HomeMy WebLinkAboutEngineeringa System Design Criteria for Focus Homes 8407 Deland Avenue, Ft. Pierce, FL 32951 Aerobic Treatment Unit With Drip Irrigation Prepared By: Todd N. Smith, PE, Inc. 1717 Indian River Boulevard Suite 302 Vero Beach, Fl. 32960 772-559-3699 I certify that the engineering features of this aerobic system have been designed or specified by me and conform to engineering principles applicable to such projects. In my professional judgment, this system, when properly constructed, operated and maintained, will achieve the established performance standard and comply with all applicable statutes of the State of Florida and the rules of the Department. 1 WQ*' i PieP.�� •.� F� r's2 ce #;4 0 2 Dkte::August 27�,�4,62�t. Z ;�e'e`RO FESsN,����� 'f Drip Design Calculator Job Name/Homeowner- . Focus Homes Address: 8407 Deland Avenue; Ft. Pierce, FL 32951 Pennit Agency St. Lucie County Health Department Installer Name Brian Davis Septic Designed.By: _Todd N. ,Smith, PE, Inc. Date: August 27.2021 Gallons Per Day: 400 gpd Soil Loading Rate (.GPD, Per Sq. Ft.) Recirculation Rate: 13.25 gpm Minutes Per Dose (Min.) Emitter Spacing (ft.) 1 Sq. Ft. of Application Area Drainfield Reduction: 0% Linear Feet of Tubing Number of Emitters Linear Feet of Tubing Per Zone Number of Zones Emitters Per Zone Drip Rate (GPH) Gallons Per Minute Per Zone Minutes Per Day Per Zone Doses Per Zone Total Doses Per Day Time Between Doses in Hours Total Run Time in Minutes Maximum Connections to Manifold Gallons Per Dose 0.8 18 500 250 250 250 250 .90 3.75 107 6 6 3.70 107 14 66.7 Total Dynamic Head Calculation (TDH = Static Head + System Operating Head + Dirty Filter + Total Friction Head) Static Head = 5.42 ft. System Operating Head (29 psi) = 67 ft. Dirty Filter = 11.5 ft. Friction Operating Head Main Discharge & Recirculation Line Transmission & Header Diameter = 1.00 in. Type of Fitting Eq. Length Quantity Total Eq. Length I" Std.' Tee 1.7 ft. 14 1" 90 Degree STD Elbow 5.3 ft. 12 Total Fitting Equivalent Length = 87.4 ft. Actual Length of Discharge Header Pipe = 84.0 ft. Total Pipe Length = 171.4 ft. Tntal Frietinn T.nsses in ecmivalent 1" diameter discharve line 23.8 ft. 63.6 ft. GPM HI in ft/100ft HI of 171.4' of 1" Dia. Static + Operating Head + Dirty Filter Total Discharge Head (ft.) 0 0 0 83.92' 83.92' 15 11.70' 20.05' 83.92' 103.97' 20 18.90' 32.39' 83.92' 1 116.31' Use Sta-Right S.T.E.P. Plus D-Series 4" Submersible Pump (20 gpm —'/z HP) Pump Curve shows 17.0 gpm @ 109 ft. of head System needs 3.75 GPM Recirculation 17.0 GPM — 3.75 GPM = 13.25 GPM Residential: 400 GPD Maximum Lot Flow (On Potable Well Water = Lot Area + Green Area in ROW in Front of Lot = (16,443 SF + 4,496 SF) / 43,560 sf/acre x 1,500 gpd/acre = .481 AC X 1,500 GPD/ AC = 721 GPD Drip Area Required: 500 sq. ft. Drip Area Provided: 500 sq. ft. Unobstructed Green Area Required: 750 sq. ft. Unobstructed Green Area Provided: 750 sq. ft. s System Design Criteria Residence is 4 Bedroom (Building Area is > 2,250 sf and < 3,300 sf) = 400 GPD Drip System to be placed in Trench System 400 GPD / .8 GPD per sq. ft. = 500 sq. ft. of drainfield No reduction for dripline drainfield proposed. Drainfield Requirement = 500 sq. ft. of drip irrigation 2 Lines @ 14', 2 Lines @ 16', 2 Lines @ 19', 2 Lines @ 22', 2 Lines @ 25' and 2 Lines @ 29' with emitters every foot and lines greater than 24" apart 250 emitters x 2 sq. ft. per emitter = 500 sf Configengy Plan 1. At high water level, the system will start alarm. The owner must contact the maintenance entity within 24 hours. 2. Maintenance entity personnel will inspect the system and make necessary repairs within 36 hours as per 64E-6.012(4)(b). 