HomeMy WebLinkAboutCONSTRUCTION PLANSTRUCTURAL DESIGN STATEMENT
PREPARED FOR:
TH❑MAS DRElER
I CERTIFY THAT, TO THE BEST OF MY KNOWLEDGE AND BELIEF, THESE PLANS AND
SPECIFICATIONS HAVE BEEN DESIGNED TO COMPLY WITH THE APPLICABLE STRUCTURAL
PORTIONS OF THE BUILDING CODES.
I ALSO CERTIFY THAT THE STRUCTURAL COMPONENTS, SYSTEMS, & RELATED ELEMENTS PROVIDE
ADEQUATE RESISTANCE TO WIND LOADS AND FORCES SPECIFIED BY THE CODES LISTED
BELOW.
DESIGN PARAMETERS & ASSUMPTIONS
CODE EDITION:
■ FLORIDA BUILDING CODE 2020, 7TH EDITION
■ ASCE 7-16 (EXPOSURE CONDITION): C
CONSTRUCTION TYPE: VB
OCCUPANCY CLASSIFICATION: R-3
BUILDING DESIGNED AS:
❑ PARTIALLY ENCLOSED
■ ENCLOSED
❑ OPEN
❑ TESTED (WIND TUNNEL)
BUILDING HEIGHT:
■ <_ 60 FT. ASCE 7.
❑ > 60 FT. MUST USE ASCE 7.
MEAN ROOF HEIGHT: 20 FT.
FOR LOW RISE BUILDING WITH SLOPED ROOFS.
RISK FACTOR: I I
DETERMINED BUILDING USE/ OCCUPANCY, REFER TO ASCE 7 TABLE 1.5-1.
INTERNAL PRESSURE COEFFICIENT: +/-0.18
ENCLOSED BUILDING.
BASIC WIND VELOCITY PRESSURES:
APPROPRIATE POSITIVE/ NEGATIVE PRESSURE COEFFICIENTS HAVE BEEN APPLIED TO MAIN
WIND FORCE RESISTING SYSTEM, AND BUILDING ENVELOPE COMPONENTS AND
CLADDING, AS APPLICABLE:
WIND SPEED (3 SEC.GUST): 160 MPH
NOTE:ACTUAL DESIGN PRESSURES FOR ALL EXTERIOR WINDOWS, DOORS, GARAGE
DOORS AND SIMILAR ENVELOPE ELEMENTS ARE INDICATED ON CONSTRUCTION PLANS.
e
e
a
0
GENERAL NOTES
1. DO NOT SCALE THESE DRAWINGS,
WRITTEN DIMENSIONS TAKE PRECEDENCE
OVER SCALED DIMENSIONS. THE
CONTRACTOR SHALL REVIEW THESE
DRAWINGS IN THEIR ENTIRETY BEFORE
COMMENCING CONSTRUCTION AND
SHALL ACCEPT FULL RESPONSIBILI1FY FOR
ANY ERRORS OR OMISSIONS NOT
REPORTED IMMEDIATELY IN WRITING TO
THE WHOLE HOUSE ENGINEERING, LLC.
BACK CHARGES WILL NOT BE ACCEPTED.
2. THE GENERAL CONTRACTOR SHALL VERIFY
THE BUILDING POSITION WITHIN THIE
SETBACK LINES PRIOR TO COMMENCING
CONSTRUCTION.
3. IT SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR TO BE FAMILIARIZED WITH
ALL EXISTING CONDITIONS AS THEY ARE
NOT NECESSARILY SHOWN ON THESE
DRAWINGS.
4. GENERAL CONTRACTOR SHALL BE:
RESPONSIBLE FOR VERIFYING LOCATIONS
OF ALL FLOOR, ROOF, AND WALL
OPENINGS AND PENETRATIONS.
5. IT IS THE CONTRACTORS SOLE
RESPONSIBILITY TO COORDINATE THE
WORK OF ALL TRADES, DETERMINE:
ERECTION PROCEDURE, AND SEQUENCE
TO INSURE THE SAFETY OF THE BUILDING, ITS
COMPONENTS, AND TRADE BASE DURING
CONSTRUCTION.
6. ALL DETAILS AND SECTIONS SHOWN ON
THESE DRAWINGS ARE INTENDED TO BE
TYPICAL AND SHALL BE CONSTRUED TO
APPLY TO ANY SIMILAR CONDITION
ELSEWHERE IN THE WORK EXCEPT'WHERE A
DIFFERENT DETAIL AND OR SECTION IS
SHOWN.
