HomeMy WebLinkAboutAPPROVED, PROJ-70206 - Johnson Residence SealedREVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEG-01CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951 CODES AND STANDARDS6505 OCALA AVE,FORT PIERCE, FL 34951JOHNSON RESIDENCEVICINITY MAPSHEET INDEXG-01COVER SHEETPROJECT DESCRIPTION:OWNERHOUSE PHOTOA-01ROOF PLANS-01MODULE LAYOUTS-02.1STRUCTURE CALCULATIONE-01ELECTRICAL LINE DIAGRAME-02WIRING CALCULATIONSE-03SYSTEM LABELINGSHEET SHEET DESCRITIONCOVER SHEETA-00NOTES AND DESCRIPTIONELECTRICAL CERTIFICATION:STRUCTURAL CERTIFICATION:DESIGN CRITERIA:WIND SPEED (ULT): 160 MPHWIND SPEED (ASD): 124 MPHRISK CATEGORY:IIEXPOSURE:CS-01.1ARTIAL RESSURE AND MODULES EXOSURESUNPRO SOLAR4492 Eagle Falls Place,Tampa, FL 33619PH: (866) 450-1012INSTALLERCastillo Engineering Services LLC620 N. Wymore Road, Suite 250, Maitland, FL 32751TEL: (407) 289-2575Ermocrates E. CastilloLicense#: FL PE 52590ENGINEERJOHNSON, MIKE21x380 LG NEON2: LG380N1C-A6 (380) MODULESROOF MOUNTED SOLAR PHOTOVOLTAIC MODULESEQUIPMENT SUMMARY21LG NEON2: LG380N1C-A6 (380) MODULES21ENPHASE: IQ7PLUS-72-2-US MICROINVERTERSSYSTEM SIZE:7.980 kW DC STCARRAY AREA #1:409.57 SQ. FT.I ERMOCRATES CASTILLO PE# 52590 AN ENGINEERLICENSED PURSUANT TO CHAPTER 471, CERTIFYTHAT THE PV ELECTRICAL SYSTEM ANDELECTRICAL COMPONENTS ARE DESIGNED ANDAPPROVED USING THE STANDARDS CONTAINED INTHE MOST RECENT VERSION OF THE FLORIDABUILDING CODE. FBC 107, THE NEC 2017, ANDTHOSE SET FORTH BY THE FLORIDA SOLARENERGY CENTER CERTIFICATION.I ERMOCRATES CASTILLO PE# 52590 AN ENGINEERLICENSED PURSUANT TO CHAPTER 471, CERTIFYTHAT THE INSTALLATION OF THE MODULES IS INCOMPLIANCE WITH FBC: RESIDENTIAL 2020 7th ED.,CHAPTER 3. BUILDING STRUCTURE WILL SAFELYACCOMMODATE WIND LATERAL AND UPLIFTFORCES, AND EQUIPMENT DEAD LOADS.RACKING: UNIRAC LIGHT RAILATTACHMENT: UNIRAC FLASHKIT PROS-02ATTACHMENT DETAIL7.980 kW PV SYSTEMDS-01-08DATA SHEETSGOVERNING CODES :FLORIDA RESIDENTIAL CODE, 7TH EDITION 2020 (FRC)FLORIDA PLUMBING CODE, 7TH EDITION 2020 (FPC)FLORIDA BUILDING CODE, 7TH EDITION 2020 (FBC)FLORIDA MECHANICAL CODE, 7TH EDITION 2020 (FMC)NATIONAL ELECTRICAL CODE 2017 (NEC)ASCE 7-16FLORIDA FIRE PREVENTION CODE, 7TH EDITION 2020 (FFPC)PROJECT SITEPROJECT SITE
System DescriptionThis system is a grid-tied, PV system, with PV generation consisting of21x380 LG NEON2: LG380N1C-A6 (380W) Modules with a combined STC rated dcoutput power of 7,980W. The modules are connected into 21 ENPHASE:IQ7PLUS-72-2-US Microinverters. The inverter has electronic maximum powerpoint tracking to maximize energy captured by the PV modules. The inverter alsohas an internal ground fault detection and interruption device that is set todisconnect the array in the event that a ground fault that exceeds one