Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
SHOP DRAWING REVIEW COMMENTS
O'BRIEN 3501 Quadrangle Blvd., Suite 100 Orlando, Florida 32817 expect a difference I 407.380.0400 1 www.salasobrien.com February 02, 2022 SHOP DRAWING REVIEW COMMENTS Reference: Trane WPB SLC Rock Road Jail Chiller #3 Replacement Salas O'Brien Florida #2104404 Subject: SUBMITTAL ID: 01 Trane Equipment Submittal Reviewed By: Joseph Detig, P.E. Mahaley Vann Engineer's review is for general conformance with the design concept and contract documents. Markings or comments shall not be construed as relieving the Contractor from compliance with the project plans and specifications, nor departures therefrom. The Contractor remains responsible for details and accuracy, compliance with the Contract Documents and intent, for confirming and correcting all quantities and dimensions, for selecting appropriate fabrication processes, for techniques of assembly, and for performance of work in a safe manner. OVERALL DISPOSITION: NO EXCEPTIONS TAKEN ST. LUCIE COUNTY BUILDING DIVISION REVIEWED FOR OMPLIANCE REVIEWED BY DATE _ PLANS AND PERMIT MUSTI3E KEPT ON JOB OR NO INSPECTION WILL BE MADE. END OF DOCUMENT TRANS Prepared For: St Lucie County Submittal Date: December 29, 2021 Job Name: SLC - Rock Road Jail Chiller Repl 2021 Trane U.S. Inc. is pleased to provide the following submittal for your review and approval. Product Summary Qty Product 1 Centrifugal Water Chiller (CH-3) Chris Cowling Trane U.S. Inc. 6965 Vista Parkway North, Suite 11 West Palm Beach, FL 33411 Office Phone: (561) 683-1521 Please Note: The attached information describes the equipment we propose to furnish for this project and is submitted for your approval. Product performance and submittal data is valid for a period of 6 months from the date of submittal generation. If six months or more has elapsed between submittal generation and equipment release, the product performance and submittal data will need to be verified. It is the customer's responsibility to obtain such verification. • Contractors & Engineer to review submittal for accuracy before order is placed. ELECTRONIC SHOP DRAWING REVIEW By: Salas O'Brien Florida, Inc. NO EXCEPTIONS TAKEN Engineers —lea, is in, general confo,mance with the design concept and contras documents. Markings or comments shall not be construed as relieving the Contractor bom compliance with the project plans and specifications, n r departures thetefmm. The Cont —, r ruins ,esponsible let detalis and —racy, compliance whh the Contract Documents and Intent, for confirming and correcting all Quantities and dlmenslors for selecting appropriate fabrication processes, for techniques ofassembly, and for p,rf nuance ofwork in a safe manner. By: Kyle J. Cartier, P.E. 02102/2022 © 2021 Trane Technologies All rights reserved Submittal - CVHE Chiller - SLC Rock Road Jail Chiller Rep[ - 11-23-21.docx Table of Contents ProductSummary ...........................................................................................................................................................1 Centrifugal Water Chiller (Item Al) ...............................................................................................................................3 TagData....................................................................................................................................................................... 3 ProductData.................................................................................................................................................................3 ProductReport..............................................................................................................................................................4 MechanicalSpecifications............................................................................................................................................6 DimensionalDrawings................................................................................................................................................13 Weight, Clearance & Rigging.....................................................................................................................................19 Accessory...................................................................................................................................................................21 FieldWiring.................................................................................................................................................................23 Field Installed Options - Part/Order Number Summary ............................................................................................25 CentrifugalWater Chiller............................................................................................................................................25 © 2021 Trane Technologies All rights reserved Submittal - CVHE Chiller - SLC Rock Road Jail Chiller Repl - 11-23-21.docx SLC - Rock Road Jail Chiller Repl 2021 Tag Data - Centrifugal Water Chiller (Qty: 1) November 23, 2021 Item Tag(s) Qt Description I Model Number Al CH-3 1 1 1 Centrifugal Chiller CTV CVHE045 Product Data - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 Standard ship cycle CVHE, CVHF & CVHG Centrifugal liquid chiller with 3 stage compressor Compressor size: 450 nominal tons Adaptiview controls Compressor motor voltage: 460 volt 3 phase Compressor motor power: 234 kW Motor frame size: 440E Compressor impeller cutback: 230 Orifice size: 400 nominal tons Evaporator: Evaporator shell size: 050 short Evaporator bundle size: 580 nominal tons Evaporator tubes: 0.75 inch (19.1 mm) dia. internally enhanced copper Evaporator tube wall:.025 inch (0.6 mm) thick Evaporator fluid type: Water Evaporator waterbox type: Non -marine Evaporator waterbox construction: Standard Evaporator water box passes: Two pass Evaporator waterbox pressure: 150 psig (1034 kPa) Evaporator waterbox connection: Victaulic Evap waterbox arrangement: in RH end - out RH end Thermal dispersion flow switch (IFM) - Field Installed (Fld) Condenser: Condenser shell size: 050 short Condenser bundle size: 500 nominal tons Condenser tube: 0.75 inch (19.1 mm) internally enhanced copper Condenser tube wall:.028 inch (0.7 mm) thick (thicker tube option) Condenser shell construction: Standard Condenser fluidtype: Water Condenser waterbox type: non -marine Condenser waterbox construction: Standard Condenser water box passes: Two pass