7. BUILDER IS RESPONSIBLE FOR ADEQUATE
BRACING OF STRUCTURAL OR
NON-STRUCTURAL MEMBERS DURING
CONSTRUCTION.
8. IT IS THE GENERAL CONTRACTORS
RESPONSIBILITY TO PROVIDE ALL
NECESSARY SHOP DRAWINGS, WINDOWS,
DOORS, ETC. TO WHOLE HOUSE
ENGINEERING, LLC FOR REVIEW AND
APPROVAL.
9. ALL WINDOWS AND DOORS SHALL BE
CAULKED AND WEATHER STRIPPED.
10.THESE DOCUMENTS, AS INSTRUMENTS OF
SERVICE, ARE THE PROPERTY OF WHOLE
HOUSE ENGINEERING, LLC., AND SHALL
NOT BE USED OR REPRODUCED WITHOUT
THE EXPRESS WRITTEN CONSENT OF WHOLE
HOUSE ENGINEERING, LLC.
11. THE CONTRACTOR SHALL BE RESPONSIBLE
FOR OBTAINING ALL REQUIRED BUILDING
AND TRADE PERMITS AND FOR THEEIR
RESPECTIVE COSTS.
12.THESE DRAWINGS ARE DIAGRAMMATICAL
AND ARE INTENDED TO SHOW DESIGN
INTENT ONLY. THEY DO NOT SHOW EVERY
MINOR DETAIL OF CONSTRUCTION. ALL
TRADES ARE RESPONSIBLE FOR FURNISHING
COMPLETE BUILDING SYSTEMS AND ALL
ITEMS THAT WOULD NORMALLY BE:
CONSIDERED INCIDENTAL TO THEIR
INSTALLATION.
FLOOR PLAN NOTES
1. SAFETY GLAZING. ALL GLAZING IN SLIDING
AND SWINGING DOORS, INCLUDING
SHOWER AND TUB ENCLOSURES, TO BE
SAFETY GLAZED AS PER FBC 2406A &
R308.4. ALL GLAZING IN ANY HAZARDOUS
LOCATION OF A BUILDING WITH STILL LESS
THAN 60" A.F.F. SHALL BE SAFETY GLAZED
AS PER FBC 2406.4 (5) & R308.4 (2) ALL
GLAZING WITHIN 24' OF AND PARALLEL TO
A DOOR SHALL BE TEMPERED.
2. FIRE BLOCKING. PROVIDE FIRE BLOCKING
AT ALL CONCEALED SPACES.
3. SHUTTERS. STORM SHUTTERS WITH AN
ACCEPTED PRODUCT APPROVAL SHALL BE
PROVIDED AT ALL OPENINGS EXCEPT
THOSE PROTECTED BY APPROVED IMPACT
RESISTANT DOORS AND WINDOWS.
4. ROUGH OPENINGS. VERIFY ALL ROUGH
OPENING AND MASONRY OPENING SIZES
WITH MANUFACTURER'S PRODUCT
SPECIFICATIONS.
5. EGRESS WINDOWS. EGRESS WINDOWS
SHALL BE OPERABLE FROM THE INSIDE
WITHOUT THE USE OF TOOLS. EGRESS
WINDOWS SHALL HAVE A MINIMUM NET
OPENING OF 24" HIGH, 20" WIDE, AND
MIN. NET AREA OF 5.7 S.F. FOR 2ND FLOOR
WINDOWS AND 5.0 S.F. FOR 1ST FLOOR
WINDOWS. THE SILL HEIGHT SHALL NOT BE
MORE THAN 44" ABOVE THE FLOOR, LATCH
AT 54" A.F.F. MAX.. OPERABLE WINDOWS
WITH A SILL PORTION OF THE OPENING
LOCATED LESS THAN 24" A.F.F. AND MORE
THAN 72" ABOVE FINISHED GRADE SHALL
INCLUDE A WINDOW OPENING CONTROL
DEVICE THAT COMPLIES WITH SECTIONS
R312.2.1 AND R312.2.2 OF THE F.R.C.
6. BATHTUB AND SHOWER SPACES. BATHTUB
& SHOWER FLOORS & WALLS ABOVE BATH
TUBS WITH INSTALLED SHOWER HEADS & IN
SHOWER COMPARTMENTS SHALL BE
FINISHED WITH AN IMPERVIOUS,
NON -CORROSIVE, NON -ABSORBENT &
WATERPROOF MATERIAL. MOISTURE
RESISTANT BACKING BOARD REQUIRED
UNDER IMPERVIOUS WALL AREAS IN BATH
TUB & SHOWER SPACES. SUCH WALL
SURFACES SHALL EXTEND NOT LESS THAN
6-0" ABOVE THE ROOM FLOOR LEVEL.