ampereshould occur. The inverter has DC and AC disconnect integrated system and labelsare provided as required by the National Electrical Code.When the sun is shining, power from the PV array is fed into the inverter,where it is converted from DC to AC. The inverter output is then used tocontribute to the power requirements of the occupancy. If PV power meets therequirements of the loads of the occupancy, any remaining PV power is sold backto the utility. When utility power is available, but PV power is not available,building loads are supplied by the utility.The inverter meets the requirements of IEEE 1547 and UL 1741.MicroinvertersPV ModulesPoint ofUtilityConnectionUtility MeterJunctionBoxFigure 1: PV System Block DiagramSection..............Elevation ...........Detail ................Detail ................(Enlarged Plan)Keyed Notes ..........Ground Terminal .....Grounding Point/rod....Solar Panel ......... orCombiner Box ..........AC Disconnect ..........Main DistributionPanel ......................Fuse ......................Overcurrent Breaker ..Inverter ....................Transformer .............Automatic ...............Transfer SwitchXX-XXXX-XXXX-XXXX-XX1CBACDMDP Sheet where section is located Detail ID Letter Sheet where section is located Detail ID Letter Sheet where section is located Detail ID Letter Sheet where section is locatedArea to be enlargedKeyed note designationon applicable sheetATS00Module with SourceCircuit numberVent, Attic fan(Roof obstruction)PV Roof AttachmentTrussesConduitFire AccessUMAC Alternating CurrentAPPROX ApproximateAWG American Wire GaugeCB Combiner BoxDC Direct CurrentACD AC DisconnectDISC Disconnect(E) ExistingEL ElevationEQ EqualJB Junction BoxMCB Main Combiner BoxMFR ManufacturerMIN MinimumMISC Miscellaneous(N) NewOCPD OverCurrent Protection DevicePOCC Point Of Common CouplingPV PhotovoltaicSF Squarefoot/feetSTC Standard Test ConditionsTBD To Be DeterminedTYP TypicalUNO Unless Noted OtherwiseVIF Verify In FieldWP Weather ProofBatteryBATUtility meterGPGeneration PanelMDPMain Distribution PanelSoladeckSDNAVD North American Vertical datumMID Microgrid Interconnect DeviceREVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEA-00CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951NOTES ANDDESCRIPTIONSymbols:Abbreviations:68.5"41.0"RAILS IN THISPOSITION UNOFALL PROTECTION:ANCHORAGES USED FOR ATTACHMENT OF PERSONAL FALL ARREST EQUIPMENTMUST BE INDEPENDENT OF ANY ANCHORAGE BEING USED TO SUPPORT ORSUSPEND PLATFORMS, AND CAPABLE OF SUPPORTING AT LEAST 5,000 POUNDSPER EMPLOYEE ATTACHED, OR MUST BE DESIGNED AND USED AS FOLLOWS:·AS PART OF A COMPLETE PERSONAL FALL ARREST SYSTEM WHICHMAINTAINS A SAFETY FACTOR OF AT LEAST TWO.·UNDER THE SUPERVISION OF A QUALIFIED PERSONADDITIONAL INFORMATION·29 CFR 1926 SUBPART M, FALL PROTECTION. OSHA STANDARD.·1926.502, FALL PROTECTION SYSTEMS CRITERIA AND PRACTICES···1926.502(D)(15)ALLOWABLE/DESIGN PRESSUREPSFDOWN PRESSURE126UPLIFT PRESSURE, 2 RAILS89LG NEON2:LG380N1C-A6(380W) MODULES