Condenser waterbox pressure: 150 psig (1034 kPa) Condenser waterbox connection: Victaulic Condenser waterbox arrangement: in RH end - out RH end Thermal dispersion flow switch (IFM) - Field Installed (Fld) Misc/Electrical: Agency listing: U.L. listed unit (United States requirement) Factory performance test: Standard air run and vibration test Selection tolerance: AHRI Standard tolerance Brass logo with customer specified engraving No unit insulation package — insulation in the field by others AHRI Certified, Complies with ASHRAE 90.1 - 2016 Generic BAS / BACnet interface Trane-supplied R514 Refrigerant, Shipped loose for field installation at start-up Low Voltage Wye -Delta Starters Starter type: Unit Mounted Wye -Delta Starter maximum RLA: 346 Amps Starter power connection: Circuit Breaker High -Interrupt Starter power connection maximum RLA: 296 Amps Starter option: Surge protector/lightning arrestor Factory Start-up 10 year Parts, Labor & Refrigerant warranty Qty 1, Refrigerant Sensor for existing Sherlock Refrigerant Monitor (Fld) — See end of submittal for data sheet Equipment Submittal Page 3 of 25 SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Product Report - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 Overview,Unit =licationtypeStanlardcooling_ `or Tracer Controls BAChet r� Compressor�450 y--- -Impeller 230 ht Certified in accordance with the AHRI Water -Cooled Water - Chilling and Heat Pump Water -Heating Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 5511591 (SI). Certified units may be found in the AHRI Directory at www. a hn directory. org. Equipment Submittal Page 4 of 25 SLC - Rock Road Jail Chiller Rep[ 2021 November 23, 2021 Product Report - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 rarts wnoio unn -�utn mans-.vvnoie•umt wistaner r auor,_ sr ytar , si year iaoor warranty wnoie unit Parts less'motorand'eomNo gaits less motor & cmpr warranty! Labor afterAst year 2= h rrLLabor Whole unit w/starter Motor/comer parts Warrup 16.10 rm ~ _ Rem frigerant qualiry,warranty 1st r-� µ No motor & compressorwarranly 1st year efngerant.quality warranty I yaarL. re._rr.__�- _---a Refrigerant bevo ty a Arran ?nil 101h year refrigerant warranty (..=. _rCeingerani cnarg nuu_u Ib _ � ... q ..NPLV.lP1(L.MMV.KW82n Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit (EAc4) due to the R-514A refrigerant GWP being less than 2. Note: Trane recognizes and respects the U.S. Green Building Council® mandate that a default 2% Refrigerant Leakage Rate (Lr) be used by all manufacturers of centrifugal chillers when calculating the Enhanced Refrigerant Management Credit because there is no industry standard. Trane has exhaustively documented a leak rate of less than 0.5% for CenTraVacT chillers (models CVHE, CVHF, CVHG, CVHS, CVHM, CDHF, CDHG, CVHH and CDHH) and utilizes an average design refrigerant charge of less than 2 lb./ton. The U.S. Green Building Council's LEED© green building program is the preeminent program for the design, construction, maintenance and operations of high-performance green buildings. It provides Independent, third -party verification that a building project meets the highest green building and performance measures. Trane Select Assist 55235 Version Number: Data Generation Date: 10/4/2021 Equipment Submittal Page 5 of 25 SLC - Rock Road Jail Chiller Repi 2021 November 23, 2021 Mechanical Specifications - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 Compressor -Motor Direct drive multiple -stage compressor, multi -stage capacity control guide vanes. Shrouded aluminum alloy impellers dynamically balanced. Motor -compressor assembly balanced to .15 in./sec (.0038m/sec) maximum vibration measured on motor and bearing housings. Refrigerant cooled, hermetically sealed, two -pole, squirrel cage induction motor. Two pressure lubricated bearings support the rotating assembly. A direct drive submerged oil pump motor, 3/4 hp (.560 kW) 115V/50/60/1 provides filtered and temperature controlled oil to compressor bearings. Evaporator -Condenser Shells are carbon steel plate. Evaporator includes rupture disk per BSR/ASHRAE 15 Safety Code. Carbon steel tube sheets are drilled, reamed and grooved to accommodate tubes. Tubes are individually replaceable externally finned seamless copper. Tubes are mechanically expanded into tube sheets. Eliminators are installed over entire length of the evaporator tube bundle. A multiple orifice control system maintains proper refrigerant flow. Condenser baffle prevents direct impingement of compressor discharge gas upon the tubes. Refrigerant side of the assembled unit is tested at both pressure(30.00 psi leak test) and vacuum. Water side is hydrostatically tested at one and one-half times design working pressure, but not less than 225.00 psi. Trane reserves the right to implement chiller technology enhancements that will reduce the chiller's refrigerant charge, with no impact on chiller performance. Changes may be reflected in the chiller's nameplate refrigerant charge and the quantity of refrigerant charge shipped to the jobsite, depending upon the final date of equipment manufacture. Water Boxes Drains and vents - Water boxes typically have 3/4-inch NPTI vents and drain connections provided. Evaporators have 2 vents and 2 drains, condensers have 1 vent and 1 drain. If grooved connections are offered, the design is based on Style 77. Non -marine water boxes have water connections that extend out from the end. Economizer A flash economizer with no moving parts provides power saving capability. Purge System The EarthWise(TM) purge includes a 1/4 hp 115V/60/1, 100V/50/1 air cooled condensing unit,, purge tank, drier elements, and a 1/20 hp (.037 kW) 115V/60/1, 110V/50/1 pump -out compressor. The purge is designed with an activated carbon filtration system that includes an autoregeneration feature which results in automatic high -efficiency removal of noncondensibles from the chiller without manual carbon maintenance. The purge meets Green Seal GS- 31 with a leak rate less than 1.0% of the charge per year and also meets ASHRAE 147 with a leak rate of less than one unit mass of refrigerant per unit of air. AdaptiView Control Panel: The Tracer(tm) AdaptiView is a microprocessor -based chiller control system that provides complete stand alone system control and monitoring for the water cooled CenTraVac (TM). It is a factory mounted package including a full complement of controls to safely and efficiently operate the CenTraVac chiller, including oil management, purge operation, interface to