7. BACKING FOR CABINETS. PROVIDE 2X4
MINIMUM HORIZONTAL BACKING IN
KITCHEN W/ TOP @ 35" A.F.F. & TOP @ 8'-0"
A.F.F. & IN BATHROOM VANITY AREAS W/
TOP @ 30" A.F.F. OR AS REQUIRED FOR
CABINET ATTACHMENT.
8. WOOD FRAME WALLS. WOOD FRAME
WALLS AND HEADERS ARE DESIGNED
USING RATIONAL ANALYSIS.
FRAMING PLAN NOTES
1. THE ROOF FRAMING PLAN SHOWS
LOCATION & DIRECTION OF ALL ROOF
MEMBERS (TRUSSES AND GIRDERS). FOR
INDIVIDUAL TRUSSES, SEE LAYOUT &
ENGINEERING SHEETS BY TRUSS
MANUFACTURER.
2. ALL CONCRETE BEAMS TO BE A MINIMUM
OF 8" X 12" WITH (2) #5 BARS TOP & (2) #5
BARS BOTTOM UNLESS NOTED OTHERWISE
ON PLANS.
3. AT ALL POURED CONCRETE BEAM AND
BOND BEAM INTERSECTIONS, EXTEND
BOND BEAM STEEL 30" INTO POURED
BEAMS.
4. ANY OF THE SPECIFICALLY NOTED BEAMS
MAY BE BUILT UP TO 1" SMALLER OR 2"
LARGER WITHOUT ANY CHANGE OF
REQUIRED STEEL.
5. STIRRUPS NOT REQUIRED UNLESS NOTED
OTHERWISE.
6. ALL HEADERS & WOOD BEAMS TO BE (2)
2"X12" HEM -FIR #2 UNLESS NOTED
OTHERWISE ON PLAN.
7. #2 S.Y.P. MAY BE SUBSTITUTED ANYWHERE
HEM -FIR IS SPECIFIED.
8. PROVIDE FILLED CELLS @ MINIMUM 6"
ABOVE & 6" BELOW ALL EXPANSION BOLT
LOCATIONS IN C.B.S. WALLS (TYPICAL).
9. SPACE FLOOR TRUSSES ACCORDINGLY TO
AVOID CONFLICT W/ PLUMBING FIXTURE
DRAINS ABOVE. COORDINATE W/
ARCHITECTURAL PLANS.
10.ANY WOOD IN CONTACT WITH CONCRETE
SHALL BE PRESSURE TREATED.
0
REVIEWED FOR,
CODE COMPLIANCE
ST. LUCIE COUNTY BOCC
3,1y`�z
2Zv 1 - o .�-66
ENGINEERING \�
;/�Yvy
WHOLE HOUSE ENGINEERING
4451 ST. LUCIE BLVD, SUITE 201
FORT PIERCE, FL 34946
CONTACT: 772.409.1003
ENGINEERING(cDWHENGINEERING.NET
I
DRAWING NOTICE:
THESE DRAWINGS AND DOCUMENTS
ARE CONFIDENTIAL AND ARE THE
SOLE PROPERTY OF WHOLE HOUSE
EbIGINEERING, LLC. AND MAY NOT BE
REPRODUCED, DISSEMINATED OR
REDISTRIBUTED WITHOUT THE
EXPRESS rVRITTEN CONSENT OF
,JHOLE HOUSE ENGINEERING, LLI-
ARNING: DO NOT SCALE DRAT/If-1GS
PLEASE CONTACT DESIGNER yvTTk
ANY UIUESTIONS REGARDII'IL
DIMENSIONS, ARCHITECTUP.IIL
SYMBOLS CONTAINED WITHIN THESE
DOCUMENTS ARE FOR GRAPHIC-
PURPOSES ONLY. SIZE AMID
LOCATION MAY VARY IN ORDER -�
MEET THE MANUFACTURER'=
S P E C I F I C A T I O N S
Digitally signed by Ryan M Bays �
DN.
E=Ryan Bays@WHEngineering net
ri O`N=Ryan M-Bays. O=Whole House
8�aS:5 I_C L=Fort Pierce,
6iIoeridanG US
Reason I am approving this document
Date: 2021.08.06 10:21:36-04'00'
®r
°`;
1f f N,s:
!