UM
MDP
CBACDSD
136'-0"160'-0"136'-0"160'-0"15'-5"41'-8"46'-1"47'-1"REVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEA-01CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951ROOF PLANROOF PLAN WITH FIRE SETBACKSAND PROPERTY LINESSCALE: 1/16" = 1'-0"A-011OCALA AVE,1-STORYHOUSEROOF #1(21) LG NEON2: LG380N1C-A6(380W) MODULES(N) (21) ENPHASE: IQ7PLUS-72-2-USMICROINVERTERSFIRE ACCESS AND PATHWAYSAS PER NFPA 1, 11.12.2(E) SERVICE POINT ANDUTILITY METERING(N) SOLADECK- FIRE SETBACK - 3 FT- ZONING SETBACK - 2 FT(N) ENPHASE IQ COMBINER BOX(E) MAIN SERVICE DISCONNECT/MAIN DISTRIBUTION PANELEXISTINGDRIVEWAY(N) ALTERNATIVE POWERSOURCE AC DISCONNECT/RAPID SHUTDOWN3'- 0" FIRE SETBACK1" IMC, RMC, FMC, LFMC,EMT OR EQUIVALENTCONDUIT RUN3'- 0" FIRE SETBACK
47'-7"36'-3"4'-0" (TYP.)REVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMES-01CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951MODULE LAYOUTS-01SCALE: 3/32" = 1'-0"1MODULE LAYOUTGENERAL INSTALLATION PLAN NOTES:1) ROOF ATTACHMENTS TO SYP TRUSSES SHALL BE INSTALLED ASSHOWN IN SHEET S-02 AND AS FOLLOWS FOR EACH WIND ZONE:WINDZONESNON-EXPOSED MODULESEDGE / EXPOSED MODULESSPANCANTILEVERSPANCANTILEVERZONE 14' - 0"1' - 4"2' - 0"0' - 8"ZONE 1'XXXXZONE 2e4' - 0"1' - 4"2' - 0"0' - 8"ZONE 2n2' - 0"0' - 8"2' - 0"0' - 8"ZONE 2r2' - 0"0' - 8"2' - 0"0' - 8"ZONE 3e2' - 0"0' - 8"2' - 0"0' - 8"ZONE 3r2' - 0"0' - 8"2' - 0"0' - 8"MODULE TYPE, DIMENSIONS & WEIGHTNUMBER OF MODULES = 21 MODULESMODULE TYPE = LG NEON2: LG380N1C-A6 (380W) MODULESMODULE WEIGHT = 41.01 LBS / 18.6 KG.MODULE DIMENSIONS = 68.5" x 41.0" = 19.50 SFUNIT WEIGHT OF ARRAY = 2.10 PSFARRAY AREA & ROOF AREA CALC'SROOFROOF TYPEARRAYAREA(sq.Ft.)ROOFAREA(Sq. Ft.)ROOFAREACOVEREDBY ARRAY(%)TILTAZIMUTHTRUSSSIZETRUSSSPACING#1ASPHALT SHINGLE409.571122.1736.5022.6°180°2"X4"24" O.C.LEGEND- WIND ZONE 1 (TYP)- WIND ZONE 2e (TYP)- WIND ZONE 2n (TYP)- WIND ZONE 2r (TYP)- WIND ZONE 3r (TYP)- WIND ZONE 3e (TYP)(E) FRONT YARD(N) UNIRAC LIGHT RAIL (TYP.)(E) BACK YARDROOF #1TILT - 22.6°AZIM. - 180°(53) PV ROOF ATTACHMENT@ 24" & 48" O.C. MAX.(SEE SHEET S-02 FORATTACHMENT DETAIL)(SEE SHEET S-01.1 FOR PARTIALPRESSURE OF THE MODULE)ROOF #1(21) LG NEON2: LG380N1C-A6(380W) MODULES(N) (21) ENPHASE: IQ7PLUS-72-2-USMICROINVERTERSSEE SHEET S-02.1 FOR SUPPORTING CALCULATIONS.2) EXISTING RESIDENTIAL BUILDING IS AN ASPHALT SHINGLE ROOFWITH A MEAN ROOF HEIGHT OF 15 FT AND SYP 2"X4" ROOF TRUSSESSPACED 24" O.C. EXISTING ROOF SLOPE FOR SOLAR SYSTEMRETROFIT IS 22.6 DEGREES. CONTRACTOR TO FIELD VERIFY ANDSHALL REPORT TO THE ENGINEER IF ANY DISCREPANCIES EXISTBETWEEN PLANS AND IN FIELD CONDITIONS.3) FIRE SETBACK TO BE 3' FROM RIDGES AND EDGES, AND 18" EACHWAY FROM HIPS AND VALLEYS PER NFPA 1, 11.12.2.4) THE EXISTING ROOF AND STRUCTURE WILL NOT BE ADVERSELYAFFECTED DUE TO THE ADDITIONAL LOADS IMPOSED BY THE SOLARSYSTEM.