the starter, and comprehensive motor protection including three phase solid state motor overload. Inlet and outlet water (fluid) temperature sensors are located in the evaporator and condenser waterbox connections as standard. The display is a touch sensitive 12 1/8" diagonal color liquid crystal display (LCD) that uses color graphics and animation to ensure ease of use. The touch sensitive interface allows the operator to view the chiller graphically and receive a status indication via subsystem animations. The operator can navigate easily between the primary chiller subsystems including: compressor, evaporator, condenser, and motor. For each subsystem, you can view status and detailed operating parameters. In addition, alarms, reports, trending, and settings can all be accessed quickly from the main screen. The display is mounted on a flexible "arm" that allows extensive height and viewing angle variations. The panel supports an extensive list of languages including the default English. The data can be set to be viewed in inch pounds IP or metric units SI. For remote starters - Class 1 control panel voltage (30-115 V) are clearly labeled in the control panel. Class 2 input voltage (30V max) is also labeled in the control panel. Equipment Submittal Page 6 of 25 SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Operating Data including: *operating hours *number of starts *chilled water setpoint *evaporator and condenser water flow status *evaporator entering and leaving water temperatures *evaporator saturated refrigerant temperatures *evaporator approach temperature *evaporator refrigerant pressure *condenser entering and leaving water temperatures *condenser saturated refrigerant temperatures *condenser approach temperature *condenser refrigerant pressure *oil differential pressure *oil tank temperature *purge mode *purge average daily pump -out time *% RLA per phase for motor *RLA per phase *volts per phase *power factor *kw *kwh *frequency The AdaptiView also contains the following dedicated reports: Evaporator, Condenser, Compressor, Motor, Purge, and ASHRAE. Each report is comprised of a detailed listing of operational data relative to that chiller subsystem. Control functions including: *leaving chilled water temperature *percent demand limit *chiller water reset (based on return water temperature *front panel control type *setpoint source *differential to start *differential to stop Status data including: *waiting to start *running *run limit *run inhibit (adaptive) *auto *free cooling (option) *preparing to shutdown *shutting down (post lube) *stopped Safeties including: Automatic safety shutdown for: *Low chilled water temperature, *low evaporator refrigerant temperature *high condenser refrigerant pressure *evaporator and condenser flow status *low evaporator/condenser differential refrigerant pressure *low oil pressure *oil pressure overdue *high or low oil temperature *high bearing oil temperature (requires enhanced protection option) *high motor current Equipment Submittal Page 7 of 25 SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 *high motor temperature *starter function faults *critical temperature and pressure sensor faults The devices are of a latching trip out type requiring manual reset. Non -latching safety trip outs for operating conditions external to the chiller automatically permits unit to resume normal operation when condition is corrected. Advanced motor protection monitors 3-phase current to provide latching trip out protection from adverse effects of phase loss, phase unbalance, phase reversal, loss of phase reversal protection, and electrical distribution faults (momentary power loss) by instantaneous trip out of motor. Surge protection - Detects surge and limits chiller loading through inlet vane modulation. Head relief through lowering cooling tower water temperature can be requested. If not corrected within 7 minutes, chiller is shut down. Enhanced Adaptive Control(TM) - Built in intelligence to keep the chiller on line (safely making maximum tons) while simultaneously preventing chiller damage/failure. During any chiller limiting mode of operation, the control panel enunciates the condition via a relay output. Trending: The controller provides 10 standard graphs for trending multiple parameters, The operator can add an additional 6 custom graphs if desired. On any one custom graph, the operator can choose to trend up to 10 unique parameters from a more comprehensive list. Two Y axes are available for any graph to facilitate readability. Diagnostics: AdaptiView includes comprehensive diagnostic monitoring. All active diagnostics are available, and up to 20 historic diagnostics are communicated to the operator via the 12 1/8" LCD display with graphic navigation system. Each diagnostic is time and date stamped. Service Tool: A PC -based service tool called Tracer TU, connected to the chiller via USB port, is available for additional cost and displays the last 100 diagnostics, indicating the time, date of occurrence, and system parameters at the time of the diagnostic. The service tool provides advanced troubleshooting and access to sophisticated configuration settings not needed during operation of the chiller. Security: The AdaptiView can be set to prevent unauthorized access to the chiller settings. The operator can choose to secure the operating settings with a password. Data and reports can still be accessed once the settings are locked out. The memory for the AdaptiView is non-volatile type, so if power is lost, operating settings are retained. A life time battery is standard, which is used only to support the clock function for the chiller. Chilled and Condenser water pump relays: Chilled water and condenser water pump relays are provided and it is recommended that they be used for pump control. BACnet(MSTP) Direct Points List: The following points are available directly from the chiller. Recognize that some of these points require chiller options or configurations. Inputs Including Chiller Auto/Stop Chiller Mode (e.g. cool) External Base Loading Enable/Disable (requires Extended Operation option) External Base Loading Setpoint (requires Extended Operation option) Chilled Water Setpoint Current Limit Setpoint Heating Setpoint (requires Extended Operation option) Wall Mounted Refrigerant Specific Monitor (requires Extended Operation option) Clear Diagnostics Outputs Including Evaporator Pump relay Equipment Submittal Page 8 of 25 SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Condenser Pump relay