HomeMy WebLinkAboutProject InformationJob: - - wrightsoft- Project Summary Date: Entire House By: QUICK CALLS, INC. 317 ST. LUCIE LN., FT PIERCE, FL 34946 Phone: For: WYNNE DEVELOPMENT. THE WINDSOR, FT. PIERCE, FL Notes: S�k Design Information Weather. Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range L Relative humidity 50 Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipmentload Sizing Structure 18467 Btuh Structure 17655 Btuh Ducts 6190 Btuh Ducts 9340 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh none (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 24657 Btuh Use manufacturers data n Rate/swing multiplier Equipment 0.95 Infiltration sensible load 25645 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2453 Btuh Ducts 2554 Btuh Central vent (0 cfm) 0 Btuh Heating Coolingg . (none) Area (ft2) 1753 1753 Equipment latent load 5007 Btuh Volume (ft3) 14741 14741 Air changes/hour 0.38 0.20 Equipment total load 30652 Btuh Equiv.AVF (cfm) 93 49 Req. total capacity at 0.70 SHR 3.1 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER AIR CONDITIONING Trade CARRIER AIR CONDITIONING Model 25HBC536A*030 Cond 25HBC536A*030 AHRI ref 7914585 Coil FX4DN(B,F)037 AHRI ref 7914585 Efficiency 8.5 HSPF Efficiency 12.0 EER, 15 SEER Heating input Sensible cooling 24360 Btuh Heating output 34600 Btuh @ 470F Latent cooling 10440 Btuh Temperature rise 27 OF Total cooling 34800 Btuh Actual air flow 1160 cfm Actual air flow . 1160 cfm Air flow factor 0.047 cfm/Btuh Air flow factor 0.043 cfm/Bfuh Static pressure 0.50 in H2O Static pressure 0.50 in H2O Space thermostat Load sensible heat ratio 0.84 Capacity balance point = 34 OF Backup: Input = 7 kW, Output = 23009 Btuh, 100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft` 2017-Apr-10 17:19:28 Right -Suite® Universal 201717.0.1.4 RSU08101, Page 1 '�' ...k Calcs%Documents\WYNNE-THE WINDSOR-REVISED.rup Calc = MJ8 Front Door faces: N - - wrightsot RighW@ Worksheet Job: Entire House Date: QUICK CALCS, INC. By: 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire. House MASTER BEDROOM 2 . Exposed wall 153.0 ft . 45.0 ft 3 Room height 8.4 ft d 8.0 ft heat/cool 4 Room dimensions 1.0 x 280.0 ft 5 Room area 1753.0 ft2 280.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2-°F) (Btuhlft2) or perimeter (ft) (Btuh) or perimeter (ft) (Stuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AAocs 0.143 ne 4 00 . 265 488 448 1795 1141 192 192 769 489 1A-c1om 1,270 ne 35 56 : 70 43 > .7 0 247 , 0 0 ; -0, 0 1A'c1om `. 1;270 ne 3556 = 7043 16 0 581 1151 0 0', 0' 0 1Ac1om 1'.270 _ne: 35,56 4524. 16 0 581 739 0: 0'-. 0 '0. 11 V�I 13A4ocs 0.143 se 4.00 2.55 64 41 165 . 105 0 0 0 , 0 �-D 11D0 0.390 se 10.92 1131 23 23 20 257 0 0 0 0 13A�ocs c 0:143 sw,; 4 00 ; 2.55 :, 437 : ' 396 - :1584 ;=1007 .56 56 : 224 :4A52am' 0770 . sw 21 56 ; 2753'. 44 45 893 : 1140 0 .. 0 ` :0 :143- .0 VL213A4ocs 0:143 nw 4.00 2.65 290 217 867 551 112 79 318 . 202 1A-c1om 1.270 nw 35:56 45.24 33 0 1162 1478 33 0 1162 1478 . 4A5-2omd 0.770 nw 2156 36.90 41 0 880 1505 0. 0 0 0 P ^12C-0sw: 0:091 ;:,. 255:' 128 '308 a308. '784 0 0: A: C 16A-Mmd 0.032 - 0.90 2.32 1753 1753 1571 4067 280 280 251 650 �F":. ; '22A7tpl :. ... 