS al OL.COM r-roject intormation • For: THE GRAND CARLTON WYNNE DEVELOPMENT, FT. PIERCE, FL Extemal static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating. 0.50 in H2O 0 in H2O .0:50 .in H2O 0.250 / 0.250 in H2O 0.285 in/100ft 1160 cfm Cooling 0.50 in H2O 0 in H2O 0.50 in H2O 0.250 / 0.250 in H2O 0.285 in/100ft 1160 cfm 176 ft Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH h 560 28 14 0.364 4.0 Ox 0. VIFx 22.4 115.0 st1 BEDROOM 2 h 4702 232 232 0.360 7.0 OxO VIFx 23.9 115.0 st1 BEDROOM -A h 3327 164 163 0.300 6.0 Ox0 VIFx 31.8 135.0 st2 BEDROOM-B h 3327 164 163 0.285 6.0 Ox 0 VIFx 40.6 135.0 st2 FOYER h 1202 59 35 0.505 4.0 Ox 0 VIFx 4.0 95.0 GREAT/DINING h 3946 195 169 0.300 7.0 OxO VIFx 31.8 135.0 st2 GREAT/DINING-A h 3946 195 169 0.300 7.0 Ox0 VIFx 31.8 135.0 st2 KITCHEN c 3437 21 153 0.379 6.0 Ox 0 VIFx 17.0 115.0 st1 LAUNDRY h 846 42 20 0.361 4.0 OxO VIFx 23.3 115.0 st1 M. BATH -A h 768 58 34 0 0 Ox 0 VIFx 0 0 wlc c 174 3 8 0.309 4.0 Ox 0 VIFx 27.0 135.0 st2 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st2 PeakAVF 721. 672 0.285 9.18 12.0 0 x 0 VinlFlx st1 st1 Peak AVF 1043 1091 0:285 1020 14.0 0 x 0 VinlFlx wri htsoft° 2017-Apr-1109:29:38 9 Right -Suited Universal 2017 17.0.14 RSU08101 Page 1 ...uick Calcs\Documents\THE GRAND CARLTON=1446.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FIR .. Veloc ..Diam' (fph) (in) H x W (in) Stud/J6ist Opening (in) Duct Matl Trunk rb1 OxO 1160 1160 0 0 0 0 Ox 0 VIFx Wrl htsoft° 2017-Apr-1109:29:38 9 Right -Suite® Universal 2017 17.0.14 RSU08101 #CCA Page 2 ...uick Calcs\Documents\THE GRAND CARLTON-1446.rup Calc = MJS Front Door faces: N