Chilled Water Flow Status Condenser Water Flow Status Evaporator Water Flow Rate (requires Flow Compensation option) Condenser Water Flow Rate (requires Flow Compensation option) Chiller capacity (requires Flow Compensation option) Leaving Chilled Water Temperature Entering Chilled Water Temperature Entering Condenser Water Temperature Leaving Condenser Water Temperature Second Condenser Entering Water Temperature (requires HR or Aux condenser bundle) Second Condenser Leaving Water Temperature (requires HR or Aux condenser bundle) Active Chilled/Hot Water Setpoint Active Current Limit Setpoint Active Base Loading Setpoint (requires Extended Operation option) Head Relief Request relay Compressor Running relay Chiller On/Off Limit Warning relay Maximum Capacity relay Alarms Description1 Manual Reset Alarm relay Auto Reset Alarm relay Purge Alarm relay Alarm Reset Condenser Refrigerant Pressure Condenser Refrigerant Temperature Evaporator Refrigerant Pressure Evaporator Refrigerant Temperature Compressor Discharge Refrigerant Temperature (requires Enhanced Protection option) Differential refrigerant pressure (not for head pressure control) Operating Status (Alarm, Run Enabled, Local Control, Limited) Chiller Modes (i.e. Off, Starting, Running, Shutting Down) Base Loading Active (requires Extended Operation option) Hot Gas Bypass Active (requires Hot Gas Bypass option) Operating Mode (e.g. Cool) Current Per Line Voltage Per Phase Unit Power Consumption (kW) Motor winding temperature Motor power factor (uncorrected) Oil Temperature Oil Pressure Differential High Side Oil Pressure Low Side Oil Pressure Compressor Starts Compressor Run Time Inlet guide vane position Inboard bearing oil temperature (requires Enhanced Protection option) Outboard bearing oil temperature (requires Enhanced Protection option) Purge Status2 Purge pumpout Average (24 hour) Purge pump -out Purge regeneration Purge carbon tank temperature Purge liquid temperature Purge suction temperature Purge time to next purge run Purge pump -out chiller on-7 days Purge pump -out chiller off-7 days Purge pump -out life Equipment Submittal Page 9 of 25 SLC - Rock Road Jail Chiller Rep[ 2021 November 23, 2021 Purge regeneration life Refrigerant Monitor AFD output frequency AFD transistor temperature Hardwire BAS Interface provides: Chilled Water Setpoint input - Provides for setpoint adjustment of control point from multiple sources Current Limit Setpoint input - provides for setpoint adjustment of control point from multiple sources Percent RLA Output - provides % RLA output Condenser Pressure Output - A hardwire output signal of condenser pressure, or differential pressure between the evaporator and condenser is provided. Operating Status: The following hardwire binary outputs are available: Compressor running relay Alarm relay - manual reset Alarm relay - auto reset Limit warning relay Purge alarm relay Head relief request relay Maximum capacity relay Evaporator Proof of Flow - Thermal Dispersion A factory provided, field installed thermal dispersion type proof of flow switch (IFM) is provided. The thermal dispersion controller is mounted in the chiller control panel, the piping probe and wiring is shipped lose for field installation in the ship with components box. Follow the installation instructions in the chiller installation manual. Reference specific IFM Installation manual (PART-SVN223*-EN) notes shipped with your rupture guard /contact local Trane sales office Condenser Proof of Flow - Thermal Dispersion A factory provided, field installed thermal dispersion type proof of flow switch (IFM) is provided. The thermal dispersion controller is mounted in the chiller control panel, the piping probe and wiring is shipped lose for field installation in the ship with components box. Follow the installation instructions in the chiller installation manual. Reference specific IFM Installation manual (PART-SVN223*-EN) notes shipped with your rupture guard /contact local Trane sales office Paint All CenTraVac(TM) painted surfaces are coated with a primer and an air-dry beige primer -finisher prior to shipment. Isolation All units ship with neoprene isolator pads as standard, except when spring isolators are chosen. Enough pads are provided to cover the area under the chiller supports. Shipment All units are of hermetic design, leak tested, charged to 5.00 psi and shipped as a single factory assembled package. Full oil charge shipped in oil sump. Refrigerant shipped to jobsite from refrigerant manufacturer. The entire chiller is shrink wrapped for protection. Unit Mounted Starter Wye Delta -Reduced Voltage, NEMA 1A (vented) enclosure with a gasket. Starter factory mounted and completely prewired to compressor motor and control panel. Factory run testing assures proper circuitry and operational reliability. The Wye Delta starter is a reduced voltage starter and therefore draws — 33% of locked rotor amps (LRA), and the motor acceleration time is 5-12 seconds typically. The starter is designed and tested in accordance with UL 1995 Features include: 115 volt control power transformer to power chiller unit controller, purge and oil system. Therefore, with line power, no other power is needed for auxiliary equipment on the chiller. Equipment Submittal Page 10 of 25 SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Environmental specification: Operation from sea level to 6000 ft (1829 m). Operating ambient temperature range 32.0 F to 104.0 F. Non -operating ambient temperature range -40.0 F to 158.0 F. Relative humidity, non -condensing 5% to 95% through the ambient temperature range. Voltage utilization ±10 % Top of starter includes access area for a wiring entrance area. Bottom entry for line power is not available. Terminal block connection is standard. Circuit breakers may be included as an option. See the following submittal pages for disconnect ratings and lug information on these optional disconnects if offered. Starter installer responsibilities The following are considered functions normally required of the equipment installer for unit mounted starters. Remove access area panel for line side wiring. The upper right quadrant of the starter provides recommended access to starter/disconnect lugs. The starter can accommodate top line power entry only. Provide and install field wiring to line side lugs of starter. Required Installer Responsibilities The following are considered functions normally required of the equipment installer./n Install unit on a foundation with flat support surfaces level within 