0.969 :: -: 27.60 ;` 0.W, 1753 `, --M 4237 0'. 280. :. .45 1246 • `0 6 c)AED excursion 1360 600 Envelope loss/gain 15594 15385 3970 3561 12 a) Infiltration 2873 810 809 228 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 2 460 0 0 Appliances/other 1000 0 Subtotal (lines 6 to 13) 18467 17655 4779 3789 Less eidemal load 0 0 0 0 Less.transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 18467 17655 4779 3789 151 Duct loads 34% 53%1 6190 9340 341/6 53%1 1602 2005 Total room load 24657 26995 6380 5794 Air required (cfm) 1160 1160 3001 249 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. � - wrightsoft' 2017-Apr=10 1 Right -Suite® Universal 2017 17.0.14 RSU08101 Page k Calcs\Documents\WYNNE-THE WINDSOR-REVISED.rup Calc = MJ8 Front Door faces: N wri htsoft, Ri ht.-M Worksheet Job: 9 9 Entire House Date: By: QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772466-6799 Fax 772466-6796 Email: QUICKCALCS@AOL.COM 1 Room name WIC M. BATH 2 3 Exposed wall Room height 0 ft 8.0 ft heat/cool 7.0 ft 8.0 ft heat/cool 4 5 Room dimensions Room area 7.0 x 9.0 ft 63.0 ft2 1.0 x 61.0 ft 61.0 ft2 Ty Construction number U-value (Btuh/ft2--°F) Or HTM (Btu 2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross NIP/S Heat Cool Gross WKS Heat Cool 6 11 °, 13AAccs 1Ac1om 1Ac1om 1Ac10m . 13A4ocs 0.143 1.270 1.270 1270 0.143 '.no • ne ne . ne se 4.00 '. 35.56 35 56 35.56 4.00 . 255 ..,76.43 i 70 43 45r24 2.55 0 0 :. <0 0 0 0 0 0 0 0. 0 0 0 0 0 0 0 0 56 7 0 0 0 49 : " 0 , -: 0 0 196 ; 247 ' 0 0 125 488 0 "0 0 11130 13A flocs . 4A5 tom 0390 0143 0:770 se sw .. sw= 10.92 4 00' 21 56; 11.31 2:55 . 27:53 0 , :0 '. 0 0 - 0 0 0 , . 0 . 0 0. .: p 0 0 '; p '. - 0 0 .. .... 0 0 0 .. 0 0 0 -0 0. V�! �G 13A4ocs 1A-c1om 0:143 1.270 nw nw 4.00 35.56 2.55 45.24 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 �-G R, C F ' 4A5.2omd 12C-0sw-- .:- . .16A-30md �22A-4p1 ° :, 0.770 0:091 0.032 0`.989:: nw . - ' - 21.56 2.55: 0.90 27-._69::: 36.90 k 1.28 2.32 000 0, : 0 63 63 0 ;.0 63 : -0 0 :. - ..:•0 56 ' . . ° i0 0 :, . 0 146 : 0 0. `; ' 0 61 .61,; 0 ' . ;..'0 61 `7 0 0 55 194V 0 r :. 0 142 0 6 c)AED excursion -5 -26 Envelope loss/gain 56 141 692 729 12 a) Infiltration 0 0 126 35 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal Qines 6 to 13) 56 141 817 . 764 Less exWemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 56 141 817 764 15 Duct loads 34% W%l 19 75 34% 53% 274 404 Total room load 75 . 216 1091 1168 Air required (cfm) 4 9 51 50 Calculations approved byACCA to meet all requirements of Manual J.8th Ed. - wrightsoft• Right -Suite® Universal 2017 17.0.14 RSU08101 2017-Apr-10 1 Page 2 ACCA ...k Calcs\DocumentskWYNNE-THE WINDSOR-REVISED.rup Cale = MJ8 Front Door faces: N 9 • - - wrightsoft' Right-M Worksheet °b Entire House Date: • QUICK CALCS, INC. By. 317 ST..LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS ,AOL.COM 1 Room name LAUDRY BEDROOM 2 2 Bcposed wall 0 ft 12.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 5 Room dimensions Room area 6.0 x 6.0 ft 36.0 ft2 15.0 x 12.0 ft 180.0 ft2 Ty Construction number U-value (Btuh/ft2-°F) Or HTM (Btuh/ft2) Area or perimeter (ft) (Btuh) (ft2) or perimeter. (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross WP/S Heat Cool 6 11 13AAocs 1Ac1om 1Ac1om _ ;1Ac1om . 