T / Nc �,
3 1 OF''rr
<�
..
0Np.1_
REVISION DATE BY REV
INITIAL SET 07/20/2021 ! JM A
I
I
PROJECT NUMBER, NAME & ADDRESS:
W H E 10294
191 TU°MBLIN KLING RD
FORT PIERCE, FL 34982
DRAWN BY: JM
SHEET TITLE:
GENERAL NOTES
a
SHEET NO.:
GN
0
0
e
c
c
a
1�X T T T 1 T T T T 0 T 0/,_ _1.
SCALE 1 /4" = 1'-0"
HDO'N I10 EE REPLACED
NDOWITO DE REPLACED
ID.bV IO BE REPLACED
cl
FILE Y
REVIEWED FOR
CODE COMPLIANCE
ST. LUCIE COUNTY BOCC
G 3`
PREPARED FOR:
�THOMr�S DREIER
I III
I
ENGINEERING
i
WHOLE HOUSE ENGINEERING
4451 ST. LUCIE BLVD, SUITE 201
FORT PIERCE, FL 34946
CONTACT: 772,409.1003
ENGINEERING@WHENGINEERING.NET
DRAWING NOTICE1
THESE DRA\/INGS AND DOCUMENTS
ARE CONFIDENTIAL AND ARE THE
S❑LE PROPERTY [IFWH❑LE HOUSE
ENGINEERING, LLCAND MAY HOT BE
REPRODUCED, DISSEMINATED OR
REDISTRIBUTED WITHOUT THE
EXPRESS WRITTEN CONSENT OF
\JH❑LE HOUSE ENGINEERING, LL'-
'ARNING: D❑ NOT SCALE DRAWINGS.
PLEASE CONTACT DESIGNER b/IT-;
ANY QUESTIONS REGARDIIIG
DIMENSI❑NS. ADCHITECTUP,,L
SYMBOLS CONTAINED WITHIN THESE
DOCUMENTS ARE FOR GRAPHIS
PURPOSES ONLY. SIZE AUZ
LOCATION MAY VARY IN ORDER TO
MEET THE MANUFACTURER'=
S P I:C I F I C A T I❑ N S
I
;l ltitlt1117fi!llt Frrr
��,lUENS''
Nu. I4
STAf
v
REVISION DATE BY REV
INITIAL SET 07/20/2021 JM A
_ .........
t
i
I
PROJECT NUMBER, NAME & ADDRESS:
W H E 10294
191 TUMBLIN KLING RD
FORT PIERCE, FL 34982
DRAWN BY: JM
%`ZZ
SKEET TITLE:
—0 7-06 FLOOR PLAN
Sl-;EET NO.:
A 1.0
PREPARED FORA
TH❑M❑iS DR❑I❑R
a
0
0
10'-0" A.F.F.
8'-0" A.F.F.
0'-0"F.F.
10 —0 A.F.F.
8 —0 A.F.F.
0'— 0 F. F.
TT T T H T T TT, TLT' �`, (_) ��I
SCALE : 1 1/4" = 1'-0"
TTOT(>TTT TT,TT TTT`, ,=,T
SCALE
c
IL OPY
+ U
REVIEWED FOR
CODE COMPLIANCE
ST. LUCIE COUNTY B®CC
y 3`91zz
, vv ! `0 2- (, 6
WHOLE HOUSE ENGINEERING
4451 ST. LUCIE BLVD, SUITE 201
FORT PIERCE, FL 34946
CONTACT: 772.409.1003
ENGINEERING@WHENGINEERING.NET
DRAWING NOTICE;
THESE DRAWINGS AND DOCUMENTS
ARE CONFIDENTIAL AND ARE THE
SOLE PROPERTY OF WHOLE HOUSE
ElJGINEERING, LLCAND MAY NOT BE
REPRODUCED, DISSEMINATED OR
'2EDISTRIBUTED WITHOUT THE
EiPRESS \✓RITTEN CONSENT OF
HOLE HOUSE ENGINEERING, LLC,'
S/ARNING: DO NOT SCALE DRAWII.IGS
PLEASE CONTACT DESIGNER WITH'
ANY QUESTIONS REGARDIIi
DIMENSIONS. ARCHITECTUP L'
SYMBOLS CONTAINED WITHIN THESE
DOCUMENTS ARE FOR GRAPHIC'i
PURPOSES ONLY SIZE AIID
LOCATION PAY VARY IN ORDER TO',
HEET THE MANUFACTURER
P F L I F r c A T r n H
\\ViNii ❑illtltlrtJ
No. J
-IV
PROJECT NUMBER, NAME & ADDRESS:
W H E 10294
191 TUMBLIN KLING RD
FORT PIERCE, FL 34982
DRAWN BY: JM
SHEET TITLE:
ELEVATION
e
SHEET NO.:
A2.0
NOTE:
WINDOW FRAME SHOULD BE COMPLETELY
SEATED ON THE BUCK. IN NO INSTANCE
SHALL THE FRAME OVERHANG THE BUCK.