1/16" and of sufficient length to support concentrated loading. (Spring isolators should be considered whenever chiller installation is planned for an upper story location.) Place isolation pads or optional spring type isolators provided by the chiller manufacturer under the unit. When spring isolators are chosen, no pads are provided. Install unit per applicable Trane Installation Manual. Complete all water and electrical connections. Where specified, provide and install valves in water piping upstream and downstream of the evaporator and condenser water boxes as means of isolating shells for maintenance and to balance and trim system. Furnish and install a flow switch or equivalent device in both the chilled water and condenser water piping properly interlocked to insure that unit can operate only when water flow is established. Furnish and install taps for thermometers and pressure gauges in water piping adjacent to inlet and outlet connections of both evaporator and condenser. Furnish and install drain valves to each water box. Install vent cocks on each water box. Furnish and install strainers upstream of chiller evaporator and condenser bundles to protect tubes from potential damage caused by debris in the circulating water. Note: Failure to install strainers in all water piping entering the chiller could result in tube plugging conditions that could damage unit components. If the circulating pumps are immediately upstream of the chiller bundles, then the strainer can be installed immediately ahead of the pumps. If the circulating pumps are downstream of the chiller bundles, then the strainers should be installed immediately ahead of the chiller bundles. Furnish sufficient refrigerant 25.0 lb per machine and dry nitrogen 50.0 lb per machine for pressure testing under manufacturer's supervision. Start-up unit under supervision of a qualified Trane field engineer. Where specified, insulate evaporator and any other portions of machine required to prevent sweating under normal operating conditions. Water connection piping must not transfer forces to the chiller. Because of cumulative tolerances in manufacture and field installation, prepiping of water connections closer than 36" is not recommended. Any problems associated with prepiping of water connections closer than 36" to the chiller are the responsibility of the installing contractor. Equipment Submittal Page 11 of 25 o SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Furnish and install vent lines for rupture disk and purge venting to atmosphere per ASHRAE 15 and unit installation manual. If RuptureGuard-Relief Valve option is ordered, remove factory rupture disk and install RuptureGuard-Relief Valve per the IOM manual. In some chiller configurations the RuptureGuard may not bolt directly to the chiller flange. Locally sourced and approved piping may be required between the chiller and the RuptureGuard. Field Disassembly With chillers that may require field disassembly (for example due to clearance concerns during unit installation) reference the Disassembly and Reassembly manual and your Trane Sales representative prior to the order being placed. Caution: if certain components are removed in the field, for example the economizer, the necessary components (gaskets, seals, etc.) are not provided as standard. Leak -Tight Warranty The CenTraVac chiller features a 5-year limited Leak -Tight Warranty which is valid for the lesser of 60 months from initial start-up or 66 months from date of shipment. The limited Leak -Tight Warranty covers models CVHE/F/L, CVHS, CVHM and CDHF chillers installed in the United States or Canada. The Company's obligations and liabilities under this warranty are limited to furnishing replacement refrigerant; no other parts or labor are covered under this limited warranty. No liability whatever shall attach to the Company until appropriate actions have been taken (acceptable to Company) to eliminate the source of the leak, and then said liability shall be limited to furnishing the replacement refrigerant. If the chiller is placed under a comprehensive Trane service and maintenance agreement (Trane Select Agreement or better) prior to the expiration of the standard Leak -Tight Warranty, the protection against refrigerant loss shall continue under the Trane Select Agreement for as long as an active Trane Select Agreement remains in effect without interruption. If a 10-Year Parts, Labor and Refrigerant Warranty was purchased for the chiller and the chiller is placed under a Trane Select Agreement (or better) prior to the expiration of the 10-Year Parts, Labor and Refrigerant Warranty, the protection against refrigerant loss shall continue under the Trane Select Agreement for as long as an active Trane Select Agreement remains in effect without interruption Equipment Submittal Page 12 of 25 d CD W 0 N) Vt LEFT SIDE VIEW CUSTOMER NOTES: GRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS. UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLARITY. UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE +1--1 J2". COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX. WATER BOX DRAIN AND VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES, TOP VIEW FRONT VIEW RIGHT SIDE VIEW SHELLTYPE CONNDIA CONNTYPE FLOWDIRECTION EVAPORATOR B" VICTAULIC IN REAR OUT FRONT COOLING COND 8.. VICTAULIC IN BOTTOM OUT TOP r 3 0 D3 o � N n O A N o �v a au 23 2� 0 cc (1) N � o C7 0 2 fD 'o N W ,..► O � N C Q NC_ G D) fD I n N Z O N B Q CD N W N O N 2 C CD CD C C 3 m N CD A O tV tr CVHE Compressor size: 450 Evap shell size: 060S Cond shell size. 050S Without additional condenser Ada toucn screen is neia instanea (See accessory drawing for details) CUSTOMER NOTES: GRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS. UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLARITY. UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE +/-1/2". COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX WATER BOX DRAIN AND VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES. 1 518" 135 7/8" TOP VIEW SHELLTYPE CONNDIA EVAPORATOR 8" COOLING COND 8" Mounted i-delta Starter CONNTYPE FLOWDIRECTION VICTAULIC IN REAR OUT FRONT VICTAULIC IN BOTTOM OUT TOP v n D o N n A ai o — tv �va m 0 �y 00 M x fD v_ N o � N C G CD n S N Z O CD B 07 CD N W N O N 3 v CVHE Compressor size: 450 Evap shell size, 050S Cond shell size. 050S Without additional condenser CUSTOMER NOTES: GRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS. UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLARITY. UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE ♦/-1/2". COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX. WATER BOX DRAIN AND VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES. FRONT VIEW SHELLTYPE CONN DIA EVAPORATOR 8" COOLING COND 8" CONNTYPE FLOWDIRECTION VICTAULIC IN REAR OUT FRONT VICTAULIC IN BOTTOM OUT TOP vCn 0 D� o A m 0 �va m 0 � � 3 �Q v U) • , f;D C W Z o � N C (O OC_ G 01 �D 0 3 fD -z Z O N 9 Or f�D N W N O N m CVHE Compressor size: 450 Evap shell size: 050S Cond shell size. 050S Without additional condenser LEFT SIDE VIEW CUSTOMER NOTES: GRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS. UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLARITY. UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE+/-1/2". COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX. WATER BOX DRAIN AND VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES. 14" SHELLTYPE CONNDIA CONNTYPE FLOWDIRECTION EVAPORATOR 8" VICTAULIC IN REAR OUT FRONT COOLING COND 8" VICTAULIC IN BOTTOM OUT TOP Z O CD Q N tJ W N O N �m d 01 CD N V O N CT CVHE Compressor size: 450 Evap shell size: 050S Cord shell size. 050S Without additional condenser 90 CUSTOMER NOTES: GRAPHICS ON SUBMITTALARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS. UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLARITY. UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE +/-1/2". COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX. WATER BOX DRAIN AND VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES. RIGHT SIDE VIEW SHELLTYPE CONNDIA CONNTYPE FLOWDIRECTION EVAPORATOR 0" VICTAULIC IN REAR OUT FRONT COOLING COND B" VICTAULIC IN BOTTOM OUT TOP v CO) r n D3 0 I T. 0 O 0 �va IN 0 � 3 s y � 2N W � o � N C 0C1 G O fD 0 fD Z O (D 3 Q f�D N W N O N 3 m LEFT SIDE VIEW SHIPPING WEIGHT 17,244.0lb OPERATING WEIGHT 19,217.0 lb COMPRESSOR SIZE 450 EVAPORATOR SIZE 050S EVAPORATOR WATERPASS 2 EVAPORATOR WAT ERBOX ARRANGEMENT RERE CONDENSER SIZE 050S CONDENSER WATERPASS 2 CONDENSER WAT ERBOX ARRANGEMENT RERE 'ALL PUBLISHED WEIGHTS ACCURATE TO+/-10 % SHIPPING WEIGHT INCLUDES REFRIGERANT. IF ORDERED WITHOUT, CONSULT PRODUCT SUPPORT FOR DRY SHIP WEIGHT. TOP VIEW Z O G O D Q N N w N O N SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Weight, Clearance & Rigging - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 WEIGHTS AND CENTER OF GRAVITY LEFT REAR LEFT FRONT RIGHT REAR RIGHT FRONT SPRING ISOLATOR SELECTION LOCATION ISOLATOR LOAD' VENDOR PM TRANE PIN ISOLATOR COLOR LEFT FRONT 4,563.0Ib LEFT REAR 3,570.0Ib RIGHT FRONT 6,116.0Ib RIGHT REAR 4,968.0Ib LEFT MIDDLE NIA RIGHTMIDDLE NIA COMPONENT WEIGHT' COMPRESSOR WEIGHT 5,418.0Ib MOTOR WEIGHT 1,832.0Ib STARTER WEIGHT 557.0Ib SUCTION ELBOW WEIGHT 280.0Ib ECONOMIZER WEIGHT 635.0Ib EVAPORATOR WEIGHT 4,025.0 Ib EVAPORATOR WATERBOXES WEIGHT 630.0Ib CONDENSER WEIGHT 2,454.0 Ib CONDENSER WATERBOXES WEIGHT 399.0Ib HEAT RECOVERY CONDENSER WEIGHT N/A _AT RECOVERY CONDENSER WATERBOXES WEIGHT NIA AUXILIARY CONDENSER WEIGHT N/A AUXILIARY CONDENSER WATERBOXES WEIGHT NIA MISCELLANEOUS WEIGHT 1,013.0Ib WEIGHTS SHIPPING OPERATING 17,244.0Ib 19,217.0Ib UNIT CENTER OF GRAVITY CG Z (DIMENSION FROM RIGHT TO LEFT) 56.000 in CG X (DIMENSION FROM FRONT TO REAR) 28.000 in CG Y (HEIGHT DIMENSION FROM FLOOR) 45.000 in RIGHT FRONT ISOLATOR MOUNTING HOLE BOTTOM OF THIS HOLE IS 0,0,0 POINT FOR CENTER OF GRAVITY DIMENSIONS Y Z X Q NAMEPLATE PRODUCT DESCRIPTION: MODL CVHE VOLT 460 PTON 300.00 tons NTON 450 EVTM TECU CDTM TECU CPKW 234 CPIM 230 CDBS 500 EVSZ 050S EVBS 580 ORSZ 400 CDSZ 050S 'ALL PUBLISHED WEIGHTS ACCURATE TO+/-10 % Equipment Submittal Page 19 of 25 SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Weight, Clearance & Rigging - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 1. HEAVY OBJECTSI DO NOT USE CABLES (CHAINS OR SLINGS) EXCEPT AS SHOWN. EACH OF THE CABLES (CHAINS OR SLINGS) USED TO LIFTTHE UNIT MUST BE CAPABLE OF SUPPORTING THE ENTIRE WEIGHT OF THE UNIT. LIFTING CABLES (CHAINS OR SLINGS) MAY NOT BE OF THE SAME LENGTH. ADJUST AS NECESSARY FOR EVEN UNIT LIFT. OTHER LIFTING ARRANGEMENTS MAY CAUSE EQUIPMENT OR PROPERTY -ONLY DAMAGE. FAILURE TO PROPERLY LIFT UNIT MAY RESULT IN DEATH OR SERIOUS INJURY. SEE DETAILS BELOW. 2. IMPROPER UNIT LIFT! TEST LIFT UNITAPPROXINIATELY 24 INCHES TO VERIFY PROPER CENTER OF GRAVITY LIFT POINT. TO AVOID DROPPING OF UNIT, REPOSITION LIFTING POINT IF UNIT IS NOT LEVEL. FAILURE TO PROPERLY LIFT UNIT COULD RESULT IN DEATH OR SERIOUS INJURY OR POSSIBLE EQUIPMENT OR PROPERTY -ONLY DAMAGE. 3. ATTACH SAFETY CHAIN OR CABLE AS SHOWN WITHOUT TENSION, NOT AS A LIFTING CHAIN OR CABLE, BUTTO PREVENT THE UNIT FROM ROLLING. 4. DO NOT FORKLIFT THE UNITTO MOVE OR LIFT. 5. LIFTING HOLES PROVIDED ON CHILLER TO ATTACH CABLES (CHAINS OR SLINGS). 6. 36" (900 MM) RECOMMENDED CLEARANCEABOVE HIGHEST POINT OF COMPRESSOR. Q FOLLOW NEC SECTION 110 AND OTHER APPLICABLE LOCAL CODES FOR CLEARANCES IN FRONT OF ELECTRICAL ENCLOSURES. 8. SPECIFIC SHIPPING AND OPERATING WEIGHTS OF THE SUBMITTED CHILLER ARE PROVIDED IF THE CENTRIFUGAL CH ILLER SELECTION WAS ENTERED IN TOPSS. DETAILED LOAD POINT AND SPRING ISOLATOR APPLICATION WEIGHTS ARE AVAILABLE FROM "CENTRAVAC ISOLATOR SELECTION REPORT" AVAILABLE FROM THE REPORT GENERATOR OFTHETRANETOPSS CHILLER SELECTION PROGRM+I. CONTACT YOUR LOCALTRANE SALES ENGINEER IF THIS DATAIS REQUIRED- 4 X .88 (22mm) DIAHOLES FOR ANCHORING UNIT TYP (127mm) TYP (67mm) )"TYP (30mm) EVAPORATOR 2"TYP TUBESHEET (51mm) HOLE DETAIL TYP SAFETY CHAINS OR CABLES 16ft MINIMUM=4877mm (SEE NOTE 8ABOVE) MAXIMUM SHIPPING 17,244.01b MAXIMUM OPERATING 19,217.0Ib CLEARANCESPACE i - 7 341l4" RIGHT HAND TUBE PULL SHOWN, APPLY TUBE PULL CLEARANCE DIMENSION TO B2" LEFT END FOR LEFT HAND TUBE PULL. REFERENCED TUBE PULL IS GOOD FOR BOTH EVAPORATOR AND CONDENSER DIMENSION INCLUDES TUBESHEETS 44 1/2" 135' 141" 320 1!2" Equipment Submittal Page 20 of 25 'SLC - Rock Road Jail Chiller Rep[ 2021 November 23, 2021 Accessory - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 ADAPTIVIEW CONTROL PANEL TOP VIEW O O O O O O �---------- L/---------� 6518" zo" TYPICAL HOME / 1 POSITION / \ 2X 1 5/16" / \ QUITS REF -BOTTOM FRONT 7 112" 1 OF PANEL DOOR I J Ir' 'LOWEST POSITION AVAILABLE 6 3/4" -1 118" DIA HOLE 7/6" DIA HOLE 26 1 /8" NOTE: DISPLAY CAN MOVE TO AN INFINITE NUMBER OF POSITIONS. Equipment Submittal Page 21 of 25 SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Accessory - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 UNIT MOUNTED WYE-DELTA STARTER 16 BREAKER SHORT CIRCUIT CURRENT LINE CONNECTION LUGS