* I CERTIFY THAT THE INSTALLATION OF THE MODULES IS INCOMPLIANCE WITH FBC: RESIDENTIAL 2020 7TH ED., CHAPTER 3.BUILDING STRUCTURE WILL SAFELY ACCOMMODATE WIND LATERALAND UPLIFT FORCES AND EQUIPMENT DEAD LOADS. *
16'-10"16'-0"P1P4P2P3P6P54'-0" (TYP.)REVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMES-01.1CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951PARTIAL PRESSURE AND MODULES EXPOSURES-01.1SCALE: 3/32" = 1'-0"1ARTIAL RESSURE ANDMODULES EXOSURELEGEND- NON- EXPOSED MODULE- MIN. MODULE EDGE DISTANCE LINE- EDGE MODULE- MODULE EXPOSURE LINE- EXPOSED MODULE- WIND ZONE 1 (TYP)- WIND ZONE 2e (TYP)- WIND ZONE 2n (TYP)- WIND ZONE 2r (TYP)- WIND ZONE 3r (TYP)- WIND ZONE 3e (TYP)NOTE: PARTIAL PRESSURES OF THE WIND ZONES ONALL MODULES HAVE BEEN VERIFIED AND ARE WITHINTHE ALLOWABLE PER THE MANUFACTURERSPECIFICATION, INSTALLER SHOULD FOLLOW THELAYOUT TO AVOID HIGHER ZONAL PARTIALPRESSURES. ANY CHANGES IN LAYOUT SHOULD BEREPORTED BACK TO THE ENGINEER OF RECORD.- MISSING MODULEFOR EXPOSED MODULES2h2DISTANCE : 0' - 10"0.5hDISTANCE : 7' - 6"FOR NON-EXPOSED MODULESALLOWABLE MODULE UPLIFT PRESSURE 2 RAILS: 89 PSFROOF #1(21) LG NEON2: LG380N1C-A6(380W) MODULES2h2(E) FRONT YARD(E) BACK YARD
5"REVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMES-02CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951ATTACHMENT DETAIL2ATTACHMENT DETAIL (ENLARGED VIEW)S-02SCALE: 6" = 1'-0"MODULE MID/END CLAMPSOLAR MODULEUNIRAC LIGHT RAIL5/16"DIA. X 2.5"MIN.EMBEDMENT LAG SCREWAT EACH ATTACHMENT POINTINTO EXISTING FRAMING(E) ROOF SHEATHINGASPHALT SHINGLE ROOFATTACHMENT DETAILS-02SCALE: 1" = 1'-0"12"X4" TRUSSES @ 24" O.C.2"X4" TRUSS SPANNER FORMISSED TRUSS ATTACHMENT(IF REQUIRED)UNIRAC L-FOOTUNIRAC LIGHT RAILGROUNDING MID/END CLAMP5/16"DIA. X 2.5"MIN.EMBEDMENT LAG SCREWAT EACH ATTACHMENT POINTINTO EXISTING FRAMINGFLASH KIT PROFLASHING2"X4" TRUSSES @ 24" O.C.SOLAR MODULEh₂
REVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMES-02.1CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951STRUCTURECALCULATION
REVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEE-01CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951 Q CABLESELECTRICALLINE DIAGRAML2L1NL2L1GN20A/2PGG(N) SOLADECK600V, NEMA 3RUL LISTEDGGGGGGGGGGL2L1L2L1 (N) 125A ENPHASE IQ COMBINER 3(X-IQ-AM1-240-3) [WITH UPTO (4)2-POLE BREAKERS AND ENVOYCOMMUNICATION GATEWAY](N) JUNCTION BOX600V, NEMA 3RUL LISTED#6 BARE CU WIRE PROTECTED PER NEC 250.64(B)GFACTORY INSTALLED 10A OR 15ABREAKER FOR THE ENVOYPV MODULESENPHASE: IQ7PLUS-72-2-USMICROINVERTERSGSOLAR ARRAY (7.980 kW-DC STC)(21) LG NEON2: LG380N1C-A6 (380W) MODULES(01) BRANCH OF 11 MODULES(01) BRANCH OF 10 MODULESTO UTILITY GRIDL1L2N(E) BI-DIRECTIONALSERVICE POINT ANDUTILITY METERING1-PHASE, 240VEXISTINGGROUNDINGELECTRODESYSTEML2L1L2L1GL2L1L2L1L2L1L2L1L1L2N(E) MAIN BREAKER200A/2P, 240VN(E) MAIN SERVICEDISCONNECT/MAINDISTRIBUTION PANEL,225A RATED, 240V1ELECTRICAL LINE DIAGRAME-01SCALE: NTSL2L1L2L1NNGG(N) ALTERNATIVE POWERSOURCE AC DISCONNECT/RAPID SHUTDOWN:240V, 60AMP RATED,NEMA 3R, UL LISTED LOCKABLE & NON FUSIBLENOTE:1. SUBJECT PV SYSTEMS HAS BEEN DESIGNED TOMEET THE REQUIREMENTS OF THE NEC 2017, ANDTHOSE SET FORTH BY THE FLORIDA SOLAR ENERGYCENTER CERTIFICATION, INCLUDING MAXIMUMNUMBER OF MODULE STRINGS, MAXIMUM NUMBER OFMODULES PER STRING, MAXIMUM OUTPUT, MODULEMANUFACTURER AND MODEL NUMBER, INVERTERMANUFACTURER AND MODEL NUMBER, AS APPLICABLE.2. THE SOLAR PV BACKFED BREAKER IS AT THE END OFTHE BUSBAR AND THERE IS NO LUG FED SUB PANEL.3. REFER SHEET DS-08 FOR LOAD CALCULATIONS.40A/2PINTERCONNECTION120% RULE - NEC 705.12(B)(2)(3)(b)UTILITY FEED + SOLAR BACKFEED200A + 40A = 240ABUSS RATING x 120%225A x 120% = 270AG(3) #6 AWG THWN-2(1) #6 AWG THWN-2 GNDIN 1" PVC, IMC, RMC, LFMC,RTRC, LFNC, EMT OR FMTCONDUIT RUNGGGGGGGGGGL2L1L2L1L2L120A/2P(2) 10/2 ROMEX RUN IN ATTICOR(2) #10 AWG THWN-2-RED(2) #10 AWG THWN-2-BLACKEGC #6 AWG THWN-2 GNDIN 1" IMC, RMC, FMC, LFMC,EMT OR EQUIVALENTCONDUIT RUN(2) #10 AWG THWN-2-RED(2) #10 AWG THWN-2-BLACKEGC #6 AWG THWN-2 GNDIN 1" IMC, RMC, LFMC, PVC,RTRC, LFNC, FMT OR EMTCONDUIT RUNL1L2N
REVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEE-02CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951 ELECTRICAL CALCULATIONELECTRICAL NOTES1.ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELEDFOR ITS APPLICATION.2.ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90DEGREE C WET ENVIRONMENT. THE TERMINALS ARE RATED FOR 75DEGREE C.3.THE WIRES ARE SIZED ACCORDING TO NEC 110.14.4.WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALLBE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS POSSIBLE TOTHE NEAREST RIDGE, HIP, OR VALLEY.5.WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICALEQUIPMENT SHALL COMPLY WITH NEC 110.26.6.DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS.CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS,FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES ANDSTANDARDS.7.WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARENOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY.8.ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED ANDREADILY VISIBLE.9.MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULEFRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIPMANUFACTURER'S INSTRUCTION.10.MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPERG.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG.11.THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE .12.UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALLPHOTOVOLTAIC SYSTEM COMPONENTS LOCATED AT THE SERVICEENTRANCE.13.MODULES CONFORM TO AND ARE LISTED UNDER UL 1703.14.RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.15.CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHTRESISTANT PER NEC ARTICLE 300.6 (C) (1) AND ARTICLE 310.10 (D).16.CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FORUSE IN WET LOCATIONS PER NEC ARTICLE 310.10 (C).17.THIS SYSTEM IS EQUIPPED WITH RAPID SHUTDOWN OF PVCONDUCTORS IN COMPLIANCE WITH NEC 690.12.18.LABELING IN COMPLIANCE WITH NEC 690.12 AND 690.56(C) IS SHOWNON SHEET E-03.19.ALL CONDUITS TO BE INSTALLED A MIN OF 7/8" ABOVE THE ROOFSURFACE.WIRING CALCULATIONSI ERMOCRATES CASTILLO PE# 52590 AN ENGINEERLICENSED PURSUANT TO CHAPTER 471, CERTIFYTHAT THE PV ELECTRICAL SYSTEM AND ELECTRICALCOMPONENTS ARE DESIGNED AND APPROVED USINGTHE STANDARDS CONTAINED IN THE MOST RECENTVERSION OF THE FLORIDA BUILDING CODE. FBC 107,THE NEC 2017, AND THOSE SET FORTH BY THEFLORIDA SOLAR ENERGY CENTER CERTIFICATION.
UM
MDP
CBACD
REVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEE-03CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951SYSTEM LABELINGRAPID SHUTDOWNSWITCH FORSOLAR PV SYSTEMLABEL LOCATION:AC DISCONNECT(PER CODE: NEC 690.56(C)(3))WARNINGELECTRIC SHOCK HAZARDLABEL LOCATION:AC DISCONNECT, POINT OF INTERCONNECTION(PER CODE: NEC 690.13(B))TERMINALS ON BOTH LINE ANDLOAD SIDES MAY BE ENERGIZEDIN THE OPEN POSITIONLABEL LOCATION:POINT OF INTERCONNECTION(PER CODE: NEC 705.12(B)(2)(3)(b))WARNINGPOWER SOURCE OUTPUT CONNECTION DONOT RELOCATE THIS OVERCURRENT DEVICELABEL LOCATION:POINT OF INTERCONNECTION(PER CODE: NEC 705.12(B)(2)(3)(b))! WARNING DUAL POWER SOURCESECOND SOURCE IS PHOTOVOLTAIC SYSTEM!TURN RAPID SHUTDOWNSWITCH TO THE "OFF" POSITION TOSHUT DOWN PV SYSTEMAND REDUCESHOCK HAZARDIN THE ARRAYSOLAR PV SYSTEM EQUIPPEDWITH RAPID SHUTDOWNSOLAR ELECTRICPV PANELSAC DISCONNECTPHOTOVOLTAICSYSTEM MICROINVERTERSLOCATED UNDER EACHPV MODULE INROOF TOP ARRAYAC COMBINER BOXLABEL LOCATION:AC DISCONNECT, POINT OF INTERCONNECTION(PER CODE: NEC 690.54)SOLARBREAKERLABEL LOCATION:COMBINER BOX(PER CODE: NEC 690.52)LABEL LOCATION:INVERTER(PER CODE: NEC 690.52)LABEL LOCATION:AC DISCONNECT, POINT OF INTERCONNECTION(PER CODE: NEC 690.54)LABEL LOCATION:POINT OF INTERCONNECTION(PER CODE: NEC 705.12(B)(2)(3)(b))NOMINAL OPERATING AC VOLTAGE -NOMINAL OPERATING AC FREQUENCY-MAXIMUM AC POWER-MAXIMUM AC CURRENT-MAXIMUM OVERCURRENT DEVICE RATING FOR