STUCCO CEMENT FINISH FILLED CELL AT JAMB BLOCK (TYP.)
CMU WATER RESISTANT COATING 1 1 X3 P.T. WOOD FURRING ALL (3)
(SEE WATERPROOFING NOTE #1) SIDES CONTINUOUS.
�i
CORROSION RESISTANT FLASHING _ _ SEE WATERPROOFING NOTE #5
PER WATERPROOFING NOTE #2
ANCHOR 1X3 P.T. (MIN.) BUCK WITH SEALANT PER WATERPROOFING
D NOTE #2 AND ANCHORED TO MASONRY W/ 1 — 1/2" CASE HARDENED
APPLY PERIMETER SEALANT CAULK _� COIL NAILS @ 8" O.C. MAX.(4" MAX FROM ENDS) (STAGGERED)
BETWEEN BUCK & WINDOW FRAME
Lo
(SEE WATERPROOFING NOTE #4) ANCHOR WINDOW FRAME TO MASONRY
IN STRICT ACCORDANCE WITH
MANUFACTURER'S PRODUCT APPROVAL
INSTALLATION REQUIREMENTS.
CI
PROPO'.-)ED EPAOR DEAN
SCALE : 1/4" 1'0"
TYP. WINDOW HEADER AND JAMS BUCK DETAIL
STUCCO CEMENT FINISH
CMU WATER RESISTANT COATING (S
WATERPROOFING NOTE #1)
1 X6 P.T. WOOD BUCK WITH
SEALANT PER WATERPROOFING NOTE #2 AND
ANCHORED TO MASONRY W/
1 - 1/2" CASE HARDENED COIL NAILS @
8" O.C. MAX. (4" MAX FROM ENDS) (STAGGEREI
APPLY PERIMETER SEALANT CAULK
BETWEEN BUCK & WINDOW FRAME (SEE
WATERPROOFING NOTE #4)
1/2" = V-0"
FILLED CELL AT JAMB BLOCK (TYP.)
1X3 F.T. WOOD FURRING ALL
(3) SIDES CONTINUOUS.
WOOD TRIM
SEE WATERPROOFING NOTE #5
ANCHOR DOOR JAMB HEADER THROUGH FRAME AND
BUCK TO MASONRY IN STRICT ACCORDANCE WITH
MANUFACTURER'S PRODUCT APPROVAL INSTALLATION
REQUIREMENTS (MIN. 1.25" EMBEDMENT)
8 EXTERIOR DOOR BUCK DETAIL
8
A3.0
WATERPROOFING NOTES:
1/2" = 1'-0"
1. PRIOR TO BUCK INSTALLATION TREAT THE MASONRY OPENING WITH A CMU WATER RESISTANT
COATING TO SEAL THE WINDOW / DOOR CAVITY TO PREVENT IT FROM ABSORBING WATER. THE
CMU WATER RESISTANT COATING SHALL BE APPLIED IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS. THE APPLICATION OF THE CMU WATER RESISTANT
COATING SHALL INCLUDE THE ENTIRE SURROUND OF THE OPENING (SILLS, JAMBS, HEAD) AND
RETURN WALLS OF THE OPENING 24" MINIMUM IN EACH DIRECTION. ALL CMU WATER RESISTANT
COATINGS SHALL BE INSTALLED PRIOR TO BUCK INSTALLATIONS.
2. INSTALL BUCKS SO THAT THERE ARE NO EDGE GAPS EXCEEDING 1/8" BETWEEN BUCK AND
MASONRY.
3. PRIOR TO BUCK INSTALLATION APPLY 3/8" NOMINAL DIAMETER BEAD OF SEALANT BETWEEN THE
BUCK AND THE MASONRY TO PREVENT THE PASSAGE OF LIQUID BEHIND THE BUCK. COMPLETELY
SEAL THE ENTIRE END OF THE WOOD BUCKS WITH SEALANT TO RESTRICT THE PASSAGE OF LIQUID
THROUGH THE CUT ENDS AND THE ENTIRE EXTERIOR FACE AND RETURN SURFACE OF THE BUCK
SHALL BE COATED WITH A LIQUID APPLIED WATER RESISTIVE COATING / SEALANT.