PANEL INTERNAL WIRE SIZE AIC AMPS RATINGS (RMSSYMETRICALAMPS) WYE-DELTA STARTERS I CONNECTION LENGTH 4DP 1 65,000 65,000 (2) 2l0-250 OR (1) 210-500 CBIC 2.5" POWER FACTOR CORRECTION CAPACITORS, WHEN SELECTED,ARE NOT CBIC = CIRCUIT BREAKER HIGH INTERRUPT CAPACITY INCLUDED IN THE UL SHORT CIRCUIT RATING OF THE STARTER. THE NON -FUSED DISCONNECT OR CIRCUIT BREAKER IS DESIGNED FOR USEASASERVICE DISCONNECT ONLY. DOOR SWINGS TO THE LEFT FORAMAX OF 145 DEGREES & 38114" ELECTRICAL ENTRANCE 7" x 14" TO P TOP VIEW ALLOW MIN. FRONT WORKING SPACE CLEARANCE PER NEC ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. FRONT ELEVATION h Equipment Submittal Page 22 of 25 SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Field Wiring - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 Q WARNING HAZARDOUS VOLTAGE! CIS_._TALLELECTRIC PC— INCLUCUIG REMOTE DISCONNMTSANOJ FOLLOW LOCKOUT AND TA GFROCEWRESEEFCRESEFVICING. INSURE THAT ALL MOTOR CAPACt .A.S NAVE DISCHARGED STCRED VOLTAGE. UNITS WITR VARIABLE SPEED OA-. REFER TO CRNE INSTRUCTIONS FOR CAPACITOR DISCHARGE. FAILURE TO CO THE ABOVE BEFORE SeeRVCINO COULD RESULT m EIN CEATH CA SEP.ICUS nN /N� RT ^n AR711SSEII�uEN7 TENSION DANGEREUSEI DIJMTCS CCWDRTAW DES ENTRAINEHENTS A VITESSE VARMELE, SE REPORTER AM INSTRUCTIONS ➢E LTNTRAINEFENT POUR WCHARGER LES CONDENSATEUIS NE PAS RESPECTER CES NESURES DE PRtCAUTIDN PEUT ENTRAMER DES BLESSURES GRAVES PCUVVANT tTRE MCRTELLES. A®V ERTEHM IVDLTAJE PELIGROSOI ➢EL CENDENSADER. NO REALIZAR LO ANTERIORMEWE PODM4 DCASIONAR LA MUERTE 0 LESIOMES PERSONALES. CAUTION USE COPPER CONDUCTORS ONLYI J NIT TERMINALS ARE NOTDESIGNED TO ACCEPT —A TIF£5 OF CONDUCTORS. FAILURE TC 00 SO MAY CAUSE CAMAGETOTHEECUI—ENT. ATTENTION N'UTILISER OUE DES CONDUCTEURS EN CUIVREI LES BURNES DE L'UN1Tt HE SONT PAS CDNCUES POUR RECEVOIR D'AUTRES TYPES DE CDND UCTEURS. L'UTILISATMN DE TDUT AUTRE CCNDUCTEUR PEUT ENDCHHACER L'CQWPEMENT. PRIE(CAUMN IUTILTCE ONICAMENTE CONDUCTORES DE COBREI LAE TERMIW CS ➢E LA UNTUAD NO ESTAN DISE.I+DAS PARA ACEPTAR DTROS TIPOS ➢E CONDUCTORES. SI NO LD mCE, PUE➢E DCASIDNRR BRAD AL EDUIPO. DEVICE PREFIX CODE 1 = MAIN UNIT CONTROL PANEL DEVICE 2 = REMOTE MOUNTED DEVICE 4 = UNIT IIIOUNTED DEVICE 5 = CUSTOMER PROVIDED DEVICE CUSTOMER SUPPLIED LINE VOLTAGE (SEE UNIT NAMEPLATE) GNO Ll L2 L3 I I I I I I I I I I I I I I I I I I I I I I I I I I d b b b G L1 L2 L3 201 OR 2S1 DISCONNECT OR 2X3 TERMINAL BLOCK TRAN E SUPPLIED UNIT MOUNTED LOW VOLTAGE WYE-DELTA STARTER PANEL WIRE NO OR DEVICE FIELD WIRING CIRCUIT SELECTION INFORMATION SUPPLY AND MOTOR LEADS 4M1 COMPRESSOR MOTOR LEADS SEE NAMEPLATE. MINIMUM CIRCUIT AMPACITY 1A' 4000VA AT 115VAC, 8 AWG MAX WIRE SIZE ZA'AND GRWYEL 4000VA AT 115VAC, 8 AWG MAX WIRE SIZE (WITHOUT OPTIONAL CPTR) 3BAND4B CIRCUIT PROTECTED AT 20A, 115VAC 1PH, 10AWG MAX WIRE SIZE(WITH OPTIONAL CPTR) 9A' AND 1CA' PUNIP MOTOR, 1PH Y4 HP, 11.7 FLA, 14 AWG MAX WIRE SIZE, CIRCUIT PROTECTED AT 15A, 110-120VAC 1PH W64 TWISTED, SHIELDED PAIR, 3OVDC, MAX LENGTH 1500 FT(4572m) BELDEN TYPE 8760 RECOMMENDED 5S1', 5S2'1. 38' AND 4B' CIRCUIT PROTECTED AT 20A, 115VAC 1PH, 10 AWG MAX WIRE SIZE 5S3 TH RU 5S8 24VDC, 1210A RESISTIVE LOAD, 14 AWG MAX WIRE SIZE ALL REMAINING LUD TERMINALS CONTACT RATING, 2.88AINDUCTNE, 113 HP, 0.25<W AT 110-120VAC 14 AWG MAX WIRE SIZE NOTES: 'TAPPED CONTROL CONO UCTO RS I DASHED L114ES INDICATE FIELD WIRING BY OTHERS WIRE NUMBERS SHOWN ARE RECOMMENDED BY TRANE. 2. DO NOT ROUTE LOW VOLTAGE (30V) WITH CONTROL VOLTAGE (110-12OV) AND DO NOT POWER UNIT UNTIL CHECK-01.17 AND START-UP PROCEDURES HAVE BEEN COMPLETED. Equipment Submittal Page 23 of 25 SLC - Rock Road Jail Chiller Repi 2021 November 23, 2021 Field Wiring - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 ANY tAB OR 1A9 DEFAULT OUTPUTS IJAY BE MAIN UNIT CONTROL PANEL 5Ht5 FEPROGRAMLIED TO ANY ALTERNATE ALARIJ TERMINAL CONNECTIONS OR STATUS OUTPUT LISTED BELOW CHILLER ALARIJ INDICATOR (ALTERNATE) OPTIONAL ail 1A72 CLSTCNERTO CONBJECT ETHERNIET FACTORY CONIJECIED C=I,TERPROVTDED ETESTO4ANDPOWER API CONTROL PANEL 110VAC 5➢HZOR 12lNAC 60HZ 15A CAHLESTO IA2ADAPTIVIEW VJS78 1A2-J4I DISPLAY UOMTOR POWER GND H N Qd 1K25 EVAPORATOR AND IK27 CCNDESSER PRIUARY WATER FLOW DETECrICNI CONTROLLERS INSTALLED BY TRANJE. CUSTOLIERSUPPUED SECONDARY EVAPORATORANDCONDENSER 'HATER PROOF OF FLOW DEVICES AR E 5573 AND SSI4. 5SI3IS RECODUENDED BY TRAN]E WHEN LEAVING WATERTEUPERATLDRE IS 38' OR LESS AND UETHOD USED IS INDEPENDENT OF THE PRIUARY WATER PROOF OF FLOW DEVICE. IF ETHER SECONDARY WATERPROOF OF FLOW DEVICES, RD.TOVETRANE FACTORY WIRE 5W BETWEEN 1X1-5 AND 11(26-4 AND INSTALL SS13 AS SHOWN, AND'OR WIRE 5T BETWEEN Ix"AND 1K27d AND INSTALL 5914 AS SHOWN TRANS RECOULI ENDS W IFSNG 51<7 EVAPORATORAND 5K2 CONDENSER AS SHOWN TO ALLOW THE IASNODLLETO NT COROL NC PROPER SEQUEINNG. CAUTION USE COPPER CONDUCTORS ONLl1 FA61JFcro TK; 9] LJY(JSS= �gvc}:s e�rorT�> Err=�L�a1u ar r� p WY 1EC YDONW N-UTILISER QUE DES C12NDUCTEURS EN CU V EI [S -KS DC -IT, W Sd PAS CONCUSS PDA RECEVDIR D'AUTRES 1rPET DE CONWCrEVRS AN PCUTTI�[N06X TOUT AUTWIK CHT. R PRECAUC06N WTILICE ONICANENTE CONDUCTORES DE COBREI LAS TERRDRALES DE LA UNIDAD W ESTM DISER I AS I— ACEPIAR DTRDS TVW a CM TORCS. TI NO L00_0 AL EwIPQ ASIDupR 583 I- --0- -0---0 1413 J2-1 EXTEWNAL AUTO STOP TN2 (RETJOVE JUJER TW2 TFUSEU I — — — — — — --0 7A73l22 SSd EIJERGEPJC( STOP r —0-/tr — — —0 IA13 Jd3 LREUCVE JU.IPER 1W31F USED) I IW3 A------ -b IA13 JZd 2.10VDC 0 1A15J2-1 %%% FLA COUPRESSOR OUTPUT (GENERIC SAS] --0 IA 15J2-3 2-10VDC - -0 t415 J2d CONDENSER REFRIGERANT PRESSURE DIFFEFEtJMP OR OUTPUT - --0 1415 J2.6 CONDENSER HEAD PRESSURE CONTROL --0 IA16J2-2 2-13VDCOR EXTERNAL CURRENT UkIT SETPONT - -0 1416 J2-3 --0 1416 JZ-5 EXTECAL HILL4 EXTEF0IA,L CHILLED WATERSETPOINT 0 t416 J2-6 OPTIONAL SS13 EVAPORATOWNATER I �--D-�-O-- 1X1-5 PULIP IIJfERLOCK ` AUX - -0 iK26d REQUIFEED 5511 59A � 5T O TXi-6 CONCENSERINATER I--o-\ RRAPINTERLOM ` AUX ---- --0 iK27-4 GRNYEL I IX1-33 Q- - -� I IA5J2-6 O- ----1 1A532-4 0- I5�KI1 LJ -4 EVAPORATOR WATER PUAF RELAY OPTIONAL -`r' 1ASJ2.3 O- ----? 