13A4ocs 0143 1270 1c270 .1:270 0.143 ne ne ne .ne se . 4.00, 35 56; 3556 ..35.56 4.00 2 55 7043 7043:= . .45.24 2.55 , 0 = 0 -:;0: 0 0 0 0 0 0 0 0 0 0 0. 0 0 0 0 .. .0 0 96 0 16 .0 0 80 ' 0 .: 0 0:., 0 319 '> 0 - 581' 0 0 203 0; 1151 :0 0 V►1 L—D 11D0 13A-0ocs `. 0 390 0143 0:T70 se sw , .sW- 10 92. . 4 00:: ..21.56;, 11.31 2 69 27:53' 0 : ,p 0 0 :. p 0 0 0 0 0 :. p 0 0 :' 0 ..: 0 0 .. •0 0... 0 _ 0 0,. 0 . _ '.0 D V�! Vi✓ 13A4ocs 1Ac1om 0.143 1.270 nw nw _ 4.00 35.56 2.55 45.24 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 p C F 4A5 2omd 4:i"sw• 16A30md 22A.tpl... 0.770 07091 0.032 0,989 nw .-. - :.: _ 21,56 2 55 0.90. .. 27.'69 36.90 ' C28 2.32 : 0.06 0 ` °. 0 36 : ` - 36 0 0. 36 0 0 0 32 ; . 0 0_ i 0 84 : p 0 .:` p 180 . -... 180 0 "0 180 : 12 0 : 0' 161 ..:: ° 332 0 , 0 418 6 c)AED a -ursion -3 -60 Envelope loss/gain 32 81 1394 1711 12: a) Infiltration 0 0 216 61 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 32 81 1609. 1772 Less exfemal load 0 0 0 0 Less transfer 0 0 0 . 0 Redistribution 6 14 6 14 14 Subtotal 38 95 1615 1786 15 Duct loads 34o/a 1 53%1 13 50 34% 53%1 541 945 Total room load I I 51 145 2156 2730 Air required (cfm) 2 6 101 117 Calculations approved byACCA to meet all requirements of -Manual J 8th Ed. AeuA - - wrightsott' Right -Suite® Universal 2017 17.0.14 RSU08101 2017-Apr-10 1 Page 3 ...k Calcs%Documents\WYNNE-THE WINDSOR-REVISED.rup Calc = MJ8 Front Doorfaces: N - - wrightsoft' . Right-M Worksheet Job: Entire House Date: QUICK CALLS; INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name DINING/GREAT ROOM KrrCHEN 2 64)osed wall 50.0 ft 11.0 ft 3 Room height 8.9 ft heat/cool 8.9 ft heat/cool 4 Room dimensions 1.0 x 588.0 ft 19.0 x 11.0 ft 5 Room area 588.0 ft2 209.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area Load number (Btuh/ft2 °F) (Btuhlftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat I Cool Gross WP/S Heat Cool Gross N/P/S Heat Cool 6 : , _ „-; 13A-flocs 0.143 •ne 4 00 - 2.55 :, 0 0 0 0 0 0 0 0 1A c1om 1Ac1om -. 1Ac.1om - 1.270 '1.270 1:•270 ne : ne °ne ` 35 56..7.0.43 3556: . 35.,i 7043 45.24 ; 0 ` .. 0 0 -0 _- A 0: 0 0 • 0.... 0 0 0 0 0 _ 0 0 :0 0 0 0 11 WW 0..11D0. 13A-4ocs 0.143 se 4.00 2.55 0 0 0 0 0 0 .0 0 • 0.390 . se. 10.92 _ 11.31 0 0 0 0 0 0 0 0 3A-0ocs 1. 0143 sw 4 00 2 55 , '" 267 226 903 574 '' 98 ` ' . 98 .. 392 . 249'. :4A52om 0770 sw' `: 2156 27 53 ,:: 41' . 22 ~893 1140 ':. 0 :. 0 0 0: —G 13A-00cs 1A-c1om 0.143 1.270 nw nw 4.00 35.56 2.55 45.24 178 0 137 0 549 0 349 0 0 0 0 0 0 0 0 0 �—G 4A5.2omd 0.770 nw 21.56 36..90 41 0 880 1505 0 0, 0 0 0 091 2:55 .1.28 :. 0 . ' 0'' 0 , 0 116 .. :,. _ :916 `:.. ` 295. ' . ' 148' C 16A-30md 0.032 0.90 2.32 588 588 527 1364 .209 209 187 485 0s989 - . , . . 27.0 .0.00 : 6M " ... : 50 1385 : 0 209 :: ; ' . _ .11 ' .' . 