4. PROVIDE CONTINUOUS 3/8" BEAD OF SEALANT ON WINDOW / DOOR FRAMES AT ALL PERIMETER
ON FRONT AND BACK SURFACE PRIOR TO WINDOW / DOOR INSTALLATION.
5. AFTER WINDOW / DOOR INSTALLATION PROVIDE FOAM SEALANT BETWEEN THE BUCK (OR
PRECAST SILL) AND THE WINDOW / DOOR TO ENSURE A WATER RESISTANT INTERIOR AIR SEAL
AROUND THE ENTIRE PERIMETER.
REVIEWED FOR
CODE COMPLIANCE
ST. LUCIE COUNTY BOCC
PREPARED FOR
THDIMAS DREIER
i
i
i
I
� ENGINEERING
,xa!Y.
WHOLE HOUSE ENGINEERING
4451 ST. LUCIE BLVD, SUITE 201
FORT PIERCE, FL 34946
CONTACT: 772.409.1003
ENGINEERING@WHENGINEERING.NET
DRAWING NOTICE:
THESE DRAWINGS AND DOCUMENTS
ARE CONFIDENTIAL AND ARE THE
SOLE PROPERTY ❑F WHOLE HOUSE
[FIGINEEPNG, LLCAND MAY NOT BE
REPRODUCED, DISSEMINATED OR
REDISTRIBUTED WITHOUT THE
EXPRESS \✓BITTEN CONSENT OF
,/HEILE HOUSE ENGINEERING, LLC
✓ARNING: DO NOT SCALE DRA�VI TNGS
PLEASE CONTACT DESIGNER WITH
ANY QUESTIONS REGARDIhdG
DIMENSIONS. ARCHITECTUP-L
SYMBOLS CONTAINED WITHIN THESE
DOCUMENTS ARE FOR GP.APHIC
PURPOSES ❑NLYSIZE Af1S
LOCATION MAY VARY IN ORDER TO
11EET THE MANUFACTURER'S
S P E C I F I C A T I O N S
tl;t............ ��/J f
)�,',
r1,1CFNs'r�»
t
r No. 1R
_t TAT _ OF
U R tU
iiT
''tt„��,�„�n�t,t,•
REVISION DATE BY REV
INITIAL SET
07/20/2021
JM A
I
I
-
PROJECT NUMBER, NAME & ADDRESS:
WHE10294
191 TUMBLIN KLING RD
FORT PIERCE, FL 34982
DRAWN BY:
JM
SHEET TITLE:
PROPOSED PLAN
SHEET NO.:
A3.0
i
FILLED CELLS WITH (1) #5 MAX. AT 4'
DOS,'EL INTO EXISTING CONCRETE L
V.LF. MIN. 12" EMBED
I I
II
I
I I
I I
II
NEW STARTER CELL. GROUT (I
NOT SOLID) OR DRILL AND EPDX'
#5 REBAR INTO EXISTING CMI
WALL, MIN. 12 EMBEDMENT (TYP
@ 24" O.C. SEE DETAILS D/S-1.
0
e
STRUCTURAL PLAN
SCALE : 1 /4" _ 1'-0'7
`\,V� SCALE : 1/4" = 1'-0"
11
(1) #5 BAR VERT IN CONC. FILLED CELL. DOWEL,
AND EPDXY IN TO EXISTING BONY BEAM AND\
EXIST. FOUNDATION WI/CELL W 6" MIN EMBED. A
,
Nf W STARTER CELL. GP.OU
IF
OCT SOLID)
OR
DRILL AND
EPDXY
.`b DEBAR
INTO
EXISTING
MU
WALL, MIN.
12"
EMBEDME
(TYP)
J
@ 24" O.C.
SEE
DETAILS
/S-1.0
POUR SOLID FOR
NEW WINDOW SILL.
j
EXISTING LINTEL OR
BOND BEAM V.I.F.