3. Owner shall pump the tank as required to keep trash out of the aeration chamber. Operation and Maintenance The operation and maintenance manuals are provided to the installer and maintenance entity at the time of installation. Installation Installation instructions will be provided by Brian Davis Septic on site to insure proper construction and installation. DRIP EFFLUENT DISPOSAL SYSTEMS DESIGN CRITERIA- 64E-6 Dated July 31, 2018 A. Drip effluent disposal systems shall receive effluent from an approved aerobic treatment unit or a performance -based treatment system designed to meet at east secondary treatment standards for CBODs and TSS and shall meet the following requirements. 1. Drip effluent disposal systems shall be designed by an engineer licensed in the State of Fl. 2. The infiltrative area required shall be the same as the area required for a mineral aggregate drainfield with reductions all for the reduction of CBODs and TSS as noted in the Florida Administrative Code, Chapter 64E-6 Part IV, Performance - Based Treatment Systems. 3. In a bed configuration, the drainfield area shall be calculated as extending one foot beyond the sides of the outermost emitter lines. 4. In a trench containing a single distribution line, the drainfield area shall be calculated as 2 feet x the emitter spacing in feet x the number of emitters. 5. Drip effluent disposal systems shall be considered pressure distribution systems. . Head loss calculations shall be provided to insure proper hydraulic pressure at the emitter. Pump selection shall be indicated in the design specifications. Pump performance curves shall be provided. 6. Re -circulation rates shall be indicated on the drawings. 7. Check valves, petcocks, inline filters, and vacuum breaking device locations shall be indicated on the drawings. 8. Drip effluent disposal systems shall be time -dosed over the 24 hour period. Demand control dosing shall override timed -dosing in periods of flow where timed dosing cannot handle the excessive flow. 9. All drip emitter systems shall be designed as continuous loop circuits with no dead- end emitter lines. All systems need to incorporate a mechanism for backwashing or flushing. 10. Drip emitter lines shall be drawn to scale and drip emitter spacing shall be indicated on the drawings. 11. Vacuum release valves shall be installed at the highpoint of the emitter lines. 12. The maximum .emitter longitudinal spacing on a distribution line shall be 2 feet. The maximum distribution line spacing in a bed configuration shall be 2 feet. 13. The setback from drip emitter lines to building foundations and property lines shall be no less than two feet. 14. There is no drainfield sidewall in a drip -effluent disposal system. The definition of a filled system in a 64E6.002(24), Florida Administrative Code, is not applicable to drip effluent disposal systems. A drip effluent disposal system is considered to be a mound system when any part of the bottom surface of any drip emitter line is located at or above the elevation of undisturbed native soil in the drainfield area. A drip effluent disposal system us considered a standard sub -surface drainfield system when the entire bottom surface of every drip emitter line is installed below the elevation of undisturbed native soil in the drainfield area. 15. For mound systems there shall be a minimum separation of 18 inches between the shoulder of the fill and the nearest drip emitter line. Mound system slopes shall be in accordance with s. 64E-6.009(3)(f), Florida Administrative Code. Mound systems shall be stabilized in accordance with s. 64E-6.009(3)(f), Florida Administrative Code. 16. For standard sub -surface systems, the elevation of any fill covering the drainfield shall extend no less than 18 inches away from all emitter lines before tapering down to natural grade. 17. Minimum cover on the distributions lines shall be 6 inches for standard sub -surface systems and 9 inches for mound systems. The maximum cover for all systems shall be no greater than 12 inches. 