305 ; 0 6 c)AED excursion 1004 -64 Envelope loss/gain 5136 5937 1179 818 12 a). Infiltration 1000 282 220 62 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 2 460 0 0 Appliances/other 0 1000 Subtotal Pines 6 to 13) 6136 6679 1399 1880 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 6 14 0 0 14 Subtotal 6142 6693 1399 1880 15 Duct loads 34% 53% 2058 3W 34% 53% 469 995 FTTotal room load 8200 10234 180 2875 Air required (cfm) 386 440 88 124 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. A wrightsoft- Right -Suite® Universal 2017 17.0.14 RSU08101 2017-AprA0 1 Page 4 k Calcs\Documents\WYNNE-THE WINDSOR-REVISED.rup Calc = MA Front Door faces: N -t - wr%ghtsoft Right-0 Worksheet Job: Entire House'Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34946-Phone: 772-466.6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BATH HALL 2 EVosed wall 5.0 ft 0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 10.0 x 5.0 ft 5.0 x 5.0 ft 5 Room area 50.0 ft2 25.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuhlft2-'F) (BtuWft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 VVI, 13A• 400s 0.143 ne ; 4 00 . 2 51 40 40 160 102 0 0 0 0 1A c1om 1.276 ne 35 56 70 43 0 0 0 0 . 0 _ . 0 0 0 1Ac1om 1270 ne i 3556 7043 0 0 0 0 0 ,,. 0:.: 0 Q ' :1Ac1om .' 1'270 .ne: 35:56 45:24 0,,-' 0' 0.. U 11 W I—D 13A-4ocs 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 11DO 0.390 se 10.92 11.31 . 0 0 0 0 0 0_ 0 0 0-143 sw ; 4 00, ; 255 : p 0 0 , p ` .. 0 . p -. 0 0 =- c. •ai�5 tom .:.. ono sw . ' . 21 ss 27:Ss :o . o o . o . o :.. . o ' . o:: p V►/ 13AAocs 0.143 nw 4.00 2.55 0 0 0 0 0 0 0 0 1Aclom 1.270 nw 35.56 45.24 0 0 0 0 0 0 0 0 _4A5.2omd 0.770 nw , 21.56 36.90 0 0 • 0 0 0 0 0 0 P 12C,Osw": rA:091 . • 2:55' 128 ' . 0 U . .. . 0 0 . : 0 0 : .: p . •. p 0.032 50 45 116 25 25 22 58 ;F 22 tplma ., ,. ,..0..989 .._ 27.69 ffb0 :'. : - 50 p5 : 138':: .0 :: 25 :0 ff 6 c)AED excursion -8 -2 Envelope loss/on 343 210 22 56 12 a) Infiltration 90 25 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal Qines 6 to 13) 433 235 22 56 Less extemal load 0 0 0 0 Less .transfer 0 0 0 0 Redistribution 6 14 -22 -56 14 Subtotal 439 249 0 0 15 Duct loads 34% 530% 147 132 349/6 53°/u .0 0 Total room load 586 381 0 0 Air required (cfm) 28 16 0 0 Calculations approved byACCA to meet all requirements of Manual 8th Ed. AA= -F[- wright: o;pA 2017-Apr-10 17:19:28 .4ark Right -Suite® Universal 2017 17.0.14 RSU08101 Page 5 ..:k Caics%Documents%WYNNE-THE WINDSOR-REVISED.rup Calc = MJ8' Front Door faces: N - - wrightsoW Right-J® Worksheet Job: Entire House Date: QUICK CALCS, INC. By: 317 ST LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6749 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name FOYER BEDROOM 3 2 Dposed wall 9.0 ft 14.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 5 Room dimensions Room area 1.0 x 92.0 ft 92.0 ft2 13.0 x 13.0 ft 169.0 ftZ Ty Construction number U-value (Btuh/ft22F) Or HTM (Btuh/ftZ) Area (ftZ) or perimeter (ft) Load (Btuh) Area (ftZ) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross WP/S Heat Cool 6 W 1A�1om 1&C om ;: 0.143 1.270 1270 ne ne ne... .4.00. 35 56 3556; 2.55 70 43 7043:. 0 . 0 0 0 : . 0 0 0 0 - _.0 0 0 .. 0 104 0 .. 0:.. 88 0 0; 351 0 p 223 0 0; 11 1Aid Iom 13A4ocs 1:270 0.143 : ne se 35 56: 4.00 , . 45:24 215 0 64 0 41 0 165 0 105 16 0 0 0 581 0 739 0 11DO 4A5 tom 0.390 0143 —0. se- sw .:_ sw:: 10.92 4 00 21.56 : 11.31 ` 2 55 ;, 27.53 23 ; 8 0 '0 23 8 0 248 32 . 