ADD NEW FILLED CELL ON EITHER SIDE OF
NEW OPENING. DOWEL INTO FOUNDATION
AND BOND BEAM
z(1) #5 BAR VERT IN CONC. FILLED CELL
DO WEL AND EPDXY W 8" tIIN EMBED
INTO EXIST. FOUNDATION AND BOND
i BEAt1
/GROUT (IF NOT SOLID) OR DRILL AND EPDXY
5 REBAR INTO E JSTING =fAU WALL. MIN. 6"
EMBEDMENT (TYP) @ 24" O.C. PROVIDE
/ MORTAR JOINT BEI,JEEN HEN AND EXISTING
BLOCK (TYP.).
NOTE: EPDXY SHALL BE HILTI
HIT-HY200 OREQUAL.
e
p
i
SNOTE: CONTRACT OR TO FIELD VERIFY ROUGH OPENING
SIZES.
OPENN I[FJEIEE DC 1E
SCALE : 1" 1'0"
0
CE;,TR (S,E KEY
FEE DUPLEX OUTLET
SWITCHED DUPLEX OUTLET
cFl F�) DUPLEX OUTLET Ground Fault Circuit Interrupter )
ARDUPLEX OUTLET ( Arc Fault Circuit Interrupter )
P.B.
-m PUSH BUTTON S`I'JITCH
_& SWITCH
-AS 3 ;NAY SWITCH
4 WAY SWITCH
{� LIGHT FIXTURE
D RECESSED LIGHT FIXTURE
VP
A RECESSED LIGHT EIXTURE (VAPOR PROOF)
CEILING FAN
1 TELEPHONE
■ TELEVISION
Wj EXHAUST FAN
220 VOLT OUTLET
FLOOD LIGHT ( MOTION DETECTOR TYPE 1
CSD SMOKE DETECTOR
CCM,A CARBON MONOXIDE ALARM
LlI ITEL.
BT P ,'EFT III (2,l F T _
1nYO-)/ C4 BLC - _
11,11,,ATICEd PL=1 COP_ L__ Tl�'
'UT ;II 1 r:- SCUD ! P DFILII OF FF'`:
PEB-F. I ITO E ISTII IG SI'I,'
IEDIIEt1T (TrP 2 Cl P-_' `SE
,TAR JOIIIT BET FT: I IIF -1 E, ISTIIIO
CK TYP ;.
� 1 DI T C ��J C E E,
-- - _ -
SCALE 1 /2" = 1'J"
I. ALL WORK SHALL BE DONE IN ACC❑RDAI.C:E '„ITN BOTH LDC4L rPID
NATIONAL ELECTRICAL CODES
2ELECTRICAL CONTRACTOR, SHALL VERIFi ELECTRICAL PLAIN, RISER
DIAGRAM, AND LEADS, AND IIHITIFY THE GF IIERAL CU' ITRT,CTOR ❑- TII
ERRORS OR DESCREPANCIES PRIOR TO INSTALL�TI❑N,
3ELECTRICAL CON RACTOR SHALL CAEPDIH,v,TE :,CTH 77HER TF_HCES TC�
MAKE CERTAIN THAT ALL AIR-CONDITI❑[TOIG TO,'ER _IID C❑HTROL. IRDIPI
AND CONDUITS ARE IN THE BID,
4ELECTRICAL CONTRACTOR 1S TO CO❑PDTIdATE ALL SER`:'ICE 'ECU-REEII'SI
WITH THE POWER COMPANY BEFORE BIDDIiHH TO RE CERT-,II ! TH TT _LL�
WORK NECESSARY TO MEET P❑ ,'ER C❑HPAHr SPEC1FTSaTIDlB iC II -I V
BID.
5, THE ELECTRICAL CONTRACTOR IS TO SIZE HOST BRANCH C-RCUTT":
MAXIMUPI VOLTAGE DRIP OF 3% IS PERMITTED
6, SMOKE DETECTORS SHALL BE DIRECT .-FRED 120V U.L. 217 -PLED, ff
TYPE WITH AUDIBLE ALARM INSTALLED PI �Si GR 4 lICE III H
MANUFACTURER'S RECOMMENDATIONS AND LISTING C IPDC1,1 i'C IT Ci IE
DETECT❑R(S) TO CDIH LY W/ UL #2034-96,
7AI_L APPLIANCE / ELECTRICAL EQll \MILL BE PROTECTED IT 111,E-�
PLATE RATING AS PER NEC 1103 & 11021
8, ALL ELECTRICAL CIRCUITS THAT SUPPLY THE FAHIL i PD❑;I DIFIJiG R❑❑I'.