18. The system shall include a petcock on the dosing pump discharge line for effluent sampling in lieu of the installation of monitoring ports required in s. 64E-6.029(2), Florida Administrative Code. 19. All systems shall incorporate an automatic mechanism for backwashing or flushing the drip lines and filters. 20. All on -site sewage treatment and disposal systems that include a drip effluent disposal system and aerobic treatment unit or performance -based treatment system shall have a biennial operating permit, maintenance contract with an approved performance -based system maintenance entity and shall be inspected in accordance with a 64E-6.027(5), Florida Administrative Code. 21. Drip effluent disposal systems shall meet the following operating parameters: * Minimum operating pressure at the emitter head shall be 10 psi. * Maximum operating pressure at the emitter head shall be 45 psi. * Maximum system operating pressure shall be 60 psi. * Maximum discharge rate per emitter shall be 1.5 gallons per hour. 22. The hydraulic surge storage requirement of Rule 64E-6.028, F.A.C., does not apply to drip irrigation systems. 23. Drip irrigation systems shall only use components approved by the Bureau of Onsite Sewage Programs. 24. Unobstructed area for drip irrigation systems may be located anywhere on the establishment property that meets the setbacks for unobstructed area and can be accessed via transmission lines, supply lines and return lines. The land containing only transmission lines, supply lines and return lines shall not be included in the calculation of unobstructed area. 25. Supply lines and return lines shall be considered as transmission lines for determining setbacks not specified in this section. 26. Except for slopes required to meet the stabilization requirements of 64E-6.009(3)(f), the area over the drip irrigation drainfield shall be stabilized in the same way or vegetated with plant species specified by the design engineer. The species specified shall not include trees. 27. For drip emitter lines using non -pressure -compensating emitters, the maximum elevation difference shall be four inches between the highest and the lowest emitter in any individual line segment between the supply and return line. For drip emitter lines using pressure -compensating emitters, there shall be no more than 18 inches of elevation difference between the highest and lowest emitter in any line. Neither property slope nor drip emitter line slope shall result in a depth of cover over the drip emitter lines to be outside of the range permitted in subparagraph 64E-6.009(5)(a)17, F.A.C. 28. The minimum effective soil depth below drip emitter lines shall be 42 inches; however, spodic layers greater than 24 inches below the drip emitter lines may remain in place at the discretion of the design engineer. B. Drip irrigation systems shall be monitored during required maintenance visits by visual inspection of the ground surface above the emitter lines for evidence of soil saturation at the ground surface. Answers for Drip Effluent Disposal Systems Design Criteria for the State of Florida 64E-6 Dated July 31, 2018 Part A 1. Compliance 2. Compliance 3. Compliance 4. Compliance 5. Head Loss Calculations Provided Pressure Loss in 171.4 feet of 1" tubing & dirty filter is 15.79 psi. Pressure Loss in return line = 5.40 psi Flow Rate while the system Is running is _17.0 GPM. Pump is capable of producing 17.0 GPM at _109 ft. of head Pressure to field will be adjusted to achieve a maximum of 30 PSI on the supple manifold by opening the by-pass petcock located in the pump tank. Pump Curve attached. 6. 17.0 GPM, filter flush return line, 3.75 GPM during field flush, 13.25 GPM recirculation to pump tank. 7. Located in Headworks. 