AC MODULE PROTECTION PER CIRCUIT-VVAHz60290A240A1.2120LABEL LOCATION:COMBINER BOX(PER CODE: NEC 690.52)DATA PER PANELLABEL LOCATION:AC DISCONNECT, POINT OF INTERCONNECTION(PER CODE: NEC 690.54)PHOTOVOLTAIC SYSTEM AC DISCONNECTRATED AC OPERATING CURRENT 25.41 AMPSAC NOMINAL OPERATING VOLTAGE 240 VOLTS7.980 kW SOLARDISCONNECT LOCATEDLABEL LOCATION:MAIN SERVICE DISCONNECT / MAIN DISTRIBUTION PANEL, PV DISCONNECTLOCATED NO MORE THAN 3FT (1M) FROM THE SERVICE DISCONNECT(TEXT HEIGHT SHOULD BE A MINIMUM OF 3/8")(PER CODE: NEC 690.56(B), NEC 705.10, NFPA 1, 11.12.2.1)CAUTION!POWER TO THIS BUILDINGSUPPLIED FROM MULTIPLE SOURCES EMERGENCY RESPONDER:THIS SOLAR PV SYSTEM IS EQUIPPEDWITH RAPID SHUTDOWN.TURN RAPID SHUTDOWN SWITCH TO THE ''OFF''POSITION TO SHUTDOWN ENTIRE PV SYSTEMADHESIVE FASTENED SIGNS:· THE LABEL SHALL BE VISIBLE, REFLECTIVE AND SUITABLE FORTHE ENVIRONMENT WHERE IT IS INSTALLED [NFPA 1, 11.12.2.1]· WHERE REQUIRED ELSEWHERE IN THIS CODE, ALL FIELD APPLIED LABELS, WARNINGS, AND MARKINGS SHOULD COMPLY WITH ANSI Z535.4 [NEC 110.21(B) FIELD MARKING].· ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IF PROPERLY ADHERED. VINYL SIGNS SHALL BE WEATHER RESISTANT [IFC 605.11.1.3]LABEL LOCATION:AC DISCONNECT, POINT OF INTERCONNECTION(PER CODE: NEC 690.56(C)(1)(a), IFC 1204.5.1SERVICE POINT ANDUTILITY METERINGENPHASE IQ COMBINER BOXMAIN SERVICE DISCONNECT/MAIN DISTRIBUTION PANELALTERNATIVE POWERSOURCE AC DISCONNECT/RAPID SHUTDOWNPV SOLAR ARRAYON ROOFWARNINGIN CASE OF EMERGENCY CONTACT:SUNPRO SOLARPH. NO. - (866) 450-1012LABEL LOCATION:MAIN DISCONNECT(PER CODE: NFPA - 1, 11.12.2.1.5)!!6505 OCALA AVE, FORT PIERCE, FL 34951
REVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEDS-01CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951DATA SHEET
REVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEDS-02CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951DATA SHEET
REVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEDS-03CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951DATA SHEET
REVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEDS-04CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951DATA SHEET
REVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEDS-05CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951DATA SHEET
REVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEDS-06CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951DATA SHEET
REVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEDS-07CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951DATA SHEET
REVSHEET NAMESHEET SIZESHEET NUMBERJOHNSON RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEDS-08CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC6505 OCALA AVE,
FORT PIERCE, FL 34951DATA SHEET