LIVING ROOM, STUDY, HALLWAYS, BEDRIIOMS, CL❑SFTS ND �UrZR CH4L-
BE AP.C-FAULT PROTECTED,
9, ALL 125 VOLT 15 & 20 All RECEPTACLES I (STALLED Ili D ELLTIIG UIIITSI
SHALT- BE TAMPER RESISTANT AS PER NEC 10611, 1
10NTERSYSTEM SANDING REDLIIRED AND SHALL C11MPL'1 IH TTCI1
250.94, NEC,
11 GARAGE DOOR OPENER TO BE GFI PROTECTED,
12ALL EQUIPMENT INSTALLED OUTSIDE OR EXPMSED TO B-
HEMA TYPE 3R
13ALL CONDUCTORS ARE TO BE COPPER, TYPE THHII, JF1l_:SS IOTED
OTHERWISE.
14, SWITCHES SHALL BE AT STANDARD GRADE ❑F SILENT-'rFE,
15, RECEPTACLES SHALL BE 15A AND 120V OF THE GR❑L11,B T1PE,
IS LIGHTING FIXTURES SHALL BE SELECTED BF THE ❑ EE `H% ❑F TIFF'
LAMPS SHALL BE HIGH EFFICACY TYPE,
17, ALL DEVICES SHALL BE SM❑OTH Tl'PE, IVCiR'i COLI-C JIILESS OTHER i F
SPECIFIED
18, ALL 120V I -PHASE 15A AND 20A BATHRF011, 4,D) E,, FRICIR RECE='T ; I FSI
SHALL HAVE GROUND FAULT J,NTERRUPTER CGF77 PR❑TECTIOFi ITH'
EXTERI❑R RECEPTACLES BE THE „,'ATERF'RO❑F T•FE ELEC ._TC-I,
CONTRACTOR MAY INSTALL INDIVIDUAL (GFI) IN LIEU [IF IFIFD BRP,KER'
WITH SEPARATE CIRCUIT
I9 ARC -FAULT CIRCUIT _T INJERRUPTER PROTECTION: ALL 120V, SINGLE PHASE, 15 AND 20 AMP',
BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED OR DEVICES IN DWELLING UNIT
KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
SUN ROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS, OR SIMILAR
ROOMS OR AREAS SHALL BE PROTECTED BY ANY OF THE MEANS DESCRIBED IN THE NEC
210.12 (A)(1) THROUGH (6)
20 G.C. TO VERIFY ALL INSTALLATION HEIGHTS ADOVE FII I01i FL❑OR.
21. BRANCH CIRCUITS SHALL BE IN THII I , ALL COP-D`JIT OF AFP�D ✓E_
P,OMEX,
2AALL FAN VENTING AND RUFF PENETRATI❑HS' SHALL BE S NF_CHhI!IC4'
C❑NTPACT❑R,
23 EXHAUST FANS IN BATHR❑❑MS CIF USED) SHALT_ BE P ; FD �,T 1 CFI1 IF ❑=
VENTILATED FLD❑R AREA.
S 4O�" ded
PREPARED FOR
THEMES DREIER
WHOLE HOUSE ENGINEERING
4451 ST. LUCIE BLVD, SUITE 201
FORT PIERCE, FL 34946
CONTACT: 772.409.1003
ENGINEERING@WHENGINEERING.NET
DRAWING N❑TICE:
THESE DRAWINGS AND DOCUMENTS
ARE CONFIDENTIAL AND ARE THE
SALE PROPERTY ❑F WH❑LE H❑USE
ENGINEERING, LLC. AND MAY N❑T BE
REPRODUCED, DISSEMINATED OR
REDISTRIBUTED WITHOUT THE
EXPRESS WRITTEN CONSENT OF
'HOLE HOUSE ENGINEERING, LLC
WARNING: D❑ NOT SCALE DOH' iIGS
PLEASE CONTACT DESIGNER \ITT'
ANY QUEATI❑NS AEGARDTII�
DIMENSIONS ARCHITECTURAL,
SYMB❑LS CONTAINED WITHIN THESE
DOCUMENTS ARE FOR GRAPHIC,
PURP❑SES ❑NLY, SIZE AllD �
LOCATION MAY VARY IN ORDER T'
HEET THE MANUFACTURER'S
S P E C I F I C A T I❑ N S
ta144�4{{Dtil fi}l Tl/,i
A.� T�
.00
No. I!` ,
Levi
of
)NAV.
PROJECT NUMBER, NAME & ADDRESS:
WHE10294
191 TUMBLIN KLING RD
FORT PIERCE, FL 34932
SHEET TITLE:
DETAILS
SHEET NO.:
A4.0