8. Compliance 9. Compliance 10. Compliance 11. Compliance 12. Compliance 13. Compliance 14. Compliance 15. Compliance 16. Compliance 17. Compliance 18. Compliance 19. Compliance 20. Compliance. Completed with FDOH and Contractor. 21. Minimum operating pressure at emitter head is greater than 10 psi Maximum operating pressure at emitter head is less than 45 PSI Maximum system operating pressure is less than 60 PSI Maximum will be .90 GPH per emitter. 22. Compliance 23. Compliance 24. Compliance 25. Compliance. 26. Bahia or Floritam Sod to be installed over drainfield. 27. Pressure compensating emitters not to have 18" of elevation change between the highest and lowest emitter in a line. 28. Minimum effective soil depth shall be 42". Part B. Inspections to be performed in accordance with the requirements set forth in the operating permit as required in the letter herein this design report. V Pentair Model S.T'.E.P. Plus-D Series 4" Multi -Stage Submersible Effluent Pump Stainless Steel 3 00 fl F- 225 LU ur Z T O 75 CAPACITY LITERS PER MINUTE 25 50 75 100 200 C•'f 45 do „ r� is 210 ys 30 ocs CAPACITY GALLONS PER MINUTE Specifications 80 N t_1 LU 60 W F Z 0 60 Body Construction: Stainless Steel (300 Grade) Horsepower: Y? HP Maximum Head: 225' Maximum Capacity: 40 gpm (model dependent) Flow At 10' Lift: model dependent Switch: None Motor: Dry -wound, double ball bearing, double -seal and thermal overload. protection, UL and CSA approved. Impellers: Precision molded Acetal for perfect balance... ultra -smooth for the highest performance and efficiency. Allows Tor .080" solids Diffusers: Polycarbonate l A V Q V a d so z th V Ato i m� x 1 we - CD cn- ro ID O C wz N t=] Y O Lam] z CIO 1-3 Lam] AQUAAIRE SEWERAGE TREATMENT SYSTEM MODEL AA5O0-35 AA500 WITH 350 GALLON PRETREATMENT TANK ONE PIECE W1 TH LID 63' F I 1 60" 2' ' i 102' ALTERNATE AERATOR LOCATIONS AERATOR 3/4" SCH 40 PVC NOT MORE THAN ; f00LF FROM PLANT 4- INLET --� TEE ASSEMBLY N cn 4' 7EEj �SSEMBL AT U T 7' GALLONtAERA GALLON REATMEN10N/MIXINGtlll�A TANKARTMENT '-1/2'TER DIM• R DROP NE FLEC110N C OUTLET �r z w 0 wm CL o w L z z � J o r` ZLu l � o ~ ` N O J LU O � O W C . C� O E Cn LIJ00 i O Q � O Lo za O `" w �l ca ~ a y � 0 M Z � s I H N m` *am � C S'd n Cn raa V I� O H o -o R a o o � o N TODD N. SMITH, P. E. INC. AA 800 1717 Indian River Boulevard, Suite 302 Vera Beach, FL 32960 SEWERAGE TREATMENT SYSTEM Ph. (772) 559-3699 Ltl j w U Lq 0:E 3"R ?s� TOP VIEW 79" 20" RISER ACCESS COVER FG RISER 59" in m CLARIFIER VOLUME 153 GALLONS 72" m NTER DIMENSIO 9" AEROBIC TANK VOLUME 756 GALLONS a 3" R SIDE VIEW NOTES: TOTAL TANK VOLUME: 908 GALLONS TO FLOW LINE. TANK TAPER FROM FLANGE TO BOTTOM: 4 INCHES AEROBIC AND CLARIFIER VOLUMES MEASURED AT FLOW LINE TODD N. SMITH, P.E. INC. ECOLOGICAL TANKS, INC. 1717 Indian Vero BeachBFLI 32 60Suite 302 AQUA SAFE MODEL (AS50OL) Ph. (772) 559-3699 DRIP FIELD CROSS SECTION FT. OF DRIP TUBE LINES ® 25" EDGE OF DRAINFIELD CENTERS WITH EMITTERS EVERY 18" MIN. 1 FOOT. • SLOPE TO FINAL GRADE O INSTALL DRIP TUBE 6"-12" BELOW FINAL GRADE WSWT IS >24" BELOW EMITTERS ** FILL COVERING THE DRAINFIELD SHALL EXTEND NO EFFECTIVE SOIL DEPTH LESS THAN 18" AWAY FROM ALL EMITTER LINES 42' BELOW EMITTERS BEFORE TAPERING TO FINAL GRADE. LOOP LOOP SUPP _INE 1"0 AP TANK TODD N. SMITH, P.E. INC. TYPICAL 1717 Indian RiverBeachBFL 32960Suite 302 DRIP TRENCH SYSTEM Ph. (772) 559-3699 HEAD WORKS UNl T JP FROM PUMP DISCHARGE 150 MICRON ME SPIN FILTER '2"0 FUNNY PIPE ADAPTER EE NOTE BELOW FOR RFORMANCE BASED SYSTEMS) 1/2"0 FUNNY PIPE ADAPTER PUMP TANK TO DRIP FIELD RETURN FROM DRIP FIELD FOR PERFORMANCE BASED SYSTEMS EFFLUENT TESTING SHALL BE TAKEN FROM FUNNY PIPE ADAPTER ON THE PUMP SUPPLY LINE TO THE DRAINFIELD AT THE FILTER WHEN PUMP IS ENGAGED. TODD N. SMITH, P. E. INC. HEAD WORKS 1717 Indian River Boulevard, Suite 302 UNIT DETAIL Vero Beach, FL 32960 Ph. (772) 559-3699 INLET FROM HOUSE SERVICE VEGETATIVE ) DIVERT SURFACE AWAY FROM TANK OUTLET TO AS500L OR AA800 PUMP TANKS INFILTRATOR SYSTEMS INC. IM-540 TRASH TANK WITH CONTROL PANEL TYPICAL TANK DETAIL TOTAL CAPACITY........... 