5<2I I 05J2-1 0----------0i FO-♦ LJ I COHC£NSERWATER I 1A8 J2-9 PULP RELAY REOUR® I 5H1 148 J2-7 0- - - - - I _ - CHILLER LATCHING ALARN INJDICATOR I OPTIONAL (DEFAULT) 1A8 J2-3 O - - - - 148 J2-1 0------I--- 5142 � CHILLER NOICATOR 0- - - - - OPTIONAL I FR11 (DE1A9J2-9 5Hd I IA9J2-7 0-- -- -� -- yI PLRGEALARIJ I INDICATOR OPTIONAL I IDEFAULT) tA.8.12-12 0- - - - - 5H5 1ABJ2-10 0------ CHILLER RUNNING INpCATOR OPTIONAL (DEFAULT) 1A8J2-6 O- ---� 5H7 CHILLER UUIT tAB J24 O- - - - _ _ _ r LIOCE IJCCATOR I OPTIONAL I I I I (DEFAULT) I I I I 1A9 J2-6 O- I I I I I --- I I I I I I CHILLER HEAD 1A9J2-4 0--------- ,,41ryry10,, -Ny1yj RELIEF REQUEST Amy INDICATOR (DEFAULT) 1A9 J2-3 0- OPTIONAL ----� 5H71 I I CHILLER AIA.1111i.1 IA9 J24 O-- -- - r- - - CAPACITY INDICATOR OPTIONAL (DEFAULT) I IK26-17 WHT WHT 4R17 0- - Ew iK26-1a O-BLU 3 1K26.19 BRNI � - -}---{- -- EE < 1 0 4 dRII a ELK t` EUC ��H TO BE INSTALLEDIK2120 I,- LK if �L - - y ��o SY CUSTOLIER GRYI I WB71� CRY 1K26-21 0- 5 1K27-17 VVHT 0- WHT2 4R18 LU t BLU IK27-18 0- \1 3 iK27-/9 BRN �- d (/ ERN �--�---- o s 1N �� Q 4R18 /r I\ z TOBY CUSTO ER 1KZ7-20 ELK 0-- ELK /1 I\--- z d2�F W 812 I I 6V RY I L 30 1K27-21 0- - 5 Equipment Submittal Page 24 of 25 ' SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Field Installed Options - Part/Order Number Summary This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the 'ob. Product Family - Centrifugal Water Chiller Item I Tag(s) Qt Descri tion Model Number Al I CH-3 1 1 Centrifugal Chiller CTV CVHE045 Field Installed Option Description Part/Ordering Number Thermal dispersion flow switch (IFM) - Field Installed Thermal dispersion flow switch (IFM) - Field Installed Equipment Submittal Page 25 of 25 Sp GENESIS INTERNATIONAL. INC. SHERLOCK" INFRA -RED REFRIGERANT GAS SENSOR SPECIFICATIONS ENCLOSURE RATING NEMA 3R Aluminum, Black Powder Coat GENERAL SHERLOCK NON -DISPERSIVE IR REFRIGERANT GAS SENSOR was designed to monitor for the presence of refrigerant gases within an enclosed space. The sensor is mounted within the space to be monitored and connect- ed by cable to a SHERLOCK, Wg44d or EMS System. Each sensor is calibrated to a specific refrigerant gas. The IR comes in two different styles depending upon the monitoring environments: machine room and cold room for refrigerated applications in NEMA 3R Aluminum (Pictured). Water -tight ABS fiberglass housing for Wash down protection (NEMA 3R) and Stainless Steel enclo- sure also available for special applications. The IR Sensor is a reliable method of monitoring for refrigerant gas leaks in environments that have air quality problems. The IR sensor will eliminate many false alarms in environments that contain gasoline, diesel, and propane exhaust and fumes from solvents, paints, cleansers, and others (Please call Genesis Customer Support for more information). APPLICATIONS Typical applications include: Wineries HVAC Chiller Equipment Rooms Bakeries Refrigeration Mechanical Rooms Refrigerated Rooms Food Processing Plants DIMENSIONS 12.86 x 4.8 x 2.44 Inches (mm) (327 x 122 x 62) OPERATING ENVIRONMENT TEMPERATURE Machine Room Model 32°-120°F (00- 50°C) Freezer Room Model-40°-120°F (-40°- 50°C) HUMIDITY 0 - 90% RH Non -Condensing POWER INPUT Sherlock l ?Vr and 12VDC, 0.4 A Stand -Alone 12V DC - 32V DC Switching OUTPUTS (Standard) Current Driven Sherlock/Wizard 4 to 20 mA (Standalone Sensor) (Please contact Genesis for custom voltage outputs for the stand-alone sensor) RANGE (Parts Per Million, PPM) SherlocklWga4d 0 - 1500* (Control Dependent) Stand -Alone 0 - 1032* *Minimum effective range due to noise is 10 - 15ppm. SENSITIVITY fl ppm at 77°F (25°C), 45% RH RESOLUTION 1 ppm RESPONSE TIME Under 30 Seconds CALIBRATION Every 6 Months WARM-UP TIME Readings will stabilize in 3 hours (Up to 18 Hours in Cold Room Applications) LIFE EXPECTANCY Average of 5 to 7 years in normal environments AVAILABLE GAS SENSORS (Part Numbers) Machinery Room/Walk-In Cooler Application RI I - 60-0057 R12 - 60-0104 R22 - 60-0053 R23 - 60-0232 R123 - 60-0137 R125 - 60-0466 R134a - 60-0054 R401a - 60-0465 R402a - 60-0231 R404a - 60-0052 R407a - 60-0223 R407c - 60-0214 R407f - 60-0514 R408a - 60-0184 R409a - 60-0066 R410a - 60-0165 R422d - 60-0546 R424a - 60-0469 R438a - 60-0246 R448a - 60-0544 R500 - 60-0067 R502 - 60-0059 R507 - 60-0061 R513a - 60-0542 R514a - 60-0550 R1233zd - 60-0548 R1234yf - 60-0551 Ammonia/NH3 - 60-0095 Extended Temperature/Freezer Application RI I - 60-0058 R22 - 60-0047 R402a - 60-0142 R404a - 60-0051 R407a - 60-0526 R407c - 60-0473 R407f - 60-0528 R408a - 60-0065 R438a - 60-0464 R448a - 60-0545 R500 - 60-0068 R502 - 60-0060 R507 - 60-0062 Ammonia/NH3 - 60-0096 Please contact Genesis if your sensor type is not listed. MULTIPLE 60 NUMBERS ON SHEET, NEMA 3R 09-12-19 W 12.861 —� O MCI! MOUNTING Sensor Placement -- The Sherlock IR Sensor must be placed in locations where a refrigerant leak is likely to occur and where leaked refrigerant gas is likely to concentrate so as to pro- vide warning of a poten- tially hazardous condition. Mounting locations are dependent upon the appli- cation and the refrigerant gas to be monitored. For Halocarbon refriger- ants such as R11, R22, R123, R134a, R404a, etc... Place the sensor 18 to 24 inches off the floor. For Ammonia, place the sensor 18 to 24 inches from the ceiling. HVAC/Refrigeration Machinery Room -- Prior to placement of the IR Sensor, the room air currents need to be determined. The maxi- mum air flow rate past the sensor should not exceed 3 feet per second. WARNING.... I I I I The infrared sensor is not to be applied Mounting -The sensor must be mounted with the wire termi- /4 all refrigerated storage applications where other toxic gases are used in the same room. Some installations are nal blocks oriented to the lower right and the sampling chamber not suitable for Infrared technology. Misapplication may in a vertical position. Failure to mount the sensor in this fash- result in damage to sensor. Contact the factory for a ion may result in inaccurate readings and can allow moisture to specific list of approved applications. enter the housing and destroy the sensor. -- 12.36 — 206 DIA. 4 HOLES O O O --4.346 -� TYPICAL WIRING DIAGRAMS SHERLOCK / WIZARD STAND ALONE (PLC, BAS) INFRARED SENSOR R R 4 GND I Al V+ —_ V+ 4 GND V+ G 3 V+ I PLC � 3 V+ SNR A IN B G 2 OUT- I G 2+1 8760 2 OUT- GND 10UT+ I 1 OUT+ I SIG COMM- I -_ COMM- V+ COMM+ I COMM+ SNR B IN GND SENSOR POWERED BY 12V DC TO 32V DC POWER SUPPLY. SIGNAL IR SENSOR I IS 4-20MA. PLC INPUT SET TO 4-20MA INPUT. MAXIMUM IN CURRENT LOOP RESISTANCE - 250 OHM. INFRARED SENSOR V+ Al 4 GND IN I PLC 3 V+ 2 I G 2+1 8760 2 OUT- 1 OUT+ I SIG HORN/ I -_ COMM- STROBE I COMM+ STROBE SENSOR POWERED BY PLC PRODUCING 12V DC TO 32V DC, 400MA. SIGNAL IS 4-20MA. PLC INPUT SET TO 4-20MA INPUT. MAXIMUM I CURRENT LOOP RESISTANCE - 250 OHM. GENESIS INTERNATIONAL, INC. 1040 FOX CHASE INDUSTRIAL DRIVE PHONE: (636) 282.0011 ARNOLD, MISSOURI 63010 FAX: (636) 282-2722 WEBSITE: EMAIL: WWW.GENESIS-INTERNATIONAL.COM MAIL@GENESIS-1NTERNATIONAL.COM DOC #44-0493-00