6 257 .. 20 :: U 0 8 . U _ 0 8 .. ; p 0 82 ' 0: 0 20 10 �G 13A4ocs 1A-c1om 0.143 1.270 nw nw 4.00 35.56. 2.55 45.24 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6 0 P C lF 2. 4A5.2omd _ 12C 0sw . . .. 16A 30md 22Petpl`' 0.770 - 0091 0.032 0989"; nw , --- - =:- 21.56 2;55 0.96 27.69_'. 36.90 ` 1?28 2.32 000i 0 _ ' 88 92 92 0 88 92 9 0 224 82 249" 0 " 113 213 0 0 104 169 169 0 > 104 169 - 14' 0, 265 151 •388:, 0 ` _ :.133 392 0 6 c)AED excursion -25 -52 Envelope loss/gain 1002 684 1768 1456 12 a) Infiltration 162 46 252 71 b) 'Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 1 0 0 Subtotal (lines 6 to 13) 1163 730 2020 1527 Less odemal load 0 0 0 0 Less.transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1163 7301 2020 1527 151 Duct loads 1 34% 53% 390 386 34% 53%1 677 808 Total room load 1553 1116 1 2697 2335 Air required (cfm) 73 48 127 100 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. .� -- wrigF�tsoft' ACCA Right -Suite® Universal 2017 17.0.14 RSU08101 2017-Apr-1017:19:28 Page 6 ...k Calcs\Ddcuments\WYNNE-THE WINDSOR-REVISED.rup' Calc = MJ8 Front Door faces: N - - wrights' 1, Duct System Summary Date : Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 7.72-466-6799 Fax 772-46676796 Email:, QUICKCALCS@AQL.COM For. WYNNE DEVELOPMENT THE-WINDSOR, FT. PIERCE, FL Heating Cooling External static pressure 0.50. in H2O 0.50 in H2O Pressure losses 0 in H2O: 0 in H2O Available static pressure 0.50 in H2O 0.50 in H2O Supply [_return available pressure 0.250 / 0.250 in H2O 0.250 / 0.250 in H2O Lowest friction rate 0.273 in/100ft 0.273 in/100ft Actual air flow 1160 cfm 1160 cfm Total effective length (TEL) 183 ft Name Design (Btuh) Htg (cfm) Cig (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH h 586 28 16 0.372 4.0 Ox 0 VIFX 19.5 115.6 st1 BEDROOM 2 c 2730 101 117 0.384 7.0 OxO VIFx 15.0 115.0 st1 BEDROOM 3 h 2697 127 100 0.353 6.0 Ox0 VIFx 26.8 115.0 st1 DINING/GREAT ROOM C 3411 129 147 0.292 7.0 Ox0 VIFx 36.5 135.0 st2 DINING/GREAT ROOM-B C 3411 129 147 0.371 7.0 OxO VIFx 19.9 115.0 st1 DINING/GREAT ROOM-C C 3411 129 147 0.278 7.0 Ox 0 VIFx 44.9 135.0 st2 FOYER h 1553 73 48 0.490 4.0 OxO VIFx 7.0 95.0 KITCHEN c 2875 88 124 0366 6.0 OxO VIFx 21.8 115.0 st1 LAUDRY c 145 2 6 0.371 4.0 Ox 0 VIFx 19.9 115.0 st1 M. BATH h 1091 51 50 0.282 6.0 Ox0 VIFx 42.3 135.0 st2 MASTER BEDROOM h 3190 150 124 0.273 6.0 OxO VIFx 48.4 135.0 st2 MASTER BEDROOM -A h 3190 150 124 0.284 6.0 Ox 0 VIFx 40.9 135.0 st2 wlc C 216 4 9 0.292 4.0 Ox 0 VIFx 36.0 135.0 st2 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st2 Peak AVF 612 602 0.273 780 12.0 0 x 0 VinlFlx st1 st1 Peak AVF 1087 1112 0.273 796 16.0 0 x 0 VihIFlx 1 wlri htsoft° 2017-Apr-1017:19:29 Right -Suite® Universal 2017 17.0.14 RSU08101 Page 1 AM, ...k CalcslDocuments\WYNNE-THE WINDSOR-REVISED'.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) . TEL (ft) Design FIR Veloc ftm) Diam (in) H x W (in) Stud/Joist Opening (in) . Duct WtF Trunk rb1 Ox0 1160 1160 0 0 0 0 Ox 1 0 VIFx wri htsoft° 2017-Apr-1017:19:29 9 Right -Suite® Universal 2017 17.0.14 RSU08101 Page 2 ACCA ..k Calcs%Documents\WYNNE-THE WINDSOR-REVISED.rup Calc = MJ8 Front Door faces: N