557 GALLONS WORKING CAPACITY......... 483 GALLONS LIQUID LEVEL ............. 44 INCHES INVERT DROP ............. 3 INCHES MAX. PIPE DIAMETER....... 4 INCHES SIZE......... 61.7"W x 54.6"H x 64.9"L APPLICATIONS....... SUITABLE FOR USE AS A PUMP TANK, TRASH TANK, RAINWATER (NON —POTABLE) TANK OR AS SECOND COMPARTMENT OF AN INE SERIES SEPTIC TANK. TODD N. SMITH, P.E. INC. INFILTRATOR 1717 Indian River Boulevard, Suite 302 IM_540 TRASH TANK Vero Beach, FL 32960 Ph. (772) 559-3699 MOUNTED SECURELY TO A POST OR BUILDING 3/4' PVC CONDUIT WIIH POWER WIRES INLET FROM SFP71C TANK TTWRT1'SpEERICAL CONTROL PANEL TO GRADE HIGH WATER FLOAT )J 3 ENABLE FLOAT.# INSTALL ON I' CONCRETE PA710 ARAINAGE STABLISH VEGETATIVE QUICK DISCONNECTOVER AND DIVERT SURFACE AWAY FROM TANK —� TO DRAIN FIELD LIQUID INFILTRATOR SYSTEMS INC. IM-540 PUMP TANK WITH CONTROL PANEL TYPICAL TANK DETAIL TOTAL CAPACITY........... 557 GALLONS WORKING CAPACITY......... 483 GALLONS LIQUID LEVEL ............. 44 INCHES INVERT DROP ............. 3 INCHES MAX. PIPE DIAMETER........ 4 INCHES SIZE......... 61.7"W x 54.6"H x 64.9"L APPLICATIONS....... SUITABLE FOR USE AS A PUMP TANK, TRASH TANK, RAINWATER (NON —POTABLE) TANK OR AS THE SECOND COMPARTMENT OF AN IN SERIES SEPTIC TANK. TODD N. SMITH, P.E. INC. INFILTRATOR 1717 Indian River Boulevard, Suite 302 Vero Beach, FL 32960 IM-540 PUMP TANK Ph. (772) 559-3699 49.5 12.1 Side View Lid View WO-.KIDE�I-L � 3 `C D-F-- Q�V2AU (3 3" Standard 6" Traffic End View Notes: Receptacle has been designed and tested in accordance with Florida Administrative Code (FAC) 381 Chapter 64E-6. When receptacle is used as a pump chamber use 12.93 gallons per inch when configuring flont placement. Poly 11 High Pressure Pipe Seal (Accepts 2",3",4" & Corrugated Pipe) Poly 11 will meet the Vacuum & Hydrostatic pressure requirements of A.S.T.M. spec. C-923 for 2", 3" & 4" SCHD.40 6V Side View Lid View 3" 629 End :View Notes: Receptacle has been designed and tested in accordance with Florida Administrative Code (FAC) 381 Chapter 64E-6. When receptacle is used as a pump chamber use 18.75 gallons per inch when configuring float placement. Poly 11 High Pressure Pipe Seal. (Accepts 2",3",4' & Corrugated Pipe) Poly 11 will meet the Vacuum & Hydrostatic pressure requirements of A.S.T.M, spec. C-923. for 2" ,'3" & 4" SCHD.40 60" 3" Side View End View Notes: Lid View Receptacle has been designed and tested in accordance with Florida Administrative Code (FAC) 381 Chapter 64E-6. When receptacle is used as a pump chamber use 18.75 gallons per inch when configuring float placement. Poly II High Pressure Pipe Seal (Accepts 2",3",4" & Corrugated Pipe) Poly II will meet the Vacuum & Hydrostatic pressure requirements of A.S.T.M. spec. C-923 for 2", 3" & 4" SCHD.40 G 60" Side View Lid View 3" 6" End View Notes: Receptacle has been designed and tested in accordance with Florida Administrative Code (FAC) 381 Chapter 64E-6. When receptacle is used as a pump chamber use 19.8 gallons per inch when configuring float placement. Poly II High Pressure Pipe Seal (Accepts 2",3",4" & Corrugated Pipe) Poly II will meet the Vacuum & Hydrostatic pressure requirements ofA.S.T:M. spec. C-923 for 2", 3" & 4" SCHDAO ASTM 20" Lid GAS (HAZARDOUS GAS WARNING) 00 LOW PROFILE PUMP (FL) 1:3 DESIGN CAPACUTY TOTAL CAPACITY WEIGHT GALLONS LITERS GALLONS LITERS POUNDS 500 1893 525 1987 225 DWG SCALE: 1:1 PLOT SCALE: 12 SHEET N: I OF 3 LIFTING HOLES (4 TYPIC, THREAD ACCESS OPENIN( 24" I.D. E a in cV r U 1 F u ROTH Mult®TanK® 500 GALLON / MODEL RMT-500 LENGTH = 60" %A11r%1r" _ nnu I'D E ROTH GLOBAL PLASTICS One General Motors Drive Syracuse N.Y. 13206 Call Toll Free 866.943.7256 TOUII®tY11�NM[3RIBW11eUHHE6S www.fralo.net